Instructions for Emergency Lighting Fixture

advertisement
ISOLITE PLE SERIES
I nstructions for Emergency Lighting F ixtur e
Important:
Battery in this unit may not be fully charged at the time
electrical connection is made. let batterycharge for at
least 24 hours. Then normal operation of this unit should
take effect . To check, press the " TEST " button . The light
inside the unit should turn on. The lamps, when used
according to these instructions with this unit equipment,
are in accordance with the requirements of csa standard
C22.2 NO. 141.
I M P O R TA N T SA F E G U A R DS
When using electrical equipment,basic safety precautions should always be followed including the following:
R EA D AND F OL L O W A L L S A F E T Y INS T RUC T I ON S
1.Do not use outdoors.
2.Equipment should be mounted in locations at heights where it will not be subject to tampering by unauthorized personnel.
3.Do not mount near gas or electric heaters.
4.The use of accessory equipment is not recommended by the manufacturer may cause an unsafe condition.
5.Do not use this equipment for other than its intended use.
6.Servicing of this equipment should be performed by qualified personnel.
7.Disconnect AC power before servicing.
S AVE T H ES E I N S T R U C T I O N S
FLEXIBLE CONDUIT ONLY
I N S T A L L AT I O N ( J -B O X M O U N T I N G )
1. Feed fixture leads through main bottom case and connecct AC power supply (Fig A).
2. Connect wires through J-Box. Main bottom case on J-Box and secure with screws.
3. Connect battery only after continuous AC power can be provided to the unit (Fig. B).
4. Align snaps and push housing directly onto main bottom case (Fig. C). Apply continuous AC power
and press "TEST" button to check light.
I N S TA L L AT I O N (C O N D U I T )
1. Secure main bottom case to wall surface . Route wires through hole in conduit flange and make conduit
connection.
2. Connect battery only after continuous AC power can be provided to the unit (Fig. B).
3. Align snaps and push housing directly onto main bottom case (Fig. C). Apply continuous AC power
and press "TEST" button to check light.
(NOTE: To appear outside blue sleeve of terminal before connecting. )
PLUG IN
Fig.A (J-Box)
Fig.B
Fig.C
WA R N I N G :
Unused wires must be capped using enclosed wire nuts.
Beghelli U.S.A., 3250 Corporate Way, Miramar, Florida, Tel: (954) 442-6600 Fax: (954) 442-6677
08/11/2010
O P E R AT I O N
1. During an electrical power failure, the lamps will automatically come on for a minimum of
90 minutes.
2. To test, depress the "TEST" switch. The emergency lamps will illuminate. When the switch
is released, the lamps will go off.
W I R I NG DI A G R A M
RED
277 VOLT
BLACK
120 VOLT
WHITE
NEUTRAL
N O T E : UNUSED LEAD TO BE PROPERLY
INSULATED WITH WIRE NUT
OTHER APPROVED METHOD.
CHARGER
BOARD
RED
RED
RED
BLACK
-
BLACK
BLACK
READY
LAMP
+
BATTERY
TEST
3.6V/ 900MAH
LAMP
Beghelli U.S.A., 3250 Corporate Way, Miramar, Florida, Tel: (954) 442-6600 Fax: (954) 442-6677
08/11/2010