Miniature circuit breakers Din-T shunt trip ❑ Coupled to left or right side of MCB. ❑ Modular width–18mm. ❑ Tunnel terminals identical to MCB. ❑ Field assembly. Voltage (V) Coil Impedance Cat. No. 110 to 415V AC ca 29ohm DIN-TSHT110415U 110 to 125V DC ca 29ohm 24 to 60V AC ca 24ohm 24 to 48V DC ca 24ohm DIN-TSHT2460U Dimensions (mm) Shunt trip will fit to either right or left side of Din-T6, Din-T10 or Din-T15. On Din-T10H the shunt trip can only be fitted on the left side. Operation The Din-T shunt trip makes it possible to remotely switch off the MCB to which it is coupled by energising the terminals of the module. An inbuilt contact in series with the coil prevents burn out if voltage remains – manual resetting of the MCB is required. Application ❑ Emergency stop. ❑ Isolation of socket outlets (see connection diagrams). Technical data Operating voltage (V) Closing current (A) Operating time (MS) 110V AC 0.3 10 240V AC 0.6 4 415V AC 1 2 24V AC 1 10 60V AC 2 4 Connection diagrams MCB + shunt trip Terminal capacity (mm2) Bottom 35 Top 25 MCB + Auxiliary contact H/HS + shunt trip MCB + Auxiliary contact H + shunt trip