Square Body Flush End Contact — 690/700V (IEC/UL): 1000-4000A 690V (IEC) 1000-4000A

advertisement
High Speed Fuses
Square Body Flush End Contact — 690/700V (IEC/UL):
1000-4000A
690V (IEC) 1000-4000A
Arc Voltage
This curve gives the peak
arc voltage, UL, which
may appear across the
fuse during its operation
as a function of the
applied working voltage,
Eg, (rms) at a power
factor of 15%.
Specifications
Description: Square body flush
end contact high speed fuses.
Dimensions: See dimensions
illustrations.
Ratings:
Volts: — 690Vac
Amps: — 1000-4000A
IR: — 200kA RMS Sym.
Ag ency Information: CE, Designed and tested to IEC
60269: Part 4, UL Recognized.
Power Losses
1.5
1)
K
1.0
0.5
0.4
0.3
0.2
Eg
100 200 300 400 500 600 690
1) Rated voltage 500V
Dimensions (mm)
Type 4B/-, 4BKN/-, 4G/-, 4GKN/Siz e
4B
4G
F (in)
M10 10 deep
1
⁄2” -13 UNC-2B 10 deep
4
G
33
38
Eg
3
200
300
400
500
600 690
1.0
Kp
0.8
0.6
0.5
High Speed
Fuses
Total Clearing I2t
UL
5
Watts loss at rated
current is given in the
electrical characteristics.
The curve allows the
calculation of the power
losses at load currents
lower than the rated
current. The correction
factor, Kp, is given as a
function of the RMS load
current, Ib, in % of the
rated current.
Electrical Characteristics
The total clearing I2t at
rated voltage and at power
factor of 15% are given in
the electrical
characteristics. For other
voltages, the clearing I2t is
found by multiplying by
correction factor, K, given
as a function of applied
working voltage, Eg, (rms).
1.4
1.2
103
9
8
7
6
0.4
0.3
0.2
Ib
0.1
30 40 50
60
70
•
•
•
•
Features and Benefits
Excellent DC performance
Low arc voltage and low energy let-through (I2t)
Low watts loss
Superior cycling capability
•
•
•
•
Typical Applications
DC common bus
DC drives
Power converters/rectifiers
Reduced voltage starters
80 90 100%
For Other Voltage Ratings in This Body Style
• See pages 154 (1000V) and 168 (1250V)
1mm = 0.0394” / 1” = 25.4mm
105
F
Ø4
G
105
15
Ø56
53
67
For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa
135
High Speed Fuses
Square Body Flush End Contact — 690V (IEC):
1000-4000A
Catalog Numbers
Catalog
-BKN/Type K
Indicator
for Micro
170M7078
170M7079
170M7080
170M7081
170M7082
170M7083
170M7084
170M7085
170M7086
-B/Visual
Indicator
170M7058
170M7059
170M7060
170M7061
170M7062
170M7063
170M7064
170M7065
170M7066
Numbers
-G/Visual
Indicator
170M7098
170M7099
170M7100
170M7101
170M7102
170M7103
170M7104
170M7105
170M7106
-GKN/Type K
Indicator
for Micro
170M7118
170M7119
170M7120
170M7121
170M7122
170M7123
170M7124
170M7125
170M7126
Electrical Characteristics
Siz e
4
Rated Current RMS
Norm.
Liquid
Cool.
Cool.
1000
1350
1250
1700
1400
1900
1600
2200
2000
2700
2500
3400
3000
4100
3500
4700
†4000
†5400
I2t (A2 Sec)
Clearing
Pre-arc
at 660V
76000
505000
145000
965000
205000
1400000
305000
2050000
600000
3950000
1200000
7800000
2000000
13500000
3250000
22000000
4700000
†28000000
Watts Loss
Norm. Liquid
Cool.
Cool.
175
315
195
355
205
375
220
405
245
445
275
495
305
555
325
585
355
640
†Rated voltage (IEC) 500V.
• Watts loss provided at rated current.
• Liquid Cool. = Liquid cooling. Temperature on the terminals not to exceed 60°C.
• Microswitch indicator ordered separately. See accessories on pages 185-186.
Size 4 — 1000-4000A: 690V
1000A
1250A
1400A
1600A
2000A
2200A
2500A
3000A
3500A
4000A
Time-Current Curve
Peak Let-Through Curve
104
106
B
Peak Let-Through Current
103
102
Virtual Pre-Arcing Time In Seconds
A
A
101
4000A
3500A
3000A
2500A
2200A
2000A
1600A
1400A
1250A
1000A
105
104
A
100
2x10
3
1x103
104
105
106
Prospective Short-Circuit Current Symmetrical RMS
10–1
4000A fuse is derated to 500V (IEC).
10–2
10–3
1x10–4
1x103
104
105
Prospective Current in Amps RMS
106
Data Sheet: 17056328
136
For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa
107
Download