IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, VOL. 39, NO. 4, NOVEMBER 1997 269 Ground Effects on Induced Voltages from Nearby Lightning Hans Kr. Høidalen, Jarle Sletbak, and Thor Henriksen Abstract— The lightning induced voltage on overhead lines from return strokes and it’s dependency of a lossy ground is analyzed using a new, analytical vector potential formulation. Norton’s approximation and the surface impedance approach are used to take loss effects into account. The surface impedance method predicts in general induced voltages in good agreement with Norton’s approximation, but the accuracy of the method is dependent on the variation of the current along the lightning channel. Norton’s method is compared with the exact Sommerfeld solution, showing a deviation <10% even for low conducting grounds and distances from 100–1000 m. The effect of stroke location and line termination is also analyzed, showing that a line terminated by it’s characteristic impedance and excited by a return stroke at the prolongation of the line is especially sensitive to lossy ground effects. Strokes near the mid-point of an overhead line gives less loss effect than strokes at the end of the line. The surface impedance approximation is derived from Norton’s method and the necessary assumptions are outlined. Index Terms— Calculation model, lightning-induced voltage, lossy ground. I. INTRODUCTION I NDUCED voltages due to nearby lightning is an important reason for insulation failures in low voltage systems. An optimal protection can only be achieved if one can predict the expected over-voltages induced by lightning. Simultaneous measurements of the lightning current and induced voltages show a large deviation between measured and calculated voltages, e.g., [1], [2]. The reasons for this are mainly: 1) an over-simplified model of the lightning channel is used; 2) the attenuation of the electric fields due to propagation over ground is not taken properly into account. This paper focuses on the latter factor, but also examines the impact of one of the lightning channel parameters. The effect of losses on fields from remote lightning is well known. While the vertical electric field is little affected by ground effects, the horizontal field is strongly affected, (decreasing from zero at the ground to a negative value when loss is taken into account). Measurements [3], [4] have even shown an inversion of the induced voltage for some special configurations. Manuscript received July 16, 1996; revised August 19, 1997. H. Kr. Høidalen and J. Sletbak are with the Norwegian University of Science and Technology, Trondheim N-7034, Norway. T. Henriksen is with the Norwegian Electric Power Research Institute, Trondheim N-7034, Norway. Publisher Item Identifier S 0018-9375(97)08377-4. Fig. 1. Configuration: cylindrical coordinates. For nearby lightning ( 1000 m), the effect of losses is more uncertain. Also the accuracy of the currently used methods for loss calculations has been questioned, but they are in [5] shown to predict the peak value of the induced voltage with reasonable accuracy. Zeddam and Degauque [6] have used and evaluated Norton’s method [7] showing better than 10% accuracy for practical dipole heights and frequencies, even for 100 m distance. Ishii et al. [8] also used Norton’s method to calculate the loss effects for nearby lightning and the loss effects are shown to be important even for distances less than 1000 m. In this paper, the induced voltages in an overhead line is calculated by using a new vector potential formulation. The modified transmission line model (MTL) [9] is used for the lightning current. Norton’s method is first evaluated, also for lower ground conductivities and other permittivities than used in [6]. II. BASIC CONFIGURATION The analyzes made in this paper are based on the configuration shown in Fig. 1. The lightning channel is assumed to be vertical, as shown in Fig. 1. This configuration is used to calculate the vector potential caused by the current dipole at a height . The observation point has a horizontal distance from the lightning channel and a height . R and R are the distances from the dipole and it’s image, respectively. The ground has and a permittivity . The system is a conductivity axial symmetric with the -axis directed along the overhead line and the -axis perpendicular to the line ( ). The vector potential will in this paper be used to calculate the induced voltage in an overhead line. The advantage of 0018–9375/97$10.00 1997 IEEE 270 IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, VOL. 39, NO. 4, NOVEMBER 1997 this formulation is that Norton’s approximation can be