Evolis HP circuit breaker

advertisement
Technical data sheet
Medium Voltage Distribution
Evolis HP circuit breaker
Evolis HP circuit breaker is used
to protect and control MV public
or industrial distribution network.
PE56545
Vacuum breaking
Evolis HP is an indoor switchgear
b Rated voltage up to 15 kV
b Rated short-circuit breaking current 50 kA
b Rated normal current up to 3150 A.
Evolis HP is available in withdrawable
version with MC cassette.
Conformity with standards
b IEC 62271-1: common specifications for high voltage switchgear
and controlgear standards
b IEC 62271-100: high voltage alternating current circuit breaker
b IEC 62271-200: AC metal-enclosed switchgear and controlgear for rated voltages
above 1 kV and up to and including 52 kV.
Certification
b By independent laboratories in accordance with ISO/IEC 17025
and EN 45011 standards
b Our factories implement a quality system certified to ISO 9001: 2000
and ISO 14001 standards by IQNET.
Installation
b Withdrawable with MC cassette
b Designed for retrofit.
Operation
b The operating mechanism is activated by a spring.
A full range of accessories and auxiliaries
factory-mounted or delivered separately
b
b
b
b
b
b
b
Electric motor (M)
Undervoltage release (YM)
Shunt opening release (YO)
Low energy release (MITOP)
Shunt closing release (YF)
Auxiliary contacts
Operations counter.
Electrical characteristics according to IEC 62271-100
Phase to phase
240
Cassette type
MC3
Rated voltage
Ur
kV 50/60 Hz
7.2
12
15
- power frequency withstand
Ud
kV 50 Hz 1 min
20
28
38
- lightning impulse withstand
Up
kV peak
60
75
Rated current
Ir
A
Insulation level
Isc
kA
Short time withstand current
Ik/tk
kA/3 s
Short-circuit making current
Ip
kA peak
–
–
–
–
–
–
–
b
–
–
–
b
2500
–
–
–
b
–
–
–
b
–
–
–
b
3150
b
b
b
b
b
b
b
b
b
b
b
b
25
31.5
40
50
25
31.5
40
50
25
31.5
40
50
25
25
31.5
40
50
25
31.5
40
50
31.5
40
50
50 Hz
63
79
100
125
63
79
100
125 (*) 63
79
100
125 (*)
60 Hz
65
82
104
130
65
82
104
130 (*) 65
82
104
130 (*)
Common characteristics according to IEC 62271-100
Rated switching sequence
Operating times
Service temperature
T
O-3 min-CO-3 min-CO
b
O-0.3 s-CO-3 min-CO
b
O-0.3 s-CO-15 s-CO
b
Opening ms
< 52
Breaking ms
< 73
Closing
< 61
ms
°C
– 5 to + 40
Mechanical endurance
Class
M2
Number of operations
10 000
Electrical endurance
Class
E2
Number of switching operations
at full Isc value
25 kA
100
31.5 kA
50
40 kA
30
50 kA
30
Capacitive current breaking capacity
Class
C1
Average relative humidity
Over 24 h
< 95%
Over 1 month
< 90%
b Available
– Not available
(*) 150 kA available on request.
Dimensions and weights
Basic device
Dimensions (mm)
W
886
H
980
D
902
Weight (kg)
DE57194EN
Withdrawable with MC3 cassette
240
240
550
285
338
H
805
370
300
W
Schneider Electric Industries SAS
35, rue Joseph Monier
CS 30323
F - 92506 Rueil Malmaison Cedex
RCS Nanterre 954 503 439
Capital social 896 313 776 €
www.schneider-electric.com
AMTED307009EN
321
611
D
100
As standards, specifications and designs change from time to time, please ask for confirmation
of the information given in this publication.
This document has been printed
on ecological paper
Publishing: Schneider Electric Industries SAS
Design: Schneider Electric Industries SAS
Printing: Imprimerie du Pont de Claix/JPF - Made in France
03-2010
ART.830621 © Schneider Electric Industries SAS - All rights reserved
Short circuit current
95
1250