Power Electronics and Renewable Energy Research
Laboratory (PEARL)
Department of Electrical Engineering
University of Malaya
Kuala Lumpur, Malaysia monir04eee@yahoo.com
Abstract —There has been an increasing interest in transformerless inverter for grid-tied photovoltaic (PV) system due to low cost, high efficiency, less weight, etc. Therefore, many transformerless topologies have been proposed and verified with real power injection only. Recently, almost every international regulation has imposed that a definite amount of reactive power should be handled by the grid-tied PV inverter.
According to the standard VDE-AR-N 4105, grid-tied PV inverter of power rating below 3.68kVA, should attain power factor (PF) from 0.95 leading to 0.95 lagging. In this paper, a new high efficient transformerless topology is proposed for grid-tied PV system. The new topology structure and detail operation principle with reactive power flow is described. The proposed circuit structure does not lead itself to the reverse recovery issues which allow utilizing MOSFET switches to increase the overall efficiency. Finally, to validate the proposed topology, a 1kW laboratory prototype is built and tested. The experimental results show that the proposed topology can inject reactive power into utility grid without any additional current distortion and leakage current. The maximum efficiency and European efficiency of the proposed topology is measured and found to be 98.54% and 98.27%, respectively.
Keywords— common mode, converter, high efficient, leakage current, reactive power, transformerless.
I.
I NTRODUCTION
Recently, the photovoltaic power generation system has been focused as one of the most significant energy sources due to the rising concern about global warming, and the increase of electrical power consumption [1]. The milestone of 100GW installed PV power all over the world was achieved at the end of 2012 and increased to 140GW at the end of 2013, and the majority are grid connected as shown in
Fig. 1 [2]. Therefore, it has been predicted that the future grid-tied PV system will play an important role in the regulation of the conventional power system [3].
In general, PV power generation system includes solar arrays and power conversion unit [4-6]. In most countries and
The authors wish to acknowledge the financial support from the
University of Malaya through HIR-MOHE project
UM.C/HIR/MOHE/ENG/24 and FRGS project no. FP014-2014A
Power Electronics and Renewable Energy Research
Laboratory (PEARL)
Department of Electrical Engineering
University of Malaya
Kuala Lumpur, Malaysia saad@um.edu.my
Fig. 1.
Share of grid-connected and standalone PV installation [2] areas, a line-frequency transformer or a high-frequency transformer has been utilized in the grid-tied PV system to create a galvanic isolation between the PV module and the grid. However, the use of line-frequency or high-frequency transformer makes the entire system bulky, costly, and less efficient. In contrast, transformerless PV inverter system has been drawing attention more and more for its low cost, high efficiency, small size and weight [7, 8]. The exclusion of transformer, and hence its isolation capability, has to be considered carefully. Because of the parasitic capacitance between the PV module and the ground, the fluctuating common mode (CM) voltage that depends on the topology structure and switching scheme can inject a capacitive leakage current [9]. The existence of leakage current increases grid current harmonics and system losses, deteriorates the electromagnetic compatibility and, more significantly, lead to a safety threat [5, 10, 11].
In order to solve the problem of leakage current, many dc-ac inverter topologies have been proposed [7, 8, 10, 12-
16]. Most of the inverter topologies described in literature and commercially available show the European efficiency in the range of 96%-98% [17]. Therefore, to boost the efficiency, some transformerless topologies use MOSFET switches because of its low switching and conduction losses
[7, 12, 18-21].
978-1-4799-6735-3/15/$31.00 ©2015 IEEE 1666
Fig. 2.
Transformerless topologies using MOSFET switches: (a) HERIC topology [20] (b) HB-ZVR topology [7] (c) H6-type topology [12]
The most attractive transformerless topology is the
Highly Efficient and Reliable Concept (HERIC) topology which is shown in Fig. 1(a). Two switches and two diodes are added in the ac side of full-bridge topology to decouple the PV module from the grid during the freewheeling period
[20]. As shown in Fig. 1(b), the topology which has been proposed in [7] replaces the two switches freewheeling branch with one bi-directional switch and four diodes. Yu et al. proposed a H6-type topology as shown in Fig. 1(c), in which two switches and two diodes are added in the dc side to decouple the PV module from the grid [12]. An extension of this topology has been presented in [21]. All the topologies can achieve high efficiency and low leakage current. However, recently almost every international regulation has imposed that a definite amount of reactive power should be handled by the grid-tied PV inverter. This is due to the problems of grid voltage stability. According to the standard VDE-AR-N 4105 which is updated in 2011, grid-tied PV inverter of power rating below 3.68kVA, should attain PF from 0.95 leading to 0.95 lagging [22]. The topologies shown in Fig. 1 have been verified with real power injection only. The dependability of these topologies will be reduced if a phase shift between the voltage and current is occurred due to the low reverse recovery issues of the MOSFETs anti-parallel diode.