used directly. Besides, the vertical and horizontal electric fields can both be expressed by the vector potential, making it easier to calculate the total line voltage and to analyze it’s dependency of the line terminations. By choosing the Lorentz gauge [ ] for the vector potential divergence, the electric fields can be written (7) (8) R R R (1) where is the -component of the vector potential. III. EVALUATION OF NORTON’S METHOD In [6] several approximations were compared to Sommerfeld’s exact formulation of fields from a vertical dipole, showing reasonable agreement for the Norton’s method. However, in [6] the ground parameters and are kept constant and a relatively high conductivity of 0.01 S/m is used. Before using Norton’s approximation for lower ground conductivities and other permittivities an extension of the analysis in [6] is presented here. The exact expression for the vector potential set up by a vertical current dipole ( ) over flat, homogeneous ground is given by Sommerfeld [10], [11] in the frequency domain R R and where erfc is the complementary error function. The first term inside the brackets in (3) is the direct wave from the dipole to the point of observation, the second term is the reflected wave from the ground surface and the third term is the ground wave. The vector potential in Norton’s formulation can also be written as a sum of the potential in a lossless situation, , and a contribution from the lossy ground, R R R R R R (10) where R R (9) R (11) R R J (2) R (12) erfc where J is the Bessel function of first kind (13) The accuracy of Norton’s method is further analyzed by comparing the Norton vector potential in (3), , with the exact vector potential from Sommerfeld’s method (2), . The vector potentials are calculated at a height 10 m above ground. The error of Norton’s approximation is defined as The integral in (2) must be solved numerically which is difficult and time consuming, due to the highly oscillatory behavior of the Bessel function at large distances and the exponential function at large dipole heights. The integrand is also nearly singular when . Norton has formulated an approximation to (2), assuming a high ground conductivity [7], [11] R R R R R R R (3) R where R (4) erfc R (5) (6) with dipole height and frequency as variables and horizontal distance and the ground characteristic and as parameters. Figs. 2 and 3 show the error in Norton’s approximation for two different radial distances, ; 100 and 1000 m. A ground conductivity of S/m and a relative permittivity of is assumed. Frequencies from 0–10 MHz and dipole heights from 0–4000 m have been investigated. As seen from Figs. 2 and 3 the error in Norton’s method is in general low and less than 5% in an important frequency range (0–1 MHz). For frequencies less than 1 MHz the accuracy of Norton’s method is better for larger distances, but above 1 MHz the error seems to increase with distance. Also, for frequencies above 1 MHz the error is larger for lower dipole heights. The dependency of the ground permittivity has also been investigated. This shows that the error is reduced with increasing permittivity and using 40 gives an error less than 2% in the whole frequency range (0–10 MHz). A relative permittivity of 2.5 gives errors between 10–37% for HØIDALEN et al.: GROUND EFFECTS ON INDUCED VOLTAGES FROM NEARBY LIGHTNING 271 Fig. 4. Ratio between lossy and lossless vector potential at ground level. Fig. 2. Error in Norton’s approximation. r = 100 m. 1 = A. Current Model 0:001 S/m, "r = 10, The simple Modified Transmission Line model (MTL) [9] has been used. In this model a current starts from the ground and travels upward with a constant velocity , and its amplitude is exponentially decaying with increasing height with the factor , where is the decay constant. In our analysis the current at ground is assumed to be a step with amplitude . An arbitrary current shape at the ground can be taken into account by a final convolution integral of the calculated voltages, since the system is assumed to be linear. In the frequency domain the current along the lightning channel can be written (14) Fig. 3. Error in Norton’s approximation. r = 1000 m. 1 = 0:001 S/m, "r = 10, frequencies 1 MHz and dipole heights 200 m when 1000 m. The attenuation of the vector potential can be expressed as the ratio between the lossy and lossless ground potential, from (9) and (10) at the ground ( ). This ratio is in Fig. 4 plotted as a function of frequency ( ) and dipole height ( ), with 0.001 S/m, 10 and 100 m. From Fig. 4 one important observation can be made: At low frequencies the impact of the lossy ground increases with dipole height. Above 