CIS Advanced Utilities Monitoring System Standard The University of Sydney Engineering & Sustainability Team CAMPUS INFRASTRUCTURE & SERVICES Document Control Document Name: CIS Advanced Utilities Monitoring System Standard Document ID: CIS-PLA-STD-Advanced Utilities Monitoring System Document Status: Final Version No: 002 Author(s): David Dunn Position: Services Engineer – Mechanical Signature: Document Owner: Engineering & Sustainability Team Approved by: Greg Robinson Position: Director of CIS Signature: Date Approved: 18 September 2015 Date of Issue: 18 September 2015 Issued by: Campus Infrastructure & Services CIS Advanced Utilities Monitoring System Standard - Final CIS-PLA-STD-Advanced Utilities Monitoring System 002 Date of Issue: 18 September 2015 ii CAMPUS INFRASTRUCTURE & SERVICES Contents 1 PURPOSE ..................................................................................................... 1 2 SCOPE ......................................................................................................... 1 3 GLOSSARY OF TERMS................................................................................. 2 4 AUTHORITIES AND RESPONSIBILITIES........................................................ 2 5 DESIGN AND CONSTRUCTION REQUIREMENTS ........................................ 2 5.1.1 5.1.2 5.1.3 5.1.4 GENERAL .............................................................................................................................................. 2 CALCULATIONS/SELECTIONS ............................................................................................................... 3 DRAWINGS AND DOCUMENTATION .................................................................................................... 3 TECHNICAL SUBMITTALS ....................................................................................................................... 3 5.2 METERING EQUIPMENT .................................................................................................................................... 4 5.3 MINIMUM METERING PARAMETERS ............................................................................................................... 4 5.4 WATER AND GAS METERS............................................................................................................................... 4 5.5 AUMS SYSTEM ARCHITECTURE ....................................................................................................................... 5 5.5.1 5.5.2 HARDWIRED ARCHITECTURE ................................................................................................................. 5 WIRELESS ARCHITECTURE ..................................................................................................................... 5 5.6 METER IDENTIFICATION PROTOCOL ............................................................................................................. 8 5.7 GATEWAYS AND EQUIPMENT........................................................................................................................ 8 5.7.1 5.7.2 5.7.3 5.7.4 SMART METER GATEWAYS................................................................................................................... 9 MODBUS GATEWAY ............................................................................................................................ 9 SERIAL-TO-ETHERNET GATEWAYS ..................................................................................................... 10 GATEWAY/WIRELESS RECEIVER ENCLOSURE AND LOCATION ......................................................... 10 5.8 SOFTWARE ....................................................................................................................................................... 10 5.8.1 5.8.2 5.8.3 METER SOFTWARE............................................................................................................................. 10 GATEWAY SOFTWARE ...................................................................................................................... 11 AUMS SERVER SOFTWARE DATA ANALYSIS AND REPORTING ......................................................... 11 CIS Advanced Utilities Monitoring System Standard - Final CIS-PLA-STD-Advanced Utilities Monitoring System 002 Date of Issue: 18 September 2015 iii CAMPUS INFRASTRUCTURE & SERVICES 5.9 AUMS SERVER SOFTWARE CONFIGURATION......................................................................................... 13 5.10 USER CONFIGURATION ................................................................................................................................ 14 5.11 CALCULATION AND ANALYSIS TOOLS ..................................................................................................... 14 5.12 ENTERPRISE INTEGRATION AND MANUAL DATA ENTRY ....................................................................... 15 5.13 ALARMS ............................................................................................................................................................. 15 5.14 WORKFLOW.................................................................................................................................................... 15 6 COMMISSIONING .....................................................................................15 6.1 VERIFICATION .................................................................................................................................................. 16 7 SAFETY IN DESIGN ....................................................................................16 8 DOCUMENTATION AND RECORDS ..........................................................16 9 OPERATIONS ............................................................................................17 10 AUTHORISATION OF VARIATIONS ..........................................................17 11 QUALITY CONTROL ..................................................................................17 11.1 DESIGN STANDARD COMPLIANCE ............................................................................................................. 17 11.2 DESIGN STANDARD CERTIFICATION .......................................................................................................... 