Door-Mounted External Operating Handle Instruction Manual Type

advertisement
Packaged Items
Applicable Breaker Types
Handle types
T1HP80
Door-Mounted
External Operating Handle
Instruction Manual
T1HPX6
Group
−
D120
D140
Applicable breaker types
XE600NS, XS600CS, XS600NS, XS600NE, XH600NE, XS600NN, XS630CJ,
XS630NJ, XS630NE, XH630NE, XS630NN, XS800CS, XS800NS, XS800NJ,
XS800NE, XS800SE, XH800PS, XH800PJ, XH800NE, XH800SE, XH800PE,
XS800NN, XS1000ND
XS1000NE, XH1000NE, XS1000NN, XS1200NE, XH1200NE, XS1200NN,
XS1250CE, XS1250NE, XS1250SE, XS1250NN
TL-600NE, TL-800NE, TL-1000NE, TL-1200NE, XS1200ND, TL-1250NE,
XS1250ND, XS1600CE, XS1600NE, XS1600SE, XS1600ND, XS1600NN
Assembly Tools
Type: T1HP80
T1HPX6
Handle unit
Mounting plate
Operation unit
(4.5×50)
This device allows the breaker installed in comparatively deep motor control center or
switchboard to be operated manually without the need for opening the panel of the motor control
center or switchboard.
Square shaft
(No.2)
Tube
Safety Notices
Please retain this manual for future reference. The Manufacturer assumes no responsibility for
damages resulting from non-application or incorrect application of the instructions provided herein.
M4×14- 4pcs.
Flat head screws (black)
M5×60- 4pcs. (T1HP80), M6×100- 4pcs.(T1HPX6)
Pan head screws
7-2-10 Kamihigashi, Hiranoku, Osaka
547-0002, Japan
TEL:81-6-6791-9323/ FAX:81-6-6791-9274
Web Site: www.terasaki.co.jp
Email: int-sales@terasaki.co.jp
Gasket for dust protection
2G0467SAA (KRB-0444)
Key (optional)
The Handle Depth/ The Mounting Direction Changing Procedure
M4×10- 4pcs.
(No.2)
Handle types
T1HP80
T1HPX6
Group
−
D120
D140
E [mm]
F [mm]
G [mm]
298∼368
368∼638
327∼397
397∼667
347∼417
417∼687
E-190.5
E-190.5
E-219.5
E-219.5
E-239.5
E-239.5
E-286
E-358
E-315
E-387
E-335
E-407
remarks
−
−
−
・
・ Perform the anti-rust treatment to the metal section.
and
steps
in the Remarks column mean that the applicable product must be followed the
and
as shown in the figures above.
Be sure to read these Instructions and other associated documents accompanying the product
thoro- ughly to be familiarize yourself with the product handling, safety information, and all other
precautions before mounting, using, servicing, or inspecting the product. In these Instructions,
safety notices are divided into " Warning" and "
Mounting
Panel Opening Procedure
Reset Open Type
・ For detailed mounting dimensions, refer to the catalogue.
T1HP80
T1HPX6
T1HP80
Panel knob
T1HPX6
H
M5
I
M6
:Screws position for removal
M5×60 mm M6×100 mm
3.6 - 4.4 N・m 6.0 - 7.4 N・m
:Screws position for mounting
Gasket for dust protection
Panel
Handle catch
OFF Open Type
Handle unit
(No.2)
(No.2)
J
・ The figure shows the upper power supply type. For the right (left) power supply type, rotate
all the components, excluding the handle unit and the panel, 90 degrees clockwise (counterclockwise).
・ After mounting, verify the function of the device.
・ Prior to removing, open an upstream circuit breaker or the like to isolate all sources of power/
voltage. Doing so may result in electric shock. When removing, remove the items in reverse
order of mounting.
M4×14 mm
1.0-1.7N・m
2G0467SAA (KRB-0444)
Panel Opening Procedure by Panel Lock Release
TRIP Operation with the Panel Open
Handle Lock Operation
Key Lock Operation (Optional)
・ Padlock is not supplied.
OFF Lock Operation
(4.5×50)
OFF Lock Operation
Max×3
(φ5.5 - 8)
・ This applies when the panel requires to be opened while the breaker is in the ┃ (ON) or
TRIP position. See
for normal panel opening procedure.
Handle Operation
ON Lock Operation
ON Lock Operation
Max×3
(φ5.5 - 8)
・ When unlocking, unlock the handle in reverse order of lock.
・ When unlocking, unlock the handle in reverse order of lock.
Download