PlantPAx™: Field Device Interface and Asset Management

advertisement
PlantPAx™: Field Device Interface and Asset
Management
Tomas Knobloch
Solution Architect Visualization, SW, Process
Tomas Babka, FBL IA
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
COTM for SI – Petrcane - Croatia
16th-18th of June
Hotel PINIJA
Petrcane, Croatia
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
2
Agenda
Digital Fieldbus Overview
FDT/DTM Technology
Integration Office
Demo Overview
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
3
Process Networks
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
4
Benefits of a Digital Fieldbus
 Self testing instruments that report problems immediately
 Empty pipe, sensor failure
 Multiple process variables with status
 Totalizing, cycle counting, temperature, density
 Network & communication monitoring and statistics
 Signal quality
 Voltages & currents
 Centralized asset management – commissioning and diagnostics
 Engineering units
 Range
 Linearity
 Last calibration date
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
5
What is HART?
 Highway Addressable Remote Transducer (HART) is a
communication technology that allows digital information
to be carried on the same wires as a field device 4-20 ma
current loop signal. The HART data consists of additional
process data as well as field device data that can be used
to configure, monitor and maintain the field device:
 Available data:
Device identification – tag, revision info, serial number,
etc.
Calibration data
Multiple process variables
Status + diagnostics Info
Analog
Signal
De Facto Standard - approximately 30 million installed nodes
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Profibus PA / Foundation Fieldbus
Comparison
Profibus PA
Foundation Fieldbus H1
Proprietary / Open
•Open
•Open
Governing Body
•Profibus Profinet
International
•Fieldbus Foundation
Physical Layer
•IEC 61158-2
•IEC 61158-2
Speed
•31.25 kB/sec
•31.25 kB/sec
Control Network
•Profibus DP
Traditional
•EtherNet/IP & ControlNet
Rockwell
Automation Offering
•HSE High Speed Ethernet
•EtherNet/IP & Control/Net
Communications
•Master / Slave
•Peer to Peer (Token Passing)
Control in the Field (CIF)
•Not Supported
•Communication between devices
•Control Blocks in Devices (PID)
Field Device Tool / DTM
•Supported
•Supported
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
7
Foundation Fieldbus & Profibus PA
Topologies
 Multiple topologies including:

Simple

Split Trunk

Dual Bus

Ring Bus

Multi-Master
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Flow Metering with EtherNet/IP Support
Promass 83 Coriolis transmitter and Promag 53 product families now includes an
EtherNet/IP communication option. Digital communications rates up to 100 Mbps
 Dual RJ45 ports supports web server and EtherNet/IP network simultaneously, or
daisy chaining function, or internal switch capability
 Compliant to the ODVA EtherNet/IP protocol
 CE marked for non-hazardous area application
 Embedded EDS fileLogix5000 support for easy device configuration on a network
 Faceplate for main measured values, error handling and totalizer control functions
 Integrated Web server for easy Instrument configuration
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
9
FDT (Field Device Tool) Group
 FDT goal is to provide customers with better
solutions via open standards
 FDT uses proven Microsoft Windows standards
 FDT is not a new digital bus or protocol
 FDT has no allegiance to any one specific bus
protocol
 FDT is supported by over 70 users and
manufacturers
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Device Integration Tools
Add-On Instructions (AOI)
and Faceplates
 Predesigned AOIs provide a twoway exchange of data between
the faceplates and the
ControlLogix controller
 FactoryTalk View SE faceplates
provide visualization of
instruments connected to a 1756
HART module, 1788EN2PAR, or
1788EN2FFR.
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
11
Demo Overview
 Configure instrumentation interface within the controller for I/O data
exchange
 Configure controller logic for faceplate data exchange
 Use faceplates objects within FactoryTalk® View SE Studio
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
12
Field Device Integration Demo
HART demo case
EN2FFR demo case
Copyright © 2014 Rockwell Automation, Inc. All rights reserved.
EN2PAR demo case
EIP Promass83 demo case
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
13
Questions?
Follow ROKAutomation on Facebook & Twitter.
Connect with us on LinkedIn.
www.rockwellautomation.com
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.