18 12 REFERENCES ..............................................................................................18 13 NOTES .......................................................................................................19 15 DOCUMENT AMENDMENT HISTORY ........................................................19 CIS Advanced Utilities Monitoring System Standard - Final CIS-PLA-STD-Advanced Utilities Monitoring System 002 Date of Issue: 18 September 2015 iv CAMPUS INFRASTRUCTURE & SERVICES 1 PURPOSE The CIS Advanced Utilities Monitoring System (AUMS) Standard sets out the University of Sydney's requirements for the installation and integration of utilities metering into the University‟s AUMS, which is used to monitor electricity, gas and water meters installed in campus buildings. Applicable requirements documented in Australian and New Zealand Standards (AS/NZS), the Building Code of Australia (BCA), Australian National Construction Codes, Workplace Health and Safety legislation and other relevant statutory requirements are minimum compliance requirements that are considered mandatory. The minimum relevant AS/NZS documents are provided in Section 11 of this standard. Where any ambiguity exists between this standard and the aforementioned mandatory requirements then: a. the highest performance requirements must apply b. applicable requirements must follow this order of precedence: i. Workplace Health and Safety legislation ii. Disability Discrimination legislation iii. State Environmental Planning and Assessment legislation iv. All other Commonwealth and State legislation v. NCC and BCA vi. AS/NZS vii. This standard and other University standards 2 SCOPE This standard specifies the metering and communication requirements to enable connection of new electricity, gas and water meters to the AUMS via the University Campus Area Network. AUMS is a platform for utility monitoring, electricity, gas and water. It is a distributed system for high reliability and uses network synchronised time stamping at the gateway to ensure highly accurate interval data. The standard applies to project managers, consultants, contractors, sub-contractors, tenants, managing agents, university staff and others involved in the design, construction and maintenance of existing, new and proposed university buildings and facilities. CIS Advanced Utilities Monitoring System Standard - Final CIS-PLA-STD-Advanced Utilities Monitoring System 002 Date of Issue: 18 September 2015 1 CAMPUS INFRASTRUCTURE & SERVICES 3 GLOSSARY OF TERMS AEST AUMS BACnet BACnet Operator Workstation (B-OWS) BACnet Advanced Workstation (B-AWS) BMS CN NTP SMS SMTP THD VPN UTC HVAC SLD 4 Australian Eastern Standard Time Advanced Utility Metering System Interoperability protocol ISO 16484-5 network level workstation advanced operator workstation Building Management System Campus Network Network Time Protocol Short Message Service Simple Mail Transfer Protocol Total Harmonic Distortion Virtual Private Network Coordinated Universal Time Heating, Ventilation and Air conditioning Single Line Diagram AUTHORITIES AND RESPONSIBILITIES This standard is issued by CIS. It is approved and signed-off by the Director CIS. The CIS Engineering and Sustainability Unit are responsible for maintaining the standard and keeping it up-to-date. The Standard must be reviewed biennially. 5 DESIGN AND CONSTRUCTION REQUIREMENTS Installation of utility meters and sub-meters are required for new buildings, refurbishment works, works involving new/replacement/upgrade of gas, water, electricity and thermal energy supplies and upgrades to, electrical distribution boards. All meters and their associated communication hardware and software must be connected to, and configured in, the University‟s AUMS. 5.1.1 GENERAL This section outlines the extent of the services to be provided by the AUMS Contractor under a Design and Construct contract. The contractor must be fully responsible for the complete design of the AUMS installation, including the selection, sizes and quantity of equipment, and must provide network architecture calculations and drawings and other documentation as necessary to demonstrate conformance with the design parameters, industry practice, CIS requirements, codes, regulations and standards The contractor must allow to fully co-ordinate the documentation with the architect, structural, mechanical, hydraulic and electrical engineers and all other services consultants / contractors. As part of the design phase, a design work shop must be held to ascertain the building specific reporting, building manager specific dashboard, alarm setup, required specific virtual meters and utilities apportioning/recovery reports. CIS Advanced Utilities Monitoring System Standard - Final CIS-PLA-STD-Advanced Utilities Monitoring System 002 Date of Issue: 18 September 2015 2 CAMPUS INFRASTRUCTURE & SERVICES 5.1.2 CALCULATIONS/SELECTIONS As part of the contractor‟s design, it is expected that the following design calculations as a minimum are produced for review by CIS for approval prior to finalising design: a. b. c. d. 5.1.3 Cable sizing Gateway capacities (processor capacity and memory) Daisy chain architecture (quantity of meters on each chain) Ensure point Licencing is sufficient DRAWINGS AND DOCUMENTATION The contractor must provide design, construction and as-built drawings, which may be either design drawings produced by the contractor or shop drawings produced by equipment manufacturers. The AUMS contractor is responsible for producing all design and as-built documentation, including, but not limited to: a. Concept design documentation (as required); b. Detailed design documentation, including: i. Layout drawings ii. Details iii. System architecture iv. Building specific reports and alarms v. Building specific virtual meters and dashboards vi. Schematics vii. Design certification viii. Equipment details ix. Testing / commissioning procedures c. Workshop drawings, including: i. Drawings for the purpose of system installation d. As Built drawings, including: i. Detailed drawings demonstrating the as installed system e. Operations and maintenance manuals. f. Training manuals All design documentation must be approved by CIS prior to any works progressing onsite. Workshop, as-Built drawings and operation and maintenance manuals must be submitted to for review prior to final sign off. 5.1.4 TECHNICAL SUBMITTALS Technical submittals must be provided with the full technical, spatial and network requirements of each proposed item. The technical submissions must include, where applicable, but not be limited to: a. Certified shop drawings of each system and control panel complete b. Electrical requirements including, operational voltage, recommended protection devices, wiring diagrams, connection and terminals details. Also detail of how cables are terminated to the equipment and earthing requirements must be provided. c. Manufacturer‟s recommendations for installation including power quality and thermal requirements. d. Confirmation of product lifespan assuming maintained to manufacturers recommendations. CIS Advanced Utilities Monitoring System Standard - Final CIS-PLA-STD-Advanced Utilities Monitoring System 002 Date of Issue: 18 September 2015 3 CAMPUS INFRASTRUCTURE & SERVICES e. Where equipment model numbers / references are stated these are indicative