HEAT LOAD CALCULATION (manual) 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. Project Location Space usage Orientation Weather properties Solar gain through glass Transmission gains (wall and roof) Partition gains Internal heat Infiltration Sensible heat Latent heat Tonnage of refrigeration Coil ADP Dehumidified air supply Room Dimension Length Width Height Area Volume Window size = 15 ft = 10 ft = 10 ft = 150 ft = 1500 ft³ = 3*3 ft 1. WEATHER Location- Trivandrum From data book PAGE NO: 20 - 21 we get, Latitude = 8.3˚N Daily Range = 15˚F (Maximum temperature difference acquiring a day during a year) Dry bulb (D.B) = 92.1˚F Wet bulb (W.B) = 79˚F Relative humidity (R.H) = 56.6 % Specific humidity (W) =129.4 gr/lb {gram/pound } We get all this details from both CARRIER’S PSYCHOMETRIC CHART SOFTWERE by entering DB&WB, and HAP by entering the location. 1.1 Recommended inside design condition for summer and winter D.B R.H W.B w = 75˚F = 50% = 62.5˚F = 64.9 gr/lb 1.2 Difference between Required and actual condition D.B W.B R.H w = ( 92.1 – 75 ) = 17.1˚F = ( 79 – 62.5 ) = 16.5˚F = ( 56.6 – 50 ) = 6.6% = ( 129.4 – 64.5 ) = 64.5 gr/lb (it is used for finding correction factor for Δt in section-6 and 7) 2. SPACE From the above drawing Length = 15 ft Width = 10 ft Floor area = 150 ft² Avg ceiling height = 10 ft 3. OA VENTILATION REQUIREMENT From data book PAGE NO : 10 we get, Occupancy category People outdoor air rates cfm/person Reception areas Area outdoor air rate Notes Occupant density #/1000ft² Or #/100m² 30 L/s Cfm/ft² L/sm² person 3 2.5 for reception area 1000 ft² for 150 ft² 0.06 0.3 Default values Combined outdoor air rate cfm/person L/s person 7 3.5 Air class 1 = 30 people = x people 30 x = 150 × x = 5 person 1000 = 4.5 cfm/person for reception area = 7/person no. of people = 5 Total cfm = 5*7 = 35 cfm 4. INTERNAL HEAT Sensible heat 4.1 People For normal person, Sensible Latent = 250 Btu/hr = 200 Btu/hr No of person = 5 From data book PAGE NO: 62 we get, Moderately active office work = 250 Btu/hr Heat gain from people = 5*250 = 1250 Btu/hr 4.2 Power 1 HP 1 RT (Refrigerant Tonnage) = 12,000 BTU/HR=3.51KW 1 WATT =3.41 BTU/HR = 2545 Btu/hr Btu – British thermal unit – unit of energy 4.3 Lights Heat gain through Lights = Power*3.41*1.2 1 watt = 3.41 Btu/hr 3.41 is a constant for converting Watts electrical power unit into mechanical. 1.2 is Ballast factor (such as choke), we can take 1 to 1.25 If, No of lights =5 Power of a single light = 40 Then, Total power = 5*40 = 200 watts Heat gain through lights = 200*3.41*1.2 = 818.4 Btu/hr 4.3 Appliances Heat gain = Power*3.41*Usage factor 1 watt = 3.41 Btu/hr 3.41 is a constant for converting Watts electrical power unit into mechanical. Usage factor is 1 for 24 hours working. If, Power = 500 watts Then, Heat gain = 500*3.41*1 = 1705 Btu/hr TOTAL SENSIBLE INTERNAL HEAT = People + Lights + Appliances = 1250 + 818.4 + 1705 = 3773.4 Btu/hr 5. HEAT GAIN THROUGH GLASS Orientation = West (from figure) Area of 1 window = 3*3 = 9 ft² Total area of windows in west side = 2*9 = 18 ft² Heat gain = Area*Δt*U A = Area of window Δt = Equivalent temperature difference / Solar factor U = Overall value Method of finding Δt Δt is get From data book PAGE NO: 42 (41 to 46) by considering LATITUDE ( in this case, it is 8.3˚N from section 1. ) Available charts for finding solar heat gain through ordinary glass is, LATITUDE 0˚,10˚,20˚,30˚,40˚,50˚. For this case we can choose chart of 10˚ LATITUDE. Heat gain is