Wiring Diagrams - ExpressOverstock.com

advertisement
Wiring Diagrams
ACCESSORY
ELECTRIC
HEATERS
FAN COIL MODEL
WITH FACTORY INSTALLED HEAT
PF1MNA018,024,030,036,005AAAA
PF1MNA018,024,030,036,008AAAA
PF1MNA018,024,030,036,010AAAA
FIELD INSTALLED
HEATER MODEL
KFCEH0401N03
KFCEH0501N05
KFCEH0601C05
KFCEH0801N08
KFCEH1001C08
KFCEH1409N09*
KFCEH0901N10
KFCEH1501F15*
KFCEH1701C15*
KFCEH1801F20*
KFCEH1901C20*
KFCEH1601315
KFCEH2001318
KFCEH2101F24*
KFCEH2201F30*
Fan
Coils
FACTORY INSTALLED
HEATER MODEL
MKFECH0501N05
MKFECH0801N08
MKFECH0901N09
NOM KW 240 V
NOMINAL KW
DESCRIPTION
5 Non-fused
8 Non-fused
10 Non-fused
LABEL DIAGRAM
Fig. 1
HEATER INSTALLED
IN PF1MNA018,
024, 030, 036, 042, 048, 060
FAN COIL
HEATER INSTALLED
IN PF1MNA071
FAN COIL
Fig. 1
Fig. 2
Fig. 3†
Fig. 1
Fig. 4†
Fig. 2
Fig. 5†
Fig. 6†
Fig. 7†
Fig. 8†
Fig. 9
Fig. 11
Fig. 10
Fig. 12
Single Phase Fig. 13
Three Phase Fig. 15
Single Phase Fig. 14
Three Phase Fig. 16
3 Non-Fused
5 Non-Fused
5 Circuit Breaker
8 Non-Fused
8 Circuit Breaker
9 Non-Fused 1 or 3-Phase
10 Non-Fused
15 Fused Dual Circuit
15 Circuit Breaker Dual Circuit
20 Fused Dual Circuit
20 Circuit Breaker Dual Circuit
15 Non-Fused 3-Phase Only
18 Non-Fused 3-Phase Only
24 Fused 1 or 3 Phase
Single or Multiple Circuit
30 Fused 1 or 3 Phase
Single or Multiple Circuit
† For heater serial numbers after 1900A56372
FIELD INSTALLED
HEATER MODEL
KFDEH0801D05
KFDEH0901D75
KFDEH1001D11
ACCESSORY SMART
HEAT PACKAGES
KFCEH0101H10
KFCEH0201H15
KFCEH0301H20
NOM KW 240 V
HEATER INSTALLED
IN FF1D FAN COIL
5 Disconnect
7.5 Disconnect
11 Disconnect
Fig. 17
NOM KW AT 240 V
LABEL DIAGRAM
10 Smart Heat
15 Smart Heat
20 Smart Heat
Fig. 18
Fig. 19
Fig. 20
FAN COIL WITH COOLING ONLY CONTROL
PF1MN018,024,030,036,042,048,060,070000AAAA
PF1MN071000AAAA
Form:
WD-PF1M-01
Cancels:
New
Printed in U.S.A.
LABEL DIAGRAM
Fig. 21
Fig. 22
6-01
Catalog No.
53PF-1M2
CAUTION:
THIS COMPARTMENT MUST BE CLOSED EXCEPT FOR SERVICING
NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING
150V TO GROUND
BLOWER MOTOR
ROTATION
ATTENTION:
NE CONVIENT PAS AUX INSTALLATIONS DE PLUS DE
150 V A LA TERRE
SCHEMATIC DIAGRAM
FIELD POWER WIRING
HTR1
HTR2
LS1
OR
L1
COMPONENT ARRANGEMENT
DISCONNECT PER NEC
SEE RATING PLATE
FOR VOLTS & HERTZ
SEE NOTE #1
OR
OR
CB
L2
DISC
DISC
L1
OR
LS2
L2
R1
CB
COM
GND
SYSTEM TRANSFORMER: 40.0VA
FAN COIL/HEATER: 8.4VA
REMAINING VA AVAILABLE: 31.6VA
TRAN
RED
24 V
YEL
208 V
230 V
BRN
HTR2
LS2
BLK
YEL
LS1 HTR1
BLK
BLK
6
8
RELAY 1
2
4
BLU
RELAY 1
BLK
BLK
6
2
8
4
1
YEL
11
11
9
9
REC
BLK
BLU
ORN
BLU
L2
VIO
3
3
7
7
0
C
T1
R
G
REC
RELAY 1
22 VDC COIL
PLUG
6 1
6 1
2
2
L1
NC
CB
4
4
PCB
60A 60A
NO
FR
RECP
BLK
F
SPT
BRN
COM
HI
MED
LO
BRN
YEL
BLK
BLU
RED
C
RED
TRAN
GRN/YEL
GND
W2
BLU-MED
BLK-HI
GRN/YEL-GND
R
W WHT
BARRIER
BRN
INDOOR
THERMOSTAT
G
SEE NOTE #7
OUTDOOR
UNIT
NOTES:
1. USE COPPER WIRE (75°C MIN) ONLY BETWEEN DISCONNECT SWITCH AND UNIT.
2. TO BE WIRED IN ACCORDANCE WITH NEC AND LOCAL CODES.
3. IF ANY OF THE ORIGINAL WIRE, AS SUPPLIED, MUST BE REPLACED, USE THE SAME OR EQUIVALENT
TYPE WIRE.
4. REPLACE LOW VOLTAGE FUSE WITH NO GREATER THAN 5 AMP FUSE.
5. (3) SPEED MOTOR SHOWN. OPTIONAL (2) SPEED MOTOR USES HI (BLK) AND LOW (BLU OR RED).
6. SMALLER HEATERS WILL HAVE FEWER COMPONENTS.
7. CONNECT R TO R, G TO G, ETC., SEE OUTDOOR INSTRUCTION
324988-101 REV. A
FOR DETAILS.
FM
BRN
BRN
YEL-COM
CAP
SEE NOTE #5 FAN MOTOR THERMALLY PROTECTED
LEGEND
BRN
FM
GRY
230V
GND
VIO
208
V
BRN
BLU
YEL
COM
CAP
RED-LOW
WHT
PCB
BLK
YEL
GRY
RED
RED
G
R
F
T1
C
NO
FR
BRN
NC
SPT
CAP
CB
COM
F
FM
FR
FU
GND
SPT
CAPACITOR
CIRCUIT BREAKER
COMMON
LOW VOLTAGE FUSE
FAN MOTOR
FIELD POWER WIRING
PCB FAN RELAY
LINE FUSE
EQUIPMENT GROUND
FAN SPEED TAP
LOCATION
HTR
LS
HEATER
LIMIT SWITCH
MARKED TERMINAL
PLUG AND RECEPTACLE
PCB
PRINTED CIRCUIT BOARD
REC
RECTIFIER
R
TRAN
RELAY
TRANSFORMER
UNMARKED TERMINAL
MINIMUM MOTOR SPEED SELECTION
018 024 030 036 042 048 060 070
FAN COIL SIZE
MOTOR SPEED ONE HTR LO LO LO LO -- -- -- -MOTOR SPEED TWO HTR LO LO LO LO LO LO LO LO
A00168
Fig. 1—Label Wiring 324988-101
—2—
THIS COMPARTMENT MUST BE CLOSED EXCEPT FOR SERVICING
CAUTION:
NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING 150V TO GROUND
BLOWER MOTOR
ROTATION
ATTENTION:
NE CONVIENT PAS AUX INSTALLATIONS DE PLUS DE 150 V A LA TERRE
LEGEND
COM
F1
ICM
SCHEMATIC DIAGRAM SINGLE SUPPLY CIRCUIT
SEE RATING PLATE
FOR VOLTS & HERTZ
DISCONNECT PER NEC
SEE NOTE #1
OR
OR
L1
OR
CB
OR
L2
DISC
DISC
L1
FU
GND
HVTB
HTR
REC
L2
CB
HTR2
LS2
LS1 HTR1
BLK
BLK
6
RELAY 1
FIELD
POWER
WIRING
L1
BLK
9
11
208/240VAC
9
11
RELAY 1
22 VDC COIL
BLK
REC
BLU
BLK
7
7
11
11
3
3
7
3 2
24VAC
3 2
7
PLUG 2
4
24VAC
RECP 2
4
6 1
6 1
COMPONENT ARRANGEMENT
VIO
ORN
HTR1
PLUG
9
9
L2
YEL
BLK
2
4
BLU
YEL
PCB
TRAN
RECP
CB
R
TDR
LIMIT SWITCH
MARKED TERMINAL
PLUG AND RECEPTACLE
PRINTED CIRCUIT BOARD
TRANSFORMER
RECEPTACLE
CIRCUIT BREAKER
RELAY
TIME DELAY RECTIFIER
FIELD POWER WIRING
BLK
8
YEL
LS
COOLING CONTROL ONLY
GND
YEL
COMMON
LOW VOLTAGE FUSE
FAN MOTOR
FIELD POWER WIRING
LINE FUSE
EQUIPMENT GROUND
HIGH VOLTAGE TERM BLOCK
HEATER
RECTIFIER
2
2
6 1
6 1
LS1
LS2
24 V
RECP 2
BRN
COM
HTR2
RED
4
4
TRAN
FIELD POWER WIRING
208 V
BRN
230 V
R1
YEL
Com 208V
BLK
230V
SEC1
SEC2
AUX HEAT KW/CFM
KW
CFM
R
W
1
VIO
F1
BRN
AC/HP SIZE
12
9
8
7
VI RE BR OR
O
D N N
10
BLU
6
2
1
ORN
BLK
NOM
G
HI
LO
BLK
YEL
PLUG 3
O
0
90
ON/OFF DELAY
30
0
90
0
HI
C
WHT
AUX1 HUM1
CONTINUOUS FAN
LO
MED
HI
5 4 3 2 1
BLK WHT VIO
BLK BLU ORN BRN
2
SEC1 SEC2
PCB
D
H
4
8
R
0
1
F1
REC
W
1
W2
Y
1
Y/Y
2
G
O
C
PL1
GND
HEATER / MOTOR
24 VAC
1
ICM
GRY
HEATER / MOTOR
16 15 14 13 12 11 10 9
8 7 6 5 4 3 2 1
6
AUX 2 HUM2
YEL
PL1
GRN WHT VIO ORN
YEL RED GRY
60A 60A
YEL
GRN/YEL
PLUG 1
L1
RELAY 1
Y/Y
2
HP-EFF
AC/HP CFM ADJUST
BLK
GR Y B W
N EL LK HT
3
HP-COMFORT
ORN
WHT
5
4
AC
L2
CB
Y
1
SYSTEM TYPE
11
SYSTEM TRANSFORMER: 40.0VA
FAN COIL/HEATER: 4.8VA
REMAINING VA AVAILABLE: 35.2VA
W
2
BLU
GR
Y
VIO
RED VIO
D
H
OUTDOOR UNIT
TRAN
PCB
INDOOR THERMOSTAT
RED
BRN
GND
NOTES:
1.
RECP 3
2.
3.
4.
ICM
RECP 4
GRY
PLUG 4
5.
6.
7.
8.
USE COPPER WIRE (75*C MIN) ONLY BETWEEN DISCONNECT
SWITCH AND UNIT.
TO BE WIRED IN ACCORDANCE WITH NEC AND LOCAL CODES.
TRANSFORMER PRIMARY LEADS, BLUE 208V, RED 230V.
IF ANY OF THE ORIGINAL WIRE, AS SUPPLIED, MUST BE REPLACED,
USE THE SAME OR EQUIVALENT TYPE WIRE.
REPLACE LOW VOLTAGE FUSE WITH NO GREATER THAN 5 AMP FUSE.
DUAL CIRCUIT WIRING SHOWN.
USE 60 AMP CLASS K FUSES ONLY, FOR REPLACEMENT.
CONNECT R TO R, G TO G, ETC., SEE OUTDOOR INSTRUCTION FOR
DETAILS.
326001-101 REV. B
LABEL (2)
SEE INSTRUCTION FOR INSTALLATION
A00183
Fig. 2—Label Wiring 326001-101
—3—
CAUTION:
THIS COMPARTMENT MUST BE CLOSED EXCEPT FOR SERVICING
NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING
150V TO GROUND
BLOWER MOTOR
ROTATION
ATTENTION:
NE CONVIENT PAS AUX INSTALLATIONS DE PLUS DE 150
V A LA TERRE
SCHEMATIC DIAGRAM SINGLE SUPPLY CIRCUIT
SEE RATING PLATE
FOR VOLTS & HERTZ
GND
COMPONENT ARRANGEMENT
DISCONNECT PER NEC
HTR1
SEE NOTE #1
BLU
L1
LS1
YEL
YEL
L3
HTR1 BLK
YEL
LS3
BLK
BLU
REC
COM
BRN
HI
MED
YEL
BLK
BLU
LO
RED
NOTE:
NOTES:
COM 208V 230V
BRN
RED
TRAN
FM
GRN/YEL
GND
BRN
4
230 V
0
6
2
8
4
C
T1
R
G
4
4
0
1
F
NC
REC
GRY
RED
PCB
NO
FR
SPT
BRN
W2 W3
E
VIO
YEL
CAP
BLK
PCB
BRN
RELAY 2
BLU
F
T1
C
YEL
8
208 V
BRN
6 1
6 1
WHT
G
R
NO
FR
24 V
REC
BRN
NC
SPT
2
2
BLK
RED
BLU
3
3
BRN
RECP
7
7
2
RED-LOW
GRY
11
11
6
1
REC
RED
VIO
ORN
BLK
RED
RELAY 1
PLUG
9
9
R2
COM
SYSTEM TRANSFORMER: 40.0VA
FAN COIL/HEATER: 15.2VA
REMAINING VA AVAILABLE: 24.8VA
RELAY 1
22 VDC COIL
BLU
LS2
R1
RELAY 2
22 VDC COIL
YEL
LS3
BLU
RELAY 2
6
8
RELAY
1
HTR3 BLK
2
4
YEL
HTR2
BLK
2
4
BLU
LS2 HTR2 BLU
BLU
LS1
L2
RELAY 2
HTR3
TRAN
FIELD POWER WIRING
GND
C
R
W2
G
WHT SEE NOTE #7
BARRIER SEE NOTE #6
INDOOR
THERMOSTAT
OUTDOOR
UNIT
FOR 3 PHASE WIRING
Denotes wire to be moved for 3 phase conversion. Dashed wire (- - -) indicates wiring after conversion.
