Door-Mounted External Operating Handle Instruction Manual Type

advertisement

Door-Mounted

External Operating Handle

Instruction Manual

Type: T1HP80

T1HPX6

This device allows the breaker installed in comparatively deep motor control center or switchboard to be operated manually without the need for opening the panel of the motor control center or switchboard.

Please retain this manual for future reference. The Manufacturer assumes no responsibility for damages resulting from non-application or incorrect application of the instructions provided herein.

          7-2-10 Kamihigashi, Hiranoku, Osaka

          547-0002, Japan

          TEL:81-6-6791-9323/ FAX:81-6-6791-9274

          Web Site: www.terasaki.co.jp

          Email: int-sales@terasaki.co.jp

2G0467SAA (KRB‑0444)

The Handle Depth/ The Mounting Direction Changing Procedure

Packaged Items

Handle unit        Mounting plate        Operation unit

( 4.5

× 50 )        ( No.2

)

Square shaft        Tube

M4 × 14- 4pcs.

       M5 × 60- 4pcs.

 

 

(T1HP80) ,   M6 ×100 - 4pcs.

(T1HPX6)

Flat head screws ( black ) Pan head screws

 

Safety Notices

Be sure to read these Instructions and other associated documents accompanying the product thoro- ughly to be familiarize yourself with the product handling, safety information, and all other precautions before mounting, using, servicing, or inspecting the product. In these Instructions, safety notices are divided into " Warning" and " Caution" according to the hazard level:

Warning : A warning notice with this symbol indicates that neglecting the suggested procedure or practice could be fatal or result in serious personal injury.

Caution : A caution notice with this symbol indicates that neglecting the suggested procedure or practice could result in moderate or slight personal injury and/or property damage.

Note that failing to observe caution notices could result in serious injury/damage in some situations.

Because safety notices contain important information, be sure to read and observe them.

Gasket for dust protection      Key ( optional )

Applicable Breaker Types

Handle types Group

T1HP80

T1HPX6

D120

D140

Applicable breaker types

XE600NS, XS600CS, XS600NS, XS600NE, XH600NE, XS600NN, XS630CJ,

XS630NJ, XS630NE, XH630NE, XS630NN, XS800CS, XS800NS, XS800NJ,

XS800NE, XS800SE, XH800PS, XH800PJ, XH800NE, XH800SE, XH800PE,

XS800NN, XS1000ND

XS1000NE, XH1000NE, XS1000NN, XS1200NE, XH1200NE, XS1200NN,

XS1250CE, XS1250NE, XS1250SE, XS1250NN

TL-600NE, TL-800NE, TL-1000NE, TL-1200NE, XS1200ND, TL-1250NE,

XS1250ND, XS1600CE, XS1600NE, XS1600SE, XS1600ND, XS1600NN

Assembly Tools

Warning

Operation Precautions

● Never touch live terminals. Doing so may result in electric shock.

Caution

■ Installation Precautions

● Electrical work should only be undertaken by suitably qualified persons.

● Prior to commencing any work on the product, open an upstream circuit breaker or isolator to ensure that no voltage is applied to the product. Otherwise, electrical shock may result.

● To remain the switchboard panel closed securely, use appropriate hardware in addition to the panel lock of the handle. Using the panel lock only may result in damage to the switchboard panel.

■ Operation Precautions

● When the breaker trips open automatically, remove the cause, then return the handle to the

|(ON) position. Should a fault be interrupted, the breaker must be inspected. Otherwise, a fire may result.

● Do not apply excessive force to the operating knob. Otherwise, damage may occur.

M 4 × 10- 4pcs.

( No.2

)

: Referring to the table below, install the square shaft in the position matched to the change in breaker mounting direction.

Square shaft installation positions

Upper power supply type Left power supply type

Mounting direction

Right power supply type

3.6 - 4.4 N ・ m

Square shaft installation positions

( Default )

3.6 - 4.4 N ・ m

Handle types

T1HP80

T1HPX6

Group

D120

D140

E [mm]

298 〜 368

368 〜 638

327 〜 397

397 〜 667

347 〜 417

417 〜 687

・ Perform the anti-rust treatment to the metal section.

F [mm]

E-190.5

E-190.5

E-219.5

E-219.5

E-239.5

E-239.5

G [mm]

E-286

E-358

E-315

E-387

E-335

E-407 remarks

・ and in the Remarks column mean that the applicable product must be followed the steps and as shown in the figures above.

Mounting

・ For detailed mounting dimensions, refer to the catalogue.

T1HP80 T1HPX6

H

M5 M6

Screws position for removal

Gasket for dust protection

Panel

Handle unit

( No.2

)

M4 × 14 mm

・ m

2G0467SAA (KRB‑0444)

Panel Opening Procedure by Panel Lock Release

( 4.5

× 50 )

TRIP Operation with the Panel Open

Handle catch

( No.2

)

・ This applies when the panel requires to be opened while the breaker is in the ┃ (ON) or

TRIP position. See for normal panel opening procedure.

Handle Operation

T1HP80 T1HPX6

I

M5 × 60 mm M6 × 100 mm

3.6 - 4.4 N ・ m 6.0 - 7.4 N ・ m

Screws position for mounting

Panel Opening Procedure

Reset Open Type

OFF Open Type

・ The figure shows the upper power supply type. For the right (left) power supply type, rotate all the components, excluding the handle unit and the panel, 90 degrees clockwise (counterclockwise).

・ After mounting, verify the function of the device.

・ Prior to removing, open an upstream circuit breaker or the like to isolate all sources of power/ voltage. Doing so may result in electric shock. When removing, remove the items in reverse order of mounting.

Handle Lock Operation

・ Padlock is not supplied.

OFF Lock Operation

Key Lock Operation

(

Optional

)

OFF Lock Operation

Max × 3

(φ 5.5 - 8 )

ON Lock Operation

Max × 3

(φ 5.5 - 8 )

ON Lock Operation

・ When unlocking, unlock the handle in reverse order of lock.

・ When unlocking, unlock the handle in reverse order of lock.

Panel knob