maximum on summer season, so take “JULY 23 & MAY 21” in “TIME OF YEAR” section Window is in west direction (in this case), so take peak value ( ie, in peak time) in WEST direction From above procedure we get Δt =158 Btu/hr Method of finding U value U value for Ordinary glass = 0.86 Btu/hr ft² ie, Heat gain = A*Δt*U = 18*158*0.86 = 2445.86 Btu/hr Similarly, we can find heat gain through glass in south direction Orientation = South (from figure) Area of 1 window = 3*3 = 9 ft² Total area of windows in west side = 1*9 = 9 ft² From above procedure we get Δt =14 Btu/hr ie, Heat gain = A*Δt*U = 9*14*0.86 = 108.36 Btu/hr TOTAL HEAT GAIN THROUGH GLASS = HEAT GAIN THROUGH WEST + HEAT GAIN THROUGH SOUTH = 2445.86 + 108.36 = 2554.22 Btu/hr 6. TRANSMISSION GAIN THROUGH ROOF Heat gain = Area*Δt*U A = Area of window Δt = Equivalent temperature + Correction factor U = Overall value Roof Area = 10*15 = 150 ft² Roof Material = Construction type, 6” thickness concrete and 1” thickness plaster Method of finding U value U vale finding is by considering ROOF MATERIAL, from data book PAGE NO: 54 & 55 Choose CONCRETE, SEND & GREVEL AGG (because, here construction type is concrete) in “TYPE OF DECK” section. Choose 4, 6, 8, [47], [70], [93] (because, here concrete of thickness is 6” is used) in “THICKNESS OF DESK (INCHES) AND WEIGHT (LB PER SQ FT)” section. (where the values in rectangular brackets [] are WEIGHT OF ROOF corresponding to the THICKNESS OF DESK, it is required for the calculation of equivalent temperature. ie, for 4 inch, weight of roof is 47 lb/ft²) Choose SUSPENDED PLASTER {6} (here plaster is used) in “CEILING” section. Take values for 1” (ie, in this case plaster thickness is 1”) in “INSULATION ON TOP OF DECK, INCHES” section. From above procedure we get U = 0.16 Btu/hr ft². Method of finding Δt Δt = Equivalent Temperature + correction factor Finding of equivalent temperature is with respect to weight of roof. Weight of room is get from the table used to find U value. From data book PAGE NO: 54 table for finding u value, we get the WEIGHT OF ROOF corresponding to the THICKNESS OF DESK. (here thickness of desk is 6 inch, ie weight of roof is 70 lb/ft²) From data book PAGE NO: 49 take the peak values for 60 lb/ft² (ie 70 lb/ft² is not available) by considering CONDITION as EXPOSED TO SUN From above procedure We get equivalent temperature = 39˚F To get correction factor, we need difference between Outdoor temperature and room temperature. That we find in section 1.2 as difference between required and actual condition, and Daily range in section 1 as weather. ΔDB = 17.1˚F Daily range = 15˚F From data book PAGE NO:49, TABLE NO: 6 `by matching “OUTDOOR DESIGN FOR MONTH AT 3PM MINUS ROOM TEMPERATURE” as 20˚F (higher than 17.1˚F) and “DAILY RANGE” as 16˚F (15 is not available, 16 is next higher value), we get CORRECTION FACTOR as 7. Δt = Equivalent temperature + Correction factor = 39 + 7 Δt = 46˚F Heat gain = Area*Δt*U = 150*46*0.16 = 1104 Btu/hr 7. TRANSMISSION GAIN THROUGH WALL Heat gain = Area*Δt*U A = Effective wall area Δt = Equivalent temperature + Correction factor U = Overall value Roof Area Wall Material = 10*15 = 150 ft² = Construction type, 8” thickness stone and 3/4” thickness gypsum board plaster WEST WALL AREA Total wall area Area of windows in west Effective area of west wall = length*height = 10*10 = 100 ft² = 2 window = 18 ft² = 100 – 18 = 82 ft² SOUTH WALL AREA Total wall area Area of windows in south Effective area of south wall = 