SEC-H-INT-KP SmartKey

advertisement
SEC-H-INT-KP SmartKey
INSTALLATION INSTRUCTIONS
This document covers the mounting and wiring of the SEC-HINT-KP remote intrusion arming display/keypad (SmartKey) in
a Honeywell Security Appliance system, hosted by a security
controller (SEC-H-201 or SEC-H-600 model controller).
Description
The SEC-H-INT-KP is a remote intrusion display/keypad used
to arm, disarm, and monitor intrusion zones. The integral
graphic LCD display features a white backlight, and 128 X 64
resolution. The keypad features a blue backlight, 4 function
keys, and 12 data keys.
SMARTKEY
OVERALL DIMENSIONS
IN INCHES AND (MM):
HEIGHT: 5.12” (130)
WIDTH: 3.23” (82)
DEPTH: 0.83” (21)
COLOR: SILVER GREY
MATERIAL: ABS
Notes
• This device is intended for installation in secure indoor
locations only. Operating temperature range is 14°F to
131°F (-10°C to 44°C).
• Power this device using the 12 VDC reader output of the
SEC-H-201, SEC-H-600, or SEC-H-R2R reader expansion
module. Device current draw is 150mA. See the
“Estimating Power and Battery Requirements” section in
the installation guide for the security controller to determine
power supply, battery, and cable requirements.
• Communication to the SmartKey device is via an RS-485
port wired to an NPB-2X-485 option card installed in the
Option Card 2 slot of the security controller. Refer to the
NPB-2X-485 Option card installation sheet for details. Note
that the SmartKey does NOT communicate on the same
RS-485 bus as the SEC-H-R2R and SEC-H-RIO modules.
• A maximum of 10 SmartKeys may be installed per security
controller.
Not covered in this document is the setup and operation of
installed SEC-H-INT-KP SmartKeys. Refer to the WEBs AX
Security Controller User's Guide (number 74-4062) for this
information.
For all other related mounting and wiring details, refer to the
appropriate mounting and wiring document. See “Related
Documentation” on page 3.
M27319
Fig. 1. SEC-H-INT-KP SmartKey.
Included in this Package
Included in this package you should find the following items:
• an SEC-H-INT-KP SmartKey, with removable mounting
backplate.
• This document SEC-H-INT-KP SmartKey Installation
Instructions, Number 62-0272.
Material and Tools Required
The following supplies and tools are required for installation:
• Small wire nuts, for making wiring terminations to
SmartKey terminals.
• Suitable tools for installing wall fasteners and preparing
wires for connections.
Recommended Cable Types
The following cable types are recommended for wiring
between an SEC-H-INT-KP SmartKey and the security
controller or SEC-H-R2R module (see Figure 4 on page 3):
• RS-485 data communications: Belden 9501 (1 pair) or
9502 (2 pair), 24AWG shielded twisted-pair, or equivalent.
• 12Vdc power: Belden 9154, 1 pair 20AWG shielded
twisted-pair, or equivalent.
62-0272-01
SEC-H-INT-KP SMARTKEY
MOUNTING
Mount the SEC-H-INT-KP backplate onto a wall junction box,
with wiring cable(s) passed through center opening. See
Figure 2 for dimensions.
WIRING
Only two connectors on the back of the SEC-H-INT-KP
(Figure 3) are used: J1 (Power) and J5 (RS-485 comm).
3-5/32 (80)
6
2-23/64 (60)
J3
1-3/16
(30)
5
4
31/64
(12)
J2
3
2
4
5
3
2
1
31/64
(12)
3 2 1 J5
2
3
1
J5 DATA
(SHIELD) EARTH
J4
1
(YELLOW) DATA (+)
3
2
1
3 2 1 J6
5 4 3 2 1 J7
3
2
1
J1
2-23/64
(60)
5
(127)
(GREEN) DATA (–)
J1 POWER
(YEL/GRN) EARTH GND
(BLACK) GND
(RED) + 12V-15 VDC
3
2
1
M27321
31/64
(12)
Fig. 3. Connector Detail, Rear View of SEC-H-INT-KP.
31/64
(12)
Connectors have pre-attached leads—make wiring
terminations to leads using small wire nuts. Lead colors are
shown (in parenthesis) in Figure 3.
Ø 1/64 (4)
CAUTION
Electrical Shock Hazard
Before making wiring terminations, remove power
from the security controller or SEC-H-R2R module.
Restore power only after making all wiring
terminations and fastening the SEC-H-INT-KP
SmartKey unit onto its mounted backplate.
M27320
Fig. 2. SEC-H-INT-KP backplate dimensions.
Fasten with the appropriate screws into the mounting slots.
Note that up to 10 SEC-H-INT-KP SmartKey units are
supported, where RS-485 wiring from the security controller
(NPB-2X-485 option card) is “daisy-chained” at the data J5
connector on each SmartKey. For any SmartKey installed on
either end of this RS-485 buss, set its EOL Resistor JUMPER
1 to the ON position.