1. Disconnect BLUE wire from limit switch 3(LS3), cut, strip, and connect to field wire L3.
2. Disconnect YELLOW wire from LS1 and connect to LS3.
3. Disconnect BLUE wire from relay 2 terminal 2 and connect to LS1.
1. USE COPPER WIRE (75°C MIN) ONLY BETWEEN DISCONNECT SWITCH AND UNIT.
2. TO BE WIRED IN ACCORDANCE WITH NEC AND LOCAL CODES.
3. IF ANY OF THE ORIGINAL WIRE, AS SUPPLIED, MUST BE REPLACED, USE THE SAME OR EQUIVALENT
TYPE WIRE.
4. REPLACE LOW VOLTAGE FUSE WITH NO GREATER THAN 5 AMP FUSE.
5. (3) SPEED MOTOR SHOWN. OPTIONAL (2) SPEED MOTOR USES HI (BLK) AND LOW (BLU OR RED).
6. CONNECT R TO R, G TO G, ETC., SEE OUTDOOR INSTRUCTION FOR DETAILS.
7. IF WIRE CRIMP IS REMOVED AN EMERGENCY HEAT RELAY IS REQUIRED.
(SEE OUTDOOR-THERMOSTAT INSTRUCTIONS)
SEE NOTE #5
BLU-MED
BLK-HI
GRN/YEL-GND
FM
BRN
BRN
YEL-COM
CAP
FAN MOTOR THERMALLY PROTECTED
LEGEND
CAP
COM
CAPACITOR
COMMON
F
FM
LOW VOLTAGE FUSE
FAN MOTOR
FIELD POWER WIRING
PCB FAN RELAY
EQUIPMENT GROUND
FAN SPEED TAP
LOCATION
FR
GND
SPT
R
RELAY
HTR
LS
HEATER
LIMIT SWITCH
MARKED TERMINAL
PLUG & RECEPTACLE
PCB
PRINTED CIRCUIT BOARD
REC RECTIFIER
R
RELAY
TRAN TRANSFORMER
UNMARKED TERMINAL
MINIMUM CFM / MOTOR SPEED SELECTION
FAN COIL SIZE
018 024 030 036 042 048 060 070
MOTOR SPEED AT 9 KW -- LO LO LO LO LO LO LO
325650-101 REV. A
A00175
Fig. 3—Label Wiring 325650-101
—4—
CAUTION:
THIS COMPARTMENT MUST BE CLOSED EXCEPT FOR SERVICING
NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING
150V TO GROUND
BLOWER MOTOR
ROTATION
ATTENTION:
NE CONVIENT PAS AUX INSTALLATIONS DE PLUS DE 150
V A LA TERRE
LEGEND
SCHEMATIC DIAGRAM SINGLE SUPPLY CIRCUIT
SEE RATING PLATE
FOR VOLTS & HERTZ
GND
DISCONNECT PER NEC
FU
GND
HVTB
HTR
REC
SEE NOTE #1
BLU
L3
L1
LS1
YEL
YEL
YEL
RELAY 2
BLK
2
4
BLU
RELAY 2
6
8
RELAY 1
HTR3 BLK
2
4
LS3
YEL
RELAY 2
22 VDC COIL
REC
9
9
BLK
7
7
11
11
3
3
RED
2
2
6 1
6 1
RED
BRN
YEL
Com 208V
BLK
230V
VIO
F1
9
8
7
GR
Y
BLU
VI RE BR OR
O
D N N
10
6
2
1
HP-COMFORT
HP-EFF
ORN
BLK
NOM
LO
G
HI
BLK
YEL
PLUG 3
O
ON/OFF DELAY
0
30
0
90
90
0
HI
5 4 3 2 1
AUX1 HUM1
GND
BLK WHT VIO
BLK BLU ORN BRN
208 V
230 V
BRN
FU4
FU2
FU1
FU3
8
PCB
D
H
4
R
0
1
F1
W
1
REC
W2
RELAY 2
Y
1
Y/Y
2
G
6
2
8
4
O
C
0
1
TDR
24 VAC
1
PL1
16 15 14 13 12 11 10 9
8 7 6 5 4 3 2 1
SEC1 SEC2
AUX 2 HUM2
YEL
R2
2
6
YEL
GRN/YEL
PLUG 1
GRN WHT VIO ORN
YEL RED GRY
C
WHT
CONTINUOUS FAN
LO
MED
HI
24 V
RELAY 1
Y/Y
2
AC/HP CFM ADJUST
BLK
GR Y BL W
N EL K HT
3
AC
COM
RED
L4
L2
L1
L3
L4 L3 L2 L1
CB2
CB1
60A 60A 60A 60A
Y
1
ORN
WHT
5
4
BLU
6 1
PLUG 2
4
24VAC
RECP 2
4
HTR2
LS2
R1
W
2
SYSTEM TYPE
11
RED VIO
R
W
1
BRN
VIO
HTR3
LS3
D
H
AC/HP SIZE
12
HTR1
LS1
AUX HEAT KW/CFM
6 1
COMPONENT ARRANGEMENT
RECP 2
SEC2
KW
CFM
3 2
24VAC
3 2
7
4
4
PCB
SEC1
7
11
208/240VAC
11
9
BRN
BRN
TRAN
BLK
YEL
OUTDOOR UNIT
PLUG
REC
VIO
ORN
SYSTEM TRANSFORMER: 40.0VA
FAN COIL/HEATER: 6.5VA
REMAINING VA AVAILABLE: 33.5VA
L2
9
INDOOR THERMOSTAT
BLU
FIELD
POWER
WIRING
L1
BLK
YEL
LIMIT SWITCH
MARKED TERMINAL
PLUG AND RECEPTACLE
PCB
PRINTED CIRCUIT BOARD
TRAN TRANSFORMER
RECP RECEPTACLE
CB
CIRCUIT BREAKER
R
RELAY
TDR
TIME DELAY RECTIFIER
COOLING CONTROL ONLY
RELAY 1
22 VDC COIL
BLU
LS
FIELD POWER WIRING
BLU
HTR2 BLU
LS2
BLU
L2
HTR1 BLK
COMMON
LOW VOLTAGE FUSE
FAN MOTOR
FIELD POWER WIRING
LINE FUSE
EQUIPMENT GROUND
HIGH VOLTAGE TERM BLOCK
HEATER
RECTIFIER
TRAN
FIELD POWER WIRING
COM
F1
ICM
PL1
GRY
HEATER / MOTOR
HEATER / MOTOR
ICM
RECP 3
GND
ICM
NOTES:
1.
RECP 4
GRY
PLUG 4
FOR 3 PHASE WIRING
Denotes wire to be moved for 3 phase conversion. Dashed wire (- - -) indicates wiring after conversion.
1. Disconnect BLUE wire from limit switch 3(LS3), cut, strip, and connect to field wire L3.
2. Disconnect YELLOW wire from LS1 and connect to LS3.
3. Disconnect BLUE wire from relay 2 terminal 2 and connect to LS1.
2.
3.
4.
5.
6.
7.
8.
USE COPPER WIRE (75*C MIN) ONLY BETWEEN DISCONNECT
SWITCH AND UNIT.
TO BE WIRED IN ACCORDANCE WITH NEC AND LOCAL CODES.
TRANSFORMER PRIMARY LEADS, BLUE 208V, RED 230V.
IF ANY OF THE ORIGINAL WIRE, AS SUPPLIED, MUST BE REPLACED,
USE THE SAME OR EQUIVALENT TYPE WIRE.
REPLACE LOW VOLTAGE FUSE WITH NO GREATER THAN 5 AMP FUSE.
DUAL CIRCUIT WIRING SHOWN.
USE 60 AMP CLASS K FUSES ONLY, FOR REPLACEMENT.
CONNECT R TO R, G TO G, ETC., SEE OUTDOOR INSTRUCTION FOR
DETAILS.
325796-101 REV. B
LABEL (2)
SEE INSTRUCTION FOR INSTALLATION
A00179
Fig. 4—Label Wiring 325796-101
—5—
CAUTION:
THIS COMPARTMENT MUST BE CLOSED EXCEPT FOR SERVICING
NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING
150V TO GROUND
BLOWER MOTOR
ROTATION
ATTENTION:
NE CONVIENT PAS AUX INSTALLATIONS DE PLUS DE 150
V A LA TERRE
(LADDER FORMAT)
COMPONENT ARRANGEMENT
DISCONNECT PER NEC
SEE RATING PLATE
FOR VOLTS & HERTZ
HTR1
LS1
SEE NOTE #1
L4
L3
CB1
HTR2
LS2
LS3
L2
CB2
CB1
SYSTEM TRANSFORMER: 40.0VA
FAN COIL/HEATER: 11.8VA
REMAINING VA AVAILABLE: 28.2VA
COM
RED
24 V
RELAY 1
YEL
YEL
LS2
HTR2
BLK
YEL
LS1
LS3
HTR1
HTR3
BLK
BLK
YEL
RELAY 2
4
2
RELAY 2
6
4
RELAY 1
2
11
11
9
9
BLU
RELAY 2
22 VDC COIL
7
7
3
3
VIO
2
2
RED
BRN
6 1
6 1
COM
HI
MED
LO
BRN
YEL
BLK
BLU
RED
RED
TRAN
FM
GRN/YEL
GND
BRN
L2
PCB
L1
CB2
GRY
VIO
BLU
SEE NOTE #6
NO
FR
SPT
60A 60A 60A 60A
GND
BLU-MED
BLK-HI
GRN/YEL-GND
FM
BRN
BRN
YEL-COM
CAP
FAN MOTOR THERMALLY PROTECTED
LEGEND
C
R
WHT
W
BARRIER
G
SEE NOTE #8
INDOOR
THERMOSTAT
SEE NOTE #7
OUTDOOR
UNIT
NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
L3
CB1
COM 208V 230V
BRN
F
NC
L4
W2
BRN
WHT
YEL
CAP
C
T1
R
G
RED-LOW
RED
PCB
BLK
YEL
GND
0
GRY
RED
BRN
FR
4
PLUG
4
4
BLK
G
R
F
T1
C
8
FU4
FU2
FU1
FU3
L4
L2
L1
L3
TDR
RECP
NO
2
1
BRN
SPT
6
230 V
BLK
ORN
NC
4
0
BLK
R EC
BLK
8
208 V
BRN
REC
RELAY 2
TDR
BLU
2
1
BLK
8
BLU
6
BLK
RELAY 1
22 VDC COIL
YEL
R2
R1
INTERNAL PROTECTION
MAY BE EITHER FUSES
OR CIRCUIT BREAKERS
CB2
L4
L2
FU2
FU3
L1
FU4
L3
FU1
GND
L1
HTR3
TRAN
SCHEMATIC DIAGRAM
FIELD POWER WIRING
Use copper wire (75°C min.) only between disconnect switch and unit.
To be wired in accordance with N.E.C. and local codes.
If any of the original wire, as supplied, must be replaced, use the same or equivalent type wire.
Replace low voltage fuse with no greater than 5 amp fuse.
Use 60 amp class K fuses only, for replacement.
(3) speed motor shown. Optional (2) speed motor uses HI (BLK) and LOW (BLU or RED).
Connect R to R, G to G, etc., see outdoor instruction for details.
If wire crimp is removed an emergency heat relay is required. (See outdoor-thermostat instructions).
