21st July 2015 MCW Application Notes www.motorcontrolwarehouse.co.uk Document number Revision Author Product MCW-E2-018 0.0 Gareth Lloyd Invertek Optidrive E2 Title Implementing a bi-polar speed reference using a single potentiometer Summary This document gives information on how to set up the Optidrive E2 for a bi-polar speed reference (-50Hz to +50Hz) using a 0 to 10V supply and a speed potentiometer without having to use a reverse switch. NOTE: Please read this document in conjunction with the Optidrive E2 User Guide. Terminal connections 1 2 5 6 7 Page 1 Parameter set up (from factory default settings) P14 = 101 : Extended parameter access P16 = b-10 - 10 : Analogue input as a bi-directional input P35 = 200.0 : Analogue input scaling P39 = 50.0 : Analogue input offset Output frequency Analogue input vs output frequency characteristic It can be seen from the above characteristic, when the potentiometer wiper is at 0V, the output frequency is -50Hz. At 5V the output frequency is 0Hz and at 10V, the output frequency is 50Hz. Page 2