THE FOLLOWING FORMULAS MAY BE OF USE IN BUILDING SYSTEMS ELECTRICAL Footcandles = lumens area in ft2 Footcandles = (lamp lumens) x (lamps per fixture) x (number of fixtures) x (CU) x (LLF) area in ft2 Number of luminaires = (footcandles) x (floor area) , (lumens) x (CU) x (LLF) where CU = coefficient of utilization LLF = Light Loss Factor DFav = 0.2 x (window area/floor area) for spaces with sidelighting or toplighting with vertical monitors watts = volts x amperes x power factor (ac circuits only) Demand charge = maximum power demand x demand tariff HVAC Btu/year = (peak heat loss) x (full-load hours/year) $/year = (Btu/year) x (fuel cost/fuel heat value) x (efficiency) Btu/h = (cfm) x (1.08) x (T) 1 kWh = 3,400 Btu/h 1 ton of air conditioning = 12,000 Btu/h Btu/h = (U) x (A) x (Td), where Td is the difference between indoor and outdoor temperatures U = 1 / Rt Uo = (Uw x Aw) + (Uop x Aop) , where o = total wall, w = window, and op = opaque wall Ao Uo = (UR x AR) + (Us x As) , where o = total roof, R = roof, and S = skylight Ao R = x / k, where x = thickness of material in inches Heat required = Btu/h temperature differential x (24 hours) x (DD °F), where DD = degree days PLUMBING 1 psi = 2.31 feet of water 1 cubic foot = 7.5 U.S. gallons ACOUSTICS Sound = λ= c , where λ = wavelength (ft), c = velocity of sound (fps), and f = frequency of sound (Hz) f NR = TL – 10 log [S / AR], NRC = a / s, TR = K x where NR TL S AR = Noise reduction (dB) = Barrier transmission loss (dB) = Area of barrier wall (ft2) = Total absorption of receiving room (sabins, ft2) where NRC = Noise reduction coefficient a = Total sabins (sound absorbing units) s = TotaI surface area in the room V , ΣA where TR K V ΣA = = = = Reverberation time in seconds a constant of 0.05 when measurements are in feet Room volume (ft3) Total room absorption, sabins (ft2) at that frequency