15*10 = 150 ft² = 1 window = 9 ft² = 150 – 9 = 141 ft² Method of finding U value U vale finding is by considering WALL MATERIAL, from data book PAGE NO:50 (50 to 53) Choose STONE (because, here stone is used for construction) in “EXTERUIR FINISH” section. Choose 8 (100) (because, here thickness of stone is 8”) in “THICKNESS (INCHES) AND WEIGHT (LB PER SQ FT)” section. (where the values in brackets () are WEIGHT OF WALL corresponding to the THICKNESS OF DESK, it is required for the calculation of equivalent temperature. ie, for 8-inch thickness stone, weight of wall is 100 lb/ft²) Take value corresponding to “¾” GYPSUM BOARD (PLASTER BOARD)” in INTERIOR FINISH section. From above procedure we get U = 0.55 Btu/hr ft Method of finding Δt Δt = Equivalent Temperature + correction factor Finding of equivalent temperature is with respect to weight of wall and Exposure (direction) of wall. Weight of room is get from the table used to find U value. From data book PAGE NO: 50 table for finding u value, we get the WEIGHT OF WALL corresponding to the THICKNESS. (here thickness of stone is 8 inch, ie weight of wall is 100 lb/ft²) WEST WALL From data book PAGE NO: 48 take the values for EXPOSURE as WEST and WEIGHT OF WALL as 100 lb/ft² at 6pm From above procedure We get equivalent temperature = 20˚F Correction factor is same as that of roof. To get correction factor, we need difference between Outdoor temperature and room temperature. That we find in section 1.2 as difference between required and actual condition, and Daily range in section 1 as weather. ΔDB = 17.1˚F Daily range = 15˚F From data book PAGE NO:49, TABLE NO: 6 `by matching “OUTDOOR DESIGN FOR MONTH AT 3PM MINUS ROOM TEMPERATURE” as 20˚F (higher than 17.1˚F) and “DAILY RANGE” as 16˚F (15 is not available, 16 is next higher value), we get CORRECTION FACTOR as 7. Δt Δt = Equivalent temperature + Correction factor = 20 + 7 = 27˚F SOUTH WALL From data book PAGE NO: 48 take the values for EXPOSURE as SOUTH and WEIGHT OF WALL as 100 lb/ft² at 6pm From above procedure We get equivalent temperature = 18˚F Correction factor is same as that of roof. To get correction factor, we need difference between Outdoor temperature and room temperature. That we find in section 1.2 as difference between required and actual condition, and Daily range in section 1 as weather. ΔDB = 17.1˚F Daily range = 15˚F From data book PAGE NO:49, TABLE NO: 6 `by matching “OUTDOOR DESIGN FOR MONTH AT 3PM MINUS ROOM TEMPERATURE” as 20˚F (higher than 17.1˚F) and “DAILY RANGE” as 16˚F (15 is not available, 16 is next higher value), we get CORRECTION FACTOR as 7. Δt Δt = Equivalent temperature + Correction factor = 18 + 7 = 25˚F Heat gain through west wall = Area of west wall * Δt of west * U = 82 * 27 * 0.55 = 1217.7 Btu/hr Heat gain through south wall Total heat gains through wall = Area of south wall * Δt of south * U = 141 * 25 * 0.55 = 1938.75 Btu/hr = 1217.7 + 1938.75 = 3156.45 Btu/hr 8. HEAT GAIN THROUGH THE UNCONDITIONED SPACE Heat gain = Area*Δt*U A = Transmission area Δt = (Outside temperature - 5˚F) – Inside temperature Where, from (Outside temperature - 5˚F) is mean by the temperature of nearest unconditioned space, it’s not same as that of outside air. U = Overall value Inside wall material = Hollow concrete block, 4” thickness, both side finished, 3/8” gypsum board plastering. ΔT = (Outside temperature - 5˚F) – Inside temperature = (92.1 – 5) – 75 = 12.1˚F Total area Door area Transmission area = 10*10=100 ft² = 