12 Workmanship, installation, control and maintenance 12.1 General This section gives recommendations for the preparation, fabrication, storage, handling, installation, control and maintenance of materials and components. These recommendations are necessary conditions for the applicability of the design rules given in the Manual. Workmanship in the preparation, fabrication and installation of materials should conform in all respects to accepted good practice. Where necessary reference may be made to BS 8000, in particular part 5121. The specified materials should be installed in such a way as to perform adequately the functions for which they are designed. For the structure to conform to the principles and practical considerations of the design there should be adequate supervision throughout its preparation, construction and maintenance. 12.2 Members 12.2.1 Condition of timber members Members which are damaged, crushed or split beyond the limits permitted for similar defects in the grading should be rejected or repaired to the satisfaction of the designers and approving authority. The deviation from straightness measured midway between the supports should, for columns and beams where lateral instability can occur, or members in frames, be limited to 1/500 times the length of glued laminated timber or LVL members and to 1/300 times the length of solid timber. 12.2.2 Moisture content Before being used in construction, solid timber and other structural timber products should be dried as near as practicable to the moisture content appropriate to their climatic condition in the completed structure (see Table 12.1). As a guide, at the time of erection the moisture content of solid timber members designed for use in service class 1 or 2 should not exceed 18%, and the moisture content of wood-based panels for use in service class 1 should not exceed 12% (see Section 12.5). The determination of moisture content by a properly calibrated moisture meter used in accordance with the manufacturer’s instructions will normally be considered sufficiently accurate if insulated probes inserted 20mm or one quarter of the timber thickness (whichever is less) are used. Where a more accurate average determination of moisture content has to be made, and for meter calibration, the oven dry method detailed in EC5 NA 4.1 should be used. 12.2.3 Dimensions The size, shape and finish of all members and materials should conform to the detailed drawings and specifications. Dimensions and spacings should not be scaled from drawings. 236 IStructE/trada Manual for the design of timber building structures to Eurocode 5 12.2.4 Modifications The cutting, notching, drilling or other modification of members, other than that allowed by the drawings and specification or by Sections 5.2.1.4, 5.2.1.5, 7.3.4 or 10.8.5.2, should not be permitted. Care should be taken to ensure that notches and holes are not so positioned in a member that the remainder of the cross-section contains a knot or other defect which will significantly affect its strength. Where service holes are drilled in wall studs, the services should be protected if necessary to avoid penetration by plasterboard nails. 12.2.5 Treatment of cut surfaces The cutting of timber after preservative treatment should be avoided. When it is unavoidable, exposed untreated timber should be given a liberal application of a permitted preservative in accordance with Manual on Preservative Treatment122. 12.3 Connections 12.3.1 General Wane, fissures, knots or other defects which have not been allowed for in the design, and which may affect significantly the load-carrying capacity, should not be permitted at a connection. The spacing and predrilling of holes for nails, screws, bolts and dowels should conform to the design drawings. It is essential that the fastener types and corrosion protection specified in the design are used, particularly square twisted nails, ringed shank nails, screws with a specified minimum root diameter, or high strength steel bolts. 12.3.2 Nailed connections If predrilling is specified in the design, holes with a diameter not exceeding 0.8 times the nail diameter must be drilled before inserting the nail. 12.3.3 Screwed connections Screws should be turned, not hammered. Screws should be tightened so that the members fit closely together. Coach screws with a timber headside member should be fitted with a special steel washer in accordance with Table 3.29. Predrilling is not required: • for special screws if their manufacturer can provide characteristic load capacities from tests on complete connections carried out in accordance with BS EN 2689188 and matching the connection configuration used in the design • for wood screws with a smooth shank diameter G 6mm in softwood, unless the Engineer has specified predrilling on the drawings In other cases predrilling is required, with the following requirements: • the lead hole for the smooth shank should have the same diameter as the shank and the same depth as the length of the shank IStructE/trada Manual for the design of timber building structures to Eurocode 5 237 • for tk G 500kg/m3 the hole for the threaded portion should have a diameter of approximately 70% of the shank diameter; while for tk > 500kg/m3 the predrilling diameter should be determined by tests where tk = the characteristic timber density. 12.3.4 Bolted connections The maximum diameter of bolt holes should be: d + 1mm in timber d + 2mm max . ) 1.1d mm in steel plates Where d = diameter of bolt (mm) Special steel washers in accordance with Table 3.29 must be fitted between timber and the bolt head or nut. Bolts should be tightened so that the members fit closely together. 12.3.5 Dowelled connections The minimum dowel diameter should be 6mm. The tolerances on the dowel diameter should be -0/+0.1mm. The diameter of pre-bored holes in the timber members should not exceed that of the dowels. 