Ministry of Municipal Affairs and Housing Ontario’s Building Code ONTARIO ONLY CHANGE NUMBER DESCRIPTION OF PROPOSED AMENDMENT PROPOSED CHANGE TO THE 2006 BUILDING CODE H-B-09-34-03 CODE REFERENCE Div. B 9.34.4.1. & 9.34.4.2. Delete requirements for the mounting of electrical meters. EXISTING 2006 BUILDING CODE PROVISION(S) 9.34.4. Service Entrance Requirements 9.34.4.1. Meter Mounting Device (1) Except in the case of externally mounted read-outs, each new residential consumer service of 200 amperes or less shall have a meter mounting device located outdoors in an accessible location. (2) For the purposes of this Subsection, the front of the building is the side nearest the utility distribution line. 9.34.4.2. Location of Meter Mounting Device (1) Meter mounting devices shall be installed on the wall of the building or where that is not possible, on a separate support, so that the midpoint of the meter after installation will be 1 750 mm (5 ft 9 in) ±100 mm (4 in) from finished grade. (2) Meter mounting devices shall be located not more than 3 m (9 ft 10 in) back from the front of the single family and semi-detached homes. Current OESC provisions 6-408 Location of meters (1) Meters and metering equipment shall be (a) located as near as practicable to the service box except as provided for in Subrule (2); (b) grouped where practicable; (c) readily accessible; (d) not located in coal bins, clothes closets, bathrooms, stairways, high ambient rooms, dangerous or hazardous locations, nor in any similar undesirable places; (e) if mounted outdoors, of weatherproof construction or in weatherproof enclosures; and (f) in compliance with the requirements of the supply authority. Building and Development Branch © Copyright Queen's Printer for Ontario 2011 Page 1 of 2 Issued January 2011 PROPOSED CODE CHANGE Delete current Building Code provisions and replace with the following: 9.34.4.1 Electrical Meters (1) Electrical meters and metering equipment shall be installed in accordance with the Ontario Electrical Safety Code. RATIONALE FOR CHANGE Problem / General Background Location of residential service meters is an electrical installation requirement and should be provided in the OESC. Additionally, the OESC currently contains requirements for location of meters. As such, the requirements for meter locations under the Building Code should be removed. A signpost in the Building Code is recommended to ensure designers are aware these requirements are in the OESC. Although the requirements that are recommended to be removed from the Building Code are more restrictive than the current requirements in the OESC, the ESA and OESC may allow the supply authority to determine the required location of meters as the agency responsible for these devices. For this reason, the requirements of the Building Code are not to be brought into the OESC. Justification / Explanation The OESC contains current and provisions for meter installations and these are enforced by the electrical inspector. Cost / Benefit Implications None. The proposed change is currently being practiced. Enforcement Implications None. Who is Affected Designers, Building Officials, electrical safety inspectors. Objective-Based Analysis Provisions deleted Provision Objective Functional Statement Building and Development Branch © Copyright Queen's Printer for Ontario 2011 Page 2 of 2 Issued January 2011