Tailor Made Concrete Structures – Walraven & Stoelhorst (eds) © 2008 Taylor & Francis Group, London, ISBN 978-0-415-47535-8 Monitoring of electrically isolated post-tensioning tendons B. Elsener ETH Zurich, Institute for Building Materials, Zurich, Switzerland ABSTRACT: Electrically Isolated Tendons (EIT) have been introduced as one possible solution to reach the highest protection level (PL3) in the framework of fib recommendation for grouted post-tensioned tendons. This approach allows to check the integrity of the plastic duct during and after construction and to monitor the corrosion protection of the high-strength steel during the whole service life with electrical impedance measurements. The paper presents results on PC structures with EIT regarding quality control, long term monitoring and location of defects. Practical experience in Switzerland over the last six years was included in the revision of the Swiss Guideline “Measures to ensure the durability of post-tensioning tendons in bridges”. 1 INTRODUCTION Post-tensioning tendons contribute decisively to the serviceability, safety and durability of pre-stressed concrete (PC) bridges. In order to reach the goals of durability (optimum corrosion protection) and of monitoring requested by the Italian Railways (Italian Standard, 1997) and the Swiss Federal Roads and RailwayAuthorities, the new system of electrically isolated tendons according to the Swiss Guideline (Swiss Guideline, 2001) has been adopted. In Switzerland about 80 bridges of different length have been constructed since 1995 with thick-walled corrugated plastic ducts and electrically isolated anchorages (Elsener et al. 2002; Ayats et al. 2002) Similar systems have been massively applied for the first time in Italy for the design and construction of several bridges and viaducts of the new high-speed lines (Della Vedova & Elsener 2006; Prevedini et al. 2004; Bonasso et al. 2006). In Italy, traditional choice for railway bridges is the use of simply supported spans and about 90% of the viaducts of the new lines are realised with partial or total pre-casting of PC decks; this allowed to carry out test programmes on the construction site and extensive quality control during construction – a point that has been recognized to be more difficult on continuous span bridges as those usually constructed in Switzerland. Electrically isolated tendons have been introduced as one possible solution to reach the highest protection level (PL3) in the framework of fib recommendations (fib 2005, Elsener (ed.) 2004). Using electrically isolated tendons allows to check the electrical isolation of the tendons and the integrity of the plastic duct during and after construction (Ayats et al. 2002, Della Vedova et al. 2004) and to monitor the corrosion protection of the tendons during service life with impedance measurements (Della Vedova et al. 2004, Elsener 2005). To achieve the required durability and safety, new post-tensioning tendons are currently designed and executed following a multi-layer protection approach. The single tendons should easily be monitored over time and damage should be detected at a very early time. Industry in the last 10 years has developed such new post-tensioning tendons, based on a complete encapsulation of the sensitive high-strength steel into a grouted polymeric duct. Combined with electrical isolation of the anchorages a simple, non-destructive monitoring of the individual tendons is possible. 2 2.1 QUALITY CONTROL OF EIT TENDONS Measuring principle The impedance measurements are performed between the steel strands in the grouted ducts and the normal reinforcement in concrete (Fig. 1). The measuring system thus includes the grout in the duct, the duct (with pores and defects) and the concrete surrounding the duct. Grout and concrete are (at least in the range of measuring frequencies between 100 and 1000 Hz) pure resistances, the polymer duct instead is essentially a capacitance in parallel with a very high resistance (Fig. 1). Any system related imperfections (e.g. not fully closed grout vents) and/or defect in the duct are represented by an ohmic resistance in parallel. 