12.3.6 Connections made with timber connectors Toothed plate, split ring and shear plate should be fitted in accordance with the design drawings. Members connected with toothed plates should be drawn tightly together by means of a high tensile steel bolt. With other types of connector recesses should be accurately cut concentric with the bolt hole, and all chips and shavings removed. The diameters of bolts used with timber connectors should conform to Table 6.32. 12.3.7 Adhesively bonded joints Joints in structural components made from separate pieces of timber, plywood or other wood based board that are fastened together with adhesive (e.g. box beams, single web beams, stressed skin panels, glued gussets) should be manufactured in accordance with BS 644695. The manufacturing process should be subject to quality control. Large (full depth) finger joints should be manufactured in accordance with BS EN 38797. The adhesive manufacturer’s recommendations with respect to mixing, environmental conditions for application and curing, moisture content of members and all factors relevant to the proper use of the adhesive should be followed. For adhesives which require a conditioning period after initial set to attain their full strength, the application of load to the joint should be delayed for the necessary time. 238 IStructE/trada Manual for the design of timber building structures to Eurocode 5 12.4Trussed rafters Requirements for the fabrication of trusses are given in BS EN 14250123. 12.5 Storage and handling 12.5.1 Protection of materials and components Precautions should be taken during storage prior to delivery, and on site, to minimise changes in moisture content due to the weather. Rain, damp and direct sunlight are all potentially harmful to timber and wood-based components. Materials and components should be stored clear of the ground on dry bases, and stacks should be evenly supported on bearers with spacer sticks at regular intervals. Stacks should be protected from the weather either by a roof, or by tarpaulins or other impervious materials so arranged to give full cover but at the same time to permit free passage of air around and through the stack. Solid timber delivered packaged, i.e. strapped, should not be stored in packaged form for lengthy periods. Where early use is not possible, packages should be opened and the timber should be open-piled and protected from the weather as above. Care should be taken not to deform stacked material. For wood-based panel products any shrink-wrapping should be left untouched until 24 to 48 hours before installation (see Table 12.1). Where it is essential that materials and components have low moisture contents, it may not be possible to maintain suitable conditions on site other than for short periods, and deliveries should be arranged accordingly. 12.5.2 Handling Undue distortion of components during transportation and handling should be avoided. Similarly, damage from chafing or slings should also be avoided. Where design assumptions for long, flexible or heavy components dictate certain methods of handling, lifting points should be marked on the components and methods of lifting should be shown on the design drawings. 12.6Assembly, erection and installation 12.6.1 General The method of assembly and erection should be such as to ensure that the geometry of assembled components, as specified by the designer, is achieved correctly within the specified tolerances. During assembly and erection, no forces should be applied to a component that could cause the permissible stresses to be exceeded in that or any other component. Special care is necessary when handling framed arches and shaped beams. Any instructions about methods and sequences of erection included in the health and safety plan or shown on the design drawings should be rigorously followed. 12.6.2 Trussed rafters Trusses should be checked for straightness and vertical alignment prior to the fixing of any bracing. IStructE/trada Manual for the design of timber building structures to Eurocode 5 239 At the time of fabrication, the truss members should be free from distortion within the limits given in BS EN 14250123. However, if members become distorted during the period between fabrication and erection but can be straightened without damage to the timber or the joints and can be maintained straight, then the truss may be considered satisfactory for use. The maximum bow in any truss member after erection should be limited. Provided that it is adequately secured in the completed roof to prevent the bow from increasing, the permitted value of the maximum bow should be taken as 10mm. The maximum deviation adev,perm of a truss from true vertical alignment after erection should be limited to: adev,perm = min. ) r 10 + 5 (H - 1) mm 25mm WhereH = height of truss (m) If a girder truss has to be assembled on site, the first truss should be laid out on level supports to ensure that it is flat. The ceiling tie members must be fastened together as specified by the designer. Rafter and web members should be bolted or nailed together in accordance with the designer’s directions or as recommended in BS PD 66932. Gaps greater than 3mm between chord members should be packed with suitable material before fastening. 12.6.3 Floors Requirements for the installation of floor decking are given in Table 12.1. Requirements for the anchoring of timber floors to masonry walls are given in Figures 12.1 to 12.3. When installing engineered timber joists the manufacturer’s instructions should be followed. See Section 8.3.6.2 for safety notes relating to joist supports. 