Comparison of H-Bridge Single-phase Transformerless PV String Inverters Jacson R. Dreher1, Filipe Marangoni2, Luciano Schuch3, Mário L. da S. Martins2,3 Leandro Della Flora4 4 1 Federal Institute of Santa Catarina, IFSC 2 Federal University of Technology – Parana, UTFPR 3 Federal University of Santa Maria, UFSM fi.marangoni@gmail.com, mariolsm@gmail.com Abstract— This paper presents a detailed comparison among single-phase transformerless string inverters for grid-connected PV systems. The characteristics of the PV modules and their nonidealities are taking into the account for the design and the performance of the inverter with respect to the IEEE 1547 Standard. Simulated and experimental results for the inverter topologies are carried out. Keywords- Grid connected PV System; String Inverter; Transformerless Inverter. I. INTRODUCTION II. GRID-CONNECTED INVERTER TOPOLOGIES PV systems are modular by nature, increasing the power by adding PV modules, [1]. These PV modules are gathered in a set of series and parallel connections by an array. Depending on the type of the array the system can be classified in different categories, [1]. If there is only one inverter for the entire set of series and parallel connections of the PV modules, the power converter system is called central inverter. Otherwise, it is named decentralized inverter. Further classification of decentralized inverters is given according to the number of modules and series strings of modules, Fig. 1. As the name implies, the module-integrated (or AC-module) concerns the inverter that operates from a single PV module. As the power converter is dedicate to only one PV module, it can be designed and optimized for the module characteristics, enhancing its performance and power generation. On the other hand, the string inverter is a system that comprises a single string of PV modules of about ten to twenty series connected PV modules. This way, higher power is achieved. Nevertheless, the total power is proportional to the system DC bus voltage and, consequently, to the number of PV modules of the string. When more power is needed, the alternative is to use multistring inverters. In this system, each string has a dedicated DCDC stage that is connected with its output in series with other ... ... ... ... ... ... ... ... On the other hand, H-bridge family of inverters requires half of the input voltage demanded by the half-bridge topology, that is, around 350 VDC. To avoid a varying common-mode voltage, the H-bridge has to be modulated with bipolar PWM, leading to high current ripple levels that should be handled by the output filter [2]. Intending to overcome these limitations several topologies have been proposed. This paper proposes a comparative analysis among the most popular single-phase Hbridge transformerless topologies. ... Domestic PV systems are mostly low-power single-phase systems (up to 10 kW) and are becoming more important worldwide. These systems are usually private where the owner aims the maximum system profitability. In this grown lowpower PV market there has an increased concern for the need of power processing systems characterized by high efficiency, small size and weight, and chiefly low cost. To achieve such characteristics, it is mandatory to eliminate the output line frequency transformer. Nevertheless, in order to avoid leakage currents and the injection of dc current into the grid, it is necessary for transformerless inverter to be modified with respect their circuit and switching strategy when compared to standard H-bridge topologies. These modifications intend to make the inverter operates with no variable common-mode voltage [1]. An interesting alternative is found in the halfbridge family of inverters, because of the natural ground of their DC bus mid-point. With two or more voltage levels the half-bridge inverters could be a simple choice to implement transformerless good quality grid-connected PV systems. The main drawback of this