only and the Contractor MUST ensure the selected equipment fully complies with the entire services standard 5.2 METERING EQUIPMENT Where revenue meters are connected these meters must be supplied fitted with Modbus ports and the Modbus data made available through the specified Serial-to-Ethernet gateway by connecting the meter to the nearest Serial-to-Ethernet gateway. It is the responsibility of the project/contractor to organise with the supply authority meter provider the Modbus connection for the AUMS to connect to. 5.3 MINIMUM METERING PARAMETERS The minimum parameters to be metered for electricity, gas and water are summarised in Table 1. TABLE 1 METERING REQUIREMENTS FOR ELECTRICITY, GAS AND WATER Type Value 3 phase kW 3 phase kVA (average maximum) 3 phase kWh (totaliser) L-N Voltage (each phase) L-L Voltage (each phase Electricity (per meter) 3 phase kVar 3 phase Current (each phase) 3 phase Power Factor Frequency Total Harmonic Distortion (total and phase %) Neutral Current (calculated) Gas Uncorrected Volume (m3) Uncorrected volume (l) Water Flow (l/s) Thermal kW (cooling) 5.4 WATER AND GAS METERS Provide a pulse measurement device to water and gas meters that will convert the water or gas meter volt free pulses (at a minimum of 100Hz, 25% duty cycle) to a Modbus value that can be accessed by the AUMS server through the gateway. Pulse measurement from water and gas meters must be connected to DIN rail based Modbus/TCP Pulse counters converting the pulses to a Modbus register to be polled by the Smart Gateway. Where existing building water and gas meters are available via BACnet controllers, the project will configure the AUMS Server to access these BACnet variables directly through the nearest BMS controller/router. CIS Advanced Utilities Monitoring System Standard - Final CIS-PLA-STD-Advanced Utilities Monitoring System 002 Date of Issue: 18 September 2015 4 CAMPUS INFRASTRUCTURE & SERVICES 5.5 AUMS SYSTEM ARCHITECTURE The AUMS system consists of a protected server, hosted in the University‟s externally operated data centre, and gateway devices fitted in a steel panel mounted in the electricity distribution hub. The gateway devices collect data from smart meters via the Campus Network (CN). The AUMS is linked to the campus time and SMTP mail servers to receive time sync and to allow notifications to be emailed to users. 5.5.1 HARDWIRED ARCHITECTURE In addition to the Smart Gateways, the AUMS implements Serial-to-Ethernet gateways for local metering interface. These are one or two port Moxa type or equivalent. The gateway is configured to allow the AUMS to access Modbus meters by polling the gateway directly from the Campus Network. Serial-to-Ethernet gateways must not be used for data transfer between buildings; they are only acceptable for internal building data transfer. Any other system requiring data from a meter that is connected to the AUMS (such as a local Building Management Control System [BMCS]) must poll the Serial-to-Ethernet gateway using the Modbus/TCP protocol. It is not permissible for a local BMCS or other system to directly access the meters on the daisy chain bus (i.e. using the lower level Modbus/RTU protocol). This approach is used to create a clean interface and use of IP protocols to promote best practice in structured cabling. Figure 1 depicts the hard wired tiered architecture of the system. Thermal meter data must be accessed via the closest BMCS controller/router and pulled back to the AUMS server. Note that the thermal meter data is utilised by both AUMS and BMCS. 5.5.2 WIRELESS ARCHITECTURE In addition to the hard-wired architecture wireless (radio) architecture is implemented where hardwiring is not feasible, the wireless system is based around the Halytech wireless product range. The radio base station collects and provides the Jace with data from the transmitters. Data is transmitted every 6 hours from the transmitters that are collecting 15 minute interval data. The base station must have the capability to collect 3 days‟ worth of data without mains power and to store six days‟ worth of data without network connectivity, upon reconnection to network data is to be automatically uploaded. The base station/transmitters must be setup to allow force polling of transmitter for its data to the AUMS server for viewing. Figure 2 depicts the wireless system architecture. CIS Advanced Utilities Monitoring System Standard - Final CIS-PLA-STD-Advanced Utilities Monitoring System 002 Date of Issue: 18 September 2015 5 CAMPUS INFRASTRUCTURE & SERVICES NEW PROJECTS INTEGRATION TO AUMS Data Centre New Building WATER AND GAS METERS TO BE CONNECTED DIRECTLY TO AUMS VIA A MODBU S/TCP PULSE COLLECTION MODULE AUMS GAT EWAY POLLS METER DATA FROM THE MODBUS SERIAL TO ET HERNET GATEWAYS Comms Rooom Patch Panel Network Connection Port MODBUS/TCP BACNET/IP LAN1 AUMS GATEWAY (JACE) LAN2 Modbus/ TCP Pulse Module AUMS GAT EWAY SENDS OR RECEIVES DATA FROM T HE BMS AUMS SERVER Campus Network AUMS GAT EWAY AND BMS POLL METER DAT A INDEPENDENTLY Comms Rooom Patch Panel Network Connection Port MODBUS/TCP NEW PROJECT SUPPLIES A SERIAL TO ET HERN ET GATEWAY WITH ALL METER S WIRED TO THE GATEWAY Serial to Ethernet Gateway (Moxa or Equal) Meter Meter THE BMS POLLS DAT A FROM THE SERIAL T O ETHERNET GATEWAYS Network Connection Port MODBUS/TCP BACNET/IP BMS AUMS GAT EWAY SENDS OR R ECEIVES DATA FROM THE BMS Figure 1 : Advanced Utiltiy Monitoring System (AUMS) Architecture - Hard Wired CIS Advanced Utilities Monitoring System Standard - Final CIS-PLA-STD-Advanced Utilities Monitoring System 002 Date of Issue: 18 September 2015 METER S ASSOC IATED WITH A BMS OR ELECT RICAL INSTALLATION 30 METER S or less per SER IAL TO ETHERNET GATEWAY Electrical Metering Point Gas Meter Meter MODBUS/RTU RS-485 Comms Rooom Patch Panel Water Meter 6 CAMPUS INFRASTRUCTURE & SERVICES Figure 2 : Advanced Utiltiy Monitoring System (AUMS) Architecture - Wireless CIS Advanced Utilities Monitoring System Standard - Final CIS-PLA-STD-Advanced Utilities Monitoring System 002 Date of Issue: 18 September 2015 7 CAMPUS INFRASTRUCTURE & SERVICES 5.6 METER IDENTIFICATION PROTOCOL Meters addressing must be configured in accordance with the requirements of CIS Engineering and Sustainability Unit to ensure that all meters are uniquely identified across the campus. The naming convention used to identify meters must be standardised in accordance with CIS direction. All labelling on meters must reflect this standard. Meters must be supplied fitted with Modbus ports and the Modbus data made available through the specified Serial-to-Ethernet gateway by connecting the meter to the nearest Serial-to-Ethernet gateway. The meters must be connected by a daisy chain buss (wired in EIA-485 compliant 2 wire communications cable) to the nearest Serial-to-Ethernet Gateway. 