In this paper, a new transformerless inverter for single phase grid-tied PV system is proposed. The proposed topology can utilize MOSFET switches to boost the efficiency because the inherent circuit structure does not lead itself to the reverse recovery issues even when inject reactive power. The proposed circuit structure and detail operation principle with reactive power flow are investigated in section
II. The control system for the proposed topology is also presented in section III. It has shown that the proposed inverter can handle a certain amount of reactive power if necessary. Finally, the proposed topology is verified with a prototype of rated 1kW/50Hz for unity power factor and other than unity power factor which is shown in section IV and section V concludes the paper.
II.
P
ROPOSED
T
OPOLOGY AND
M
ODULATION
S
CHEME
A.
Structure of the proposed topology
Fig.1 shows the proposed transformerless inverter topologies consisting of six MOSFET switches (S1-S6) and six diodes (D1-D6). The proposed topology is derived from
[12] by splitting the MOSFET phage-legs. The inherent structure of the proposed topology can overcome the low reverse-recovery issues of MOSFETs body-diode even when
(a)
(b)
Fig. 3.
(a) Circuit structure of the proposed transformerless topology for grid-tied PV system (b) circuit structure with coupled inductor inject reactive power into the utility grid which allows utilizing MOSFET switches without any reliability or efficiency penalty. The proposed topology can also employ unipolar-SPWM with three-level output voltage.
B.
Operation principle analysis with reactive power flow
The switching pattern of the proposed topology is shown in Fig. 4, where S1, S2, S3, S4, S5, and S6 represent the gate drive signals of the switches S1, S2, S3, S4, S5, and S6, respectively. The operation principle of the proposed topology within a grid period which is shown in Fig. 5 is divided into four regions that can be explained as follows:
Region I: In this region, both the grid current and voltage are positive. During the period within this region, S2 is always on, while S1 & S3 synchronously and S5 complementary commutate with switching frequency. There are always two states that generate the output voltage state of
+V
PV
and 0.
State 1(t0:t1): In this state, the switches S1 & S3 are turned-on and the inductor current increases through grid as shown in Fig. 5(a). The inverter output voltage V
CM voltage can be defined as: V
V
CM
=1/2(V
1N
+V
2N
) =1/2(V
PV
+0) =1/2V
PV
.
AB
AB
=+V
, and the
PV
and
State 2(t1:t2): When the switches S2 and S3 are turnedoff, the inductor current freewheels through S2 and D5. In
1667
Fig. 4.
Switching pattern of the proposed topology with reactive power flow this state, the inverter output voltage and the CM voltage could be as follows: V
1/2(1/2V
PV
+1/2V
PV
AB
= 0 and V
) = 1/2V
PV
.
CM
= 1/2(V
1N
+V
2N
) =
Region II: In this region, the inverter output voltage is negative, but the current remains positive. During the duration of this region, S5 is always on, while S4 & S6 synchronously and S2 complementary commutate with switching frequency. There are also two states which generate the output voltage state of -V
PV
and 0.
State 3(t3:t4): In this state, the switches S4 and S6 are turned-on and the filter inductors are demagnetized. Since the inverter output voltage is negative and current remains positive; therefore, the inductor current is forced to freewheel through the diode D1 and D2, and decreases rapidly for enduring the reverse voltage. The output voltage and the CM voltage become: V
1/2V
PV
AB
, respectively.
= -V
PV
and V
CM
= 1/2(V
3N
+V
4N
) =
State 4(t4:t5): At t=t4, the switches S4 and S6 are turnedoff and S2 is turned-on. Therefore, the inductor current flows through S2 and D5 like as state 2 (Fig. 5(b) can be referred as equivalent circuit). This state is called as energy storage mode. The output voltage and the CM voltage become: V
AB
= 0 and V
CM
= 1/2V
PV
, respectively.