alternative is the need of high input voltages, which involves either the use of a large PV string or a step-up stage, offsetting the low component count advantage of the transformerless inverters. Danfoss Power Electronics Loves Park, Illinois, USA ldellaflora@gmail.com ... (a) (b) (c) (d) Fig. 1. Grid connected PV systems concepts. (a) module-integrated, (b) string, (c) multistring and (d) central inverter concept. DC-DC stages to the input of a single inverter stage. This way, the multi-string inverter has the advantages of both string and central inverters, i.e., it has decentralized MPPT for a small group of PV modules, but a single standard inverter. A. H-bridge inverter The H-bridge topology with standard unipolar modulation cannot be used in transformerless PV systems, due to leakage currents problem aforementioned. Fig. 2(a) shows the main voltages of a H-bridge with unipolar PWM. The grid voltage is the blue trace, the H-bridge pulsating voltage is shown in red and the common voltage (VCM) is shown in gray. It can be observed that VCM swings at the switching frequency around the half of the bus voltage value. This voltage variation discharges the parasitic capacitances, injecting the leakage current through the circuit into the grid. To reduce the leakage current, the VCM must be kept constant. Fig. 2(b) shows the main voltages of a H-bridge with bipolar PWM. It can be observed that VCM remains still at half of the bus voltage value. In spite of solute the leakage current problem, the bipolar PWM impose twice the dv/dt (Fig. 3) to the inverter output filter compared to the unipolar PWM, causing the increase of inductor value, size and, consequently cost. As can be seen in Fig. 3, to keep Imax the same the value of the inductance must be the double. In order to keep VCM constant with a three level voltage applied to the output filter, some modifications of the H-bridge will be present in the next sections. B. HERIC inverter This topology, shown in Fig. 4, is comprised by a standard H-bridge circuit that is modulated in a bipolar PWM mode. However, the switches at the same branch do not operate complementarily, instead of, they operate only for a half-cycle of the grid voltage and are hold inactivate in the other one [3]. To implement the freewheeling stage, an additional branch is VDC 0 vagv VDC 2 vagv t VAB vagv 0 i t -VDC 2 i Imax i Imax ipp ipp t t Imax d Imax d TAB TAB (a) (b) Fig. 3. Output voltage and current waveform of (a) unipolar PWM and (b) bipolar PWM. used. It is placed in parallel with the load, before the output filter and comprises two switches in opposite direction, which provides an alternative path for the load current in each halfcycle of the grid voltage waveform. This AC-bypass provides a zero voltage level to the output voltage waveform, reducing the occurrence of leakage currents, since the PV array is decoupled from the grid during the freewheeling stage. The operating stages during the positive output voltage half-cycle are shown in Fig. 3. It can be observed that during the free-wheeling stage the DC bus is disconnected off. The AC switch S5 could stay on during the entire positive output voltage half-cycle, or to be modulated complementarily to S1/S4. In practice voltage at the middle point of both inverter legs is equal during free-wheeling interval, however it is at a potential is not clamped and thus it can vary between VDC and zero, as will be demonstrated later. C. H5 inverter This inverter, shown in Fig. 5, basically consists of a standard H-bridge with two high-frequency switches and two low-frequency switches per cycle. Likewise the HERIC +VDC S3 S1 Vcm +VDC/2 PV 0 C VDC S6 -VDC/2 B -VDC PV 0 4.16 8.33 12.50 16.67 20.83 25.00 29.17 Time (ms) S4 S1 Vcm PV C 0 VDC S3 S6 B PV -VDC 4.16 8.33 12.50 16.67 20.83 25.00 29.17 33.34 Time (ms) (b) Fig. 2. Main voltage of H-bridge inverter. (a) With unipolar PWM modulation (b) With bipolar PWM modulation. 