3*7 = 21 ft² = 100 – 21 = 79 ft² Method of finding U value U vale finding is by considering INSIDE WALL MATERIAL, from data book PAGE NO: 53 Choose HOLLOW CONCRETE BLOCK (because, here construction type is hollow concrete) in “RACKING” section. Choose 4 (20) (because, thickness is 4”) in “THICKNESS (INCHES) AND WEIGHT (LB PER SQ FT)” section. (where the values in brackets () are WEIGHT OF INSIDE WALL corresponding to the THICKNESS.) Choose NO. OF SIDES FINISHED as Both Take value corresponding to “3/8” GYPSUM BOARD (PLASTER BOARD)” in FINISH section. From above procedure we get U = 0.32 Btu/hr ft². Heat gain = Area * Δt * U = 79 * 12.1 * 0.32 = 305.89 Btu/hr 9. INFILTRATION .DSASADA VOLUME (ft2 ) × ACH (Air change per hour) CFM = 60 ACH (Air change per hour) = 0.5 to 1.5 Cfm = 1500 ×1 60 Specific heat formula Qs = 1.08*CFM*ΔT Where, Qs= sensible heat gain. 1.08=sensible heat value. CFM=dry air ΔT= difference of required and actual temperature. = 25 cfm INFILTRATION HEAT GAIN = CFM * ΔT * 1.08 CFM – Infiltration ΔT = (Outside temperature - 5˚F) – Inside temperature 1.08 = Sensible heat value (for more details refer last page) Infiltration Heat gain 10. Q=m*c*ΔT Where, Q= heat added/ subtracted to that substance/ control volume. m= mass flow into that substance/ control volume. ΔT= difference of required and actual temperature. = CFM*ΔT*1.08 = 25 * [(92.1 – 5) – 75] * 1.08 = 326.7 Btu/hr BYPASSED OUT SIDE AIR HEAT GAIN BY BYPASSED AIR = CFM * ΔT * 1.08 * B.F CFM – OA VENTILATION REQUIREMENT (from section 3) ΔT = (Outside temperature – Inside required temperature) 1.08 = Sensible heat value B.F = Bypass factor, normally we take 0.12 Heat gain by bypassed air 11. = CFM * ΔT * 1.08 * B.F = 35 * (92.1 – 75) * 1.08 * 0.12 = 70.92 Btu/hr TOTAL SENSIBLE HEAT TOTAL SENSIBLE HEAT = TOTAL SENSIBLE INTERNAL HEAT SOLAR GAIN THROUGH GLASS TRANSMISSION GAIN THROUGH ROOF TRANSMISSION GAIN THROUGH WALL TRANSMISSION GAIN THROUGH UNCONDITIONED SPACE INFILTRATION BYPASSED OUTSIDE AIR + + + + + + TOTAL SENSIBLE HEAT Adding 10% extra for safety = 3773.4 + 2554.22 + 1104 + 3156.45 + 305.89 + 326.7 + 70.92 = 11,291.58 Btu/hr = 1.1 * 11,291.58 = 12,420.738 Btu/hr EFFECTIVE ROOM SENSIBLE HEAT [ERSH] 12. = 12,420.738 Btu/hr TOTAL LATENT HEAT TOTAL SENSIBLE HEAT = LATENT HEAT DUE TO PEOPLE + LATENT HEAT DUE TO BYPASSED OA + LATENT HEAT DUE TO INFILTRATION 12.1 Latent heat due to people Heat gain = No. of people * Latent heat/person For normal person, latent heat/person = 200 Btu/hr Heat gain = No. of people * Latent heat/person = 5 * 200 = 1000 Btu/hr 12.2 Latent heat due to Bypassed outside air Bypassed OA = CFM * Δw * B.F * 0.68 CFM - OA VENTILATION REQUIREMENT (from section 3) Δw = Grain size difference, or specific humidity difference (from section 1.2) B.F = Bypass factor, normally we take 0.12 0.68 = Latent heat value Bypassed OA = CFM * Δw * B.F * 0.68 = 35 * 64.5 * 0.12 * 0.68 = 184.212 Btu/hr 12.3 Latent heat due to infiltration Infiltration = CFM * Δw * 0.68 CFM – Infiltration Air (from section 9) Δw = Grain size difference, or specific humidity difference (from section 1.2) 0.68 = Latent heat value Infiltration = CFM * Δw * 0.68 = 25 * 64.5 * 0.68 = 1096.5 Btu/hr TOTAL SENSIBLE HEAT Adding 10% extra for safety = LATENT HEAT DUE TO PEOPLE + LATENT HEAT DUE TO BYPASSED OA + LATENT HEAT DUE TO INFILTRATION = 1000 + 184.212 + 1096.5 = 2,280.712 Btu/hr = 1.1 * 2280.71 = 2508.78 Btu/hr EFFECTIVE ROOM LATENT HEAT [ERLH] 13. = 2508.78 Btu/hr EFFECTIVE ROOM TOTAL