CB
CAP
COM
F
FM
FR
FU
GND
SPT
CIRCUIT BREAKER
CAPACITOR
COMMON
LOW VOLTAGE FUSE
FAN MOTOR
FIELD POWER WIRING
PCB FAN RELAY
LINE FUSE
EQUIPMENT GROUND
FAN SPEED TAP
LOCATION
HTR
LS
PCB
REC
R
TRAN
TDR
HEATER
LIMIT SWITCH
MARKED TERMINAL
PLUG AND RECEPTACLE
PRINTED CIRCUIT BOARD
RECTIFIER
RELAY
TRANSFORMER
UNMARKED TERMINAL
TIME DELAY
RECTIFIER
MINIMUM MOTOR SPEED SELECTION
018 024 030 036 042 048 060 070
FAN COIL SIZE
MOTOR SPEED AT 15 KW -- MED LO LO LO LO LO LO
325651-101 REV. A
A00176
Fig. 5—Label Wiring 325651-101
—6—
CAUTION:
THIS COMPARTMENT MUST BE CLOSED EXCEPT FOR SERVICING
BLOWER MOTOR
ROTATION
NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING 150V TO GROUND
ATTENTION:
NE CONVIENT PAS AUX INSTALLATIONS DE PLUS DE 150 V A LA TERRE
SCHEMATIC DIAGRAM SINGLE SUPPLY CIRCUIT
SEE RATING PLATE
DISCONNECT PER NEC
FOR VOLTS & HERTZ
SEE NOTE #1
LEGEND
L1
FU3
CB1
GND
L3
L4
CB2
INTERNAL PROTECTION
MAY BE EITHER FUSES
OR CIRCUIT BREAKERS
CB2
L2
CB1
L4
L2
FU2
L3
FU4
L1
FU1
FIELD POWER WIRING
COM
F1
ICM
FU
GND
HVTB
HTR
REC
COMMON
LOW VOLTAGE FUSE
FAN MOTOR
FIELD POWER WIRING
LINE FUSE
EQUIPMENT GROUND
HIGH VOLTAGE TERM BLOCK
HEATER
RECTIFIER
LS
LIMIT SWITCH
MARKED TERMINAL
PLUG AND RECEPTACLE
PCB
PRINTED CIRCUIT BOARD
TRAN TRANSFORMER
RECP RECEPTACLE
CB
CIRCUIT BREAKER
R
RELAY
TDR
TIME DELAY RECTIFIER
FIELD POWER WIRING
HTR2
RELAY 2
4
2
BLK
YEL
HTR1
BLK
LS3 HTR3
BLK
LS1
YEL
BLK
6
RELAY 1
2
4
YEL
BLU
FIELD
POWER
WIRING
RELAY 2
8
YEL
COOLING CONTROL ONLY
BLK
BLK
L1
L2
BLK
YEL
BLK
9
11 7
208/240VAC
11
7
9
RELAY 2
22 VDC COIL
RELAY 1
22 VDC COIL
REC
YEL
BLU
PLUG 9
9
REC
VIO
ORN
BLK
7
7
11
11
SYSTEM TRANSFORMER: 40.0VA
FAN COIL/HEATER: 6.5VA
REMAINING VA AVAILABLE: 33.5VA
3
3
RED
2
2
3 2
24VAC
3 2
COMPONENT ARRANGEMENT
HTR1
6 1
6 1
HTR3
LS1
LS3
LS2
24 V
RECP 2
SEC2
AUX HEAT KW/CFM
KW
CFM
VIO
F1
BRN
AC/HP SIZE
R2
12
11
9
8
7
VI RE BR OR
O
D N N
10
BLU
6
2
1
ORN
BLK
NOM
G
HI
LO
BLK
YEL
PLUG 3
O
0
90
ON/OFF DELAY
30
0
90
0
HI
C
WHT
AUX1 HUM1
CONTINUOUS FAN
LO
MED
HI
5 4 3 2 1
BLK WHT VIO
BLK BLU ORN BRN
PCB
D
H
4
8
R
0
1
F1
REC
W
1
W2
Y
1
Y/Y
2
G
RELAY 2
6
2
8
4
O
C
0
1
TDR
PL1
GND
HEATER / MOTOR
24 VAC
1
ICM
GRY
HEATER / MOTOR
16 15 14 13 12 11 10 9
8 7 6 5 4 3 2 1
SEC1 SEC2
AUX 2 HUM2
YEL
PL1
GRN WHT VIO ORN
YEL RED GRY
FU4
FU2
FU1
FU3
YEL
GRN/YEL
PLUG 1
230 V
2
6
Y/Y
2
HP-EFF
AC/HP CFM ADJUST
BLK
GR Y BL W
N EL K HT
3
HP-COMFORT
ORN
WHT
5
4
AC
208 V
BRN
RELAY 1
Y
1
SYSTEM TYPE
L4
L2
L1
L3
L4 L3 L2 L1
CB2
CB1
60A 60A 60A 60A
W
2
BLU
GR
Y
VIO
RED VIO
R
W
1
OUTDOOR UNIT
BLK
230V
SEC1
D
H
INDOOR THERMOSTAT
YEL
Com 208V
PCB
COM
HTR2
RED
4
4
R1
TRAN
6 1
PLUG 2
4
24VAC
RECP 2
4
BRN
BRN
RED
BRN
6 1
TRAN
LS2
GND
NOTES:
1.
RECP 3
2.
3.
4.
ICM
RECP 4
GRY
PLUG 4
5.
6.
7.
8.
USE COPPER WIRE (75*C MIN) ONLY BETWEEN DISCONNECT
SWITCH AND UNIT.
TO BE WIRED IN ACCORDANCE WITH NEC AND LOCAL CODES.
TRANSFORMER PRIMARY LEADS, BLUE 208V, RED 230V.
IF ANY OF THE ORIGINAL WIRE, AS SUPPLIED, MUST BE REPLACED,
USE THE SAME OR EQUIVALENT TYPE WIRE.
REPLACE LOW VOLTAGE FUSE WITH NO GREATER THAN 5 AMP FUSE.
DUAL CIRCUIT WIRING SHOWN.
USE 60 AMP CLASS K FUSES ONLY, FOR REPLACEMENT.
CONNECT R TO R, G TO G, ETC., SEE OUTDOOR INSTRUCTION FOR
DETAILS.
325797-101 REV. B
LABEL (2)
SEE INSTRUCTION FOR INSTALLATION
A00180
Fig. 6—Label Wiring 325797-101
—7—
CAUTION:
THIS COMPARTMENT MUST BE CLOSED EXCEPT FOR SERVICING
NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING 150V
TO GROUND
BLOWER MOTOR
ROTATION
ATTENTION:
NE CONVIENT PAS AUX INSTALLATIONS DE PLUS DE
150 V A LA TERRE
SCHEMATIC DIAGRAM
COMPONENT ARRANGEMENT
DISCONNECT PER NEC
SEE RATING PLATE
FOR VOLTS & HERTZ
SEE NOTE #1
HTR3
HTR1
CB1
GND
YEL
LS3 HTR3
BLK
LS2 HTR2
BLK
YEL
LS1 HTR1
HTR4
LS4
YEL
BLK
BLK
L4
L2
CB2
INTERNAL PROTECTION MAY
BE EITHER FUSES OR CIRCUIT
BREAKERS
YEL
YEL
L4
CB1
L2
RELAY 3
4
2
RELAY 2
4
2
RELAY 2
8
6
RELAY 1
2
4
R3
RELAY 1
BLK
6
2
8
4
1
BLK
0
6
2
RELAY 2
22 VDC COIL
BLK
8
4
0
1
TDR
RELAY 3
RELAY 1
22 VDC COIL
22 VDC COIL
RED
BRN
RED
24 V
BRN
2
8
4
C
T1
R
G
REC
REC
11
11
BLU
PCB
YEL
CO
M
CAP
HI
MED
LO
BRN
YEL
BLK
BLU
RED
BRN
GRY
RED
G
R
NO
BLK
F
T1
C
FM
GND
BRN
SEE NOTE #6
208V 230V
C R
BRN
GRN
YEL
GND
FR
TDR
W2
YEL
COM
BLK
NC
FR
4
4
PCB
0
1
VIO
SPT
3
3
7
7
BLU
RECP
BRN
VIO
6 1
2
2
6 1
WHT
9
9
ORN
RED
PLUG
BLK
GRY
BLU
GRY
BRN
YEL
RED
TRAN
BRN
W WHT
G
BARRIER
SEE NOTE #8
INDOOR
THERMOSTAT
OUTDOOR
UNIT
NOTES:
1. Use copper wire (75*C min.) only between disconnect switch and unit.
2. To be wired in accordance with N.E.C. and local codes.
3. If any of the original wire, as supplied, must be replaced, use the same or
equivalent type wire.
4. Replace low voltage fuse with no greater than 5 amp fuse.
5. Use 60 amp class K fuses only, for replacement.
6. (3) speed motor shown. Optional (2) speed motor uses HI (BLK) and LOW
(BLU or RED).
7. Connect R to R, G to G, etc., see outdoor instruction for details.
8. Smaller heaters will have fewer components.
325652-101 REV. A
208 V
230 V
GND
TDR
RELAY 3
6
R2
COM
FU4
FU2
FU1
FU3
L4
L2
L1
L3
BLK
BLU
R1
SYSTEM TRANSFORMER: 40.0VA
FAN COIL/HEATER: 11.8VA
REMAINING VA AVAILABLE: 28.2VA
REC
RELAY 2
BLK
LS2
HTR4
L3
CB2
FU2
FU3
FU1
L1
FU4
L3
L1
HTR2
LS 3
& 4
LS1
TRAN
FIELD POWER WIRING
F
NC
NO
L4 L3 L2 L1
CB1
CB2
60A 60A 60A 60A
SPT
RED-LOW
BLU-MED
BLK-HI
FM
BRN
BRN
YEL-COM
CAP
GRN/YEL-GND
FAN MOTOR THERMALLY PROTECTED
LEGEND
HTR
LS
HEATER
LIMIT SWITCH
MARKED TERMINAL
PLUG AND
RECEPTACLE
PRINTED CIRCUIT
PCB
BOARD
RECTIFIER
REC
R
RELAY
TRAN TRANSFORMER
UNMARKED
TERMINAL
TIME DELAY
TDR
RECTIFIER
MINIMUM MOTOR SPEED SELECTION
CB CIRCUIT BREAKER
CAP CAPACITOR
COM COMMON
LOW VOLTAGE
FUSE
F
FM FAN MOTOR
FIELD POWER
WIRING
FR PCB FAN RELAY
FU LINE FUSE
GND EQUIPMENT GROUND
SPT FAN SPEED TAP
LOCATION
FAN COIL SIZE
MOTOR SPEED AT 20 KW
018 024 030 036 042 048 060 070
--
-- MED LO LO LO LO LO
A00177
Fig. 7—Label Wiring 325652-101
—8—
CAUTION:
THIS COMPARTMENT MUST BE CLOSED EXCEPT FOR SERVICING
NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING
150V TO GROUND
BLOWER MOTOR
ROTATI ON
ATTENTION:
NE CONVIENT PAS AUX INSTALLATIONS DE PLUS DE 150
V A LA TERRE
LEGEND
20KW 1PH SCHEMATI C DIAGRAM
L3
CB2
GND
LS2 HTR2 BLK
YEL
LS1 HTR1 BLK
HTR4
LS4
YEL
L4
L2
CB1
RELAY 3
4
2
RELAY 2
4
2
RELAY 2
6
8
RELAY 1
2
4
LS3 HTR3 BLK
YEL
YEL
CB2
INTERNAL PROTECTION MAY
BE EITHER FUSES OR CIRCUIT
BREAKERS
YEL
L2
L4
BLK
FU
GND
HVTB
HTR
REC
BLK
BLK
RELAY 2
22 VDC COIL
BLK
L1
BRN
PLUG 2
4
4
6 1
6 1
YEL
Com 208V
BLK
230V
PCB
SEC1
AUX HEAT KW/CFM
KW
CFM
VIO
BRN
11
9
8
7
VI RE BR OR
O
D N N
10
BLU
6
2
1
ORN
BLK
NOM
G
HI
LO
BLK
YEL
PLUG 3
O
0
90
ON/OFF DELAY
30
0
90
0
HI
C
WHT
AUX1 HUM1
CONTINUOUS FAN
LO
MED
HI
5 4 3 2 1
YEL
BLK WHT VIO
BLK BLU ORN BRN
230 V
FU4
FU2
FU1
FU3
2
8
PCB
D
H
4
R
0
1
F1
REC
RELAY 2
6
2
8
4
Y
1
Y/Y
2
G
O
0
1
C
TDR
RELAY 3
6
2
8
4
W
1
W2
PL1
GND
24 VAC
0
1
1
HEATER / MOTOR
ICM
REC
GRY
HEATER / MOTOR
16 15 14 13 12 11 10 9
8 7 6 5 4 3 2 1
L4
L2
L1
L3
208 V
BRN
AUX 2 HUM2
PL1
GRN WHT VIO ORN
YEL RED GRY
R2
SEC1 SEC2
YEL
GRN/YEL
PLUG 1
6
Y/Y
2
HP-EFF
AC/HP CFM ADJUST
BLK
GR Y BL W
N EL K HT
3
HP-COMFORT
ORN
WHT
5
4
AC
R1
24 V
RELAY 1
Y
1
SYSTEM TYPE
PLUG 2
4
24VAC
RECP 2
4
COM
R3
L4 L3 L2 L1
CB2
CB1
60A 60A 60A 60A
W
2
BLU
GR
Y
12
RED VIO
F1
AC/HP SIZE
VIO
R
W
1
6 1
RED
LS2
D
H
SEC2
6 1
HTR2
LS 3
& 4
LS1
RECP 2
FU3
TRAN
HTR3
HTR1
HTR4
2
2
GRY
3 2
24VAC
3 2
COMPONENT ARRANGEMENT
OUTDOOR UNIT
3
3
RELAY 3
22 VDC COIL
BRN
BRN
RED
BRN
BLK
REC
REC
VIO
ORN
7
7
11
11
L2
11 7
208/240VAC
11 7
9
INDOOR THERMOSTAT
9
9
RED
SYSTEM TRANSFORMER: 40.0VA
FAN COIL/HEATER: 8.2VA
REMAINING VA AVAILABLE: 31.8VA
9
TDR
BLK
FIELD
POWER
WIRING
YEL
RELAY 1
22 VDC COIL
BLU
LIMIT SWITCH
MARKED TERMINAL
PLUG AND RECEPTACLE
PCB
PRINTED CIRCUIT BOARD
TRAN TRANSFORMER
RECP RECEPTACLE
CB
CIRCUIT BREAKER
R
RELAY
TDR
TIME DELAY RECTIFIER
FIELD POWER WIRING
BLK
YEL
LS
COOLING CONTROL ONLY
BLK
BLU
YEL
COMMON
LOW VOLTAGE FUSE
FAN MOTOR
FIELD POWER WIRING
LINE FUSE
EQUIPMENT GROUND
HIGH VOLT AGE TERM BLOCK
HEATER
RECTIFIER
TRAN
FU1
L1
CB1
FU2
L3
L1
COM
F1
ICM
DISCONNECT PER NEC
SEE RATING PLATE
FOR VOLTS & HERTZ
SEE NOTE #1
FU4
FIELD POWER WIRING
GND
NOTES:
1.