0 igrid A -VDC/2 0 vgrid VAB (a) (a) +VDC +VDC/2 S5 S2 0 33.34 igrid A S2 S5 vgrid VAB S4 (b) Fig. 4. HERIC inverter operating stages during positive output voltage half-cycle. (a) Power transfer stage (b) Free-wheeling stage. topology, the H-bridge switches are not complementary operated. To implement the PWM modulation, a DC-bypass approach is introduced, which consists of the switch (S5) that is activated every time the high-frequency switches are on [3]. It can be seen that besides to modulate the PWM, the switch S5 also decouple the PV array from the grid. The main advantage of H5 is that only five switches are required, instead of six, like the HERIC inverter. The main difference in the operation of the inverter is that three devices are on during the power transfer stage, which augments the conduction losses. The free-wheeling stage is accomplished by the H-bridge devices. During this stage, it can be seen in Fig. 5(b) that voltage VDC is applied across switches S5 and S2 and hence, the middle point of the inverter legs is effectively in the half potential. Nevertheless, to make the freewheeling always with switches S3 on, it will present high conduction and switching efforts than the other H-bridge devices. D. H6 inverter In the H6 inverter topology, there is the addition of the S6 switch (Fig. 6) that is placed in series connections with the negative DC-rail. It operates in a very similar way as the H5 topology, nevertheless, the free-wheeling stage can be accomplished keeping S1 and S4 on (for the positive half cycle) or S2 and S3 on (for the negative half cycle). It distributes equally the device efforts and balances the thermal distribution. Voltage VDC will appear across the switches S5 and S6 during the free-wheeling stages. The disadvantage of the H6 is that four devices are on during the power transfer stages. On the other hand, all switches anti-parallel diodes are put on conduction during the free-wheeling stages, which requires that they present low reverse recovery losses. It implies that IGBT is preferable for the H6 inverter. E. H6D1 inverter To implement the H-bridge switches with high speed MOSFETs, it is required to give an alternative path to the freewheeling current to flow. It is accomplished by an extra diode placed across the H-bridge, as shown in Fig. 7. In this topology the extra disadvantage is that the freewheeling stage presents three devices on that enlarge the PV C PV C S3 S1 VDC 0 S6 S2 C igrid 0 S2 PV C B PV 0 S3 PV C igrid VDC PV C VDC 0 S3 A PV C igrid S2 S4 S2 S1 S4 (c) Fig. 5. H5 inverter operating stages. (a) Power transfer stage for positive output voltage half-cycle; (b) Power transfer stage for negative output voltage half-cycle; (c) Free-wheeling stage. S3 A VDC igrid vgrid VAB vgrid VAB 0 S6 (c) B PV vgrid B PV S5 S1 igrid VAB (b) S5 S3 A S4 S2 S4 S1 vgrid VAB 0 S2 S5 B PV S6 (b) A VDC vgrid VAB S4 S1 igrid A VDC (a) S5 S3 S1 vgrid VAB S4 (a) B PV vgrid VAB B PV PV A VDC igrid A S5 S5 S3 S1 S5 B PV 0 S6 S2 S4 (d) Fig. 6. H6 inverter operating stages. (a) Power transfer stage for positive output voltage half-cycle; (b) Free-wheeling stage for positive output voltage half-cycle; (c) Power transfer stage for negative output voltage half-cycle; (c) Free-wheeling stage for negative output voltage half-cycle. S5 PV VDC C S3 S1 TABLE I. igrid A CURRENT vgrid D VAB 0 S2 S6 S4 S5 VDC C S3 S1 igrid A vgrid D VAB B PV 0 S6 S4 S2 (b) Fig. 8. H6D1 free-wheeling stages. (a) For positive output voltage half-cycle; (b) For negative output voltage half-cycle. conduction losses. F. H6D2 inverter The high conduction losses of H6 and H6D1 can be reduced if the DC bus MOSFETs and free-wheeling diodes could be rated for low voltages, which are possible using the approach shown in Fig. 8. It can be noticed that only half of the bus voltage is applied across the DC bus MOSFETs and freewheeling diodes. Aiming to summarize the main features of the abovementioned topologies Table I presents concise information about all inverters