Region III: In this region, both the grid current and voltage are negative. During the period of this region, S5 is always on, while S4 & S6 synchronously and S2 complementary commutate at the switching frequency. There are always two states that can be explained as follows: the output voltage become, V
PV
and the inductor current increases through the utility grid. In this mode, V
V
PV
State 5(t6:t7): When the switches S4 & S6 are turned-on,
and V
1/2(V
3N
+V
4N
4N
) = 1/2(V
PV
AB
= -V
= 0. Therefore, the CM voltage is V
+ 0) = 1/2V
PV
.
3N
CM
=
=
State 6(t7:t8): At t=t7, the switches S4 and S6 are turnedoff and S2 is turned-on. Therefore, the inductor current freewheels through the switch S5 and D6. In this state, V
3N
1/2V
PV
and V
4N
= 1/2V
PV computed as: V
CM
= 1/2(V
3N 4N
.
=
. Therefore, the CM voltage can be
+V ) = 1/2V
PV
Region IV: In this region, the inverter output voltage is positive, but the current remains negative. There are also two states.
Fig. 5.
Operation principle of the proposed topology: (a) state 1 (b) state 2
(c) state 3 (d) state 4 (e) state 5 (f) state 6
State In this state, the switches S1 and S3 are turned-on and the filter inductors are demagnetized. Since the inverter output voltage is positive and the current remains negative; therefore, the inductor current is forced to freewheel through the diode D3 and D4 as shown in Fig 5(f).
The output voltage and the CM voltage are defined as: V
+V
PV
and V
CM
= 1/2(V
1N
+V
2N
) = 1/2V
PV
, respectively.
AB
=
State At t=t10, the switches S1 and S3 are turned-off and S5 is turned-on. Therefore, the inductor current flows through S5 and D6 (Fig. 5(e) can be referred as equivalent circuit). Therefore, the CM voltage can be computed as: V
CM
= 1/2V
PV
.
According to the above analysis, it is clear that the proposed topology can keep the CM voltage constant when inject reactive power.
III.
C
ONTROLLING OF THE
P
ROPOSED
T
OPOLOGY
The control system for the proposed topology is depicted in Fig. 6, which contains an orthogonal signal generator
(OSG) unit to calculate active and reactive power, two proportional integral (PI) controllers for active and reactive power control, a grid current controller and a SPWM generation block [3]. Based on the OSG system, the active power P and reactive power Q for the proposed topology can be calculated by using the following equation which is shown in Fig. 7 [3, 23, 24]:
P cal
= 1 2 v i + v i (1)
Q cal
= 1 2 − (2) where v g α
, v g β
, i g α
, and i g β
represents the α and β components of grid voltage and current. Based on equation (1) and (2), the current in αβ -reference frame can be derived as follows: i g α
= 2
(
P cal
* v g α
+ Q cal
* v g β
) i g β
= 2
(
P cal
* v g β
+ Q cal
* v g α
)
( v 2 g α
( v g
2
α
+ v g
2
β
+ v g
2
β
)
)
(3)
(4)
1668
Fig. 6.
Control diagram of the proposed topology
Fig. 7.
OSG based power calculation
According to the single phase P-Q theory, the grid-in current reference can be generated by regulating the averaged active and reactive power [23, 25, 26]. Since the active and reactive power are constant in steady state, so to control them two PI controllers has been used as shown in
Fig. 6. The grid reference current can be derived with the help of OSG system in the following equation [23, 25]: i
* g
= (
P ref
− P cal
)
*G p
( )
* g α
+
(
Q ref
− Q cal
)
*G q
( )
* g β
( v
2
α
+ v
2
β
(5)
) where P ref and Q ref
are the power references, G defined as follows: p
(s) and G q
(s) are the transfer function of PI based controller that can be
( )
( ) where K pp
=
=
, K pi pp qp
+
+
, K
K
K qi qp pi
*
*
1
1 s s
, and K qi
(6)
(7)
are the proportional and integral gain for the active and reactive power.
In order to control the grid current, several existing control methods such as conventional PI, repetitive controller
(RC), proportional resonant (PR) controller, and deadbeat
(DB) controller can be adopted due to the capability of tracking reference signal without steady state error [27-29].
Since the PR controller has better performance of tracking the reference signal if compared to the normal PI and RC controller, it is selected to control the grid current for the proposed topology. The block diagram of the PR controller
Fig. 8.