RECP 3
2.
3.
4.
ICM
RECP 4
GRY
PLUG 4
5.
6.
7.
8.
USE COPPER WIRE (75*C MIN) ONLY BETWEEN DISCONNECT
SWITCH AND UNIT.
TO BE WIRED IN ACCORDANCE WITH NEC AND LOCAL CODES.
TRANSFORMER PRIMARY LEADS, BLUE 208V, RED 230V.
IF ANY OF THE ORIGINAL WIRE, AS SUPPLIED, MUST BE REPLACED,
USE THE SAME OR EQUIVALENT TYPE WIRE.
REPLACE LOW VOLTAGE FUSE WITH NO GREATER THAN 5 AMP FUSE.
DUAL CIRCUIT WIRING SHOWN.
USE 60 AMP CLASS K FUSES ONLY, FOR REPLACEMENT.
CONNECT R TO R, G TO G, ETC., SEE OUTDOOR INSTRUCTION FOR
DETAILS.
325653-101 REV. B
LABEL (2)
SEE INSTRUCTION FOR INSTALLATION
A00178
Fig. 8—Label Wiring 325653-101
—9—
CAUTION:
THIS COMPARTMENT MUST BE CLOSED EXCEPT FOR SERVICING
NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING
150V TO GROUND
BLOWER MOTOR
ROTATION
ATTENTION:
NE CONVIENT PAS AUX INSTALLATIONS DE PLUS DE
150 V A LA TERRE
SCHEMATIC DIAGRAM SINGLE SUPPLY CIRCUIT
SEE RATING PLATE
FOR VOLTS & HERTZ
SEE NOTE #1
COMPONENT ARRANGEMENT
DISCONNECT PER NEC
HTR1
GND
LS1
L3
L1
YEL
RELAY 2
HTR3 BLK
6
8
R1
BLK
HTR1 BLK
LS1
BLU
2
4
4
RELAY 1
BLK
2
RELAY 2
22 VDC COIL
RELAY 1
22 VDC COIL
BLU
11
11
9
9
BL
U
RECP
SPT
7
7
3
3
TDR
2
2
FR
BRN
4
0
6
2
8
4
C
T1
R
G
4
4
BRN
NO
8
YEL
CO
M
CAP
COM
HI
MED
LO
BRN
YEL
BLK
BLU
BRN
NC
TDR
PCB
FR
E
VIO
GRY
W3
BLU
WHT
RED
W2
RED-LOW
208V 230V
C
RED
TRAN
BRN
FM
BRN
BRN
T1
C
BLK
PCB
GRN/YEL
GND
R
GND
W2
G
WHT SEE NOTE #7
BARRIER SEE NOTE #6
INDOOR
THERMOSTAT
BLU-MED
BLK-HI
GRN/YEL-GND
FM
N
O
SPT
BRN
BRN
YEL-COM
CAP
SEE NOTE #5
FAN MOTOR THERMALLY PROTECTED
LEGEND
OUTDOOR
UNIT
RED
NOTES:
1. USE COPPER WIRE (75°C MIN) ONLY BETWEEN DISCONNECT SWITCH AND UNIT.
2. TO BE WIRED IN ACCORDANCE WITH NEC AND LOCAL CODES.
3. IF ANY OF THE ORIGINAL WIRE, AS SUPPLIED, MUST BE REPLACED, USE THE SAME OR EQUIVALENT
TYPE WIRE.
4. REPLACE LOW VOLTAGE FUSE WITH NO GREATER THAN 5 AMP FUSE.
5. (3) SPEED MOTOR SHOWN. OPTIONAL (2) SPEED MOTOR USES HI (BLK) AND LOW (BLU OR RED).
6. CONNECT R TO R, G TO G, ETC., SEE OUTDOOR INSTRUCTION FOR DETAILS.
7. IF WIRE CRIMP IS REMOVED AN EMERGENCY HEAT RELAY IS REQUIRED.
(SEE OUTDOOR-THERMOSTAT INSTRUCTIONS)
F
0
1
F
YEL
230 V
RELAY 2
GRY
RED
G
R
2
208 V
BRN
REC
6 1
6 1
BLK
NC
6
1
REC
RED
VIO
ORN
BLK
24 V
BLK
BLU
YEL
RED
RELAY 1
YEL
PLUG
R2
COM
SYSTEM TRANSFORMER: 40.0VA
FAN COIL/HEATER: 15.2VA
REMAINING VA AVAILABLE: 24.8VA
RELAY 2
HTR2 BLK
LS2
LS2
LS3
BLK
BLK
BLU
YEL
HTR2
L2
BLU
LS3
HTR3
TRAN
FIELD POWER WIRING
CAP
COM
CAPACITOR
COMMON
F
FM
LOW VOLTAGE FUSE
FAN MOTOR
FIELD POWER WIRING
PCB FAN RELAY
EQUIPMENT GROUND
FAN SPEED TAP
LOCATION
FR
GND
SPT
R
RELAY
HTR
LS
HEATER
LIMIT SWITCH
MARKED TERMINAL
PLUG & RECEPTACLE
PCB PRINTED CIRCUIT BOARD
REC RECTIFIER
TDR TIME DELAY RECTIFIER
TRAN TRANSFORMER
UNMARKED TERMINAL
MINIMUM CFM / MOTOR SPEED SELECTION
018 024 030 036 042 048 060 070
FAN COIL SIZE
MOTOR SPEED AT 15 KW -- -- -- LO LO LO LO LO
324995-101 REV. A
A00174
Fig. 9—Label Wiring 324995-101
—10—
CAUTION:
THIS COMPARTMENT MUST BE CLOSED EXCEPT FOR SERVICING
NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING
150V TO GROUND
BLOWER MOTOR
ROTATION
ATTENTION:
NE CONVIENT PAS AUX INSTALLATIONS DE PLUS DE 150
V A LA TERRE
LEGEND
SCHEMATIC DIAGRAM SINGLE SUPPLY CIRCUIT
SEE RATING PLATE
FOR VOLTS & HERTZ
SEE NOTE #1
FIELD POWER WIRING
COM
F1
ICM
DISCONNECT PER NEC
GND
L3
L1
FU
GND
HVTB
HTR
REC
L2
BLU
HTR3 BLK
LS3
YEL
RELAY 2
BLK
BLK
6
8
COMMON
LOW VOLTAGE FUSE
FAN MOTOR
FIELD POWER WIRING
LINE FUSE
EQUIPMENT GROUND
HIGH VOLTAGE TERM BLOCK
HEATER
RECTIFIER
FIELD POWER WIRING
HTR1 BLK
LS1
LIMIT SWITCH
MARKED TERMINAL
PLUG AND RECEPTACLE
PCB
PRINTED CIRCUIT BOARD
TRAN TRANSFORMER
RECP RECEPTACLE
CB
CIRCUIT BREAKER
R
RELAY
TDR
TIME DELAY RECTIFIER
BLK
BLU
HTR2 BLK
LS2
YEL
LS
RELAY 2
2
4
COOLING CONTROL ONLY
BLU
RELAY 1
BLK
2
4
L1
YEL
RELAY 2
22 VDC COIL
RELAY 1
22 VDC COIL
SYSTEM TRANSFORMER: 40.0VA
FAN COIL/HEATER: 6.5VA
REMAINING VA AVAILABLE: 33.5VA
L2
BLK
YEL
BLK
BLU
FIELD
POWER
WIRING
9
11
208/240VAC
9
11
7
3 2
24VAC
3 2
7
6 1
6 1
TDR
PLUG 2
4
24VAC
RECP 2
4
COMPONENT ARRANGEMENT
3
3
2
2
BRN
HTR1
4 PLUG
4
6 1
6 1
RED
BRN
YEL
Com 208V
BLK
230V
PCB
SEC1
AUX HEAT KW/CFM
W
1
VIO
F1
BRN
AC/HP SIZE
12
9
8
7
VI RE BR OR
O
D N N
10
BLU
6
2
1
ORN
BLK
NOM
G
HI
LO
BLK
YEL
PLUG 3
O
ON/OFF DELAY
0
30
0
90
90
0
HI
C
WHT
5 4 3 2 1
LO
AUX1 HUM1
CONTINUOUS FAN
MED
HI
BLK WHT VIO
BLK BLU ORN BRN
FU4
FU2
FU1
FU3
6
2
SEC1 SEC2
PCB
D
H
4
8
R
0
1
F1
REC
W
1
W2
Y
1
Y/Y
2
G
RELAY 2
6
2
8
4
O
C
0
1
TDR
PL1
HEATER / MOTOR
24 VAC
1
ICM
GRY
HEATER / MOTOR
16 15 14 13 12 11 10 9
8 7 6 5 4 3 2 1
230 V
AUX 2 HUM2
YEL
GND
PL1
GRN WHT VIO ORN
YEL RED GRY
208 V
BRN
YEL
GRN/YEL
PLUG 1
R2
RELAY 1
Y/Y
2
HP-EFF
AC/HP CFM ADJUST
BLK
GR Y B W
N EL LK HT
3
HP-COMFORT
ORN
WHT
5
4
AC
L4
L2
L1
L3
L4 L3 L2 L1
CB2
CB1
60A 60A 60A 60A
Y
1
SYSTEM TYPE
11
24 V
R1
W
2
BLU
GR
Y
VIO
RED VIO
R
COM
RED
LS2
LS3
D
H
SEC2
KW
CFM
LS1
HTR2
RECP 2
BRN
TRAN
HTR3
TRAN
7
7
11
11
RED
OUTDOOR UNIT
9
9
REC
VIO
ORN
BLK
BLU
INDOOR THERMOSTAT
YEL
GND
NOTES:
1.
RECP 3
2.
3.
4.
ICM
RECP 4
GRY
PLUG 4
5.
6.
7.
8.
USE COPPER WIRE (75*C MIN) ONLY BETWEEN DISCONNECT
SWITCH AND UNIT.
TO BE WIRED IN ACCORDANCE WITH NEC AND LOCAL CODES.
TRANSFORMER PRIMARY LEADS, BLUE 208V, RED 230V.
IF ANY OF THE ORIGINAL WIRE, AS SUPPLIED, MUST BE REPLACED,
USE THE SAME OR EQUIVALENT TYPE WIRE.
REPLACE LOW VOLTAGE FUSE WITH NO GREATER THAN 5 AMP FUSE.
DUAL CIRCUIT WIRING SHOWN.
USE 60 AMP CLASS K FUSES ONLY, FOR REPLACEMENT.
CONNECT R TO R, G TO G, ETC., SEE OUTDOOR INSTRUCTION FOR
DETAILS.
325799-101 REV. B
LABEL (2)
SEE INSTRUCTION FOR INSTALLATION
A00182
Fig. 10—Label Wiring 325799-101
—11—
CAUTION:
THIS COMPARTMENT MUST BE CLOSED EXCEPT FOR SERVICING
NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING
150V TO GROUND
BLOWER MOTOR
ROTATION
ATTENTION:
NE CONVIENT PAS AUX INSTALLATIONS DE PLUS DE
150 V A LA TERRE
SCHEMATIC DIAGRAM SINGLE SUPPLY CIRCUIT
COMPONENT ARRANGEMENT
FIELD POWER WIRING
DISCONNECT PER NEC
HVTB
SEE RATING PLATEFOR VOLTS & HERTZ
SEE NOTE #1
BLU
L1
YEL
L2
YEL LS6
YEL LS5
HTR5 BLK
BLU LS4
HTR4 BLK
YEL LS3
HTR3 BLU
YEL LS2
HTR2 BLK
6
8
RELAY 3
4
2
8
6
L1 L2 L3
COM
RED
4
2
BLK
BLK
6
8
RELAY 1
LS1 HTR1 BLK
BLK
2
4
11
11
RELAY 3
22 VDC COIL
RED
BRN
BRN
HI
MED
YEL
BLK
BLU
LO
RED
G
R
NO
F
T1
C
208
V
BRN
TRAN
FM
GRN/YEL
GND
2
NC
4
FR
0
RED-LOW
BRN
C
F
N
O
SPT
TDR
W2 W3
E
GND
SEE NOTE #5
R
W2
G
WHT SEE NOTE #8
BARRIER SEE NOTE #6
BRN
INDOOR
THERMOSTAT
NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
0
1
GRY
RED
230V
RED
C
T1
R
G
PCB
GRY
CO
M
4
6
4
4
VIO
PCB
8
TDR
RELAY 3
BRN
NC
YEL
CAP
COM
6 1
6 1
2
1
BRN
GRY
6
8
BLK
YEL
4
REC
RELAY 2
BLK
FR
8
230 V
0
RELAY 2
22 VDC COIL
BLU
SPT
2
2
WHT
BL
U
3
3
RED
RECP
7
7
BRN
9
9
2
1
REC
VIO
ORN
BLK
6
208 V
BRN
SYSTEM TRANSFORMER: 40.0VA
FAN COIL/HEATER: 15.2VA
REMAINING VA AVAILABLE: 24.8VA
RELAY 1
BLU
TDR
BLU
HTR5
BLK
RELAY 1
22 VDC COIL
YEL
LS 2
& 5
LS 4
& 3
24 V
RELAY 2
HTR2
HTR3
HTR6
BLK
BLU
TDR
PLUG
HTR4
LS 1
& 6
L3
HTR6 BLU
BLU
HTR1
HVTB
TRAN
GND
Use copper wire (75°C min) only between disconnect switch and unit.