5.7 GATEWAYS AND EQUIPMENT Deemed-to-comply gateways are provided in Table 2. Alternatives may be used with prior review and approval of the CIS Engineering and Sustainability Unit. TABLE 2 DEEMED-TO-COMPLY GATEWAYS Meter Gateway/Equipment JACE-200/300/400/600 Manufacturer Tridium NBP-PWR 24V DIN Rail mounted Power supply (or equal) MODBUS Driver (DR-MDBTC-AX) BACNET Driver (DR-BACNETAX) for BMS integration Spider AMR Spider WRX-OB Wireless transmitters WTX-OB Wireless transmitters WTX-C Wireless transmitters Tridium WTX-IB Wireless transmitters Halytech WTX-IM Wireless transmitters Halytech Tridium Tridium Halytech Halytech Halytech Halytech Description DIN rail mounted gateway device (shipped with the most recent Niagara version). To be fitted in 600x400x200 steel panel to drawing. DIN rail mounted 24 VAC power supply Modbus/TCP Driver to be used when installing with MODBUS meters. Driver to be installed Base-station Wireless Logger device Wireless transmitters connected to pulse meter Battery powered wireless transmitter (Outdoor use) Battery powered wireless transmitter (Outdoor use in high moisture containing environments) Battery powered wireless transmitter (Indoor use) Mains powered wireless transmitter (Indoor use) CIS Advanced Utilities Monitoring System Standard - Final CIS-PLA-STD-Advanced Utilities Monitoring System 002 Date of Issue: 18 September 2015 8 CAMPUS INFRASTRUCTURE & SERVICES 5.7.1 SMART METER GATEWAYS The smart meter gateway is a device that allows data to be gathered and stored as a history (time stamped data) in the memory of the device. All smart gateways must satisfy the following requirements: a. They must be diskless, low maintenance and of sufficient capacity to allow for all data gathered to be stored locally for at least 72 hours, in the event that the WAN is unavailable, after which the data may be overwritten b. Each gateway must have the capacity to gather log data from a minimum of 32 meters at 15 minute intervals for 7 days while offline from the WAN c. They must support Modbus/RTU, Modbus/TCP, BACnet/MSTP and BACnet/IP for integration of metering directly from meters or from BCMS. d. A Serial-to-Ethernet gateway is required for new electrical installations to allow the University‟s AUMS to access the Modbus meters by polling the gateway directly from the Campus Area Network. Each electrical switch room containing metering equipment is to be provided with a Serial-to-Ethernet gateway, such that any system, including the local BCMS, can access the meters e. They must be capable of multi-master operation. This means, the server may poll the gateway for adhoc live data in response to a user graphic request while logging is carried on in the background without any interruption of the 15 minute data logging f. They must be capable of logging any selected variable at user configurable intervals from 30 seconds to 10 minutes. When in this mode, historical logging at 15 minute intervals must continue normally and must not be affected by live viewing g. All data logged must be logged with an inherent floating point accuracy to class 0.5s (AS 62053.22:2005) for active power and class 1 (AS 62053-21:2005) for reactive power h. They must support pulse counting (to 100Hz) and analog inputs for whole current electricity meters, water, gas, and heat meters must be supported by the gateways i. They must be capable of operating independently on local batteries for at least 5 minutes during mains power outages. All programming and configuration will be stored in non-volatile memory in the event of prolonged mains power failure for at least 7 days without mains power. j. The ability to timestamp all data for storage and update the gateway clock via a central master device 5.7.2 MODBUS GATEWAY The smart gateway is complemented by an advanced industrial grade Modbus Gateway that integrates Modbus the Modbus/RTU protocol with Modbus/TCP, allowing the meters to be polled across the Campus Area Network. Detailed information is provided in the MGate MB3180 Modbus gateway quick installation guide, available from the manufacturer. Where water and gas meters are remote, a DIN rail mounted Modbus IO server may be deployed within an adjacent switchboard and MODBUS cable reticulated from the nearest GATEWAY. CIS Advanced Utilities Monitoring System Standard - Final CIS-PLA-STD-Advanced Utilities Monitoring System 002 Date of Issue: 18 September 2015 9 CAMPUS INFRASTRUCTURE & SERVICES 5.7.3 SERIAL-TO-ETHERNET GATEWAYS In addition to the gateways, the AUMS implements Serial-to-Ethernet gateways for local metering interface within building only, the Serial-to-Ethernet gateways must not be used for building to building communication they are only permissible for internal building communication. An ethernet data port is to be supplied within 5 meters of the Serial-to-Ethernet gateway. The gateways must be connected to the data port using as a minimum CAT6A patch lead. Serial-to-Ethernet gateway devices must be Moxa MB3170/3270 or equivalent to permit simultaneous polling of meters by the AUMS server or other masters to communicate with the Modbus serial network. Modbus serial networks can only handle one query at a time; queries from different masters are queued and processed one by one. No more than 30 meters must be connected to any one Serial-toEthernet gateway. Any requirement of the BMS or other local system to communicate with electricity meters must pass through the Serial-to-Ethernet gateway using Modbus/TCP protocol. 5.7.4 GATEWAY/WIRELESS RECEIVER ENCLOSURE AND LOCATION The Serial-to-Ethernet gateways, smart (meter) gateways and wireless receivers must be located in the switch room or other location approved by CIS Engineering and Sustainability Unit. Each gateway must be equipped with ELV power supply at 24VAC or 24VDC, DIN rail mounted and fitted in a lockable industrial 600x400x200mm steel panel enclosure. Small backup power supply must be included in wireless ARM power supply circuit to allow for 3 days operation without mains power. Where external enclosure is required for wireless receiver then it must be weather proof and of an IP rating of at least 65. Power point must be fitted in board with appropriate RCD protection and surge diverter installed inside the cabinet on the incoming power supply. The steel panel enclosure must be labelled “University Advanced Utilities Monitoring System” with the following contact details “Campus Infrastructure Services, Engineering and Sustainability Unit” using traffolyte labels. Where gas meters are connected to the AUMS an intrinsically safe barrier must be provided or an appropriate certification from a hazardous area consultant confirming the classification for the area/installation. 