Block diagram of PR controller with harmonic compensator with harmonic current compensator is shown in Fig 8, where
G c
(s), G h
(s), G d
(s), and G fundamental current controller, harmonic compensator, inverter and LC filter, respectively. The transfer functions are given below [27, 30]: f
(s) are the transfer function of
( ) =
pi
+ K ii
* s 2 s
+ ω f
2
(8)
( ) =
h = 3,5,...
s 2 +
( ) 2
(9)
( ) =
1
(10) where K
+ T s pi
and K ii
are the proportional and resonant gain, ω f
is the fundamental frequency, nth-order harmonic, h is the harmonic order, and T sampling period.
K ih
is the resonant gain at the s
is the
TABLE I. S PECIFICATION OF THE P ROTOTYPE
Inverter Parameter
Input Voltage
Grid Voltage / Frequency
Rated Power
Value
400VDC
230V / 50Hz
1000 W
AC output current
Switching Frequency
4.2A
20kHz
Filter capacitor 2.2µF
Filter Inductor L
A
, L
B
1mH
PV parasitic capacitor Cpv1, Cpv2 75nF
IV.
E
XPERIMENTAL
R
ESULTS
In order to experimentally verify the performance of the proposed topology, a 1 kW prototype is built and tested. The specifications of the prototype are listed in table I. The PV module is replaced with a 400VDC voltage source and the parasitic capacitance between the PV module and the ground is emulated using a thin film capacitor of 75nF.
A.
Differential-mode and Common-mode Characteristics
Varification with Unity Power factor
The experimental waveforms of the DM characteristics are shown in Fig 9 for unity power factor. It can be seen that the grid voltage and the grid current are pure sinusoidal and achieved unity power factor. The total harmonic distortion is measured and found to be 2.5% that can meet the requirement of IEEE Std. 1547.1™-2005 [31]. Furthermore, in Fig 9, the inverter output voltage (DM voltage) has three levels as +V
PV
, 0 and -V
PV
, which proves that the proposed topology is modulated using unipolar-SPWM.
1669
Fig. 9.
Experimental waveforms of V g
, i g
and V
AB for unity power pactor Fig. 11.
Experimental waveforms of V g
, i g
and V
AB power pactor with other than unity
Fig. 10.
Experimental waveforms of V
AN factor
, V
BN
and V
CM for unity power
Fig. 10 shows the experimental waveforms of V and V
CM
AN
, V
BN for unity power factor. It is concluded in [5] that If the filter inductor is placed symmetrically in phase and neutral line of a full-bridge transformerless inverter, the leakage current then depends on the amplitude and frequency of the CM voltage . It is clear from Fig. 10 that the CM voltage is kept at constant value. Therefore, it can be concluded that the DM and CM characteristics of the proposed topology with unity power factor are good and very suitable for transformerless grid-tied PV application.
B.
Differential-mode and Common-mode Characteristics
Varification with Other than Unity Power Factor
The experimental waveform of grid current voltage V g i g
and grid
with 0.95 lagging power factor is shown in Fig.
11. It is noticeable that no extra distortion is occurred in grid current when inject reactive power. However, the total harmonic distortion (THD) of grid current is measured 2.9% that can meet the requirement of IEEE Std. 1547.1™-2005
[31]. In addition, it can be seen from Fig. 11 that the inverter output voltage has three levels as +V demonstrate good DM characteristics.
PV
, 0 and -V
PV
, which
The experimental waveforms of V
AN
, V
BN
and V
CM for
0.95 lagging power factor are shown in Fig. 12. It is clear that the CM voltage is kept constant at 200V. Therefore, it can be concluded that the DM and CM characteristics of the proposed topology with other than unity power factor are good and acceptable for grid-tied PV application.
Fig. 12.
Experimental waveforms of V
AN factor
, V
BN
and V
CM under unity power
Fig. 13.
Measured efficiency of the proposed topology
The measured efficiency of the proposed topology for unity power factor is depicted in Fig 13. The YOKOGAWA
WT1800 precision power analyzer has been used to measure the efficiency. It can be noted that during the efficiency measurement only the losses for power switches and filter circuit are taken into consideration. The maximum efficiency of the proposed inverter is measured 98.54%. The European efficiency is calculated using equation (11) and found to be
98.27%.
η
EU
= 0.03
η
5%
+ 0.06
η
10%
+ 0.13
η
20%
+ 0.10
η
30%
+ 0.48
η
50%
+ 0.2
η
100%
(11)
V.