231 Table 1. Calculated specific values of the ohmic resistance R, the capacitance C and the loss factor D from the flyover “P.S. du Milieu” (length 100 m). Measurements performed 28 days after grouting. Tendon Nr. R (km) C (nF/m) D (–) 1 2 3 4 5 6 723 1370 2087 1781 2825 short circuit 2.34 2.33 2.35 2.37 2.35 0.093 0.048 0.032 0.037 0.023 Figure 1. Principle of measuring the electrical impedance of a tendon with an LCR meter. Recommended measuring frequency is 1 kHz. 2.2 Results from laboratory measurements Measurements on 1 m long grouted plastic ducts (ø 59 mm) in concrete blocks (Elsener et al. 2002) have shown that intact (reference), welded or coupled ducts have a very high resistance value (>2.3 M at 1 kHz) and very low loss factors D (<0.034), thus they behave essentially as capacitance. Ducts with a 2 mm hole show comparably low resistance values (<100 k) and the resistance drops to less than 1 k for 40 mm holes. The loss factor is very high, thus at 1 kHz these systems behave as resistance. An open grout vent that ends in the concrete (thus a very small electrolytic contact is possible) has a resistance of 573 k and a loss factor of 0.098. As a not perfectly closed grout vent represents a “defect” for the impedance measurement but by no means a loss in durability, this situation was chosen as borderline between acceptable and nonacceptable defect. The acceptance criteria in the Swiss Guideline (2001) was defined as R = 500 km, the control value D < 0.1. The capacitance values C of the 1 m long segments of plastic ducts were measured to 2.34 ± 0.04 nF/m irrespective of the presence of holes. 2.3 Results from field applications – Switzerland Both resistance and capacitance values measured depend on the length L of the tendon: the resistance values R decrease proportional to the length L, the capacitance value C increase. For quality control the specific values R in km and C in nF/m have to be used. The first structures constructed with EIT posttensioning tendons were built in Switzerland (Ayats et al. 2002). In these pilot projects the acceptance Figure 2. Capacitance C of the individual EIT tendons in a flyover near Basel as a function of the tendon length. Diameter of plastic duct 59 mm. criteria of the Swiss Guideline (2001) could be reached (Elsener et al. 2002). In one of the flyovers a 100 m long tendon (Nr. 5) even reached the maximum theoretical value of the resistance R, indicating a perfect isolation at the anchorages and execution on site (table 1). The increasing number of PC structures constructed with EIT tendons in Switzerland allowed to gain more practical experience. Often contractors and owners complained about the difficulty or even impossibility to reach the acceptance criteria fixed in the Swiss guideline (2001). Some case studies are documented in a report by Büchler et al. (2005), other examples are given in this paper. A flyover constructed for a highway link with about 60 EIT tendons of different length showed that the capacitance values of the individual tendons are proportional to the tendon length L as expected (Fig. 2). From the slope of the diagram a value of C = 2.35 nF/m was obtained in good agreement with laboratory results. The results of the resistance values R (multiplied by the length of the tendons) showed values from 10 to 232 Table 2. Experimentally measured capacitance C (mean value and standard deviation) of 71 decks of the Piacenza viaduct. Tendon length 32.1 m. Measurements performed 28 days after grouting. Type C (nF) std dev (nF) C spec (nF/m) ø 76 mm ø 100 mm 70.3 73.5 2.34 2.33 2.2 2.3 Figure 3. Cumulative probability plot of the resistance values measured for EIT tendons in a flyover near Basel. Diameter of plastic duct 59 mm. 1800 km. In the cumulative probability plot (Fig. 3) clearly two distributions (lines) could be observed: the one at high R values was associated to “good” tendons (acceptance criteria fulfilled). However, ca. 50% of the tendons did not reach the acceptance criteria. Overall the percentage of success in different PC structures showed big differences: bridge structures with EIT tendons where 100% were considered as “good”, others where only 30% of the tendons fulfilled the acceptance criteria. Many reasons, e.g. the beginning of the transfer of the EIT technology to practice, the length of the cables, the presence of couplers, design or execution problems were discussed. 