240 IStructE/trada Manual for the design of timber building structures to Eurocode 5 Table 12.1 Requirements for the installation of wood-based decking for floors and roofs Plywood decking Particleboard and OSB decking Item Solid timber boards Storage All decking materials must be fully protected from the weather before installation Time of installation Decking should not be installed until the building is weathertight unless it is factory-faced with a protective film No special Moisture contenta m.c. G 18% at requirement but installation. Floor boarding intended must be dry as a decorative feature must dry out to 12% ± 2% m.c. before being laid, and should not be laid until the building has dried out Boards should be conditioned by laying them in place at least 24 hours before fixing down. They should not be fixed to joists or noggings which have a m.c. > 20% Dust and debris Before fixing decking, all dust and debris should be brushed or blown from the joist surfaces Fastener type and size Decking should be attached to joists with flat head annular ringed shank nails, or countersunk head traditional wood screws in predrilled holes, 3.0mm to 3.35mm in diameterb; or with countersunk head self-drilling wood screws, No.8 screw gauge or 4.00mm in diameter. Nails should have a minimum length of 2.5t and screws a minimum length of 2.0t where t is the decking thickness. Nail heads should be punched and screw heads driven 2-3mm below the surface. Where necessary a countersinking hole should be drilled for screws Access provision Screws should be used where access to underfloor services is required. With panel products a purpose-designed screwed access panel should be provided 1 nail at each joist Recommended crossing, maximum fastener spacingc or 3 for boards wider than 175mm Position of fasteners 150mm around the edges of a board, 300mm wherever boards cross a joist (EC5 10.8.1) Nails should be 15 to Fasteners should be positioned at least 20mm from the edges of 3d from the edges of boards, joists and the board. (If there is a noggings third nail it should be in the centre) IStructE/trada Manual for the design of timber building structures to Eurocode 5 241 Table 12.1 Continued Solid timber boards Gluing In addition to nailing or screwing as above, it is recommended that all decking should be glued to clean, dry, frost-free joists using a PVAc adhesive of durability class D3 to BS EN 204124. (This is to improve the floor performance and reduce the risk of creaking. The site gluing of floor decking should not be treated as a substitute for mechanical fixings) Orientation of boards Boards should be laid across the joists Continuity over joists Boards should span over at least 3 joists Support on joists Floorboard ends should meet in the centre of a joist Edges supported on joists should meet on the centre of joists at least 38mm thick End joints End joints supported on the same joist should be at least 2 board widths apart The joints between the short ends of adjacent boards should be staggered. (This improves the strength of the floor as a horizontal diaphragm. See Figure 5.4) Support of edges Before fixing, squareedged boards should be butted tightly. Square edged solid timber boards should not be used in timber frame buildings or in any buildings where floor diaphragm action is required (EC5 10.8.1). T & G boards should be glued with a PVAc adhesive of durability class D3 to BS EN 204 or an equivalent adhesive, and be cramped tightly together All edges should be tongued and grooved to adjacent boards, or supported on joists or noggings, or (at the walls supporting the joists) be supported on header joists or perimeter noggings. T & G joints should be glued with a generous bead of PVAc adhesive of durability class D3 to BS EN 204 or an equivalent adhesive, applied to both tongue and groove before fixing. All boards should be tightly pulled together before fixing with nails or screws. Softwood noggings minimum 38mm wide x 38mm deep should be skew nailed at each end to the joists with two 3mm z nails. Panel edges should be fastened and glued to noggings as to joists 242 Plywood decking Particleboard and OSB decking Item Board should be laid with the face grain at rightangles to the joists (see Table 3.17 note a) Square-edge chipboard is normally laid with the long edges along the joists. In all other cases the long edge should be at rightangles to the joists IStructE/trada Manual for the design of timber building structures to Eurocode 5 Table 12.1 Continued Item Solid timber boards Expansion gap Plywood decking Particleboard and OSB decking Timber floors in masonry buildings – An expansion gap of at least 10mm should be allowed between the decking and the perimeter wall in each room area to prevent possible buckling as it absorbs moisture. On floors longer than 10m the gap should be 2mm per metre run of deck, divided between each end of the floor, but manufacturers may recommend intermediate expansion gaps instead. The gap may be masked by skirting board or loose cover strip, or filled with an easily compressible material. It must be kept clear of plaster and other building debris Timber floors in timber frame buildings – The decking must be connected to the outer edge of the perimeter joists to provide adequate diaphragm action. It is therefore imperative that the decking be conditioned to the in-service temperature and humidity before it is fastened down Notes a Moisture content for roof decking will be dependent on the form of construction and building control requirements. b 3.00mm diameter is preferable for 38mm thick joists to reduce the possibility of splitting. c For service class 2 buildings the maximum fastener spacing around the perimeter of a floor may be determined by tying requirements (see Appendix A). IStructE/trada Manual for the design of timber building structures to Eurocode 5 243 Wherever possible the tongue of the hanger to be located away from perpend joint below Strap skew-nailed to joist Underside of joist notched to provide flat soffit for ceiling Strap to turn down a minimum of 100mm and be tight against the