described in this section. III. PV STRING AND GRID SPECIFICATIONS Intending to analyze practical aspects of the previously S5 C1 VDC PV 2 C VDC C2 2 PV S6 0 S3 S1 D1 PV S5 C1 VDC 2 C C2 VDC 2 S6 0 1.5 0.6 0.3 5.0 discussed inverters this section presents a brief discussion about some key design and implementation characteristics that may benefit or offset a specific topology in detriment of the others. A. Grid connection and Standards Most of standards dealing with utility interconnection regard for the level of the DC current injected to the grid (see IEEE 929-2000, IEC 61727, IEEE 1547, EN 61000-3-2) and this varies between 0.5 and 1% of the rated current. They also concern about the harmonic content that is always limited. Table II show the limits for the IEEE 1547. In addition, some standards, like the German DIN VDE 0126-1-1, in case of transformerless PV inverters connected to the grid, impose the need for a Residual Current Monitoring Unit (RCMU), which is sensitive for DC and AC currents and can sense DC fault currents. In case the leakage current to ground (peak value) is greater than 300mA, then disconnection is necessary within 0.3s. Hence, the design of the inverter filter must cope with the requirements impose by the Standard. Furthermore, the leakage current also has an important role in the filter specification as will be discussed later. In buck derived inverter topologies, the DC-bus must be at a voltage slightly higher than the peak of the grid voltage, so that the current flows only from the inverter to the grid. This way, the number of PV modules in the string and the irradiation/temperature conditions that guaranty such conditions must be taken into account in the design of the PV vgrid VAB D2 TABLE II. COMPARATIVE OF H-BRIDGE STRING INVERTERS B S2 S1 D1 2.0 igrid A Inverter Features S4 Topology S3 Bipolar Hbridge Unipolar Hbridge (a) PV 4.0 * Even harmonics are limited to 25% of the odd harmonic limits above. (a) PV Harmonic order h H < 11 ≤ h 17 ≤ h 23 ≤ h 35 ≤ Total Harmonic (odd)* 11 < 17 < 23 < 35 h Distortion (THD) Percent (%) B PV MAXIMUM HARMONIC CURRENT DISTORTION IN PERCENT OF A igrid vgrid VAB D2 B S2 S4 (b) Fig. 7. H6D2 inverter operating stages during positive output voltage half-cycle. (a) Power transfer stage; (b) Free-wheeling stage. HERIC N. of switches / diodes Output voltage Switches on (diodes on) 4/4 2 levels 2 (0) / 0 (2) 4/4 3 levels 2 (0) / 1 (1) 6/2 3 levels 2 (0) / 1 (1) H5 5/4 3 levels 3 (0) / 1 (1) H6 6/4 3 levels 4 (0) / 2 (2) H6D1 6/5 3 levels 4 (0) / 2 (1) H6D2 6/6 3 levels 4 (0) / 2 (2) Freewheeling diodes of the bridge diodes of the bridge AC bypass (a) diodes of the bridge diodes of the bridge DC bypass (b) DC bypass (c) a) 1 switch and 1 diode on; b) 1 diode on; c) 2 diodes on. system. 2000 1800 1600 1400 1200 1000 800 600 400 200 0 Expression (1) can be used to determine the minimum voltage to the DC-bus and further the number of PV modules in the string (expression (2)). 1 2t VS VDC min Vgrid max ma max Ts Where, VΔS represents the total voltage drop of all on semiconductors in conduction; tΔ is the defined as blanking time or dead time; Vgrid is the peak of grid voltage; mamax is the modulation index. N mod VDC min VPV min , N mod Z Where, Nmod is the number of the modules, VDC(min) is the minimum voltage required for the DC-bus and VPV(min) is the minimum voltage of a single PV module under the worst irradiation/temperature conditions. Figure 9 show the VDC(min) in function of the switching frequency. The curve is plotted for a grid voltage of 127 V and also takes into account the data for a standard PV module given in Table III. B. PV characteristics and DC-bus voltage As the PV modules have a characteristic curve that is modified with temperature and solar irradiation, during the day, the voltage and the current at the maximum power point of the PV array will vary in a large range of values. The least irradiation value (100 W/m2), at 25°C, produces a voltage