DTAV40 Series Defrost Timer Project: Location: DTAV40 Series Product Type: Auto-Voltage Defrost Timer The Grässlin DTAV40 Series Auto Voltage Defrost Timer is applicable to air defrost (compressor shutdown) and electric or hot gas defrost systems where the defrost is terminated by the timer. If the coil is frost free, the timers can also be terminated by temperature or pressure switches before the programmed defrost termination time has been reached. The time termination functions as a fail-safe and terminates the defrost cycle if the temperature or pressure switch fails to do so. Contact/Phone: Model #: Features • DTAV40 replaces over 40 competitive models • Auto-Voltage automatically adjusts for 120-240 VAC • Mounts in existing enclosures, no tools required • Box lug terminals • Defrost times programmable in 15-minute intervals with captive trippers • UL Type 3R outdoor enclosure (DTAV40IM - UL Type 1 Metallic) • 40 Amp, 2 HP Rating • Moisture resistant conformal coated board • LED indicators for defrost and refrigeration cycles • Defrost cycles are programmed independently • "Real-time" clock face for quick, easy and accurate setting • Min ON/OFF time: 15 minutes • Max ON/OFF time: 23 hours, 45 minutes DTAV40 Inside Ratings Input Voltage: Auto-Voltage 120-240 VAC, 60 Hz "Q" Models 50/60 Hz Electrical Ratings: 40 Amp Resistive, 120-240 VAC 1 HP, 120 VAC 2 HP, 240 VAC Operating Tempearature: -40º F to 104º F (-40ºC to 40ºC) Quartz: -4º F to 104º F (-20ºC to 40ºC) Operating Humidity: 0-95% RH, non-condensing Enclosure: UL Type 1 or UL Type 3R Min ON/OFF: 15 minutes Max ON/OFF: 23 hours, 45 minutes Electrical Life: 50,000 Operations at full load Wire Size: AWG #8 Shipping Weight: 3 lbs. Warranty: Limited 1 year DTAV40 HVACR #E10694 Energy Controls DTAV40 Series Model Number Input Voltage Enclosure Carryover DTAV40 120-240 VAC, 60 Hz UL Type 3R Raintight plastic No DTAV40IM 120-240 VAC, 60 Hz UL Type 1 Metallic not raintight No DTAV40M 120-240 VAC, 60 Hz None, Mechanism only No DTAV40Q 120-240 VAC, 50/q60 Hz UL Type 3R Raintight plastic Yes (7 Days) None, Bracket Mount No DT-B Specification Furnish and install a Grässlin___________defrost control, which will automatically adjust between 120 VAC and 240 VAC operation and shall have defrost initiation times settable in 15-minute intervals with captive trippers. The defrost timer shall be housed in a UL Type 3R indoor/outdoor plastic enclosure or UL Type 1 metallic enclosure. The relay output will be rated for 40A Resistive, 2 HP @ 240 VAC. Defrost termination to be by time (or by a remote temperature or pressure switch). For carryover, the time controls shall have quartz drive with 7-Day reserve carryover from a rechargeable battery. Diagrams Energy Controls 6.61" [16.79 cm] 5.73" [14.55 cm] 8143 Replacement CONTROL POWER TERMINATE INPUT 8.88" [22.56 cm] 1 N 3 4 2 X 8143 LABEL L1 LINE FAN HOT GAS VALVE TERMINATION THERMOSTAT W/FAN DELAY CONNECT ACROSS COMPRESSOR THERMOSTAT L2 3" [7.62 cm] 8145 Replacement Mode A - No Label Required 8045 Replacement CONTROL POWER F 3 1-N L1 2 THERMOSTAT LINE DEFROST HEATER COMPRESSOR OR SOLENOID VALVE OR CONTACTOR COIL 4 X TERMINATE INPUT CONTROL TERMINATE POWER INPUT 8045 LABEL F 3 1 L1 FAN MOTOR 4 N X THERMOSTAT DEFROST HEATER LINE L2 2 TERMINATION THERMOSTAT W/FAN DELAY FAN MOTOR COMPRESSOR OR SOLENOID VALVE OR CONTACTOR COIL L2 8141 Replacement Mode A with 8141 Terminal Block Label Applied CONTROL POWER N 1 3 2 4 X TERMINATE INPUT 8141 LABEL THERMOSTAT L1 FAN LINE L2 www.intermatic.com DEFROST HEATER COMPRESSOR OR SOLENOID VALVE OR CONTACTOR COIL TERMINATION THERMOSTAT W/FAN DELAY