2.4 Results from field application – Italy In the Italian high speed network the Piacenza viaduct on the Milano-Bologna line is an example for fullspan pre-casting of 151 simply supported pre-cast prestressed concrete decks composed by a monolithic box girder with two cells, spanning 33.1 m and weighting about 1000 tons. The design of the elements and of the viaduct has been reported previously (Prevedini et al. 2004, Bonasso et al. 2006). Data have been collected from the first 71 decks of the Piacenza viaduct (Della Vedova & Elsener 2006), each deck containing 9 cables with 12 wires, duct ø 76 mm (in the lower slab) and 15 cables with 19 wires, duct ø 100 mm (in the webs). The values of the capacitance C (table 2) allow a first control on the execution quality. The values of the capacitance are Gaussian distributed and show a very small standard deviation, indicating the good reproducibility. The mean value is higher for ducts with higher diameter, the specific capacitance (per meter length) is well below the control values specified in the Swiss Guideline (2001). The statistical analysis of the measured resistance R on more then 1000 tendons is more complicated Figure 4. Cumulative probability plot of the resistance values measured for EIT tendons in 71 segments of the Piacenza viaduct. Diameter of plastic duct 100 mm. The numbers correspond to individual tendons position in the web. Note the logarithmic x-axis. (Della Vedova & Elsener 2006). because the values – despite the constant length of the tendons – do not show a Gaussian distribution. The analysis is thus performed with the cumulative probability plot (Fig. 4, 5). For the tendons with ø 100 mm from the segments of the Piacenza viaduct (Fig. 4), less then 1% of all values are below 10 Ohm, thus cables with a short circuit (electrical contact between tendon and normal rebars). From the limiting value of the specific resistance R (300 km in the Swiss Guideline 2001) a limiting resistance value R of 9 k can be calculated for the tendon with length 32.1 m. As can be seen from figure 4 the limiting value is not reached by only 9% of the tendons (Della Vedova & Elsener 2006). The cumulative probability plot shows further that there is no distinct tendon position that makes more difficulties then others. In addition, it can be noted 233 Table 3. Limiting values (acceptance criteria) for the electrical resistance measured 28 days after grouting the tendon for the three main criteria “monitoring”, “fatigue” and “stray current” according to the new Swiss guideline (2007). Figure 5. Evolution of the resistance measured for the 6 tendons in the flyover “Pré du Mariage” with time. Diameter of plastic duct 76 mm. that for each tendon position about 5% of all segments were produced with perfect isolation (reaching the theoretical value of a completely tight plastic duct). For the tendons in the lower slab with diameter 76 mm the situation is similar (Della Vedova & Elsener 2006). About 20% of all the tendons did not reach the acceptance criteria (resistance R 12 k). For each tendon position about 5% of all segments showed a perfect electrical isolation (Della Vedova & Elsener 2006). The broad distribution of resistance values measured on EIT tendons in prefabricated decks shows that there is a strong influence of the human factor, as written procedures, approved material and components, deck formwork, reinforcement and pre-stressing were always the same. 3 REVISED SWISS GUIDELINE Practical experience reported in part above, in a report by Büchler et al. (2006) and from a great number of PC structures with EIT not published lead to the conclusion that the acceptance criteria in the Swiss Guideline (2001) were in part too severe and not sufficiently related to engineers and owner needs. Tendons that do not reach the old acceptance criteria at 28 days but are without short circuit cannot be considered “defective” for several reasons: 1) these tendons with plastic ducts have a better protection against fatigue and chloride ingress compared to metallic ducts, 2) the electrical impedance can still be measured and followed over time (see chapter 4) and 3) the resistance will increase with time and might reach the criteria. For this reason the new Swiss guideline (2007) defines limiting values for the three main causes to Diameter (mm) Monitoring R (km) Fatigue R () Stray current R (km) 60 75 100 130 Maximum Failure 50 50 50 50 10% 20 20 20 20 0% 250 200 150 125 20% apply electrically isolated tendons in PC structures: a limiting value of the resistance for monitoring, for fatigue and for stray current (table 3). In addition a simple formula to account for the influence of time is given, too. The guideline establishes also what actions have to be taken is the acceptance criteria are not fulfilled: For the main criteria “fatigue” a resistance value R < 20 indicates a metallic contact between the rebars and the high-strength steel in the duct. This might lead to fretting corrosion (Oertle 1988). The position of the short-circuit has to be located (see chapter 5). If the contact is in an area critical for fatigue the consequences for a failure of this tendon have to be checked. For the main criteria “stray current” all the tendons should have a very high resistance in order to prevent stray current on the high-strength steel. Tendons that do not fulfill the acceptance criteria have to be electrically connected to the normal reinforcement. These connections can be opened for monitoring purpose. For the main criteria “monitoring” the acceptance criteria is 50 km (table 3). If this criteria is not reached the tendon is not necessarily less durable, but the detection of the ingress of water (and chlorides) at defects is less sensitive. The defect should be located and if it is found in an area critical for the ingress of water additional protection measures can be applied. 