KRB0444 800-1600AF Panel Mount Handle

advertisement
D140
F [mm]
E-190.5
E-190.5
E-219.5
E-219.5
E-239.5
E-239.5
E [mm]
298~368
368~638
327~397
397~667
347~417
417~687
・Perform the anti-rust treatment to the metal section.
T1HPX6
-
T1HP80
D120
Group
Handle types
E-286
E-358
E-315
E-387
E-335
E-407
G [mm]
-
-
-
remarks
The Handle Depth/ The Mounting Direction Changing Procedure
2G0467SAA (KRB
KRBKRB-0444)
0444
7-2-10 Kamihigashi, Hiranoku, Osaka
547-0002, Japan
TEL:81-6-6791-9323/ FAX:81-6-6791-9274
Web Site: www.terasaki.co.jp
Email: int-sales@terasaki.co.jp
Please retain this manual for future reference. The Manufacturer assumes no responsibility for
damages resulting from non-application or incorrect application of the instructions provided herein.
This device allows the breaker installed in comparatively deep motor control center or
switchboard to be operated manually without the need for opening the panel of the motor control
center or switchboard.
Type: T1HP80
T1HPX6
Door-Mounted
External Operating Handle
Instruction Manual
and
・
steps
(No.2)
Tube
Operation unit
Gasket for dust protection
Key (optional)
M5×60- 4pcs. (T1HP80), M6×100- 4pcs.(T1HPX6)
Pan head screws
Mounting plate
in the Remarks column mean that the applicable product must be followed the
and
as shown in the figures above.
M4×10- 4pcs.
M4×14- 4pcs.
Flat head screws (black)
Square shaft
Handle unit
Packaged Items
(4.5×50)
(No.2)
XE600NS, XS600CS, XS600NS, XS600NE, XH600NE, XS600NN, XS630CJ,
XS630NJ, XS630NE, XH630NE, XS630NN, XS800CS, XS800NS, XS800NJ,
XS800NE, XS800SE, XH800PS, XH800PJ, XH800NE, XH800SE, XH800PE,
XS800NN, XS1000ND
XS1000NE, XH1000NE, XS1000NN, XS1200NE, XH1200NE, XS1200NN,
XS1250CE, XS1250NE, XS1250SE, XS1250NN
TL-600NE, TL-800NE, TL-1000NE, TL-1200NE, XS1200ND, TL-1250NE,
XS1250ND, XS1600CE, XS1600NE, XS1600SE, XS1600ND, XS1600NN
Applicable breaker types
3.6 - 4.4 N・m
Be sure to read these Instructions and other associated documents accompanying the product
thoro- ughly to be familiarize yourself with the product handling, safety information, and all other
precautions before mounting, using, servicing, or inspecting the product. In these Instructions,
safety notices are divided into " Warning" and " Caution" according to the hazard level:
Warning : A warning notice with this symbol indicates that neglecting the suggested procedure
or practice could be fatal or result in serious personal injury.
Caution : A caution notice with this symbol indicates that neglecting the suggested procedure or
practice could result in moderate or slight personal injury and/or property damage.
Note that failing to observe caution notices could result in serious injury/damage in some situations.
Because safety notices contain important information, be sure to read and observe them.
Safety Notices
Assembly Tools
D140
D120
-
T1HP80
T1HPX6
Group
Handle types
Applicable Breaker Types
Warning
Square shaft
installation
positions
Mounting
direction
(Default)
Upper power supply type
Square shaft installation positions
Left power supply
type
3.6 - 4.4 N・m
Right power supply
type
:Referring to the table below, install the square shaft in the position matched to the
change in breaker mounting direction.
■Installation Precautions
●Electrical work should only be undertaken by suitably qualified persons.
●Prior to commencing any work on the product, open an upstream circuit breaker or isolator
to ensure that no voltage is applied to the product. Otherwise, electrical shock may result.
●To remain the switchboard panel closed securely, use appropriate hardware in addition to
the panel lock of the handle. Using the panel lock only may result in damage to the
switchboard panel.
■Operation Precautions
●When the breaker trips open automatically, remove the cause, then return the handle to the
|(ON) position. Should a fault be interrupted, the breaker must be inspected. Otherwise, a
fire may result.
●Do not apply excessive force to the operating knob. Otherwise, damage may occur.
Caution
■Operation Precautions
●Never touch live terminals. Doing so may result in electric shock.
Mounting
M6
M4×14 mm
1.0-1.7N・m
(No.2)
Handle unit
Panel
:Screws position for removal
M5
T1HPX6
Handle Operation
・This applies when the panel requires to be opened while the breaker is in the ┃ (ON) or
for normal panel opening procedure.
TRIP position. See
(4.5×50)
Gasket for dust protection
Panel Opening Procedure by Panel Lock Release
2G0467SAA (KRB
KRBKRB-0444)
0444
J
H
T1HP80
・For detailed mounting dimensions, refer to the catalogue.
TRIP Operation with the Panel Open
(No.2)
Handle catch
:Screws position for mounting
M5×60 mm M6×100 mm
3.6 - 4.4 N・m 6.0 - 7.4 N・m
T1HPX6
ON Lock Operation
OFF Lock Operation
・When unlocking, unlock the handle in reverse order of lock.
Max×3
(φ5.5 - 8)
・Padlock is not supplied.
Handle Lock Operation
Max×3
(φ5.5 - 8)
・The figure shows the upper power supply type. For the right (left) power supply type, rotate all
the components, excluding the handle unit and the panel, 90 degrees clockwise (counterclockwise).
・After mounting, verify the function of the device.
・Prior to removing, open an upstream circuit breaker or the like to isolate all sources of power/
voltage. Doing so may result in electric shock. When removing, remove the items in reverse
order of mounting.
I
T1HP80
・When unlocking, unlock the handle in reverse order of lock.
ON Lock Operation
OFF Lock Operation
Key Lock Operation (Optional)
)
OFF Open Type
Panel Opening Procedure
Reset Open Type
Panel knob
Download