C
ONCLUSION
This paper has presented a new high efficient transformerless topology for grid-tied PV system. The
1670
inherent circuit configuration of the proposed topology does not lead itself to the reverse recovery issues which allow utilizing MOSFET switches even though when inject reactive power, thereby increasing the overall efficiency. The
CM voltage kept constant at the mid-point of DC bus voltage, as a result, the ground leakage current is reduced considerably. The proposed inverter can inject reactive power into the utility grid with low leakage current and low harmonic distortion. Finally, to demonstrate the feasibility and effectiveness of the proposed topology, a 1 kW prototype was built and tested. The experimental results verified the theoretical analysis. Therefore, it can be concluded that the proposed inverter is an attractive solution for grid-tied PV system.
R
EFERENCES
[1] I. Patrao, E. Figueres, F. González-Espín, and G. Garcerá,
"Transformerless topologies for grid-connected single-phase photovoltaic inverters," Renewable and Sustainable Energy Reviews, vol. 15, pp. 3423-3431, 2011.
[2] I. PVPS, "Trends in photovoltaic applications. Survey report of selected IEA countries between 1992 and 2013," Report IEA-PVPS
T1–25, 2014.
[3] Y. Yang and F. Blaabjerg, "Low-Voltage Ride-Through Capability of a Single-Stage Single-Phase Photovoltaic System Connected to the Low-Voltage Grid," International Journal of Photoenergy, vol.
2013, pp. 1-9, 2013.
[4] S. B. Kjaer, J. K. Pedersen, and F. Blaabjerg, "A review of singlephase grid-connected inverters for photovoltaic modules," IEEE
Transactions on Industry Applications, vol. 41, pp. 1292-1306, 2005.
[5] X. Huafeng and X. Shaojun, "Leakage Current Analytical Model and
Application in Single-Phase Transformerless Photovoltaic Grid-
Connected Inverter," IEEE Transactions on Electromagnetic
Compatibility, vol. 52, pp. 902-913, 2010.
[6] A. Safari and S. Mekhilef, "Simulation and Hardware
Implementation of Incremental Conductance MPPT With Direct
Control Method Using Cuk Converter," IEEE Transactions on
Industrial Electronics, vol. 58, pp. 1154-1161, 2011.
[7] T. Kerekes, R. Teodorescu, P. Rodriguez, G. Vazquez, and E.
Aldabas, "A New High-Efficiency Single-Phase Transformerless PV
Inverter Topology," IEEE Transactions on Industrial Electronics, vol. 58, pp. 184-191, 2011.
[8] Y. Bo, L. Wuhua, G. Yunjie, C. Wenfeng, and H. Xiangning,
"Improved Transformerless Inverter With Common-Mode Leakage
Current Elimination for a Photovoltaic Grid-Connected Power
System," IEEE Transactions on Power Electronics, vol. 27, pp. 752-
762, 2012.
[9] O. Lopez, F. D. Freijedo, A. G. Yepes, P. Fernandez-Comesaa, J.
Malvar, R. Teodorescu , et al.
, "Eliminating Ground Current in a
Transformerless Photovoltaic Application," IEEE Transactions on
Energy Conversion, vol. 25, pp. 140-147, 2010.
[10] Z. Li, S. Kai, F. Lanlan, W. Hongfei, and X. Yan, "A Family of
Neutral Point Clamped Full-Bridge Topologies for Transformerless
Photovoltaic Grid-Tied Inverters," IEEE Transactions on Power
Electronics, vol. 28, pp. 730-739, 2013.
[11] T. Kok Soon and S. Mekhilef, "Modified Incremental Conductance
Algorithm for Photovoltaic System Under Partial Shading
Conditions and Load Variation," IEEE Transactions on Industrial
Electronics, vol. 61, pp. 5384-5392, 2014.
[12] W. Yu, J.-S. Lai, H. Qian, and C. Hutchens, "High-efficiency
MOSFET inverter with H6-type configuration for photovoltaic nonisolated AC-module applications," IEEE Transactions on Power
Electronics, vol. 26, pp. 1253-1260, 2011.
[13] X. Huafeng, X. Shaojun, C. Yang, and H. Ruhai, "An Optimized
Transformerless Photovoltaic Grid-Connected Inverter," IEEE
Transactions on Industrial Electronics, vol. 58, pp. 1887-1895,
2011.
[14] R. Gonzalez, J. Lopez, P. Sanchis, and L. Marroyo,
"Transformerless Inverter for Single-Phase Photovoltaic Systems,"
IEEE Transactions on Power Electronics, vol. 22, pp. 693-697,
2007.