5.8 SOFTWARE 5.8.1 METER SOFTWARE All meters must be loaded with the latest software version as per the manufacturer‟s specification. Changes to meter software must be agreed with CIS Engineering and Sustainability Unit. All meter addressing must be unique and the meter addresses submitted to CIS for approval. The project must ensure that meter schematics are submitted for inspection of meter configuration and addressing. CIS Advanced Utilities Monitoring System Standard - Final CIS-PLA-STD-Advanced Utilities Monitoring System 002 Date of Issue: 18 September 2015 10 CAMPUS INFRASTRUCTURE & SERVICES 5.8.2 GATEWAY SOFTWARE All Serial-to-Ethernet gateways must be loaded with the latest software version as per the manufacturer‟s specification. Serial-to-Ethernet gateway addressing must be approved by the CIS Engineering and Sustainability Unit to ensure that all gateways are accessible from the AUMS Server. 5.8.3 AUMS SERVER SOFTWARE DATA ANALYSIS AND REPORTING The AUMS software loaded on the University‟s server provides the following reporting tools and data output capabilities. 5.8.3.1 Graphical Data Outputs a. Time-series daily load profiles displayed with time, in intervals of an hour or less, along the horizontal axis and load along the vertical axis b. Overlay plots displaying multiple daily profiles on a single 24-hour time-series graph c. Viewing of multiple time series data points on the same graph d. Calendar profile: view up to an entire month of consumption profiles on a single screen as one long time series e. X-Y scatter plots: X-Y scatter plots for visualizing correlations between two variables f. Intuitive graphical axes that are scaled and labelled g. A comprehensive and simple graphical programming tool allowing the University users to create their own views, graphs, charts, gauges, and other widgets for viewing live or historical data. Dashboards must be capable of export to printers or .pdf, .csv, .xls or .jpg formats for use in reports, spreadsheets or as live media to campus display systems. h. Dashboards must be accessible using simple web browsers. They must at least be readable by Internet Explorer, FireFox, Safari and mobile smart phone web browsers. Secure dashboard access via web browsers must be provided via username and password to access. A customised navigation tree with hyperlinked graphics must be provided such that each user (or user group) is provided with personalised access to data relevant to their specific requirements. Users must be able to access utility metered data by clicking on a digital map showing campus buildings. i. Dashboards as a minimum must contain (for each building group, building, area, switchboard, or grouping in the metering tree) graphics showing live and historical utilities usage, loads, CO2 emissions, utility targets and maximum demand. System administrators must be able to manage meter lists, add new meters, create virtual meters and remove decommissioned meters. j. See Attachment 1 for existing dashboard configuration and standard tabs setup k. Building specific dashboards must be developed on a project by project basis refer to Table 3 l. Direct access to schematics and Single Line Diagrams showing current utilities reticulation relevant to the meter being interrogated. m. Alarms CIS Advanced Utilities Monitoring System Standard - Final CIS-PLA-STD-Advanced Utilities Monitoring System 002 Date of Issue: 18 September 2015 11 CAMPUS INFRASTRUCTURE & SERVICES TABLE 3 : BUILDING SPECIFIC DASHBOARDS Meter Gateway Total mechanical services Virtual meter Total general load virtual meter Total building lighting load virtual meter Total building Tennant Total Building PV Meter Total Building Hydraulics meter Total Building Hydraulics meter Treatment Chilled water 5.8.3.2 Meter Type Description Electrical/Gas/Water Provide Dashboard under the building tab for mechanical (collate on an individual dashboard w Mechanical gas, water ,electrical and thermal usage) Electrical Provide Dashboard under the building tab for General electrical loads (This would be all meters that are not lighting and HVAC related) Electrical Provide Dashboard under the building tab for Lighting loads (not including any tenancy lighting loads) Electrical/Gas/Water Provide Dashboard under the building tab for Tennant (collate on an individual dashboard with gas, water, electrical and thermal usage)Note a Dashboard for each tenancy must be provided. Electrical Provide Dashboard under the building tab for mechanical usage such as Gas Provide Dashboard under the building tab for Building Gas usage (excludes mechanical gas usage) Water Provide Dashboard under the building tab for Building hydraulics (excludes water treatment and mechanical usage) Water Provide dashboard for water treatment plants Thermal Provide dashboard with thermal meters where available Analytical Data Outputs a. b. c. d. Basic statistical analysis such as mean, median, standard deviation, correlation, and regression Benchmarking against set building energy standards Intra/inter-facility comparisons against the building‟s historical data or across multiple buildings Aggregate data among multiple data points. Integrate different energy units using energy conversions e. Data mining (data slice/drill-down) time series data by monthly, weekly, daily, hourly, or trended interval f. Normalisation of energy usage or demand by factors such as building area, number of occupants, outside air temperature, and cooling or heating degree-days (CDD, HDD) to make a fair comparison between buildings g. Hierarchical summary of usage and cost information by different levels. 5.8.3.3 System Specific Outputs a. Validation, editing, estimation to ensure quantities (kWh, kW, kVar, etc.) retrieved from meters are correct. The process includes validation of data within acceptable error tolerances, editing or correcting erroneous data, and estimating missing data. CIS Advanced Utilities Monitoring System Standard - Final CIS-PLA-STD-Advanced Utilities Monitoring System 002 Date of Issue: 18 September 2015 12 CAMPUS INFRASTRUCTURE & SERVICES b. Equipment fault detection and diagnostics to identify equipment failure or degradation based on customised algorithms and parameters. c. Power quality analysis of voltage or current phases for conditions that could affect electrical equipment. d. Forecasting future trends based on historical data and related parameters. 