1 MHz the loss effect is largest for low dipole heights, however. Norton’s method is often used to calculate the loss effects on electrical far-fields which are dominated by the radiation term. The attenuation of the radiation fields is similar to that of the vector potential and this approach has been used in e.g., [12], [13]. The electrical close-fields show a more complex dependency of lossy ground obtained by differentiating (10) according to (1). The full expressions for the electrical fields using Norton’s method are given in [14]. Calculating the induced voltage from a vector potential formulation allows the Norton’s method to be used directly. IV. VECTOR POTENTIAL FROM A LIGHTNING CHANNEL The vector potential from a current element ( ) is given by (9) and (10). To calculate the total potential, the lightning current must be modeled. The situation occurring when the lightning current wave reaches the top of the lightning channel is not analyzed in this paper. The height of the lightning channel is assumed to be so large that this does not occur within the studied time span. The limited height is anyhow of no practical importance if it is large compared to the decay constant . B. Total Vector Potential The total vector potential equals the integral over the lightning channel (15) is the total height of the lightning channel. where Inserting the Norton’s approximation expressions from (4) and (5) gives R R R R (16) (17) is plotted as In Fig. 5 the absolute value of the ratio a function of frequency and radial distance . The height of the observation point is 10 m. The height of the lightning channel is assumed to be 4000 m and the decay constant in the current model is 1500 m. The ground has 0.001 S/m and a relative permittivity a conductivity 10. Clearly the attenuation increases with frequency, , and distance, . Up to 400 kHz the vector potential is almost 272 IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, VOL. 39, NO. 4, NOVEMBER 1997 Fig. 7. Overhead line terminations. Fig. 8. End stroke configuration. Fig. 5. Attenuation of the vector potential from a lightning channel. j = 0 j. A A Fig. 9. Side stroke configuration. Fig. 6. Induced voltage configuration. unaffected by the lossy ground. At 1 MHz the vector potential is reduced to 65% 1000 m away from the lightning channel. in our analysis. The scattered voltage can, however, be decomposed in a sum of an incoming wave and a reflected wave dependent on the termination. The incoming voltage wave, which will be focused in our study, consists of the time delayed, reflected wave from the other terminal plus a contribution from the horizontal electric field, called the horizontal field contribution . This gives (22) V. INDUCED VOLTAGE CONFIGURATION where The configuration used when calculating the induced voltage in an overhead line is shown in Fig. 6. The overhead line has two terminals A and B with -coordinates and , respectively ( ). The length of the overhead line is . The observation point has coordinates ( ). All the electromagnetical fields handled in this paper are incident fields written without superscript . The overhead line is modeled by the Agrawal coupling model [15]. The total line voltage is in this model a sum of the scattered voltage and the incident voltage (23) is the transmission coefficient of the overhead line (being equal to in a lossless situation). When performing calculation examples, the two stroke locations, as shown in Figs. 8 and 9, will be used. VI. HORIZONTAL FIELD CONTRIBUTION ( The voltage wave coming in to an overhead line terminal ) due to the horizontal electric field is given by [5], [16] (18) where (19) and the following two equations being valid for (20) (24) This voltage wave is equal to the scattered voltage if the line is terminated by it’s characteristic impedance at both ends. Replacing the horizontal electric field by the vector potential formulation in (1) gives (21) The terminations of the overhead line can be included as shown in Fig. 7 when the line is terminated by impedances. which is the solution of the wave The scattered voltage equations (20) and (21) is dependent on the terminations of the line and is therefore not so useful as a key parameter (25) HØIDALEN et al.: GROUND EFFECTS ON INDUCED VOLTAGES FROM NEARBY LIGHTNING 273 Fig. 10. Loss effect on horizontal field contribution, far end. End stroke, r0 100 m, 1 0.001 S/m. Solid line: MTL model ( 1500 m). Dotted line: TL model. Fig. 11. Loss effect on horizontal field contribution, far end. End stroke, r0 1000 m, 1 0.001 S/m. Solid line: MTL model ( 1500 m). Dotted line: TL model. where the two terms outside the integral in (25) will