Universal auto-manual stations AMS400A Typical application of AMS400A The AMS400A modules are interface devices which are used between controllers / PLCs and valves / actuators in the field. They implement aouto-manual transfer operations for automatically controlled processes. AMS400A Typical applications are: 137.0 mm 96.6 mm 48.8 mm 44.4 mm 143.5 mm AUTO Wall thickness Max 18.0 mm MAN ENT 92.0 mm (+0.8/-0.0 mm) 15.5mm 18.0 mm Cut-out 15.5mm 96.6 mm In AA (analogue-analogue) mode, it is possible for a remote source to switch between manual and automatic operations using digital inputs. Ramp rates and additional handover. Two options are available for the method of returning to automatic control, in order to ensure a bumpless transfer. PLC sensor, etc. Status output automatic/manual The AMS400A offers three different I/O configurations, which serve as interfaces between: Analogue control equipment and analogue control devices • • Digital control equipment and analogue control devices • Digital control equipment and digital control devices Acknowledge 4 to 20 mA input PLC • Manual start-up of sensitive processes before handover to automatic control • Manual over-ride in case of controller failure or malfunction. F Proportional 4 to 20 mA output Digital high/ low output from PLC Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com 45.0 mm (+0.6/-0.0 mm) Universal auto-manual stations 60.0 mm Indicators and configurable displays Process value displays with LED display AMS400A AMS400A Universal interface device • Display instrument for control panel installation • 1/8 DIN standard front • IP 65 fully insulated • Pluggable connection terminals Universal interface device Indicators and configurable displays Process value displays with LED display 1 11 12 8 9 10 H L W Technical data 2 +24 V Vout/Iout PS V/I V/I 3 0V 4 0V 5 Automatic / manual 6 Change operating mode 7 Connections Display Type Display value Display range Input Type 4-digit, red LED, 14.2 mm Percentage or real value display -9999...9999 Current input or digital input (pulse-controlled or no-voltage contact) 0...24 mA / 0...12 V DC 50 Ω (mA) / 10 MΩ (V) 5x per sec. (current input) 64 ms (digital input) Input signal Input resistance Sampling rate Pulse width, min. Output Type Output analogue Output current Output voltage Last resistor, max. Alarm (RO version only) Type Number of channels Type of contact Ratings General data Supply voltage Power consumption Accuracy Repeat accuracy Temperature coefficient Cut-off frequency (-3 dB) Step response time Impulse withstand voltage Insulation voltage Ambient temperature / Storage temperature EMC standards Approvals Dimensions Clamping range (nominal / min. / max.) Length x width x height Note Vin/Iin 0V Common Signal amplifier Signal amplifier 0V Analogue and digital output Current or voltage, configured with jumper 0...24 mA 0...18 V 900 Ω @ 20 mA Terminal 1 2 3 4 5 6 7 8 9 10 11 12 Signal – + Signal + Signal – Signal – 0 V Automatic / manual Change operating mode Common Signal amplifier Signal reduction Signal + Signal – Supply voltage Analogue Output Status outputs Digital inputs Analogue inputs Status relay 2 CO contact 3 A @ 240 V AC or 5 A @ 24 V DC 24 V DC ± 10 %, other voltages on request 6 W @ 24 V DC Typically ± 0.1 % of signal range ± 0.02 % of signal range ≤ 0.02 % / °C 5 Hz 300 ms (10...90 %) 4 kV (1.2/50 µs) 1 kV input / output / power supply 0 °C...+60 °C / -25 °C...+70 °C DIN EN 61326 CE; cULus mm² mm Screw connection 1.5 / 0.5 / 2.5 137 / 96.6 / 48.8 Ordering data Analogue output Type AMS400A 4-20mA/AO Qty. 1 Order No. 7940011895 Note Accessories Note Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com F