HEAT [ERTH] EFFECTIVE ROOM TOTAL HEAT = EFFECTIVE ROOM SENSIBLE HEAT + EFFECTIVE ROOM LATENT HEAT ERTH = ERSH + ERLH ERTH = 12,420.738 + 2508.78 = 14,929.518 Btu/hr 14. OUTSIDE AIR HEAT (EXCLUDING BYPASS FACTOR) TOTAL HEAT = ΔHS + ΔHL Where, ΔHs = Sensible heat ΔHL = Latent heat 14.1 Sensible heat ΔHS = Q * ΔT * (1 – B.F) * 1.08 Q = O.A VENTILATION REQUIRED (from section 3), or fresh air required ΔT = (Outside temperature – Inside required temperature) 1.08 = Sensible heat value (1 - B.F) = Excluding bypass factor Q ΔT = 35 cfm = (92.1 – 75) = 17.1˚F B. F = 0.12 ΔHS = Q * ΔT * (1 – B.F) * 1.08 = 35 * 17.1 * (1 – 0.12) * 1.08 = 568.81 Btu/hr 14.2 Latent heat ΔHL = Q * Δw * (1 – B.F) * 0.68 Q = O.A VENTILATION REQUIRED (from section 3), or fresh air required ΔT = Specific humidity (from section 1.2) 0.68 = Latent heat value (1 - B.F) = Excluding bypass factor Q = 35 cfm ΔT = 64.5 gr/lb B. F = 0.12 ΔHS = Q * Δw * (1 – B.F) * 0.68 = 35 * 64.5 * (1 – 0.12) * 0.68 = 2145.53 Btu/hr TOTAL HEAT = ΔHS + ΔHL = 568.81 + 2145.53 = 2714.34 Btu/hr Adding 5 % extra for safety = 1.05 * 2714.34 = 2850.06 Btu/hr 15. GRAIN TOTAL GRAIN TOTAL = EFFECTIVE ROOM TOTAL HEAR [ERTH] + TOTLA OUTSIDE AIR HEAT = 14,929.518 + 2850.06 = 17,779.578 Btu/hr 16. TONS OF REFRIGERATION 1 TON = 12,000 Btu/hr Tons of refrigeration = 17,779.578 12,000 = 1.48 TR 17. COIL APPARATUS DEW POINT (COIL ADP) To get coil ADP from data book, we need i. Inside room temperature (from section 1.1) ii. R.H (from section 1.1) iii. Effective room sensible heat factor (ESHF) ESHF ESHF = = ERSH ERTH 12,420.738 14,929.518 = 0.8316 = 83.16% From data book PAGE NO: 67 By using this data’s we get coil ADP = 52˚F 18. SUPPLY AIR DEHUMIDIFIED AIR RISE DEHUMIDIFIED AIR RISE = (1- B.F) * (ROOM D.B – COIL ADP) Dehumidified air rise = (1 – B.F) * (room D.B – coil ADP) = (1 – 0.12) * (75 – 52) = 20.24˚F DEHUMIDIFIED AIR QUANTITY (SUPPLY AIR) VOLUME OF SUPPLY VOLUME OF SUPPLY = = = ERSH 1.08×DEHUMIDIFIED AIR RISE ERSH 1.08×DEHUMIDIFIED AIR RISE 12,420.738 1.08×20.24 = 568.22 cfm 19. RESULT Tonnage Supply air Fresh air Coil ADP = 1.4 TR = 568.22 cfm = 35 cfm = 52˚F Specific heat formula Qs = 1.08*CFM*ΔT Where, Qs 1.08 CFM ΔT Where, Q M ΔT = sensible heat gain. =sensible heat value. =dry air = difference of required and actual temperature. Q = m*c*ΔT = heat added/ subtracted to that substance/ control volume. = mass flow into that substance/ control volume. = difference of required and actual temperature. From a chart “Ideal gas specific heat of various common gases at 80˚F) We get, for Air, cp, a = 0.24 Btu/lb ˚F moist air/steam, cp, v = 0.445 Btu/lb ˚F Abbreviation used, Cp = specific heat at constant pressure Cp, a = spec. heat at const. press. of air Cp, v = spec. heat at const. press. of vapour ma = mass of air mv = mass of vapour Q̇ = heat flow ṁ a = mass flow of air (lb/hr) ṁ v = mass flow of vapour (lb/hr) Q = ma cp, a (ΔT) + mv cp, v (ΔT) By dividing both side by t (time), we get its rate, Q̇ = ṁ a cp, a (ΔT) + ṁ v cp, v (ΔT) Substitute the values for cp, a & cp, v Q̇ = ṁ a (0.24) (ΔT) + ṁ v (0.445) (ΔT) For typical air-conditioning process Q̇ ṁv ṁa = 0.01 = ṁ a (0.24) (ΔT) + (0.01) ṁ a (0.445) (ΔT) By rearranging Q̇ = ṁ a (ΔT) [0.24 + 0.0045] In many case, we can neglect the value 0.0045, it won’t make any difference in final answer. Q̇ = ṁ a (ΔT) (0.24) Conversion of ṁ a from lb/hr to cfm. ṁ a lb hr = 𝑓𝑡² 𝑚𝑖𝑛 × 60 𝑚𝑖𝑛 1 ℎ𝑟 × 1 𝑙𝑏 13.3 𝑓𝑡³ Q̇ = (4.5 CFM) (ΔT) (0.24) Q̇ = 1.08 * CFM * ΔT = 4.5 𝐶𝐹𝑀