[15] M. Islam, S. Mekhilef, and F. M. Albatsh, "An improved transformerless grid connected photovoltaic inverter with common mode leakage current elimination," in 7th IET International
Conference on Power Electronics, Machines and Drives (PEMD
2014) , 2014, pp. 1-6.
[16] M. Islam and S. Mekhilef, "An improved transformerless grid connected photovoltaic inverter with reduced leakage current,"
Energy Conversion and Management, vol. 88, pp. 854-862, 2014.
[17] G. Bin, J. Dominic, L. Jih-Sheng, C. Chien-Liang, T. LaBella, and
C. Baifeng, "High Reliability and Efficiency Single-Phase
Transformerless Inverter for Grid-Connected Photovoltaic
Systems," IEEE Transactions on Power Electronics, vol. 28, pp.
2235-2245, 2013.
[18] M. Islam and S. Mekhilef, "High efficiency transformerless
MOSFET inverter for grid-tied photovoltaic system," in Twenty-
Ninth Annual IEEE Applied Power Electronics Conference and
Exposition (APEC) , 2014, pp. 3356-3361.
[19] S. V. Araujo, P. Zacharias, and R. Mallwitz, "Highly Efficient
Single-Phase Transformerless Inverters for Grid-Connected
Photovoltaic Systems," IEEE Transactions on Industrial
Electronics, vol. 57, pp. 3118-3128, 2010.
[20] D. Schmidt, D. Siedle, and J. Ketterer, "Inverter for transforming a
DC voltage into an AC current or an AC voltage," ed: EP Patent
1,369,985, 2009.
[21] J. Baojian, W. Jianhua, and Z. Jianfeng, "High-Efficiency Single-
Phase Transformerless PV H6 Inverter With Hybrid Modulation
Method," IEEE Transactions on Industrial Electronics, vol. 60, pp. 2104-2115, 2013.
[22] T. F. Wu, C. L. Kuo, K. H. Sun, and H. C. Hsieh, "Combined
Unipolar and Bipolar PWM for Current Distortion Improvement
During Power Compensation," IEEE Transactions onPower
Electronics, vol. 29, pp. 1702-1709, 2014.
[23] R. Bojoi, L. R. Limongi, D. Roiu, and A. Tenconi, "Enhanced
Power Quality Control Strategy for Single-Phase Inverters in
Distributed Generation Systems," IEEE Transactions on Power
Electronics, vol. 26, pp. 798-806, 2011.
[24] S. Dasgupta, S. K. Sahoo, and S. K. Panda, "Single-Phase Inverter
Control Techniques for Interfacing Renewable Energy Sources
With Microgrid-Part I: Parallel-Connected Inverter Topology With
Active and Reactive Power Flow Control Along With Grid
Current Shaping," IEEE Transactions on Power Electronics, vol.
26, pp. 717-731, 2011.
[25] Y. Yongheng, F. Blaabjerg, and W. Huai, "Low-Voltage Ride-
Through of Single-Phase Transformerless Photovoltaic Inverters,"
IEEE Transactions on Industry Applications, vol. 50, pp. 1942-
1952, 2014.
[26] Y. Yongheng, F. Blaabjerg, and Z. Zhixiang, "Benchmarking of
Grid Fault Modes in Single-Phase Grid-Connected Photovoltaic
Systems," IEEE Transactions on Industry Applications, vol. 49, pp. 2167-2176, 2013.
[27] M. Monfared and S. Golestan, "Control strategies for single-phase grid integration of small-scale renewable energy sources: A review," Renewable and Sustainable Energy Reviews, vol. 16, pp.
4982-4993, 2012.
[28] M. Ciobotaru, R. Teodorescu, and F. Blaabjerg, "Control of single-stage single-phase PV inverter," in European Conference on Power Electronics and Applications , 2005, pp. P.1-P.10.
[29] F. Blaabjerg, R. Teodorescu, M. Liserre, and A. V. Timbus,
"Overview of control and grid synchronization for distributed power generation systems," IEEE Transactions on Industrial
Electronics, vol. 53, pp. 1398-1409, 2006.
[30] W. Yong and L. Rui, "Novel High-Efficiency Three-Level
Stacked-Neutral-Point-Clamped Grid-Tied Inverter," IEEE
Transactions on Industrial Electronics, vol. 60, pp. 3766-3774,
2013.
[31] "IEEE Standard Conformance Test Procedures for Equipment
Interconnecting Distributed Resources With Electric Power
Systems," IEEE Std 1547.1-2005, pp. 0_1-54, 2005.