dominate in most cases except for the side stroke (Fig. 9) where the two terms evaluated at and partly cancel each other for symmetry reasons. between two consecutive frequency points. is set equal to Hz and to 10 MHz. , The lossy part of the horizontal field contribution is calculated in the time domain and shown in Figs. 10 and . The overhead line is 11, together with the lossless part 1000 m and height assumed lossless with length 10 m. The velocity of the lightning current is set to m/s. The current amplitude is 1 and the height of the lightning channel is assumed to be 4000 m. The decay constant has the values 1500 m or 10 m corresponding to the MTL and the transmission line TL, lightning channel models, respectively. Figs. 10 and 11 show how the lossy ground affects the horizontal field contribution. For the distance 1000 m the loss effect is large and the total horizontal field contribution will be negative up to around 10 s, while at 100 m, will only have a negative initial peak. We also observe that the lossy part of the horizontal field is more dependent on the decay constant contribution than , and thus on the variation of the current along the lightning channel. The reason for this is that the upper parts of the lightning channel contribute less for smaller , and as seen from Fig. 4 the loss effect at low frequencies is more pronounced for the upper than for the lower parts of the lightning channel. The peak voltage is, however, almost the same for the two decay constants. Besides, it is important to keep in mind that a step current has been used in the calculations and a more realistic current shape will make the first peak more significant. Increasing the conductivity by a in factor 10 reduces the horizontal field contribution Fig. 10 by a factor 4. Another observation is that the lossless will be higher for the MTL horizontal field contribution than for the TL model. The importance of the loss effect on wave propagation in the overhead line has also been investigated. The overhead line’s transmission coefficient, , was calculated by Cable Constants in ATP-EMTP [17] which uses Carson’s formulas, assuming a 5 mm diameter Cu-line 10 m above ground. The result shows that the overhead line losses are ignorable compared to the attenuation of the horizontal electrical field when the = = = A. Loss Effects on the Horizontal Field Contribution The horizontal field contribution expressed in (25) can be split in a lossless part and a lossy ground part dependent only on from (17). This latter voltage contribution, called , is the key quantity when analyzing the loss effects on induced voltage in an overhead line. The ground conductivity and the importance of the decay constant in the lightning channel model will also be studied. Instead of differentiating the vector potential in (25) with respect to , the theorem of reciprocity can be utilized, , resulting in (26) Inserting (26) in (25) gives a complete analytical expression for the lossy part of the horizontal field contribution. The function is smooth and well behaved. It approaches for low frequencies and for high frequencies. Thus, the voltage in the time domain can be calculated numerically by the inverse Fourier transform, using only ten frequency samples per decade and the sine form of the inverse Fourier transform (27) By assuming the function to vary linearly between each sample point, the integration can be performed analytically = = = 274 IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, VOL. 39, NO. 4, NOVEMBER 1997 Fig. 12. Loss effect on horizontal field contribution, far end. End stroke, r0 100 m, 1 0.001 S/m. Solid line: MTL model ( 1500 m). Dotted line: TL model. = = = line is short. Our simulations suggest that the line losses can be ignored for lines shorter than 1000 m whereas [5] suggests 500 m. Similar results have also been obtained in [18]. This result enables a very simplified calculation model of induced voltages in short overhead lines. This model is based on calculating the horizontal field contribution and the incident voltage in the frequency domain, using an inverse Fourier transform and finally keep track of reflections at the line terminations in the time domain. VII. SURFACE IMPEDANCE FORMULATION A commonly used approximation for taking loss effects into account is the surface impedance approach. This technique is used e.g., in [5], [20]–[22]. A simplified version of this technique (neglecting the displacement current) was also used in [19, Eq. (95)]. The surface impedance method has been evaluated by Cooray and compared with Norton’s method showing less than 15% error for the considered parameter range [5], [20]. According to the surface impedance approach the horizontal electric field is approximated by (28) is the lossless electric field at line height and where is the lossless magnetic field at ground and where the surface impedance is (29) The loss effect on the horizontal field contribution due to the attenuation of the horizontal field can be written Fig. 13. Loss effect on horizontal field contribution, far end. End stroke, r0 1000 m, 1 0.001 S/m. Solid line: MTL model ( 1500 m). Dotted line: TL model. = = = where R (32) R assuming a step lightning current with decay constant and traveling upward with a velocity . The vector potential is calculated at ground level so that R . The curves in Fig. 10 and 11 have been recalculated, as shown in Figs. 12 and 13, using the surface impedance approach. Comparing Figs. 10 and 11 with Figs. 12 and 13, respectively, shows a reasonably good agreement between the Norton’s method and the surface impedance method when 1000 m for both the MTL and TL lightning channel models. At distance 100 m, the agreement between the two models is best when the MTL model is used. The surface impedance approach is less dependent on the decay constant, than Norton’s method. This is due to the fact that the variation of the loss effects along the lightning channel is ignored in the surface impedance approach. From Fig. 4 we see that the loss effect is strongest for the highest dipoles at low frequencies. When a decay constant of 1500 m is assumed the contribution from the upper parts of the lightning channel is reduced. This will therefore lead to an improved accuracy of the surface impedance method. A. Deducing the Surface Impedance Approach from Norton’s Method The surface impedance approach gives the same result as Norton’s approximation if (31) equals lossy part of (25). This is true if (33) (30) Utilizing that , (30) can be expressed , to Requiring the contribution from each current dipole, be equal in the two cases (instead of the total integral) results in R (31) R (34) HØIDALEN et al.: GROUND EFFECTS ON INDUCED VOLTAGES FROM NEARBY LIGHTNING 275 The hypothesis in (34) is now investigated, and the necessary assumptions are outlined. For small (small frequencies and/or small dipole heights), can, by a series expansion, be expressed as R R and taking the limit Performing the differentiation of as approaches zero gives R Multiplying the right hand side of (36) with R (35) R (36) Fig. 14. Induced voltage, open ends. Dotted line: lossless. Solid line: Norton’s approximation. Dashed line: surface impedance. 1 0.001 S/m, "r 10. r0 100 m. = = gives = R R (37) Assuming R (or ) will make the surface impedance approach equivalent to Norton’s method. This assumption is reasonable for large distances or short times ( ). For short times however, the high frequency content makes the series expansion approximation in (35) doubtful. When the lightning current is decaying along the lightning channel the lower parts of the channel will contribute more than the upper ones, making the surface impedance method more accurate for lower decay constants, . The surface impedance approach is a good approximation if the following conditions are met: 1) low frequencies dominate ( is small); 2) the overhead line height, is small compared to the horizontal distance ; 3) the approximation, R , holds. This assumption is reasonable for: Large distances , small decay constants or short times . formulation are compared with those obtained in [18] based on the surface impedance method. The incident voltage in (19) can also be expressed by the vector potential using the formulation in (1) (38) A. Open Ends If the line terminations are open, the overhead line voltage at end can be written (39) Inserting the vector potential formulation from (25) and (38) this gives VIII. TOTAL LINE VOLTAGE The total voltage in an overhead line is the sum of the scattered and incident voltage. The horizontal field contribution , has been shown to be strongly affected by a lossy ground in contrast to the incident voltage which is little affected for short distances. Due to the vector potential formulation analytical expressions for the total line voltage can be developed and the lossy ground effect on the whole line can be studied, including the dependency on line terminations. Two different situations are here analyzed: 1) open end; 2) matched termination. The lightning current is no longer assumed to be a pure step function but is approximated by the Heidler model [23] with the same parameters as in [18], [24] resulting in a peak current of 12 kA and a maximum current/time derivative of 40 kA/ s. [This current shape is taken into