To be wired in accordance with N.E.C. and local codes.
If any of the original wire, as supplied, must be replaced, use the same or equivalent type wire.
Replace low voltage fuse with no greater than 5 amp fuse.
(3) speed motor shown. optional (2) speed motor uses HI (BLK) and LOW (BLU or RED).
Connect R to R, G to G, etc., see outdoor instruction for details.
Largest heater shown, smaller heaters have fewer components.
If wire crimp is removed an emergency heat relay is required. (See outdoor-thermostat instructions)
OUTDOOR
UNIT
BLU-MED
BLK-HI
GRN/YEL-GND
FM
BRN
BRN
YEL-COM
CAP
FAN MOTOR THERMALLY PROTECTED
LEGEND
CAP
COM
CAPACITOR
COMMON
F
FM
LOW VOLTAGE FUSE
FAN MOTOR
FIELD POWER WIRING
PCB FAN RELAY
EQUIPMENT GROUND
FAN SPEED TAP
LOCATION
H I VOLTAGE
TERMINAL BLOCK
FR
GND
SPT
HVTB
HTR
LS
HEATER
LIMIT SWITCH
MARKED TERMINAL
PLUG & RECEPTACLE
PCB PRINTED CIRCUIT BOARD
REC RECTIFIER
TDR TIME DELAY RECTIFIER
TRAN TRANSFORMER
UNMARKED TERMINAL
MINIMUM CFM / MOTOR SPEED SELECTION
FAN COIL SIZE
018 024 030 036 042 048 060 070
MOTOR SPEED AT 18 KW -- -- -- -- LO LO LO LO
324990-101 REV. A
A00170
Fig. 11—Label Wiring 324990-101
—12—
CAUTION:
THIS COMPARTMENT MUST BE CLOSED EXCEPT FOR SERVICING
NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING
150V TO GROUND
BLOWER MOTOR
ROTATION
ATTENTION:
NE CONVIENT PAS AUX INSTALLATIONS DE PLUS DE 150
V A LA TERRE
LEGEND
SCHEMATIC DIAGRAM SINGLE SUPPLY CIRCUIT
COM
F1
ICM
FIELD POWER WIRING
DISCONNECT PER NEC
HVTB
SEE RATING PLATEFOR VOLTS & HERTZ
SEE NOTE #1
BLU
L1
L3
YEL LS6
HTR6 BLU
YEL LS5
HTR5 BLK RELAY 3 BLK
2
4
YEL
HTR4 BLK
BLU LS4
FU
GND
HVTB
HTR
REC
L2
YEL LS3 HTR3 BLU
8
FIELD POWER WIRING
COOLING CONTROL ONLY
BLK
6
RELAY 2
4
BLK
BLU
6
8
RELAY 2
22 VDC COIL
BLU
2
FIELD
POWER
WIRING
L1
HTR2 BLK
BLK
6
8
RELAY 1
LS1 HTR1 BLK
BLK
2
4
BLU
BLU
YEL
RELAY 1
22 VDC COIL
REC
VIO
ORN
BLK
PLUG
9
9
TDR
BLK
7
7
11
11
3
3
9
11
208/240VAC
9
11
RELAY 3
22 VDC COIL
RED
BRN
TDR
2
2
6 1
6 1
7
3 2
24VAC
3 2
7
HTR1
4
4
HTR4
HTR3
LS 2
& 5
LS 4
& 3
LS 1
& 6
HTR6
BLK
230V
AUX HEAT KW/CFM
KW
CFM
W
1
VIO
BRN
11
9
8
7
VI RE BR OR
O
D N N
10
BLU
6
2
1
ORN
BLK
NOM
G
HI
LO
BLK
YEL
PLUG 3
O
0
90
ON/OFF DELAY
30
0
90
0
LO
CONTINUOUS FAN
MED
HI
HI
C
WHT
5 4 3 2 1
AUX1 HUM1
BLK WHT VIO
BLK BLU ORN BRN
FU4
FU2
FU1
FU3
4
PCB
D
H
R
0
F1
REC
RELAY 2
6
2
8
4
Y
1
Y/Y
2
G
O
C
TDR
RELAY 3
6
2
8
4
W
1
W2
0
1
24 VAC
0
1
1
HEATER / MOTOR
ICM
REC
GRY
HEATER / MOTOR
16 15 14 13 12 11 10 9
8 7 6 5 4 3 2 1
8
PL1
GND
PL1
GRN WHT VIO ORN
YEL RED GRY
208 V
230 V
AUX 2 HUM2
YEL
PLUG 1
2
1
YEL
GRN/YEL
6
SEC1 SEC2
Y/Y
2
HP-EFF
AC/HP CFM ADJUST
BLK
GR Y B W
N EL LK HT
3
HP-COMFORT
ORN
WHT
5
4
AC
24 V
RELAY 1
Y
1
SYSTEM TYPE
L4
L2
L1
L3
L4 L3 L2 L1
CB2
CB1
60A 60A 60A 60A
W
2
BLU
GR
Y
12
RED VIO
F1
AC/HP SIZE
VIO
R
COM
RED
BRN
HTR5
D
H
SEC2
OUTDOOR UNIT
YEL
Com 208V
SEC1
INDOOR THERMOSTAT
TRAN
PCB
N
RED
BRN
6 1
PLUG 2
4
24VAC
RECP 2
4
HTR2
RECP 2
BRN
6 1
COMPONENT ARRANGEMENT
BRN
GRY
SYSTEM TRANSFORMER: 40.0VA
FAN COIL/HEATER: 8.2VA
REMAINING VA AVAILABLE: 31.8VA
L2
YEL
YEL LS2
LIMIT SWITCH
MARKED TERMINAL
PLUG AND RECEPTACLE
PCB
PRINTED CIRCUIT BOARD
TRAN TRANSFORMER
RECP RECEPTACLE
CB
CIRCUIT BREAKER
R
RELAY
TDR
TIME DELAY RECTIFIER
TRA
GND
LS
COMMON
LOW VOLTAGE FUSE
FAN MOTOR
FIELD POWER WIRING
LINE FUSE
EQUIPMENT GROUND
HIGH VOLTA GE TERM BLOCK
HEATER
RECTIFIER
GND
NOTES:
1.
RECP 3
2.
3.
4.
ICM
RECP 4
GRY
PLUG 4
5.
6.
7.
8.
USE COPPER WIRE (75*C MIN) ONLY BETWEEN DISCONNECT
SWITCH AND UNIT.
TO BE WIRED IN ACCORDANCE WITH NEC AND LOCAL CODES.
TRANSFORMER PRIMARY LEADS, BLUE 208V, RED 230V.
IF ANY OF THE ORIGINAL WIRE, AS SUPPLIED, MUST BE REPLACED,
USE THE SAME OR EQUIVALENT TYPE WIRE.
REPLACE LOW VOLTAGE FUSE WITH NO GREATER THAN 5 AMP FUSE.
DUAL CIRCUIT WIRING SHOWN.
USE 60 AMP CLASS K FUSES ONLY, FOR REPLACEMENT.
CONNECT R TO R, G TO G, ETC., SEE OUTDOOR INSTRUCTION FOR
DETAILS.
325798-101 REV. B
LABEL (2)
SEE INSTRUCTION FOR INSTALLATION
A00181
Fig. 12—Label Wiring 325798-101
—13—
CAUTION:
THIS COMPARTMENT MUST BE CLOSED EXCEPT FOR SERVICING
NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING
150V TO GROUND
BLOWER MOTOR
ROTATION
ATTENTION:
NE CONVIENT PAS AUX INSTALLATIONS DE PLUS DE
150 V A LA TERRE
SCHEMATIC DIAGRAM
COMPONENT ARRANGEMENT
DISCONNECT PER NEC
SEE RATING PLATE
FOR VOLTS & HERTZ
HTR1
SEE NOTE #1
L1
L3
L5
YEL
L6
GND GND GND
YEL
FU5
YEL
LS6
YEL
FU3
YEL
FU1
YEL LS5
HTR5
YEL LS4
HTR4
YEL LS3
HTR3
LS2
HTR2
YEL
BLK
BLK
BLK
BLK
4
2
8
6
4
RELAY 2 BLK
2
BLK
YEL
4
2
BLU
BLU
YEL
11
11
9
9
BLU
RECP
3
3
BLK
BLK
FU2
2
8
4
0
1
REC
RELAY 2
RELAY 2
22 VDC COIL
BLK
6
6
2
8
4
RELAY 3
22 VDC COIL
RED
BRN
NO
2
2
BRN
GRY
6
6 1
6 1
2
FR
0
1
BRN
HI
MED
YEL
BLK
BLU
LO
RED
RED-LOW
E
GND
GRY
VIO
BLU
RED
W2 W3
WHT
CO
M
SEE NOTE #6
208V 230V
BLU-MED
BLK-HI
GRN/YEL-GND
FM
BRN
BRN
YEL-COM
CAP
FAN MOTOR THERMALLY PROTECTED
LEGEND
BRN
RED
TRAN
FM
GRN/YEL
GND
BRN
C
R
W2
WHT
G
SEE NOTE #8
BARRIER SEE NOTE #7
INDOOR
THERMOSTAT
OUTDOOR
UNIT
CAP
COM
F
FU
FM
FR
NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
N
O
SPT
TDR
BRN
BRN
YEL
CAP
COM
BLK
PCB
F
NC
PCB
4
F
YEL
230 V
C
T1
R
G
GND
4
4
GRY
RED
T1
C
208 V
BRN
TDR
RELAY 3
BRN
FR
FU5
FU3
FU1
FU6
FU4
FU2
0
1
TDR
BLK
G
R
L5
L3
L1
L6
L4
L2
RED
24 V
TDR
8
NC
SPT
COM
BLK
7
7
HTR5
SYSTEM TRANSFORMER: 40.0VA
FAN COIL/HEATER: 15.2VA
REMAINING VA AVAILABLE: 24.8VA
RELAY 1
BLK
REC
VIO
ORN
BLK
HTR6
FU4
RELAY 1
22 VDC COIL
PLUG
BLK
FU6
BLK
6
8
RELAY 1
LS 2
& 5
L2
BLK
BLK
LS1 HTR
1
YEL
BLK
8
6
RELAY 3
HTR2
HTR3
LS 4
& 3
LS 1
& 6
L4
BLK
HTR6
HTR4
TRAN
FIELD POWER WIRING
Use copper wire (75°C min) only between disconnect switch and unit.
To be wired in accordance with N.E.C. and local codes.
If any of the original wire, as supplied, must be replaced, use the same or equivalent type wire.
Replace low voltage fuse with no greater than 5 amp fuse.
Use 60 amp class K fuses only, for replacement.
(3) speed motor shown. optional (2) speed motor uses HI (BLK) and LOW (BLU or RED).
Connect R to R, G to G, etc., see outdoor instruction for details.
If wire crimp is removed an emergency heat relay is required.
