This device allows the breaker installed in comparatively deep motor control center or switchboard to be operated manually without the need for opening the panel of the motor control center or switchboard.
Please retain this manual for future reference. The Manufacturer assumes no responsibility for damages resulting from non-application or incorrect application of the instructions provided herein.
7-2-10 Kamihigashi, Hiranoku, Osaka
547-0002, Japan
TEL:81-6-6791-9323/ FAX:81-6-6791-9274
Web Site: www.terasaki.co.jp
Email: int-sales@terasaki.co.jp
2G0467SAA (KRB‑0444)
The Handle Depth/ The Mounting Direction Changing Procedure
Packaged Items
Handle unit Mounting plate Operation unit
( 4.5
× 50 ) ( No.2
)
Square shaft Tube
M4 × 14- 4pcs.
M5 × 60- 4pcs.
(T1HP80) , M6 ×100 - 4pcs.
(T1HPX6)
Flat head screws ( black ) Pan head screws
Safety Notices
Be sure to read these Instructions and other associated documents accompanying the product thoro- ughly to be familiarize yourself with the product handling, safety information, and all other precautions before mounting, using, servicing, or inspecting the product. In these Instructions, safety notices are divided into " Warning" and " Caution" according to the hazard level:
Warning : A warning notice with this symbol indicates that neglecting the suggested procedure or practice could be fatal or result in serious personal injury.
Caution : A caution notice with this symbol indicates that neglecting the suggested procedure or practice could result in moderate or slight personal injury and/or property damage.
Note that failing to observe caution notices could result in serious injury/damage in some situations.
Because safety notices contain important information, be sure to read and observe them.
Gasket for dust protection Key ( optional )
Applicable Breaker Types
Handle types Group
T1HP80
T1HPX6
−
D120
D140
Applicable breaker types
XE600NS, XS600CS, XS600NS, XS600NE, XH600NE, XS600NN, XS630CJ,
XS630NJ, XS630NE, XH630NE, XS630NN, XS800CS, XS800NS, XS800NJ,
XS800NE, XS800SE, XH800PS, XH800PJ, XH800NE, XH800SE, XH800PE,
XS800NN, XS1000ND
XS1000NE, XH1000NE, XS1000NN, XS1200NE, XH1200NE, XS1200NN,
XS1250CE, XS1250NE, XS1250SE, XS1250NN
TL-600NE, TL-800NE, TL-1000NE, TL-1200NE, XS1200ND, TL-1250NE,
XS1250ND, XS1600CE, XS1600NE, XS1600SE, XS1600ND, XS1600NN
Assembly Tools
■
Operation Precautions
● Never touch live terminals. Doing so may result in electric shock.
■ Installation Precautions
● Electrical work should only be undertaken by suitably qualified persons.
● Prior to commencing any work on the product, open an upstream circuit breaker or isolator to ensure that no voltage is applied to the product. Otherwise, electrical shock may result.
● To remain the switchboard panel closed securely, use appropriate hardware in addition to the panel lock of the handle. Using the panel lock only may result in damage to the switchboard panel.
■ Operation Precautions
● When the breaker trips open automatically, remove the cause, then return the handle to the
|(ON) position. Should a fault be interrupted, the breaker must be inspected. Otherwise, a fire may result.
● Do not apply excessive force to the operating knob. Otherwise, damage may occur.
M 4 × 10- 4pcs.
( No.2
)
: Referring to the table below, install the square shaft in the position matched to the change in breaker mounting direction.
Square shaft installation positions
Upper power supply type Left power supply type
Mounting direction
Right power supply type
3.6 - 4.4 N ・ m
Square shaft installation positions
( Default )
3.6 - 4.4 N ・ m
Handle types
T1HP80
T1HPX6
Group
−
D120
D140
E [mm]
298 〜 368
368 〜 638
327 〜 397
397 〜 667
347 〜 417
417 〜 687
・ Perform the anti-rust treatment to the metal section.
F [mm]
E-190.5
E-190.5
E-219.5
E-219.5
E-239.5
E-239.5
G [mm]
E-286
E-358
E-315
E-387
E-335
E-407 remarks
−
−
−
・ and in the Remarks column mean that the applicable product must be followed the steps and as shown in the figures above.
Mounting
・ For detailed mounting dimensions, refer to the catalogue.
T1HP80 T1HPX6
H
M5 M6
:
Screws position for removal
Gasket for dust protection
Panel
Handle unit
( No.2
)
M4 × 14 mm
・ m
2G0467SAA (KRB‑0444)
Panel Opening Procedure by Panel Lock Release
( 4.5
× 50 )
TRIP Operation with the Panel Open
Handle catch
( No.2
)
・ This applies when the panel requires to be opened while the breaker is in the ┃ (ON) or
TRIP position. See for normal panel opening procedure.
Handle Operation
T1HP80 T1HPX6
I
M5 × 60 mm M6 × 100 mm
3.6 - 4.4 N ・ m 6.0 - 7.4 N ・ m
:
Screws position for mounting
Panel Opening Procedure
Reset Open Type
OFF Open Type
・ The figure shows the upper power supply type. For the right (left) power supply type, rotate all the components, excluding the handle unit and the panel, 90 degrees clockwise (counterclockwise).
・ After mounting, verify the function of the device.
・ Prior to removing, open an upstream circuit breaker or the like to isolate all sources of power/ voltage. Doing so may result in electric shock. When removing, remove the items in reverse order of mounting.
Handle Lock Operation
・ Padlock is not supplied.
OFF Lock Operation
Key Lock Operation
(
Optional
)
OFF Lock Operation
Max × 3
(φ 5.5 - 8 )
ON Lock Operation
Max × 3
(φ 5.5 - 8 )
ON Lock Operation
・ When unlocking, unlock the handle in reverse order of lock.
・ When unlocking, unlock the handle in reverse order of lock.
Panel knob