4 LONG TERM MONITORING One of the major concerns regarding internal bonded post-tensioned tendons is the inability to inspect the tendons visually and the absence of established nondestructive techniques to monitor corrosion of the steel strands (Matt 2000). Using electrically isolated tendons with plastic ducts, the evolution of the resistance values over time can be used to control the integrity of the corrosion protection system. 234 Figure 7. Experimental setup of magnetic flux measurements to locate short circuits in a electrically isolated tendon (Büchler et al. 2005). One tendon clearly shows a decrease in the resistance value, indicating the ingress of water at a defect in the duct. Figure 6. Evolution of the normalized electrical resistance measured for four tendons in a small bridge (tendon length 22.9 m) with time. Diameter of plastic duct 76 mm. 4.1 First example The flyover “Pré du Mariage” is a relatively simple, short box girder structure with only one column in the centre of the span. Six electrically isolated tendons of ø 76 mm and length 49.3 m were used. At “Pré du Mariage” electrical impedance measurements have been performed at frequent intervals since the time of grouting (Elsener et al. 2002). The evolution of the electrical resistance with time is shown in figure 6. As can be noted, the values for the six individual tendons show a certain scatter, but the overall trend is an increase of the electrical resistance with time over a period of nearly 8 years. In the log R vs log t plot (Fig. 5) a straight line with slope 0.5 is found (annotated “trend”). This increase of the electrical resistance with time is due to the progressive hydration and drying out of grout and concrete (Bürchler et al. 1996). The results can be interpreted in the way that none of the six tendons shows water (and chloride) ingress so far and the high strength steel is protected against corrosion. 4.2 Second example In a second example, a small 22.9 m long bridge, impedance measurements have been performed over time, too. The resistance values of the individual tendons differed strongly, so the resistance was normalized at 28 d (giving all tendons the resistance value 1 at this time). This allows to follow the resistance over time more easily and without being influenced by the initial amount of defects present. As can be seen from figure 6, the trend line corresponding to an asymptotic increase of the electrical resistance of the tendons hold also for this example. 5 DEFECT LOCATION When short circuits (resistance R < 10 ) or very low resistance values are measured at the time of quality control (acceptance), the question arises whether the defect can be located in order to estimate its consequences for the durability, to improve the system in upcoming applications, or to repair the defect. Techniques for detecting these defects were developed and tested (Büchler et al. 2005) 5.1 Locating short circuits Imposing an AC electric field (frequency 500– 1000 Hz) between the high strength steel and the reinforcement (using the electrical connections provided for the impedance measurements), a current is flowing through the tendon. Measuring the magnetic flux B of the resultingAC-current allows determine the areas with current flow and, as a consequence, to locate the preferred sites (short circuits) where the current is leaving the tendon. A schematic representation of the experimental setup is shown in figure 7. As instrument a commercial cable locater CL20 (company BAUR Prüf- und Messtechnik, Sulz, Austria) was used. Figure 8 shows the result of short-circuit location on a 100 m long bridge deck with 16 tendons. The electrical connection to the tendon was made at the left end (position 100 m). The magnetic flux B varies along the tendons due to the different distance from the deck surface (high points at 30 m and 70 m). Tendon Nr. 1 shows a short circuit at 32.5 m, tendon 16 two defects at 27.6 and 31.6 m, tendon 14 a short circuit at 71.6 m and tendon 3 might have a defect in the anchorage zone. The technique primarily locates the defect with the lowest resistivity (e.g. metallic contacts between tendon and reinforcement). Such low resistive defects might mask other defects (e.g. small holes in the duct). 