324994-101 REV. A
(see outdoor-thermostat instructions)
GND
SPT
CAPACITOR
COMMON
LOW VOLTAGE FUSE
LINE FUSE
FAN MOTOR
FIELD POWER WIRING
PCB FAN RELAY
EQUIPMENT GROUND
FAN SPEED TAP
LOCATION
HTR
LS
HEATER
LIMIT SWITCH
MARKED TERMINAL
PLUG & RECEPTACLE
PCB PRINTED CIRCUIT BOARD
REC RECTIFIER
TDR TIME DELAY RECTIFIER
TRAN TRANSFORMER
UNMARKED TERMINAL
MINIMUM CFM / MOTOR SPEED SELECTION
018 024 030 036 042 048 060 070
FAN COIL SIZE
MOTOR SPEED AT 24 KW -- -- -- -- -- LO LO LO
MOTOR SPEED AT 30 KW -- -- ---- -- -- LO LO LO
A00173
Fig. 13—Label Wiring 324994-101
—14—
CAUTION:
THIS COMPARTMENT MUST BE CLOSED EXCEPT FOR SERVICING
NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING
150V TO GROUND
BLOWER MOTOR
ROTATION
ATTENTION:
NE CONVIENT PAS AUX INSTALLATIONS DE PLUS DE 150
V A LA TERRE
LEGEND
30KW 1PH SCHEMATIC DIAGRAM
COM
F1
ICM
DISCONNECT PER NEC
HVTB
SEE RATING PLATE
FOR VOLTS & HERTZ
GND
SEE NOTE #1
FU
GND
HVTB
HTR
REC
L2
L1
YEL
LS6
YEL
FU5
HTR6 BLK
BLK
8
6
RELAY 3
BLK
4
2
HTR5
BLK
YEL LS5
YEL
CB/FU3
YEL LS4
HTR4 BLK
YEL LS3
HTR3 BLK
YEL LS2 HTR2 BLK
9
7
7
11
11
3
3
2
2
4 PLUG 2
4
RECP 2
6 1
6 1
BLK
230V
AUX HEAT KW/CFM
KW
CFM
VIO
F1
BRN
AC/HP SIZE
12
9
8
7
BLU
VI RE BR OR
O
D N N
10
6
2
1
ORN
BLK
HP-EFF
NOM
PLUG 3
LO
G
HI
O
ON/OFF DELAY
0
30
0
90
90
0
HI
C
WHT
5 4 3 2 1
LO
AUX1 HUM1
CONTINUOUS FAN
MED
HI
GND
BLK WHT VIO
BLK BLU ORN BRN
COM
RED
24 V
208 V
BRN
230 V
2
PCB
D
H
4
R
0
1
F1
REC
RELAY 2
6
2
8
4
W2
Y
1
Y/Y
2
G
O
0
1
C
TDR
RELAY 3
6
2
8
4
W
1
0
1
24 VAC
PL1
TDR
HEATER / MOTOR
ICM
GND
1
GRY
HEATER / MOTOR
16 15 14 13 12 11 10 9
8 7 6 5 4 3 2 1
8
AUX 2 HUM2
YEL
PL1
GRN WHT VIO ORN
YEL RED GRY
6
FU5
FU3
FU1
FU6
FU4
FU2
HTR5
YEL
GRN/YEL
PLUG 1
RELAY 1
Y/Y
2
BLK
YEL
BLK
GR Y B W
N EL LK HT
3
HP-COMFORT
AC/HP CFM ADJUST
WHT
5
4
AC
ORN
L5
L3
L1
L6
L4
L2
SEC1 SEC2
Y
1
SYSTEM TYPE
11
SYSTEM TRANSFORMER: 40.0VA
FAN COIL/HEATER: 8.2VA
REMAINING VA AVAILABLE: 31.8VA
W
2
BLU
GR
Y
VIO
RED VIO
R
W
1
LS 2
& 5
LS 4
& 3
HTR6
D
H
SEC2
HTR2
HTR3
L1 L2 L3
OUTDOOR UNIT
YEL
Com 208V
6 1
HTR4
HTR1
LS 1
& 6
BRN
GRY
PCB
SEC1
PLUG 2
4
24VAC
RECP 2
4
6 1
3 2
24VAC
3 2
7
HVTB
RELAY 3
22 VDC COIL
RED
BRN
TDR
INDOOR THERMOSTAT
RED
BRN
7
COMPONENT ARRANGEMENT
BRN
TRAN
LIMIT SWITCH
MARKED TERMINAL
PLUG AND RECEPTACLE
PCB
PRINTED CIRCUIT BOARD
TRAN TRANSFORMER
RECP RECEPTACLE
CB
CIRCUIT BREAKER
TDR
TIME DELAY RECTIFIER
TDR
REC
VIO
ORN
BLK
11
208/240VAC
9
11
RELAY 2
22 VDC COIL
LS
COOLING CONTROL ONLY
BLK
BLK
6
8
CB/FU2
RELAY 1
BLK
4
2
RELAY 1
BLU
22 VDC COIL
BLK
BLU
9
9
FIELD
POWER
WIRING
YEL LS1 HTR1 BLK
YEL
YEL
BLK
BLK
BLK
8
6
CB/FU4
RELAY 2
BLK
4
2
YEL
CB/FU1
FU6
COMMON
LOW VOLTAGE FUSE
FAN MOTOR
FIELD POWER WIRING
LINE FUSE
EQUIPMENT GROUND
HIGH VOLTAGE TERM BLOCK
HEATER
RECTIFIER
TRAN
FIELD POWER WIRING
NOTES:
1.
USE COPPER WIRE (75°C MIN) ONLY BETWEEN DISCONNECT
SWITCH AND UNIT.
TO BE WIRED IN ACCORDANCE WITH NEC AND LOCAL CODES.
TRANSFORMER PRIMARY LEADS, BLUE 208V, RED 230V.
IF ANY OF THE ORIGINAL WIRE, AS SUPPLIED, MUST BE REPLACED,
USE THE SAME OR EQUIVALENT TYPE WIRE.
5. REPLACE LOW VOLTAGE FUSE WITH NO GREATER THAN 5 AMP FUSE.
6. 20KW HEATER USES ONE DOUBLE POLE LS ON MIDDLE TOP ELEMENT.
7. 18, 24 AND 30KW HEATERS USE DOUBLE POLE LIMIT SWITCHES.
8. LARGEST HEATERS ARE SHOWN, SMALLER HEATERS WILL HAVE
FEWER ELEMENTS AND COMPONENTS.
9. 1 PHASE HEATERS ARE SHOWN WIRED FOR SINGLE SUPPLY CIRCUIT.
10. USE 60 AMP CLASS K FUSES ONLY, FOR REPLACEMENT.
11. CONNECT R TO R, G TO G, ETC., SEE OUTDOOR INSTRUCTION FOR
DETAILS.
2.
3.
4.
RECP 3
ICM
RECP 4
GRY
PLUG 4
324985-101 REV. C
LABEL (2)
A00166
Fig. 14—Label Wiring 324985-101
—15—
CAUTION:
THIS COMPARTMENT MUST BE CLOSED EXCEPT FOR SERVICING
NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING
150V TO GROUND
BLOWER MOTOR
ROTATION
ATTENTION:
NE CONVIENT PAS AUX INSTALLATIONS DE PLUS DE
150 V A LA TERRE
SCHEMATIC DIAGRAM SINGLE SUPPLY CIRCUIT
GND
COMPONENT ARRANGEMENT
DISCONNECT PER NEC
SEE RATING PLATE
FOR VOLTS & HERTZ
HTR1
SEE NOTE #1
YEL
L1
YEL LS6
FU5
YEL
FU3
YEL
(1 PHASE)
YEL
YEL
YEL
HTR6 BLK
LS5
HTR5 BLK
LS4
HTR4 BLK
LS3
HTR3 BLK
LS2
BLK
6
8
RELAY 3
BLK
8
6
RELAY 2
4
HTR2 BLK
BLK
6
8
FU1
HTR6
HTR5
FU6
COM
SYSTEM TRANSFORMER: 40.0VA
FAN COIL/HEATER: 15.2VA
REMAINING VA AVAILABLE: 24.8VA
BLK
FU4
RELAY 1
BLK
FU2
6
2
8
4
0
1
REC
RELAY 1
BLK
YEL LS1 HTR1 BLK
4
2
RED
24 V
BLK
2
LS 2
& 5
L2
BLK (1 PHASE)
2
4
HTR2
HTR3
LS 4
& 3
LS 1
& 6
BLK
L3
HTR4
RELAY 2
22 VDC COIL
TRAN
FIELD POWER WIRING
HVTB
L5
L3
L1
L6
L4
L2
FU5
FU3
FU1
FU6
FU4
FU2
208 V
BRN
230 V
RELAY 2
2
6
TDR
BLK
11
11
YEL
CAP
COM
HI
MED
LO
BRN
YEL
BLK
BLU
CO
M
FM
BRN
RED
GRN/YEL
GND
BRN
W2 W3
GND
E
R
W2
WHT
G
SEE NOTE #8
BARRIER SEE NOTE #7
INDOOR
THERMOSTAT
OUTDOOR
UNIT
RED
SEE NOTE #6
RED-LOW
BLU-MED
BLK-HI
GRN/YEL-GND
FM
BRN
BRN
YEL-COM
CAP
FAN MOTOR THERMALLY PROTECTED
CAP
COM
F
FU
FM
FR
GND
SPT
NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
GND
LEGEND
C
TRAN
N
O
SPT
FR
0
1
208V 230V
BRN
4
8
TDR
VIO
BLK
YEL
NC
PCB
F
T1
C
F
2
6
GRY
RED
G
R
FR
PCB
RELAY 3
BRN
NO
C
T1
R
G
0
TDR
4
4
6 1
6 1
BLK
NC
SPT
2
2
BLU
BLU
RECP
3
3
7
7
WHT
9
9
4
8
1
GRY
BLU
BR
N
RED
YEL
PLUG
RELAY 3
RELAY 1
22 VDC COIL
22 VDC COIL RED
BRN
TDR
REC
BRN
GRY
VIO
ORN
Use copper wire (75°C min) only between disconnect switch and unit.
To be wired in accordance with N.E.C. and local codes.
If any of the original wire, as supplied, must be replaced, use the same or equivalent type wire.
Replace low voltage fuse with no greater than 5 amp fuse.
Use 60 amp class K fuses only, for replacement.
(3) speed motor shown. optional (2) speed motor uses HI (BLK) and LOW (BLU or RED).
Connect R to R, G to G, etc., see outdoor instruction for details.
If wire crimp is removed an emergency heat relay is required. (see outdoor-thermostat instructions)
HVTB
CAPACITOR
COMMON
LOW VOLTAGE FUSE
LINE FUSE
FAN MOTOR
FIELD POWER WIRING
PCB FAN RELAY
EQUIPMENT GROUND
FAN SPEED TAP
LOCATION
H I VOLTAGE
TERMINAL BLOCK
HTR
LS
HEATER
LIMIT SWITCH
MARKED TERMINAL
PLUG & RECEPTACLE
PCB PRINTED CIRCUIT BOARD
REC RECTIFIER
TDR TIME DELAY RECTIFIER
TRAN TRANSFORMER
UNMARKED TERMINAL
MINIMUM CFM / MOTOR SPEED SELECTION
FAN COIL SIZE
018 024 030 036 042 048 060 070
MOTOR SPEED AT 24 KW -- -- -- -- -- LO LO LO
MOTOR SPEED AT 30 KW -- -- -- -- -- LO LO LO
324993-101 REV. A
A00172
Fig. 15—Label Wiring 324993-101
—16—
CAUTION:
THIS COMPARTMENT MUST BE CLOSED EXCEPT FOR SERVICING
NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING
150V TO GROUND
BLOWER MOTOR
ROTATION
ATTENTION:
NE CONVIENT PAS AUX INSTALLATI ONS DE PLUS DE 150
V A LA TERRE
LEGEND
SCHEMATIC DIAGRAM SINGLE SUPPLY CIRCUIT
GND
L3
YEL LS6
FU5
YEL
HTR6 BLK
6
8
BLK
FU6
LS4
HTR4 BLK
YEL
LS3
HTR3 BLK
YEL
LS2
HTR2 BLK
8
6
RELAY 2
4
2
BLK
YEL
BLU
3
3
2
2
6 1
6 1
HVTB
AUX HEAT KW/CFM
VIO
BRN
11
9
8
7
BLU
VI RE BR OR
O
D N N
10
6
2
1
ORN
BLK
HP-EFF
NOM
PLUG 3
LO
G
HI
O
ON/OFF DELAY
0
30
0
90
90
0
HI
C
WHT
5 4 3 2 1
LO
AUX1 HUM1
CONTINUOUS FAN
MED
HI
GND
BLK WHT VIO
BLK BLU ORN BRN
COM
RED
24 V
208 V
BRN
230 V
2
PCB
D
H
4
R
0
1
F1
REC
RELAY 2
6
2
8
4
Y
1
Y/Y
2
G
O
C
TDR
RELAY 3
6
2
8
4
W
1
W2
0
1
PL1
0
1
24 VAC
TDR
HEATER / MOTOR
ICM
GND
1
GRY
HEATER / MOTOR
16 15 14 13 12 11 10 9
8 7 6 5 4 3 2 1
8
AUX 2 HUM2
YEL
PL1
GRN WHT VIO ORN
YEL RED GRY
6
FU5
FU3
FU1
FU6
FU4
FU2
HTR5
YEL
GRN/YEL
PLUG 1
RELAY 1
Y/Y
2
BLK
YEL
BLK
GR Y B W
N EL LK HT
3
HP-COMFORT
AC/HP CFM ADJUST
WHT
5
4
AC
ORN
L5
L3
L1
L6
L4
L2
SEC1 SEC2
Y
1
SYSTEM TYPE
LS 2
& 5
LS 4
& 3
SYSTEM TRANSFORMER: 40.0VA
FAN COIL/HEATER: 8.2VA
REMAINING VA AVAILABLE: 31.8VA
W
2
BLU
GR
Y
12
RED VIO
F1
AC/HP SIZE
VIO
R
W
1
HTR2
HTR3
HTR6
D
H
SEC2
KW
CFM
PLUG 2
4
24VAC
RECP 2
4
L1 L2 L3
OUTDOOR UNIT
BLK
230V
6 1
HTR4
HTR1
LS 1
& 6
INDOOR THERMOSTAT
YEL
Com 208V
PCB
SEC1
7
4
4
N
RED
BRN
6 1
3 2
24VAC
3 2
TDR
BRN
TRAN
LIMIT SWITCH
MARKED TERMINAL
PLUG AND RECEPTACLE
PCB
PRINTED CIRCUIT BOARD
TRAN TRANSFORMER
RECP RECEPTACLE
CB
CIRCUIT BREAKER
TDR
TIME DELAY RECTIFIER
COMPONENT ARRANGEMENT
RELAY 3
RELAY 1
22 VDC COIL
22 VDC COIL RED
BRN
TDR
REC
BRN
GRY
VIO
ORN
7
7
7
BLK
FU2
6
BLK
11
11
9
RECP 2 9
11
208/240VAC
9
11
RELAY 2
22 VDC COIL
LS
COOLING CONTROL ONLY
9
BLK
RELAY 1
BLK
YEL LS1 HTR1 BLK
4
2
COMMON
LOW VOLTAGE FUSE
FAN MOTOR
FIELD POWER WIRING
LINE FUSE
EQUIPMENT GROUND
HIGH VOLTAGE TERM BLOCK
HEATER
RECTIFIER
FIELD
POWER
WIRING
BLK
FU4
BLK
8
FU1
PLUG 2
FU
GND
HVTB
HTR
REC
L2
LS5
YEL
(1 PHASE)
BLK
HTR5 BLK RELAY 3 BLK (1 PHASE)
2
4
YEL
FU3
COM
F1
ICM
SEE NOTE #1
YEL
L1
DISCONNECT PER NEC
TRA
SEE RATING PLATE
FOR VOLTS & HERTZ
FIELD POWER WIRING
HVTB
NOTES:
1.