account by performing a convolution integral based on the step responses (40 or 42)]. In Fig. 16 our results using the analytical vector potential cosh sinh (40) in (40) is for The loss effect on the total line voltage high frequencies (corresponding to the initial part in the time domain) mainly determined by the first term which in since the lossless part actually (40) is written with index is zero at ground level ( 0). For lower frequencies the integral term contribution becomes important (typically after the first reflection in the time domain) and this will reduce the loss effect. Fig. 14 shows a simulation of the induced voltage for an end stroke at distance 100 m from a 1000 m long and 10 m high overhead line with open ends. The simulations taking a lossy ground into account are compared with a lossless simulation. The lightning current parameters are 1.1 10 m/s and 1500 m and 4000 m. 276 IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, VOL. 39, NO. 4, NOVEMBER 1997 Fig. 15. Induced voltage, matched terminations. Dotted line: lossless. Solid 0.001 line: Norton’s approximation. Dashed line: surface impedance. 1 S/m, "r 10. r0 100 m. Fig. 16. Induced voltage, side stroke. Dotted line: lossless. Solid line: Lossy ground (Norton). Dashed line: Lossy ground (Surf. imp.). Dots () from [18] Fig. 12. 1 0.001 S/m, "r 10. r0 50 m. From Fig. 14 we observe that the initial part of total line voltage at the far end is strongly influenced by the lossy ground and actually the polarity is reversed. After a while the lossy ground effect is reduced, but a negative peak occurs in the lossy ground voltage at each reflection in the line. Fig. 16 shows the induced voltage at the end of a 1000 m long overhead line terminated by it’s characteristic impedances and excited by a side stroke 50 m from the center of the line. The Norton’s method is compared with the results using the surface impedance method in [18]. The lightning current parameters are 1.3 10 m/s and 1700 m and 4000 m. Fig. 16 shows that our simulations give results similar to those in [18]. Also the surface impedance approach gives very good agreement with Norton’s method except at the initial negative peak and the positive peak. This is due to the high steepness of the induced voltage. = = = B. Matched Terminations If the line terminations are matched i.e., terminated by the characteristic impedance, the overhead line voltage of end becomes (41) Inserting the vector potential formulation from (25) and (28) gives (42) The loss effect on the total line voltage in (42) is dominated by the first two terms which in (42) are written with index since the lossless part actually is zero at ground ( 0). For the side stroke these terms tend to cancel each other ( ). Fig. 15 shows a simulation of the induced voltage for an 100 m from a 1000 m long and end stroke at distance 10 m high overhead line with matched ends. The simulation taking a lossy ground into account is compared with a lossless simulation. The lightning current parameters are 1.1 10 m/s and 1500 m and 4000 m. From Fig. 15 we observe that a line terminated by it’s characteristic impedance and excited by an end stroke is very sensitive to lossy ground effects. However, the application of the telegraph equations and thus Agrawal’s coupling model becomes doubtful for an end stroke since the variation of the exciting field , is large along the line. This is discussed by Agrawal et al. [15]. = = = IX. DISCUSSION The performed evaluations of Norton’s method in Figs. 2 and 3, show that this method is highly accurate ( 10% deviation) even for short distances (100 m) and low conducting ground ( 0.001 S/m). Lower relative permittivity than 10 reduces the accuracy. Fig. 4 shows how the loss effect on the vector potential from a vertical electric dipole is affected by dipole height and frequency. The important observation is the increased loss effect with dipole heights for low frequencies. Figs. 10 and 11 show that the lossy part of the horizontal field contribution , after the first initial peak is strongly affected by the decay constant . Beyond 10 s the dependency is largest for short distances. The dependency of is important to notice and it stresses the necessity of using an adequate current model when calculating induced voltages from nearby lightning. The lossless part of the horizontal field contribution , is for 100 m also very dependent on the decay constant and is in fact larger for the MTL model than for the TL model. Equation (43) shows the slope of the horizontal field contribution for an end stroke at large times R R (43) HØIDALEN et al.: GROUND EFFECTS ON INDUCED VOLTAGES FROM NEARBY