of 21.7V and a current of 0.757A per PV module. At this operation point the produced power is the lower and the DCbus voltage is at VPV(min). The high irradiation condition (1000 W/m2) at 25° produces a voltage of 26.2V and a current of 7.637A per PV module. The DC-bus voltage achieves the VDC(max). Hence, during the PV system operation the DC-bus TABLE III. PV MODULE PARAMETERS FROM KC200GT Parameter Irradiation Temp. VPV (IPV) 100 W/m² 25°C VPV (IPV) 1000 W/m² 25°C 215 210 205 200 195 190 185 180 Value 21.7 [V] (0.757 [A]) 26.2 [V] (7.637 [A]) 11 modules 40 60 0 50 100 150 200 250 VDC(min)VPV(min) VDC(max) 300 Voltage (V) VPV(max) Fig. 10. PV String power versus voltage. voltage variation can be defined as Vop. Analogously, the power of the PV string also varies as determined by PPV. Nevertheless, when the PV string is disconnected, the voltage of each PV module reaches its highest value that is the open circuit voltage. At this point, the PV string is at VPV(max). From the inverter design perspective, the power stage must be designed to support the open circuit voltage of the PV string (VPV(max)) and the maximum PV module current IPV at 1000 W/m2. On the other hand, the controller design should be able to handle the inverter operation with a DC-bus disturbance of Vop. C. Inverter output voltage and ripple of the grid current For bipolar modulation the output voltage assumes two values, VDC or -VDC. The frequency fAB of the output voltage is the same as the switching frequency, i.e., fAB = fs. For the HERIC, H5 and H6*, the bypass switches clip the voltage waveforms at the zero voltage level, yielding a three level PWM, due to additional switches used during the freewheeling stage, thus the voltage levels are VDC, 0 (zero) and -VDC. Thus, the current ripple can be determined by means of Fig. 3(a). From the inverter circuit it can be observed that, i pp VDC vgrid t d t .TAB L Where VDC is the bus voltage; vgrid (t) is grid voltage during a period TAB; and d(t) is the duty-cycle of the PWM at a switching period. Since the vgrid and d(t) varies in during the output voltage period, an average ripple should be determined in order to define L. This way, the ripple factor (RFsw) was proposed by [5] and it stands for the ratio between the current ripple and its fundamental component. It can be seen as a quality factor of the total current injected in the grid and is given by (4), 20 Vop RFsw IR 100 % I o1 Expression (3) can be expressed in terms of output voltage angle (θ) as follows, 10 modules 0 PPV 80 100 120 140 160 180 Switching frequency [kHz] Fig. 9. Minimum DC-bus voltage versus the switching frequency. i pp VDC TAB 1 ma sin ma sin L Where θ varies in the interval 0 < θ < π of the output voltage. Thus, the switching ripple factor of grid-connected singlephase inverters (RFsw) can be found dividing expression (8) by expression (9). Reversely, the filter inductor can be given by 16 14 Bipolar 12 10 f = f AB sw 8 6 f = 2fsw 4 AB 2 0 100 200 300 400 500 600 Irradiation (W/m²) 0 700 800 900 1000 Fig. 12. Filter inductor versus PV string irradiation. The ripple current waveform for a grid period is shown in Fig. 11(a) and Fig. 11(b), describes the distribution of the filter inductor current (triangle waveforms), where the magnitude of any k-th triangle waveform can be calculated as (6). In analogy, the peak-to-peak value of the filter inductor current Δipp that results imax k VDCTAB 1 ma sin k ma sin k 2L where, k 2k 1 4m f , k 1, 2,..., m f . Since the RMS value of each triangle wave is Δimax(θk)/√3, the RMS value of IR is, IR 2 imax k mf k 1 k 2 3 2 3 /2 0 2 imax d L 1 TAB 4 3ma2 Lgrid 1 RFsw T 3 4 4 4ma 3 Figure 12 shows the expression (10) versus the solar irradiation for three conditions of VAB, bipolar PWM, unipolar PWM, and double frequency unipolar PWM. It can be seen that the inductor size is inversely proportional to the irradiation. It also is observed that inductor value reduces with the reduction of dv/dt