RECP 3
ICM
RECP 4
GRY
PLUG 4
USE COPPER WIRE (75°C MIN) ONLY BETWEEN DISCONNECT
SWITCH AND UNIT.
2. TO BE WIRED IN ACCORDANCE WITH NEC AND LOCAL CODES.
3. TRANSFORMER PRIMARY LEADS, BLUE 208V, RED 230V.
4. IF ANY OF THE ORIGINAL WIRE, AS SUPPLIED, MUST BE REPLACED,
USE THE SAME OR EQUIVALENT TYPE WIRE.
5. REPLACE LOW VOLTAGE FUSE WITH NO GREATER THAN 5 AMP FUSE.
6. 20KW HEATER USES ONE DOUBLE POLE LS ON MIDDLE TOP ELEMENT.
7. 18, 24 AND 30KW HEATERS USE DOUBLE POLE LIMIT SWITCHES.
8. LARGEST HEATERS ARE SHOWN, SMALLER HEATERS WILL HAVE
FEWER ELEMENTS AND COMPONENTS.
9. 1 PHASE HEATERS ARE SHOWN WIRED FOR SINGLE SUPPLY CIRCUIT.
10. USE 60 AMP CLASS K FUSES ONLY, FOR REPLACEMENT.
11. CONNECT R TO R, G TO G, ETC., SEE OUTDOOR INSTRUCTION FOR
DETAILS.
326114-101 REV. B
LABEL (2) 3 PHASE
A00185
Fig. 16—Label Wiring 326114-101
—17—
SCHEMATIC DIAGRAM
CAUTION:
NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING 150V TO GROUND
SEE RATING PLATE FOR VOLTS & HERTZ
ATTENTION:
NE CONVIENT PAS AUX INSTALLATIONS DE PLUS DE 150 V A LA TERRE
FIELD POWER WIRING
COOLING CONTROLS
ELECTRIC HEAT
L2
L2
LS
LS
DISC
GND
SEE NOTE #8
DISC
SEE NOTE #1
DISCONNECT PER NEC
DISC
L1
DISC
SEE NOTE #8
L1
COMPONENT ARRANGEMENT
HTR
HTR
SYSTEM TRANSFORMER 40.0 VA
FAN COIL/HEATER: 8.4 VA
REMAINING VA AVAILABLE: 31.6VA
COM
YEL
YEL
LS2
YEL
HTR2
BLU
BLU
BLK
RELAY 1
4
NO
F
T1
C
208V
230V
BRN
C
T1
R
G
REC
RELAY 1
22 VDC COIL
L2
L1
DISC
60A 60A
BLK
G
R
RED
24V
1
2
PC8
GND
ORN
NC
PCB
6
REC
BLK
YEL
BLK
8
BLK
BLK
FR
YEL
BLK
HTR1 BLK
LS1
YEL
SPT
RELAY 1
6
8
2
4
BLK
TRAN
SEE NOTE #6
NC
NO
FR
SPT
VIO
RED- LOW
FM
GRY
RED
BLK-HI
GND
ORN
F
GRY
GRN/YEL-GND
BRN
BRN
CAP
YEL-COM
SEE NOTE #5
YEL
VIO
BRN
FAN MOTOR THERMALLY PROTECTED
CAP
COM 208V 230V
LEGEND
COM
R
G
W
BRN BRN
C
CAP
CAPACITOR
COM
COMMON
RED
YEL
DISC
DISCONNECT
HI BLK
BARRIER SEE NOTE#7
TRAN
FM
F
FUSE
BRN
GRN/YEL
FM
FAN MOTOR
INDOOR
OUTDOOR
LO RED
GND
THERMOSTAT
UNIT
FIELD POWER WIRING
NOTES
FR
PCB FAN RELAY
GND
EQUIPMENT GROUND
1. Use copper wire (75oc min) only between disconnect switch and unit
HTR
HEATER
2. To be wired in accordance with nec and local codes.
LS
LIMIT SWITCH
3. If any of the original wire, as supplied, must be replaced, use the same
MARKED TERMINAL
or equivalent type wire.
PLUG AND RECEPTACLE
4. Replace low voltage fuse with no greater than 5 AMP fuse.
PCB
PRINTED CIRCUIT BOARD
5. (2) Speed Motor uses HI (BLK) and LOW (RED).
6. Smaller heaters will have fewer components.
REC
RECTIFIER
7. Connect R to R, G to G, etc.., see outdoor instructions for details.
SPT
FAN SPEED TAP LOCATION
8. Cooling controls wiring not used with electric heaters.
TRAN
TRANSFORMER
UNMARKED TERMIINAL
RED
This compartment must be closed except
when servicing
ROTATION
324494-101 REV.A
MINIMUM MOTOR SPEED SELECTION
FAN COIL SIZE
018 024 030
MOTOR SPEED ONE HTR LO LO
LO
MOTOR SPEED TWO HTR LO LO LO
A00163
Fig. 17—Label Wiring 324994-101
—18—
CAUTION:
THIS COMPARTMENT MUST BE CLOSED EXCEPT FOR SERVICING
NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING
150V TO GROUND
BLOWER MOTOR
ROTATION
ATTENTION:
NE CONVIENT PAS AUX INSTALLATIONS DE PLUS DE 150
V A LA TERRE
SCHEMATIC DIAGRAM
HTR3
BLK
LS2
HTR2
BLK
RELAY 2
6
8
LS1
HTR1
COM
SYSTEM TRANSFORMER: 40.0VA
FAN COIL/HEATER: 19.0VA
REMAINING VA AVAILABLE: 21.0VA
BLK
RELAY
2
BLK
YEL
ORG
RELAY
1
PCB
LED
3 2 1
6 5 4
9 8 7
DUMMY
T2
240 VAC
T3
LO
5
4
9
8
7
T3
F
RED
BRN
BLK
COM
HI
MED
BRN
F1
HI
F2
LO
O
W2D
G
Y
C
SEC 2
SEC 1
R
Y
TRAN BRN
SEE NOTE #3
GRN/YEL
GND
GND
Y G
O
CAP
COMM
F
FW
GND
HPLV
HTR
LS
E W2
MINIMUM MOTOR LO SPEED TAP SELECTION
FAN COIL SIZE
018-240V018-208V 024 030 033
MOTOR SPEED AT 10 KW MED
HI
LO
LO
LO
CAPACITOR
COMMON
LOW VOLT FUSE
FAN MOTOR
EQUIPMENT GROUND
HEAT PUMP LOW VOLT
HEATER
LIMIT SWITCH
324986-101
REV. A
TRAN
4
8
4
FM
BRN
BRN
YEL-COM
STEADY LIGHT
LED
LVTB
R
TRAN
XFORM
0
1
0
C
STEADY FLASH
1 FLASH
DIAGNOSTIC LIGHT
LOW VOLT TERM BRD
RELAY
TRANSFORMER
PCB TRAN TERMINALS
FIELD HIGH VOLTAGE
FIELD LOW VOLTAGE
HPLV LEADS
MARKED TERMINAL
036
LO
8
NO LIGHT OR FLASH
LEGEND
Use copper wire (75°C min) only between disconnect switch and unit.
Connect low voltage wiring as shown (24VAC).
Connect transformer primary to the proper voltage terminal
To be wired in accordance with N.E.C. and local codes.
If any of the original wire, as supplied, must be replaced,
use the same or equivalent type wire.
6. Replace low voltage fuse with no greater than 5 amp fuse.
7. Refer to thermostat instructions for "E" jumper installation.
8. Do NOT connect thermostat "E" to PCB "W3".
2
R
SEE NOTES #2,#7, AND #8
NOTES:
6
CAP
LED FLASH CODES
INDOOR THERMOSTAT
LO
2
1
BLU-MED
BLK-HI
GRN/YEL-GND
O
C
RELAY 2
6
FAN MOTOR THERMALLY PROTECTED
W2
R
FM
230 V
RELAY 1
RED-LOW
HPLV
LEADS
RED
CAP
208 V
T2
JW1
BLK
BLU
24 V
GND
AUX +
T1
COM 208V 230V
YEL
1.
2.
3.
4.
5.
6
YEL
YEL
F2
BLK
1
Yo
FAN
240
DUMMY VAC
2
LVTB
HI
3
W3
COMM
AUX -
PCB
W2T
F1
R
C
Y
G
O
W2D
W2T
W3
Yo
SEC 2
BRN
RED
BRN
SEC 1 F
RED
XFORM
T1
R2
JW1
YEL
R1
BLK
4
2
LS2
L2
RELAY 2
BLK
HTR2
LS3
JW2
YEL
LS3
BLK
BLK
VIO
YEL
HTR3
LS1
RELAY 1
4
2
BRN
YEL
YEL
HTR1
SEE RATING PLATE
FOR VOLTS & HERTZ
SEE NOTE #1
GND
L1
COMPONENT ARRANGEMENT
DISCONNECT PER NEC
FIELD POWER WIRING
PCB JUMPER (JW)
UNMARKED TERMINAL
2 FLASHES
3 FLASHES
4 FLASHES
NO POWER OR
BOARD FAILURE
BOARD FAILURE
STAND BY CONDITION
OR FAN ONLY
HEAT PUMP HEAT
ONLY OPERATING
HEAT PUMP PLUS
1 RELAY
HEAT PUMP PLUS
2 RELAYS
HEAT PUMP PLUS
3 RELAYS
5 FLASHES
COOL MODE
6 FLASHES
DEFROST MODE
7 FLASHES
EMERGENCY HEAT
MODE
A00167
Fig. 18—Label Wiring 324986-101
—19—
CAUTION:
THIS COMPARTMENT MUST BE CLOSED EXCEPT FOR SERVICING
NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING
150V TO GROUND
BLOWER MOTOR
ROTATION
ATTENTION:
NE CONVIENT PAS AUX INSTALLATIONS DE PLUS DE 150
V A LA TERRE
COMPONENT ARRANGEMENT
SCHEMATIC DIAGRAM
DISCONNECT PER NEC
2
HTR3
4
HTR2
LS2
YEL
BLK
RELAY 1
2
4
BLK
BLK
RELAY
3
RELAY 2
BLK
BLK
4
2
YEL
BLK
RED
RELAY
1
4
8
7
T3
Yo
LVTB
W3
W2T
O
Y
G
C
R
COM 208V 230V
CAP
RED
BLK
BRN
COM
HI
MED
BRN
GRN/YEL
GND
F2
LO
4
GND
208 V
0
6
2
8
4
0
6
2
8
4
L4 FU4 30A
L2 FU2 60A
L1 FU1 60A
FM
BLU-MED
BLK-HI
GRN/YEL-GND
L3 FU3 30A
0
1
RED-LOW
BRN
BRN
YEL-COM
CAP
FAN MOTOR THERMALLY PROTECTED
O
LED FLASH CODES
R
C Y G
O
E W2
NO LIGHT OR FLASH
C
STEADY LIGHT
INDOOR THERMOSTAT
STEADY FLASH
SEE NOTES #2,#7, AND #8
LO
LEGEND
NOTES:
1.
2.
3.
4.
5.
8
RELAY 1
HI
W2
RED
TRAN BRN
SEE NOTE #3
2
1
F1
HPLV
LEADS
Y
R
FM
24 V
BRN
RELAY 2
GND
YEL
BLU
T2
BRN
YEL
F
6
1
AUX +
T1
JW1
BLK
F2
5
9
SEC 2
YEL
LO
240 VAC
T3
1
2
6
DUMMY
T2
FAN
240
DUMMY VAC
BRN
3
W2D
HI
PCB
SEC 1
COMM
RELAY
2
VIO
XFORM
T1
RED
230 V
R
SEC 1 F C
Y
SEC 2
G
LED
O
W2D
W2T
3 2 1
W3
6 5 4
Yo
9 8 7
AUX -
ORG
F1
COM
PCB
BRN
HTR1
LS1
YEL
R1 R2
RELAY 3
BLK
8
6
R3
SYSTEM TRANSFORMER: 40.0VA
FAN COIL/HEATER: 26.3VA
REMAINING VA AVAILABLE: 13.7VA
BLK
RELAY 2
LS2
LS3/4
TRAN
LS3
HTR2
HTR4
3
1
YEL
RELAY 3
BLK
2
4
LS1
JW1
HTR4
L4
HTR3
JW2
LS4
L2
FU4
FU1
YEL
YEL
GND
HTR1
BLK
L1
SEE RATING PLATE
FOR VOLTS & HERTZ
SEE NOTE #1
FU2
L3
FU3
FIELD POWER WIRING
Use copper wire (75°C min) only between disconnect switch and unit.
Connect low voltage wiring as shown (24VAC).
Connect transformer primary to the proper voltage terminal
To be wired in accordance with N.E.C. and local codes.
If any of the original wire, as supplied, must be replaced,
use the same or equivalent type wire.