face of the walling inner leaf Fig 12.1 Timber joists supported by joist hangers on blockwork 244 IStructE/trada Manual for the design of timber building structures to Eurocode 5 Strap to turn down a minimum of 100mm and be tight against the face of the walling inner leaf Note No straps are necessary in dwellings up to 3 storeys if the joist spacing is 1200mm or less and the joists bear at least 90mm into the wall or are supported on specially designed joist hangers. Otherwise strap as shown – either on top of the joist with the strap turned up, or on one side of the joist with the strap turned sideways – 2m apart up to 3 storeys or 1.25m apart above 3 storeys. Straps to be galvanized mild steel 5mm x 30mm, nailed as indicated in Table 5.9 to resist the forces specified in Appendix A. Fig 12.2 Timber joists supported on blockwork IStructE/trada Manual for the design of timber building structures to Eurocode 5 245 Strap to turn down 100mm and be tight against the facing of the walling inner leaf Strap to be rebated into top of joists to allow the floorboards to lay flat Nogging should extend at least half the depth of the joist and be at least 38mm thick Solid nogging to be fixed between joists under the straps to take the fixings Gap between the wall and the first joist to be filled with a timber packing at strap positions Alternative strap location using full depth noggings Note The strap should be carried over at least three joists and be secured with four fixings of which at least one should be in the third joist or in a nogging beyond the third joist. Strap specification, spacing and nailing as for Figure 12.2. Fig 12.3 Timber joists spanning parallel to a blockwork wall 246 IStructE/trada Manual for the design of timber building structures to Eurocode 5 12.7 Treatments 12.7.1 Preservative and flame retardant treatments Preservative and flame retardant treatments should be applied in accordance with the manufacturer’s instructions. Flame retardants should be used under such conditions and in such a manner that they will not adversely affect other materials or processes. Leach resistant retardants should be used for materials exposed to the weather or to regular wetting, and they may need to be renewed after a period recommended by the manufacturer. 12.7.2 Anti-corrosive treatments The anti-corrosive treatment of metal fasteners and fittings should be sufficient to ensure their satisfactory performance and structural integrity throughout the intended life of the structure. The degree of protection required will depend on the dimensions of the fittings and the environment to which they are to be exposed (see Table 3.25). 12.7.3 Decorative treatments Where structural timber is painted, varnished or otherwise decorated, the work should be in accordance with BS 6150125. Care should be taken to ensure that paints, preservatives, flame retardants and adhesives are compatible. Advice can be obtained from the Wood Protection Association. 12.8 Production and site control 12.8.1 Control plan A control plan should be drawn up to ensure that the construction is built in accordance with the design specification. As a minimum the control plan should cover: • any necessary preliminary tests, e.g. tests for suitability of materials and production methods • checking of delivered materials and their identification, e.g. – for wood and wood-based materials: species, grade, marking, treatments and moisture content – for glued constructions: adhesive type, production process, glue-line quality – for fasteners: type, corrosion protection – for all materials, checking of correct dimensions and quantities • transport, handling of materials and site storage • checking of assembly and erection • checking of structural details, e.g. – splitting – number of nails, bolts etc. – sizes of holes, correct predrilling – spacings and distances to end and edge of members • final checking of the result of the production process, e.g. by visual inspection or proof loading. IStructE/trada Manual for the design of timber building structures to Eurocode 5 247 12.8.2 Inspection Reasonable facilities and access for inspection should be provided during and at completion of fabrication and erection of a structure. These facilities and access conditions should be agreed between the parties concerned. 12.9 Maintenance 12.9.1 Responsibility The responsibility for maintenance should be agreed between the parties concerned. A maintenance schedule should be drawn up to ensure that the building continues to function properly. 12.9.2 Tightening of bolts It is advisable to check the tightness of bolts some six weeks to eight weeks after completion of the structure, when the timber may have reached equilibrium moisture content. Where tightening is to be carried out access for this purpose should be provided. A second inspection of large solid timber members about 12 months after completion is recommended. 12.9.3 Ancillary components It is imperative that features of the construction which are essential to the structural performance of timber and timber-based components, e.g. vapour barriers, ventilators, seals, etc., are maintained in an effective condition throughout the intended life of the structural timberwork. 12.9.4 Structural metal-work Any corroded fittings should be treated with an anti-corrosive or, if necessary, replaced. 12.9.5 Other matters The maintenance schedule should include inspection (and renewal when necessary) of wood stains or other protective treatments on exterior woodwork, the removal of any debris or vegetation which could retain moisture, and normal building maintenance on drains, gutters, flatroofing, etc., to ensure that the structural timberwork remains well ventilated and either remains dry or does not remain wet for prolonged periods. 248 IStructE/trada Manual for the design of timber building structures to Eurocode 5