LIGHTNING Calculations in Figs. 12 and 13, using the surface impedance approach, show that this method is a reasonable approximation for distances larger than 1000 m. The approximation is poor for high frequencies and large dipole heights. In a practical situation assuming a standard 1.2/50 s lightning impulse the surface impedance method will give wrong results for very short times (high frequencies) and for large times (large dipole heights). Within these boundaries where often the maximum value of the induced voltage occurs the method is accurate, however. Figs. 14 and 15 show how the loss effect on the total induced voltage depends on the line terminations. When the line terminals are open the loss effect is initially about twice as large as when the line is matched. This is also seen from (40) and (42) where the term initially dominate and where the voltage in (42) is multiplied by a factor 0.5. One exception is the side stroke configuration where the two terms in (42) tend to cancel each other. A matched line is therefore more sensitive to the stroke location. Figs. 14–16 show that the end stroke configuration is very sensitive to loss effects while the side stroke configuration is less sensitive, which is in good agreement with the results in [25], [26]. The reason for this is that the latter configuration is less dependent on the horizontal field contribution and the loss effect on the total voltage will actually decrease with increasing distance until the loss effect on the incident voltage becomes important. Figs. 14–16 show that the surface impedance method is accurate compared to Norton’s method for the applied current waveform. A deviation arises when the voltage is steep like at the far end in an end stroke configuration and for the side stroke configuration. For times beyond the first peak value in the voltage the surface impedance method cause the voltage to drift off due to the increased dipole height. It is also worth mention that the used current waveform is very steep with a front time below 1 s. Larger front times will improve the accuracy of the surface impedance method around the first peak in induced voltage. X. CONCLUSION Norton’s approximation for calculating the loss effects on the vector potential from a vertical current dipole has been evaluated, showing very good agreement also for ground conductivities as high as 0.001 S/m. The significance of loss effects on the horizontal field contribution has been studied. The lossy ground has significant effect on the vector potential while the line loss in overhead lines shorter than 1000 m long is insignificant. The first peak of the induced voltage is independent on the decay constant but after the first micro second the lossy part of the horizontal field contribution is strongly dependent on the variation of the current along the lightning channel. The total induced voltage is strongly dependent on the line terminations. When the line terminations are open the loss effect is initially twice as high as when the line terminations are matched. However, after the first reflection the voltage in the open end configuration approaches the lossless situation. 277 The loss effect is in general large even for distances in the range of 100 m and may lead to an inversion of the voltage. Lightning induced voltages in a side stroke configuration is less influenced by lossy ground effects than for an end stroke. The surface impedance method has also been analyzed, showing a reasonable agreement with Norton’s approximation for distances larger than 1000 m. Usage of the MTL lightning channel model ( 1–2 km) gives higher accuracy of the surface impedance method than the TL model. The surface impedance method has in this work been derived from Norton’s method. REFERENCES [1] P. P. Barker, T. A. Short, A. R. Eybert-Berard, and J. P. Berlandis, “Induced voltage measurements on an experimental distribution line during nearby rocket triggered lightning flashes,” in Proc. IEEE/PES Summer Meeting, Portland, OR, 1995. [2] M. Rubinstein, M. Uman, P. J. Medelius, and E. M. Thomson, “Measurements of the voltage induced on an overhead power line 20 m from triggered lightning,” IEEE Tran. Electromag. Compat., vol. 36, May 1994. [3] N. Georgiadis, M. Rubinstein, M. Uman, P. J. Medelius, and E. M. Thomson, “Lightning induced voltages at both ends of a 448-m powerdistribution line,” IEEE Trans. Electromag. Compat., vol. 34, Nov. 1992. [4] V. Cooray and F. de la Rosa, “Shapes and amplitude of the initial peaks of lightning-induced voltage in power lines over finitely conducting earth: Theory and comparison with experiment,” IEEE Trans. Antennas Propagat., vol. 34, Jan. 