Wire 12VDC power to the unit from the reader input of the
security controller, or if closer, the reader input of an SEC-HR2R module. Use shielded, twisted-pair cabling for all wiring,
with the shield continuously connected and grounded to earth
at one point only. See “Recommended Cable Types,” page 1.
62-0272—01
2
SEC-H-INT-KP SMARTKEY
EXAMPLE WIRING DIAGRAM
JUMPER 1
SEC-H-INT-KP
SMARTKEY 2
J5
C4
BELDEN
9502 OR
EQUIVALENT
NC4
NC3
NO4
2 1
2 1
PAIR 1
-
PS–
NPB-2X-485
OPTION CARD IN
OPTION SLOT 2
S
PS+
BB
SECURITY CONTROLLER
AX3
AX2
AX1
D1
BT–
BT+
PS+
PS–
SI6
SI5
GND
SI4
GND
SI3
SI2
GND
SI1
DI3
DI2
GND
DI1
D0
S
DC+
+
S
GND
-
+
DC+
-
+
S
AX2
AX3
BB
-
+
AX1
PS+
PS–
BB
SEC-H-R2R
-
D1
PS–
PS+
BB
D0
S +
GND
-
CUT AND TAPE
BACK SHIELD
TO OTHER
UNITS
SI1
SI2
SI3
GND
GND
C2
SI4
NC2
PS–
PS+
S +
PAIR 2
BELDEN
9502 OR
EQUIVALENT
C1
DI1
DI2
+
S
3
3
BELDEN 9154
OR EQUIVALENT
NPB-2X-485 OPTION
CONNECTOR PLUG
(SHOWN SCREW
SIDE UP)
C3
C1
NC1
NO2
NO1
D1
DC+
D0
-
GND
AX1
AX3
AX2
DC+
D1
D0
AX1
GND
AX3
BELDEN
9501 OR
EQUIVALENT
AX2
J1
BELDEN
9501 OR
EQUIVALENT
C2
2 1
2 1
NC2
J1
3
3
NO3
J5
NO1
CUT AND TAPE BACK SHIELD
OFF
NC1
EOL RESISTOR JUMPER 1
SHOULD BE IN THE ON POSITION
ON AN END UNIT ONLY
ON
GND
JUMPER 1
SEC-H-INT-KP
SMARTKEY 1
From the SEC-H-R2R module, another 2-pair cable is run to
the SmartKey #2 unit, which allows for RS-485 “multidrop”
wiring (using one pair to return back to the SEC-H-R2R
module). Wiring can continue in this fashion to other SEC-HR2R modules and SmartKey units, if needed.
NO2
Figure 4 shows an example wiring diagram for a system using
two SEC-H-INT-KP SmartKeys. Note in this example,
SmartKey #1 is installed at the end of the RS-485 buss, on
which the security controller is daisy-chain connected on its
NPB-2X-485 option connector. From there, this SmartKey
buss continues on one pair of a 2-pair cable run to the SEC-HR2R module (the other pair is used for RS-485
communications between the security controller and its
expansion modules).
M27322
Fig. 4. Example wiring diagram for system with two SEC-H-INT-KP SmartKey units.
RELATED DOCUMENTATION
When done wiring, insert the SEC-H-INT-KP SmartKey onto
its backplate and secure with the screw in the bottom of its
case.
Wiring Checkout
After completing wiring terminations and restoring power to
the security controller, the LCD display on the SEC-H-INT-KP
SmartKey should display time, and keys should be backlit in
blue. This verifies power to the SmartKey.
To verify RS-485 communications, refer to the WEBs AX
Security User's Guide for setup procedures.
For more information on mounting and wiring a WEBs
Security system, refer to the following documents:
• SEC-H-201 Security Controller Installation Guide, 95-7750
• SEC-H-600 Security Controller Installation Guide, 95-7759
• SEC-H-R2R Remote Reader Module Installation Guide,
95-7749
• SEC-H-RIO Remote I/O Installation Guide, 74-4060
• SEC-ENC-H-1 and SEC-ENC-H-2 Medium and Large
Enclosure Installation Guide, 95-7747
• SEC-ENC-H-3 Small Enclosure Installation Guide,
95-7748
For details on software configuration for a fully functioning
security system, refer to the following document:
• WEBs AX Security Controller User's Guide, 74-4062
3
62-0272—01
SEC-H-INT-KP SMARTKEY
By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the
literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including
attorneys’ fees, arising out of, or resulting from, any modification to the literature by you.
Automation and Control Solutions
Honeywell International Inc.
Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North
35 Dynamic Drive
Golden Valley, MN 55422
Toronto, Ontario M1V 4Z9
customer.honeywell.com
® U.S. Registered Trademark
© 2008 Honeywell International Inc.
62-0272—01 M.S. 03-08
Download