5.8.3.4 Utility Outputs a. Energy cost breakdown using energy tariff and usage data to calculate daily or hourly energy cost breakdown and validate utility bills. b. Real-time cost tracking to calculate electricity costs daily or hourly using real-time meter reading and rate tariffs. c. End-use cost allocation to tenants using user-defined parameters and algorithms to estimate end-use energy consumption from whole-building energy. d. Provide cost recovery report where applicable 5.9 AUMS SERVER SOFTWARE CONFIGURATION A qualified System Integrator must be engaged to configure the AUMS meter hierarchy. The software must automatically aggregate meters, create virtual meters (by load subtraction or addition) and logical meters (by user defined grouping of meters, such as for light and power or mechanical load groups). Driver configuration to link meters into the gateways must be integrated with the server software by the System Integrator. Meters must be set up as templates allowing easy replication where meters are added or deleted. The software configuration must: a. b. c. d. e. Define the structure of the metering system. Apply and create analytical processes. Create and edit visualisation dashboards and reports. Apply dashboards and reports to any part of the energy metering system. Set alarm levels to trigger on detection of anomalies A data model tree must be created, defining nodes that reflect the metering structure. The software will define aggregation rules for various data types, allowing nodes that do not have physical meters installed to be aggregated in dashboards and reports without specific virtual meters or calculations being required. Additionally configure the below, where applicable: a. b. c. d. e. Network time-of-use (TOU) schedules, Tariffs Normalisation metrics such as energy per floor area or per cooling degree day. Modelling water and gas usage per time interval, area or function Alarm triggering levels (with suppression of false alarms) CIS Advanced Utilities Monitoring System Standard - Final CIS-PLA-STD-Advanced Utilities Monitoring System 002 Date of Issue: 18 September 2015 13 CAMPUS INFRASTRUCTURE & SERVICES The software must calculate variables to be trended and stored in the SQL database, visualised in dashboards. All analytical tools, calculations must be made available to authorised CIS users and be able to be edited using drag and drop techniques in real time via a graphical “wire sheet”. The System Integrator must develop a comprehensive intelligent user interface to accurately model and interact with building users. All tools to edit and apply dashboards to all parts of the system must be provided within the web browser functionality. The system must provide a full suite of dashboard tools including: a. b. c. d. e. f. Line, bar and pie Charting Tools Tabular data Symbols, Indicators and the like. Embedded multimedia, webpages etc Ability to develop and add custom widgets Energy, water and gas alarms All charts must allow drill down capability based on defined aggregation rules. Additionally data can be dragged and dropped into charts as required. The system must be able to save any dashboard created as a template and to then apply this across any or all nodes in the system. The system must include data reporting and export tools that allow users to export data and dashboards in PDF, XLS and CSV formats. Reports must be able to be created a scheduled or exported as required. The contractor must work with the CIS Engineering and Sustainability Unit to develop required reports. The system must be designed to allow flexibility to develop the system based on evolving needs. The system must allow third party reporting and other data tools from Excel to Microsoft Reporting Services to be used without fundamentally altering the underlying hardware and database infrastructure. Licensing for Microsoft Reporting Services will be provided by the University. 5.10 USER CONFIGURATION User permissions must be approved by CIS Engineering and Sustainability Unit. The AUMS contractor must ensure that appropriate user login`s are created at the end of each project. 5.11 CALCULATION AND ANALYSIS TOOLS The System Integrator must develop calculation and analytical reports using scripted mathematical operators, logical and scientific functions built into the server software suite. All these functions must be transparently recorded in the AUMS. The software must offer an accessible programming environment (such as Visual Basic) or other scripting language such that complex calculations and formulas can be created using the stored data. For example, the software must be able to calculate greenhouse gas equations, or create a water leak detection model that can be used to generate alerts, or generate load profiles, peak demand prediction and other energy demand management functions. Note that systems that require an external controller to be deployed to provide this capability are not acceptable. CIS Advanced Utilities Monitoring System Standard - Final CIS-PLA-STD-Advanced Utilities Monitoring System 002 Date of Issue: 18 September 2015 14 CAMPUS INFRASTRUCTURE & SERVICES Data must be stored for review and later manipulation using built-in energy analysis tools for load collection and reconciliation to the NMI meters, load profiling, load duration, rollup (into varying periods), load base-lining (period comparison), comparison and rating of building performance, identification of cyclic loads, abnormal loads, service outage events, load contribution from each meter, cost comparison, tariff modelling, normalisation to parameters such as Gross Floor Area (GFA) and ambient conditions (e.g. Degree Days). 5.12 ENTERPRISE INTEGRATION AND MANUAL DATA ENTRY The System Integrator must configure the system to export data to SQL database or spreadsheets. The system must offer open SQL data connectivity (such as ODBC) in addition to export of .csv files. The software must be capable of user-friendly import of meter data either by meter or in bulk by defining a data structure and method for users to input adhoc data or historical utility data. The method of manual data entry is via a web-based form where data for meters can be manually entered into the AUMS using a wireless connected tablet computer or smart phone. 5.13 ALARMS The System Integrator must set alarms for thresholds on each individually metered value and send alert notifications for corrective action via SMS, SNMP and Email. Alarm thresholds levels must be displayed in dashboards using colour. An alarm management system must be included allowing users to view, prioritise, acknowledge and archive alarms. Alarms must be setup for each project including: max demand, water/gas leakage, meter disconnection, controller fault, comms failure and out of parameter data. Alarms shall be setup and sent to nominated users, further alarms identified during the design phase must be emailed. For the wireless systems alarms must be setup for low battery alarm and loss of communication alarm. 5.14 WORKFLOW The System Integrator must provide functionality that allows users to create workflows based on triggered events (such as alarms). For example, in the event of a water leak alarm, the system may create a water leak report and email it automatically to relevant personnel for action. Another example is the creation of energy reports (e.g. .csv files) which are automatically exported to a carbon reporting system on a daily, or weekly or monthly frequency. 