Energy- and Power Cable / Power Cables / Power cables for energy supply NAY2Y power cable, 0,6/1kV, with PE-outer sheath Technical data Ⴠ Power and control cable to DIN VDE 0276 part 603, HD 603 S1 and IEC 60502 Ⴠ Temperature range flexing -5°C to +50°C fixed installation -40°C to +70°C Ⴠ Permissible operating temperature at conductor +70°C Ⴠ Permissible short circuit temperature (short circuit duration max. 5 s) +160°C Ⴠ Nominal voltage U0/U 0,6/1 kV Ⴠ Test voltage 4 kV Ⴠ Max. permissible tensile stress with cable grip at conductor 30 N/mm² Ⴠ Minimum bending radius 12x cable Ø Cable structure Properties Ⴠ Aluminium-conductor, to DIN VDE 0295 cl.1, single-wire, BS 6360 cl.1, IEC 60228 cl.1 Ⴠ Core insulation of PVC Ⴠ Core identification GN-YE, BN, BK, GY Ⴠ Cores stranded in concentric layers Ⴠ Common core sheath Ⴠ Outer sheath of PE Ⴠ Sheath colour black Ⴠ outer sheath PE of not self-extinguishing and flame retardant Ⴠ The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers Highest permissible voltage Ⴠ Direct current systems 1,8 kV Ⴠ Alternating current systems • Single-phase systems both outer conductors insulated 1,4 kV • Single-phase systems one outer conductor earthed 0,7 kV Ⴠ Three-phase systems 1,2 kV Note Ⴠ re = round conductor, single-wire se = sectional conductor, single-wire Ⴠ AWG sizes are approximate equivalent values. The actual cross-section is in mm². Application Power cables for energy supply are installed in open air, in underground, in water, in concrete, indoors, in cable ducts, power stations, for industry and distribution boards as well as in subscriber networks. Usable in extreme working conditions due to the robust PE outer sheath. = The product is conformed with the EC Low-Voltage Directive 2006/95/EC. Part no. 31129 31139 31149 31159 31169 31179 31189 31199 31209 No.cores x cross-sec. mm² 4 x 25 4 x 35 4 x 50 4 x 70 4 x 95 4 x 120 4 x 150 4 x 185 4 x 240 Outer Ø app. mm re re se se se se se se se 26,0 28,0 30,0 33,0 38,0 42,0 45,0 51,0 55,0 Dimensions and specifications may be changed without prior notice. (RQ01) 546 Alu weight kg / km 290,0 406,0 580,0 812,0 1102,0 1382,0 1740,0 2146,0 2784,0 Weight app. kg / km 970,0 1145,0 1184,0 1578,0 2186,0 2501,0 3180,0 3807,0 4996,0 AWG-No. 4 2 1 2/0 3/0 4/0 300 kcmil 350 kcmil 500 kcmil