and also with the increasing of frequency. D. Synchronism and Current Control In grid-connected applications, the current control is the key to the inverter performance. For a single-phase inverter to use PI controllers in D-Q frame, it is required an additional imaginary or orthogonal signal to move to D-Q frame. At synchronous frame the PI controllers provide zero steady state error. The block diagram of the inverter and the current controller in D-Q frame is shown in Fig. 13(a) and Fig. 13(b), respectively. The construction of the synchronous frame consists in measure the grid current and passes it through a Kalman filter to get its orthogonal value. The complete diagram of the system is shown in Fig. 14. The Kalman blocks are applied to generate the orthogonal signals for the PLL and to estimate the current in quadrature to the synchronous frame for the current controller. The system performance can be evaluated with respect of By calculating the integral, the RMS value of the switching ripple current, it can be found that IR VDC TAB 2L 2ma2 3ma2 1 3 4 4 4 ma 3 And the fundamental component is given by, I o (1) VDC ma 2 Z grid VDC maT 2 2 Lgrid (a) IR Imax| ipp| t /2 0 k IR ir (a) max(k) Imax(k)| ipp(k)| Ir(k) k = 2mf t (b) Fig. 11. Ripple current. (a) RMS value and (b) detail of RMS ripple current. (b) Fig. 13. Block diagrams in D-Q frame. (a) Inverter model; (b) Current controller. Fig. 15. Block diagrams for the whole system. sudden shadowing that can change rapidly the reference for the D-Q frame current controller. The current Id response for a step change of 100% is shown in Fig. 15(a). The system reaches the steady-state in 48.12 ms. On the other hand, grid disturbance can also affect the current controller. The current Id response for a step change of 10% in the grid voltage is shown in Fig. 15(b). It can be seen that the system respond quickly ensuring a good performance. Figure 16 show the experimental waveforms for the grid voltage and current of the HERIC inverter for an emulated irradiation of 500 W/m2. It can be observed that the synchronism is achieved and the current is of good quality. IV. COMPARATIVE ANALYSIS Besides the HERIC inverter to provide the AC decoupling of the grid, the common mode voltage of the inverter is not 30 48.12 ms 48.12 ms 20 10 0 0.3 0.35 0.4 Time (s) Aiming to compare the impact of the leakage current in the grid current, Table V, VI, VII and VIII show the comparison of the grid current harmonics for the HERIC, H5, H6 and H6D2. The simulation results take into account a parasitic PV capacitance of 200 nF. It can be seen for the HERIC inverter that for irradiation below 400 W/m2, the THD is larger than the permit by IEEE 1547 Standard. It means that the leakage current degraded the harmonic performance of the HERIC inverter in such way that, in spite of the design consider its operation for irradiation as low as 100 W/m2, the HERIC inverter should be turned off at four times high due to Standard compliance. In Table VI, the simulated results for the H5 inverter show a slightly better numbers. The THD for H5 inverter do not reach the requirements for irradiation lower than 300 W/m2. -10 -20 -30 0.25 kept constant. It presents a variation at high frequency as shown in Fig. 17. These voltage variations reach almost 100V of peak, which can increase the leakage current and degrade the grid current harmonic performance, mainly for low irradiation conditions, as can be seen in Table IV. The experimental current measured THD for irradiations below 400 W/m2 do not comply with IEEE 1547 Standard. The H6 inverter presented results comparable to the HERIC inverter and also do not comply with the IEEE Standard for irradiation lower than 400 W/m2. 