6 COMMISSIONING Building tuning and re-commissioning must be undertaken post commissioning as required by the USYD contract and as appropriate to achieve the agreed energy performance targets. Commissioning, tuning and re-commissioning must be carried out to ASHRAE Guideline 1-1996 The HVAC Commissioning Process and to the HVAC commissioning process described in ASHRAE Handbook „HVAC Applications‟ chapter 43 Commissioning or CIBSE. The design Service Provider must actively participate in commissioning to confirm the correct operation of the building. CIS Advanced Utilities Monitoring System Standard - Final CIS-PLA-STD-Advanced Utilities Monitoring System 002 Date of Issue: 18 September 2015 15 CAMPUS INFRASTRUCTURE & SERVICES An Independent Commissioning Agent must facilitate the commissioning process if required by the University contract. 6.1 VERIFICATION Commissioning of the connection of the meters to the AUMS must: a. Verify communication to each meter from the AUMS b. Complete successful AUMS remote reading of meter data and verification of stored values against those stored within the meter register (meter values = stored values) c. Validate of the meters‟ communication to the remote metering system in accordance with the NABERS validation protocols d. Include schedule and checking of all ratios applied to meter data e. Confirm correct operation of scheduled data polling over a period of 7 days at the AUMS f. Complete successful retrieval of data from storage database for each meter to the AUMS g. Provide access details and logins/passwords to any software components required by the AUMS to connect or maintain the interface to metering h. Demonstrate the end-to-end system, including dashboards, meter hierarchy, historical data, scheduled polling and adhoc polling. i. Conduct user training for up to 5 USYD staff. All for two full days of training on site. 7 SAFETY IN DESIGN The contractor must consider risk during the design. A design safety report must be submitted to the relevant CIS Project Manager for every design project. Contractors must confirm, within reasonable practicable (SFAIRP), that the structure is without risks to health and safety. Design risks must be considered for the asset lifecycle covering construction, operational and maintenance, refurbishments and decommissioning. The design safety report must include the following: a. b. c. d. e. f. Description of design element; Description of potential risks and hazards associated with the design element; A low/medium/high risk assessment considering likelihood and consequence; Proposed measures to eliminate risks where practicable; Control measures to mitigate and manage design risks; Nominating responsibilities for managing the design risks This may be provided as a design risk register where appropriate and must include results of any calculations, testing and analysis etc. 8 DOCUMENTATION AND RECORDS The following documents must be provided during the design phase and upon practical completion: a. b. c. d. New meter ID schedule New metering connections and configuration Commissioning records Product manufacturer specific information CIS Advanced Utilities Monitoring System Standard - Final CIS-PLA-STD-Advanced Utilities Monitoring System 002 Date of Issue: 18 September 2015 16 CAMPUS INFRASTRUCTURE & SERVICES e. System schematics f. Network Addressing schedule g. Metering Single SLD A project handover plan must be developed by the consultant/designer to allow systems to be handed over to the University, including updating all AUMS documentation (Operations and Maintenance manuals, configuration records, commissioning and equipment records) to ensure that it remains current. 9 OPERATIONS N/A 10 AUTHORISATION OF VARIATIONS Project managers, consultants, contractors, commissioning agents and facilities maintenance personnel must ensure compliance with these requirements is achieved. Variations to this standard must only be considered where: a. the University Standard‟s requirement cannot physically or technically be achieved. b. the alternative solution delivers demonstrated and proven superior performance for the same capital and life cycle cost or better. Consultants and contractors must identify and justify requirements of the standard that do not apply to the project or which need to be varied and these which must be approved by the issuer of this standard. Formal requests for all variations to this Standard must be submitted using the CIS Request Dispensation from Standard Form (CIS-ENG-F001). The issuer of this standard or their delegated authority must review and consider requirements of stakeholders from clients, projects and facilities management before deciding whether to approve variations. Their formal sign-off is required for acceptance of any non-compliances and departures from this standard‟s requirements. 11 QUALITY CONTROL 11.1 DESIGN STANDARD COMPLIANCE Compliance with requirements of this standard must be checked throughout the design, construction and commissioning phases of projects by CIS‟ services consultant. Any issues or deviations from this standard must be reviewed and approved in writing by the issuer of this standard. Competent CIS consultants and representatives must check compliance with this standard during design reviews and formal site inspections. Any non-conformances with requirements of this standard must be documented and provided to the CIS Project Manager for issue to contractors and their consultants. Project Managers must maintain a formal register of non-conformances and manage close out of outstanding non-conformances. Contractors and their consultants issued with non-conformances must take appropriate corrective actions. The CIS Project Manager must ensure: a. proposed corrective actions are implemented CIS Advanced Utilities Monitoring System Standard - Final CIS-PLA-STD-Advanced Utilities Monitoring System 002 Date of Issue: 18 September 2015 17 CAMPUS INFRASTRUCTURE & SERVICES b. close out of non-conformances in relation to this standard is formally approved and signed off by the author of the standard or their delegate 11.2 DESIGN STANDARD CERTIFICATION Contractors and their consultants must certify compliance to the design standard by completing and submitting the CIS Project Design Certification Form, CIS-PROJ-F001 to the CIS Project Manager at each of the following project phases: a. Design and Documentation b. Tender c. Construction Notwithstanding CIS‟ internal quality control processes, contractors and their consultants must implement their own robust quality assurance and control procedures to ensure compliance with requirements of this standard. 