235 Figure 8. Experimental setup of magnetic flux measurements to locate short circuits in a electrically isolated tendon (Büchler et al. 2005). The most reliable location is possible if the tendon is electrically connected from both ends. 6 CONCLUSIONS Electrically isolated tendons (EIT) are a new system to enhance the durability of structures with post-tensioned tendons to the protection level PL3. Measurements of the electrical impedance on electrically isolated tendons have shown to be an efficient way for quality control of the tendons. Monitoring over time allows detecting the penetration of (chloride containing) water at defects in the ducts. Thus for the first time, a simple, cost-effective early warning system for post-tensioned tendons is available. Magnetic flux measurements allow locating defects (short circuits and holes) in the tendons. For optimum success the tendons should be electrically connected at both ends. ACKNOWLEDGMENTS The colleagues of WG2 “New Systems” of COST 534 “New materials and systems for pre-stressed concrete structures” – M. Della Vedova, M. Büchler, A. Gnägi – are greatfully acknowledged for their collaboration. REFERENCES Ayats J., Gnägi A., Elsener B. (2002). Electrical Isolation as Enhanced Protection for Post-tensioning Tendons in Concrete Structures, Proc. Int. fib Congress 2002, October 13–19, Osaka, Japan. Bonasso R., Traini G., Della Vedova M. (2006). High speed railway prestressed concrete bridges, Proc. 2nd International fib congress, 5/8 July 2006, Naples. Büchler M., Schiegg, Y. and Voûte C.-H. (2005). Electrically isolated tendons: Use in regions with stray currents and localization of short circuits to the reinforcement and of defects. Report 585, VSS, Zürich. In German. Bürchler D., Elsener B. and Böhni H. (1996). Electrical resistivity and dielectric porperties of hardened cement paste and mortar., Electrically based Microstructural Characterization, ed. R.A. Gerhardt, S.R. Taylor and E.J. Garboczi, Mat. Res. Soc. Symp. Proc. Vol. 411 p. 407. Della Vedova M., Elsener B., Evangelista L. (2004). Corrosion protection and monitoring of electrically isolated post-tensioning tendons, Schriftenreihe der Technischen Universität Wien, Proc. Third European Conference on Structural Control, 3ESCC, Vienna July 2004, ed. R. Fleisch, H. Irschik and M. Krommer, Vol. II pp. S5-47– S5-51. Della Vedova M. & Elsener B. (2006). Enhanced Durability, Quality Control and Monitoring of Electrically isolated tendons, Proc. 2nd International fib congress, 5/8 July 2006, Naples. Elsener B. (ed.) (2004). Proceedings of the second international workshop on durability of post-tensioning tendons, Zurich 10.–13. October 2004. ETHZ Institute of Building Materials. Elsener B. (2005). Long-term monitoring of electrically isolated post-tensioning tendons, fib Journal Structural Control 6: 101–106 Elsener B., Toller L., Voute C., Böhni H. (2002). Ueberprüfen des Korosionsschutzes von Spanngliedern mit Kunststoffhüllrohren, Report Nr. 564 (VSS) Zürich fib recommendation (2005). “Durability of post-tensioning tendons”, fib bulletin Nr. 33 Ganz H.R. (1997). Plastic ducts for enhanced performance of post-tensioning tendons, FIP Notes 1997/2, The Institution of Structural Engineers, London, pp. 15–18. Italian Standard (1997), Istruzione F.S. n. I/SC/PS-OM/2298 del 2.6.1995 “Sovraccarichi per il calcolo dei ponti ferroviari – Istruzioni per la progettazione, l’esecuzione e il collaudo”, Final review 1997. Matt P. (200). Non-destructive evaluation and monitoring of post-tensioning tendons, fib bulletin 15 Durability of posttensioning tendons pp. 103–108. Oertle J. (1988). Reibermüdung einbetonierter Spannkabel, Bericht No. 166, Institut für Baustatik und Konstruktion ETHZ, Birkhäuser (Basel). Prevedini C., Averardi Ripari F., Della Vedova M. (2004). “Il Viadotto Piacenza per la Linea ad Alta Velocità Milano-Bologna, una soluzione costruttiva tecnologicamente avanzata con un sistema di precompressione innovativo”, Giornate Aicap, 27/29 Maggio 2004, Verona. Swiss Guideline (2001), “Measures to ensure the durability of post-tensioning tendons in bridges”, Swiss Federal Roads Authority and Swiss Federal Railways, edition 2001. PDFDownload under www.astra.admin.ch. Swiss Guideline (2007). “Measures to ensure the durability of post-tensioning tendons in bridges”, Swiss Federal Roads Authority and Swiss Federal Railways, edition 2007. PDFDownload under www.astra.admin.ch. 236