6. Replace low voltage fuse with no greater than 5 amp fuse.
7. Refer to thermostat instructions for "E" jumper installation.
8. Do NOT connect thermostat "E" to PCB "W3".
CAP
COMM
F
FW
GND
HPLV
HTR
LS
MINIMUM MOTOR LO SPEED TAP SELECTION
FAN COIL SIZE
018 024 030 033 036 038 042 048
MOTOR SPEED AT 15 KW -- MED LO LO LO LO LO LO
CAPACITOR
COMMON
LOW VOLT FUSE
FAN MOTOR
EQUIPMENT GROUND
HEAT PUMP LOW VOLT
HEATER
LIMIT SWITCH
LED
LVTB
TRAN
XFORM
1 FLASH
DIAGNOSTIC LIGHT
LOW VOLT TERM BRD 2 FLASHES
TRANSFORMER
PCB TRAN TERMINALS 3 FLASHES
FIELD HIGH VOLTAGE
4 FLASHES
FIELD LOW VOLTAGE
5 FLASHES
HPLV LEADS
MARKED TERMINAL
324989-101
REV. B
6 FLASHES
PCB JUMPER (JW)
UNMARKED TERMINAL 7 FLASHES
NO POWER OR
BOARD FAILURE
BOARD FAILURE
STAND BY CONDITION
OR FAN ONLY
HEAT PUMP HEAT
ONLY OPERATING
HEAT PUMP PLUS
1 RELAY
HEAT PUMP PLUS
2 RELAYS
HEAT PUMP PLUS
3 RELAYS
COOL MODE
DEFROST MODE
EMERGENCY HEAT
MODE
A00169
Fig. 19—Label Wiring 324989-101
—20—
CAUTION:
THIS COMPARTMENT MUST BE CLOSED EXCEPT FOR SERVICING
NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING
150V TO GROUND
BLOWER MOTOR
ROTATION
ATTENTION:
NE CONVIENT PAS AUX INSTALLATIONS DE PLUS DE 150
V A LA TERRE
SCHEMATIC DIAGRAM
COMPONENT ARRANGEMENT
YEL
LS3
2
BLK
HTR3 BLK RELAY 1
4
2
4
BLK
HTR4 BLK
HTR2
LS2
BLK
RELAY 2
BLK
RELAY 2
HTR1 BLK
LS1
PCB
RELAY
3
BLK
4
2
YEL
YEL
SEC 2
LED
RELAY
2
3 2 1
6 5 4
9 8 7
BRN
VIO
BLK
DUMMY
T2
5
RED
7
RED
BLK
BRN
COM
HI
MED
GRN/YEL
GND
Yo
LVTB
W3
W2T
Y
G
8
4
208 V
0
RELAY 2
6
2
8
4
L4 FU4 60A
0
1
HI
F2
LO
6
L2 FU2 60A
8
GND
RED-LOW
BLU-MED
BLK-HI
GRN/YEL-GND
4
0
1
HPLV
LEADS
L1 FU1 60A
2
L3 FU3 60A
GND
RED
TRAN BRN
SEE NOTE #3
FM
BRN
BRN
YEL-COM
CAP
FAN MOTOR THERMALLY PROTECTED
O
LED FLASH CODES
R
C
Y G
O
SEE NOTES #2, #7,AND #8
LEGEND
NOTES:
Use copper wire (75°C min) only between disconnect switch and unit.
Connect low voltage wiring as shown (24VAC).
Connect transformer primary to the proper voltage terminal
To be wired in accordance with N.E.C. and local codes.
If any of the original wire, as supplied, must be replaced,
use the same or equivalent type wire.
6. Replace low voltage fuse with no greater than 5 amp fuse.
7. Refer to thermostat instructions for "E" jumper installation.
8. Do NOT connect thermostat "E" to PCB "W3".
CAP
COMM
F
FW
GND
HPLV
HTR
LS
MINIMUM MOTOR LO SPEED TAP SELECTION
030 033 036 038 042 048 060 070
FAN COIL SIZE
MOTOR SPEED AT 20 KW MED MED LO LO LO LO LO LO
NO LIGHT OR FLASH
NO POWER OR
BOARD FAILURE
STEADY LIGHT
BOARD FAILURE
C
E W2
INDOOR THERMOSTAT
LO
1.
2.
3.
4.
5.
T3
Y
R
FM
2
1
F1
W2
BRN
24 V
BRN
RELAY 1
JW1
COM 208V 230V
CAP
6
T2
BRN
YEL
BLU
RED
230 V
AUX +
T1
RELAY
1
4
8
YEL
C
BLK
6
AUX -
F
R
YEL
LO
F2
1
2
9
240 VAC
T3
SEC 2
FAN
240
DUMMY VAC
3
W2D
HI
SEC 1
COMM
PCB
O
XFORM
T1
R
C
Y
G
O
W2D
W2T
W3
Yo
SEC 1 F
ORG
F1
COM
SYSTEM TRANSFORMER: 40.0VA
FAN COIL/HEATER: 26.3VA
REMAINING VA AVAILABLE: 13.7VA
RELAY 3
8
6
LS2
LS3/4
HTR4
RELAY 3
2
4
3
LS1
HTR2
TRAN
YEL
LS4
1
L2
HTR3
JW2 JW1
FU3
YEL
YEL
L4
BRN
FU1
GND
FU2
L3
HTR1
BLK
L1
SEE RATING PLATE
FOR VOLTS & HERTZ
SEE NOTE #1
FU4
DISCONNECT PER NEC
FIELD POWER WIRING
CAPACITOR
COMMON
LOW VOLT FUSE
FAN MOTOR
EQUIPMENT GROUND
HEAT PUMP LOW VOLT
HEATER
LIMIT SWITCH
LED
LVTB
TRAN
XFORM
STEADY FLASH
1 FLASH
DIAGNOSTIC LIGHT
2
FLASHES
LOW VOLT TERM BRD
TRANSFORMER
3 FLASHES
PCB TRAN TERMINALS
FIELD HIGH VOLTAGE 4 FLASHES
FIELD LOW VOLTAGE
5 FLASHES
HPLV LEADS
MARKED TERMINAL
324991-101
REV. A
COOL MODE
6 FLASHES
DEFROST MODE
7 FLASHES
EMERGENCY HEAT
MODE
PCB JUMPER (JW)
UNMARKED TERMINAL
STAND BY CONDITION
OR FAN ONLY
HEAT PUMP HEAT
ONLY OPERATING
HEAT PUMP PLUS
1 RELAY
HEAT PUMP PLUS
2 RELAYS
HEAT PUMP PLUS
3 RELAYS
A00171
Fig. 20—Label Wiring 324991-101
—21—
CAUTION:
THIS COMPARTMENT MUST BE CLOSED EXCEPT FOR SERVICING
NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING 150V TO GROUND
BLOWER MOTOR
ROTATION
ATTENTION:
NE CONVIENT PAS AUX INSTALLATIONS DE PLUS DE 150 V A LA TERRE
SCHEMATIC DIAGRAM
COMPONENT ARRANGEMENT
DISCONNECT PER NEC
SEE RATING PLATE
FOR VOLTS & HERTZ
GND
L1
COM
SEE NOTE #1
RED
24 V
L2
208 V
230 V
BRN
BLK
YEL
TRAN
FIELD POWER WIRING
SYSTEM TRANSFORMER: 40.0VA
FAN COIL/HEATER: 5.0VA
REMAINING VA AVAILABLE: 35.0VA
YEL
208V 230V
C R
BRN
HI
MED
YEL
BLK
BLU
LO
RED
BRN
RED
TRAN
FM
GRN/YEL
GND
BRN
W2
WHT
SPT
GRY
BRN
E
CO
M
BLK
NO
FR
VIO
PCB
YEL
CAP
GRY
RED
G
R
F
T1
C
W3
FR
YEL
NO
F
NC
PCB
BLU
NC
4
4
BRN
RED
SPT
BRN
RECP
6 1
6 1
3 2
3 2
11 7
11 7
BLU
BLK
W2
9
9
WHT
PLUG
COM
C
T1
R
G
BLK
G
BARRIER
SEE NOTE #6
INDOOR
THERMOSTAT
OUTDOOR
UNIT
GND
RED-LOW
BLU-MED
BLK-HI
GRN/YEL-GND
FM
CAP
BRN
BRN
YEL-COM
SEE NOTE #5
FAN MOTOR THERMALLY PROTECTED
LEGEND
NOTES:
1. USE COPPER WIRE (75°C MIN.) ONLY BETWEEN DISCONNECT
SWITCH AND UNIT.
2. TO BE WIRED IN ACCORDANCE WITH NEC AND LOCAL CODES.
3. IF ANY OF THE ORIGINAL WIRE, AS SUPPLIED, MUST BE REPLACED,
USE THE SAME OR EQUIVALENT TYPE WIRE.
4. REPLACE LOW VOLTAGE FUSE WITH NO GREATER THAN 5 AMP FUSE.
5. (3) SPEED MOTOR SHOWN. OPTIONAL (2) SPEED MOTOR USES HI
(BLK) AND LOW (BLU OR RED).
6. CONNECT R TO R, G TO G, ETC., SEE OUTDOOR INSTRUCTION FOR
DETAILS.
CAP
COM
F
FM
CAPACITOR
COMMON
LOW VOLTAGE FUSE
FAN MOTOR
FIELD POWER WIRING
FR PCB FAN RELAY
FU LINE FUSE
GND EQUIPMENT GROUND
SPT FAN SPEED TAP
LOCATION
HEATER
LIMIT SWITCH
MARKED TERMINAL
PLUG AND
RECEPTACLE
PCB PRINTED CIRCUIT
BOARD
SEQ SEQUENCER
TRAN TRANSFORMER
UNMARKED TERMINAL
HTR
LS
321210-101 REV. G
A00162
Fig. 21—Label Wiring 321210-101
—22—
CAUTION:
THIS COMPARTMENT MUST BE
CLOSED EXCEPT FOR SERVICING
NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING 150V TO
GROUND
BLOWER MOTOR
ROTATION
ATTENTION:
NE CONVIENT PAS AUX INSTALLATIONS DE PLUS DE 150 V
A LA TERRE
LEGEND
20KW 1PH SCHEMATIC DIAGRAM
DISCONNECT PER NEC
FIELD POWER WIRING
SEE RATING PLATE
FOR VOLTS & HERTZ
SEE NOTE #1
L1
L2
GND
YEL
CB
COM
F1
FU
GND
BLK
PLUG 2
9
11 7
3
2
6 1
4
9
11 7
3
2
6 1
4
HTR
FIELD POWER
WIRING
MARKED TERMINAL
PLUG AND
RECEPTACLE
CIRCUIT BREAKER
COMMON
LOW VOLTAGE
FUSE
LINE FUSE
EQUIPMENT
GROUND
HEATER
HVTB
ICM
LS
PCB
R
REC
RECP
TDR
TRAN
HIGH VOLTAGE
TERM BLOCK
FAN MOTOR
LIMIT SWITCH
PRINTED CIRCUIT
BOARD
RELAY
RECTIFIER
RECEPTACLE
TIME DELAY
RECTIFIER
TRANSFORMER
RECP 2
BRN
COMPONENT ARRANGEMENT
SEC1 SEC2
BLK
Com 208V
AUX HEAT KW/CFM
KW
CFM
W
1
VIO
230V
F1
BRN
AC/HP SIZE
12
9
8
7
BLU
VI RE BR OR
O
D N N
10
6
2
1
NOM
PLUG 3
LO
HI
O
ON/OFF DELAY
0
30
0
90
90
0
HI
C
WHT
5 4 3 2 1
LO
CONTINUOUS FAN
MED
HI
AUX1 HUM1
BLK WHT VIO
BLK BLU ORN BRN
COM
RED
24 V
BRN
ICM
208 V
230 V
GND
24 VAC
1
GRY
HEATER / MOTOR
16 15 14 13 12 11 10 9
8 7 6 5 4 3 2 1
HEATER / MOTOR
AUX 2 HUM2
YEL
GND
PL1
GRN WHT VIO ORN
YEL RED GRY
C
YEL
GRN/YEL
PLUG 1
O
PL1
G
BLK
YEL
Y
1
Y/Y
2
G
Y/Y
2
HP-EFF
AC/HP CFM ADJUST
ORN
BLK
BLK
GR Y B W
N EL LK HT
3
HP-COMFORT
ORN
WHT
5
4
AC
W
1
W2
Y
1
SYSTEM TYPE
11
F1
W
2
BLU
GR
Y
VIO
RED VIO
R
D
H
R
D
H
SEC2
TRAN
SEC1
PCB
OUTDOOR UNIT
YEL
PCB
INDOOR THERMOSTAT
RED
TRAN BRN
NOTES:
1.
RECP 3
2.
ICM
3.
4.
RECP 4
GRY
5.
PLUG 4
6.
7.
8.
326014-101 REV. B
USE COPPER WIRE (75*C MIN) ONLY BETWEEN
DISCONNECT SWITCH AND UNIT.
TO BE WIRED IN ACCORDANCE WITH NEC AND LOCAL
CODES.
TRANSFORMER PRIMARY LEADS, BLUE 208V, RED 230V.
IF ANY OF THE ORIGINAL WIRE, AS SUPPLIED, MUST BE
REPLACED, USE THE SAME OR EQUIVALENT TYPE
WIRE.
REPLACE LOW VOLTAGE FUSE WITH NO GREATER
THAN 5 AMP FUSE.
DUAL CIRCUIT WIRING SHOWN.
USE 60 AMP CLASS K FUSES ONLY, FOR REPLACEMENT.
CONNECT R TO R, G TO G, ETC., SEE OUTDOOR
INSTRUCTION FOR DETAILS.
A00184
Fig. 22—Label Wiring 326014-101
—23—
© 2001 Payne Heating & Cooling
P.O. Box 70, Indianapolis, IN 46206
—24—
wdpf1m01