12 REFERENCES Standard AS 60044.120017/Amdt 12012 AS 60044.1-2007. Title Instrument transformers – Current transformers AS 62053.22 (2005) Electricity Metering Equipment (AC) Static meters for active energy (Classes 0.2S and 0.5 S) AS 62053.23 (2006) Electricity metering equipment (AC) –Particular Requirements – static meters for reactive energy (Class 2 and 3). BCA Building Code of Australia Building Code of Australia, specifically Section J energy efficiency All Health Authority Requirements All Local Council regulations American Society of Heating Refrigeration and Air-conditioning Engineers. BACnet PICs (protocol Implementation Conformance Statement) --------- Instrument Transformers (IEC 60044-1 Ed. 1.2 (2003) MOD) Building Automation and Control Systems Using ANSI/ASHRAE Standard 1351995, BACnet Electricity Safety (Installations) Regulation NABERS Energy and Water for offices (version 3.0) National Institute of Standards and Technology (NIST). GSA Guide to Specifying Interoperable National Institute of Standards and Technology (NIST). GSA Guide to Specifying Interoperable Building Automation and Control Systems Using ANSI/ASHRAE Standard 135-1995, BACnet CIS Advanced Utilities Monitoring System Standard - Final CIS-PLA-STD-Advanced Utilities Monitoring System 002 Date of Issue: 18 September 2015 18 CAMPUS INFRASTRUCTURE & SERVICES Standard ---- Title State Fire Brigade requirements Workcover requirements www.bacnet.org -- www.modbus.org 13 NOTES N/A 14 DOCUMENT AMENDMENT HISTORY Revision 001 002 Amendment First Issue 5.1.1 General clause added 5.1.2 Calculations/Selections clause added. 5.1.3 Drawings and Documentation clause added. 5.5.1 Hard Wired Architecture clause added. 5.5.2 Wireless Architecture clause added. 5.7.3 Serial to Ethernet Gateways clause added. 5.7.4 Gateway/Wireless Receiver Enclosure and Location clause added. Table 3 Building Specific Dashboards added. 7 Safety in design clause added. Design & construct checklist now included in attachment 2; New Forms added to the website; CIS Design & Construct Services Checklist Form (CIS-ENGF009) Commencing 4 September 2013 18 September 2015 ATTACHMENTS Attachment 1 Attachment 2 Dashboard Layouts Design and Construction Checklist for Consultants CIS Advanced Utilities Monitoring System Standard - Final CIS-PLA-STD-Advanced Utilities Monitoring System 002 Date of Issue: 18 September 2015 19 CAMPUS INFRASTRUCTURE & SERVICES ATTACHMENT 1 DASHBOARD LAYOUTS ANALYSIS TAB CIS Advanced Utilities Monitoring System Standard - Final CIS-PLA-STD-Advanced Utilities Monitoring System 002 Date of Issue: 18 September 2015 20 CAMPUS INFRASTRUCTURE & SERVICES PERFORMANCE TAB CIS Advanced Utilities Monitoring System Standard - Final CIS-PLA-STD-Advanced Utilities Monitoring System 002 Date of Issue: 18 September 2015 21 CAMPUS INFRASTRUCTURE & SERVICES WEEKLY COMPARISON TAB CIS Advanced Utilities Monitoring System Standard - Final CIS-PLA-STD-Advanced Utilities Monitoring System 002 Date of Issue: 18 September 2015 22 CAMPUS INFRASTRUCTURE & SERVICES TABULAR DATA TAB CIS Advanced Utilities Monitoring System Standard - Final CIS-PLA-STD-Advanced Utilities Monitoring System 002 Date of Issue: 18 September 2015 23 CAMPUS INFRASTRUCTURE & SERVICES METER STRUCTURE TAB CIS Advanced Utilities Monitoring System Standard - Final CIS-PLA-STD-Advanced Utilities Monitoring System 002 Date of Issue: 18 September 2015 24 CAMPUS INFRASTRUCTURE & SERVICES POWER AND ENERGY COMPARISONS TAB CIS Advanced Utilities Monitoring System Standard - Final CIS-PLA-STD-Advanced Utilities Monitoring System 002 Date of Issue: 18 September 2015 25 CAMPUS INFRASTRUCTURE & SERVICES BUILDING ELECTRICAL METER TAB CIS Advanced Utilities Monitoring System Standard - Final CIS-PLA-STD-Advanced Utilities Monitoring System 002 Date of Issue: 18 September 2015 26 CAMPUS INFRASTRUCTURE & SERVICES BUILDING WATER METER TAB CIS Advanced Utilities Monitoring System Standard - Final CIS-PLA-STD-Advanced Utilities Monitoring System 002 Date of Issue: 18 September 2015 27 CAMPUS INFRASTRUCTURE & SERVICES BUILDING GAS METER TAB CIS Advanced Utilities Monitoring System Standard - Final CIS-PLA-STD-Advanced Utilities Monitoring System 002 Date of Issue: 18 September 2015 28 CAMPUS INFRASTRUCTURE & SERVICES ATTACHMENT 2 DESIGN AND CONSTRUCT CHECKLIST FOR CONSULTANTS (CIS-ENG-F009) Design and Construct List The following is a list of AUMS documents which CIS require the building service consultant and contractors to provide as part of their package. This is a guide for the consultant/contractor to ensure they meet minimum design components in all projects. These documents will be reviewed by the relevant CIS Services Engineer or their delegate during the design phases. This list does not alleviate the building services consultant’s responsibility to design to the online CIS Design standards. Design Input - Provided by all AUMS Services Consultants on all Projects Phase 1 Project Planning and Assessment Phase 2 Approved Project Initiation Phase 3 Phase 4 Design and Documentation Tender Item Required Detail of the Design Item to be Completed System metering diagrams Design drawings in Autocad (and Revit 3D model where applicable) format including plans, schematics and single line diagrams. x Cabling routes Provide Design Drawings for Cabling routes and co-ordination of data outlets x Phase 5 Phase 6 Post Construction Compliance Construction and DLP Achieved Yes / No or N/A Yes / No or N/A Yes / No or N/A Confirm room spatial allowances for AUMS Confirm all equipment installed will fit within the room\riser\ceiling space and maintain equipment accessibility and egress as per Australian Standards x Detailing of building specific reports & alarms required Provide documention on project specific reports and alarms that will be reuiqred outputs of the AUMS x Equipment sizing Calculations & selections to be provided on the proposed equipment. AUMS specification (Where applicable) Complete an AUMS specification for the project. Include all schedules for points\meters and functional\user requirements x Supply of statutory design certifications and certification of compliance to the University standards and other relevant standards. Complete the design certificate in line with the relevant standards and requirements. x x x Safety in Design Documentation Provide a Safety in Design document for review and approval by the Services Engineer. x x x Asset List Proposed final asset list to be submitted for approval Inspection, testing and maintenance Confirm all inspection, testing and preventive maintenance to be perfomed during DLP together with proposed dates when the tasks will be performed CIS Advanced Utilities Monitoring System Standard - Final CIS-PLA-STD-Advanced Utilities Monitoring System 002 Date of Issue: 18 September 2015 x Yes / No or N/A Yes / No or N/A x x x 29 Yes / No or N/A Yes / No or N/A Yes / No or N/A Building Services Consultant Comments