1986. [5] V. Cooray, “Lightning-induced overvoltages in power lines: Validity of various approximations made in overvoltage calculations,” in Proc. 22nd Int. Conf. Lightning Protection, ICLP’94, Budapest, Hungary, 1994. [6] A. Zeddam and P. Degauque, “Current and voltages induced on telecommunication cables by a lightning stroke,” in Lightning Electromagnetics, R. Gardner, Ed. New York: Hemisphere, pp. 377–400. [7] K. A. Norton, “The propagation of radio waves over the surface of the earth in the upper atmosphere,” Proc. IRE, vol. 25, pp. 1203–1237, 1937. [8] M. Ishii, K. Michishita, Y. Hongo, and S. Oguma, “Lightning-induced voltage on an overhead wire dependent on ground conductivity,” IEEE Trans. Parallel Distrib. Syst., vol. 9, Jan. 1994. [9] C. A. Nucci, C. Mazzetti, F. Rachidi, and M. Ianoz, “On lightning return stroke models for LEMP calculations,” in Proc. 19th Int. Conf. Lightning Protection, Graz, Apr. 1988. [10] A. Sommerfeld, Partial Differential Equations in Physics. New York: Academic, 1949. [11] T. S. M. Maclean and Z. Wu, Radiowave Propagation Over Ground, 1st ed. London, U.K.: Chapman and Hall, 1993. [12] C. Hopf, “Effects of propagation on the electrica fields radiated by return strokes in distances up to 15 km,” in Proc. ICLP’94, 1994. [13] V. Cooray and H. Pérez, “Propagation effects on first return stroke radiation fields: Homogenous paths and mixed two section paths,” in Proc. ICLP’94, 1994. [14] R. King, “Electromagnetic field of a vertical dipole over an imperfectly conducting half-space,” Radio Sci., vol. 25, pp. 149–160, Mar./Apr. 1990. [15] A. K. Agrawal, H. J. Price, and S. Gurbaxani, “Transient response of multi-conductor transmission line excited by a non uniform electromagnetic field,” IEEE Trans. Electromag. Compat., vol. EMC-22, pp. 110–129, 1980. [16] T. Henriksen, “Calculation of lightning overvoltages using EMTP,” in Proc. Int. Conf. Power Syst. Transients, Lisbon, 1995. [17] Alternative Transients Program (ATP) Rule Book, Can/Am EMTP User Group, Leuven EMTP Center, Belgium, 1987. [18] F. Rachidi, C. A. Nucci, M. Ianoz, and C. Mazzetti, “Influence of a lossy ground on lightning-induced voltages on overhead line,” IEEE Trans. Electromag. Compat., vol. 38, Aug. 1996. [19] S. Rusck, “Induced lightning over-voltages on power-transmission lines with special reference to the over-voltage protection of low-voltage networks,” Ph.D. dissertation, Royal Institute of Technology, Stockholm, Sweden, 1957. [20] V. Cooray, “Horizontal fields generated by return strokes,” Radio Sci., vol. 27, no. 4, pp. 529–537, July/Aug. 1992. 278 IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, VOL. 39, NO. 4, NOVEMBER 1997 [21] M. Rubinstein, “Voltages induced on a test power line from artificially initiated lightning: Theory and experiment,” Ph.D. dissertation, Univ. of Florida, Gainesville, 1991. [22] V. F. Hermosillo, “Voltages induced on overhead power distribution lines by lightning return strokes,” Ph.D. dissertation, Univ. of Uppsala, Sweden. [23] F. Heidler, “Analytische Blitzstrom-function zur LEMP-Berechnung,” in Proc. Int. Conf. Lightning Protection, ICLP’85, Munich, Germany, 1985, paper 1.9, pp. 63–66. [24] C. A. Nucci, F. Rachidi, M. Ianoz, and C. Mazzetti, “Lightning-induced voltage on overhead lines,” IEEE Trans. Electromag. Compat., vol. 35, Feb. 1993. [25] Y. Hongo, K. Michishita, and M. Ishii, “Distribution of lightninginduced voltage along an overhead wire,” in Proc. Int. Conf. Lightning Protection, ICLP’96, 1996. [26] S. Guerrieri, M. Ianoz, C. Mazzetti, C. A. Nucci, and F. Rachidi, “Lightning-induced voltages on an overhead line above a lossy ground: A sensitivity analysis,” in Proc. Int. Conf. Lightning Protection, ICLP’96, 1996. Hans Kr. Høidalen was born in Draugedal, Norway, in 1967. He received the M.Sc. degree in electrical engineering from the Norwegian Institute of Technology, in 1990 and is currently pursuing the Ph.D. degree at the Norwegian University of Science and Technology. Jarle Sletbak was born in Namdalseid, Norway, in 1928. He received the M.Sc. degree in electrical engineering from the Norwegian Institute of Technology, in 1953. He is presently a Professor at the Norwegian University of Science and Technology. His main field of interest is insulating materials and their application in high voltage equipment. Thor Henriksen was born in Trondheim, Norway, in 1946. He received the M.Sc. degree in electrical engineering from the Norwegian Institute of Technology, in 1970, and the Dr.Ing. degree in 1973. He is presently working at the Norwegian Electric Power Research Institute as a Senior Research Scientist, mainly in the field of transient studies.