MTR-1
1 Introduction
MTR-1 is a convert interface between
GTR-Series generator controller and PC for
communication purpose. It transforms RS-232
interface into RS-485. MTR-1, an electrical switch,
makes it possible for parameter setting and status
monitoring as well as controlling the generator by
your computer equipment such as Desktop,
Notebook, PDA, etc.. Relative connection software
please refer to Monicon Official Website:
http://www.monicon.com.tw (Free software)
2 Profile
RS485 Rx Indicator
When it lights on, it means waiting for receiving
the data on the RS-485 port.
RS-485 Tx Indicator
When it lights on, it means conveying the data to
the RS-485 port.
RS-232 Rx Indicator
When it lights on, it means waiting for receiving the data on the RS-232 port.
RS-232 Tx Indicator
When it lights on, it means conveying the data to the RS-232 port.
Power Indicator
Power on
Reset Push button
Reset MTR-1 sequence.
RJ-45 Connector
A.
1st Pin: Positive power input (B+).
B.
2nd Pin: RS-485 transmit/ receive pin (D+).
C.
3rd Pin: RS-485 transmit/ receive pin (D-).
D.
4th Pin: Negative power input (B-), (GND).
Ver.:MTR1-v01
RJ-45 Connector
1st Pin
MONICON Instruments Co., Ltd.
MTR-1
3 Operation
A . Uni-controller Connection
Explanation
¾ Plug RS-232 terminal into the RS-232 connector on the MTR-1.
¾ Plug RS-232 terminal on the other side into RS-232 port on PC.
¾ Plug one side of the telephone terminal into RJ-45 socket on the MTR-1. And plug the
telephone terminal of the other side into the RJ45 Box.
¾ Plug on the RJ485 cable into the RS-485 socket on the GTR controller’s rear, then the
Power and RS232 RX indicator lights on, shows the wiring connection between Controller
and the MTR-1 is done.
Wiring Diagram
B . Multiprocessor linking
Instruction
¾ Every single controller needs to configure different address to provide the software
recognition.
¾ Parallel all the 2nd pin (D+) and the 3rd (D-) pin on each controller RS485 port.
¾ Connect only one controller’s 1st pin (B+) and 4th pin (B-) to the MTR-1.
¾ While software running, key in the address code that you desired to connect.
Wiring Diagram
Ver.:MTR1-v01
MONICON Instruments Co., Ltd.
MTR-1
4 Mechanism
5 Specifications
z DC POWER:
9V~35V (In Near-End, provided by controller. But if communication distances over 25
meters long, suggested user plug-in External DC power.)
z Power Consumption:
Max. 1.8 W。
z Working Temperature:
-10 ℃ ~ 60 ℃
z Dimension(W * H * D):
103.6 mm × 61.5 mm × 29 mm
z Carton Weight:
104 g (0.23 lb.)
Ver.:MTR1-v01