0.45 0.5 Table VIII show the results for the H6D2 inverter. (a) 30 20 10 0 Vgrid(d) 10 -10 -20 -30 Vgrid(d) - 10% 10 Overshoot Settling time 0.25 0.3 0.35 Time (s) 0.4 0.45 (b) Fig. 14. System response for Id and Igrid. (a) Id step of 100%; (b) Vgrid step of 10%. Fig. 16. Grid voltage and current for the HERIC inverter. [3] [4] [5] F. Schimpf, L. E. Norum, “Grid Connected Converters for Photovoltaic, State of the Art, Ideas for Improvement of Transformerless Inverters.” Nordic Workshop on Power and Industrial Electronics. B. Yang, W. LI and Y. DENG, “A novel single-phase transformerless photovoltaic inverter connected to grid.” Power Electronics, Machines and Drives, p.1-6. H. Kim, K.H. Kim, “Filter design for grid connected PV inverters,” IEEE ICSET 2008, p. 1070-1075. HERIC INVERTER SIMULATED THD TABLE V. Fig. 17. Measured common mode voltage for the HERIC inverter. TABLE IV. Irradiation [W/m²] 500 400 300 200 100 HERIC INVERTER EXPERIMENTAL THD Pin [W] Pout [W] 950.2 746.8 537.8 341.3 151.1 η [%] THD 913 96.063 4.373 718 96.186 5.781 * 519 96.421 6.101 * 331 97.018 8.302 * 148 97.923 14.571 * * Do not comply with IEEE 1547 Standard Compared to the other topologies, it presented the worst performance and it complies with the IEEE 1547 Standard for irradiation higher than 700 W/m2. V. CONCLUSION This paper presented a comparison among single-phase transformerless inverters for grid-connection applications. It demonstrate that in spited of the design of the output filter to allow the inverter operation for low irradiation conditions, the leakage current injected to the grid due to the absence of the of the line transformer, degrades the THD, limiting the operation of most of String inverters to irradiations of 300 W/m2, 400 W/m2 and even 600 W/m2. This limitation in the range of operation of the inverters quite reduces the power generated by the inverters. ACKNOWLEDGMENT The authors would like to express their gratitude to ‘Conselho Nacional de Desenvolvimento Científico e Tecnológico–CNPq’ (proc. 554103/2010-9 and proc. 481432/2011-6) for financial support and Xilinx for material support. REFERENCES [1] [2] M. Calais, and V. G. Agilidis, “Multilevel converters for single-phase grid connected photovoltaic systems-an overview.” IEEE International Symposium on Industrial Electronics, p.224-229. G. Spagnuolo, G. Petrone, S.V. ARAUJO, et al, “Renewable Energy Operation and Conversion Schemes: A Summary of Discussions During the Seminar on Renewable Energy Systems,” IEEE Industrial Electronics Magazine, v.4, n.1, p.38-51. Irradiation [W/m²] 1000 900 800 700 600 500 400 300 200 100 igrid [A] 14.273 12.726 11.195 9.682 8.187 6.716 5.270 3.856 2.485 1.174 TABLE VI. Irradiation [W/m²] 1000 900 800 700 600 500 400 300 200 100 H5 INVERTER SIMULATED THD igrid [A] 14.287 12.741 11.209 9.697 8.202 6.730 5.280 3.869 2.497 1.190 TABLE VII. Irradiation [W/m²] 1000 900 800 700 600 500 400 300 200 100 Irradiation [W/m²] 1000 900 800 700 600 500 400 300 200 100 ileakage [mA] % ileakage THD % 26.578 0.19 4.977 24.372 0.19 4.527 21.958 0.20 3.928 19.055 0.20 3.652 17.627 0.21 3.514 14.738 0.22 3.744 12.093 0.23 4.287 10.291 0.24 5.438 * 10.162 0.41 7.861 * 9.677 0.81 14.665 * * Do not comply with IEEE 1547 Standard H6 INVERTER SIMULATED THD igrid [A] 14.262 12715 11.183 9.670 8.174 6.702 5.255 3.840 2.469 1.151 TABLE VIII. ileakage [mA] % ileakage THD % 12.967 0.09 4.901 13.218 0.10 4.641 13.675 0.12 3.986 15.037 0.16 3.896 11.802 0.14 3.743 10.555 0.16 4.421 9.93 0.19 5.326 * 9.668 0.25 6.792 * 9.602 0.39 9.521 * 9.738 0.83 16.177 * * Do not comply with IEEE 1547 Standard ileakage [mA] % ileakage THD % 12.361 0.09 4.932 12.289 0.10 4.639 13.051 0.12 3.988 13.055 0.14 4.007 15.611 0.19 3.725 10.332 0.15 4.294 9.657 0.18 5.220 * 9.843 0.26 6.610 * 9.801 0.40 9.367 * 9.689 0.84 15.636 * * Do not comply with IEEE 1547 Standard H6D2 INVERTER SIMULATED THD igrid [A] 14.258 12.714 11.186 9.673 8.180 6.710 5.266 3.855 2.446 1.161 ileakage [mA] % ileakage THD % 48.753 0.34 3.892 48.195 0.38 3.821 47.450 0.42 3.993 46.469 0.48 4.439 45.282 0.55 5.202 * 44.125 0.66 6.069 * 42.652 0.81 7.290 * 40.334 1.05 9.430 * 37.307 1.53 12.949 * 32.214 2.44 17.845 * * Do not comply with IEEE 1547 Standard