ETS Emergency Transfer Switch from IOTA Engineering

advertisement
ETS
3-AMP EMERGENCY LIGHTING CONTROL DEVICE
PRODUCT SPECIFICATION SHEET
TYPE:
PROJECT:
COMMENTS:
OUTPUT
Full Light Output
LOADS OPERATED
DESCRIPTION
The IOTA ETS Emergency Lighting Control Device allows local switch control of designated emergency luminaires when emergency power is provided by a generator or
inverter. The ETS senses the loss of normal AC power and bypasses the local switch
device allowing emergency power directly to the fixture regardless of switch position.
The ETS is rated for any lamp load up to 3 amps continuous power including LED
loads per NEMA 410 standards. The ETS is an ideal solution for achieving increased
energy savings in accordance with most energy efficiency standards by eliminating
the need to operate the designated emergency fixtures 24/7 when emergency power is
sourced from a generator or inverter. Dimming ballasts require one ETS for each hot lead.
Allows operation of any LED,
fluorescent, or incandescent
switched fixture from the
generator or inverter supply up
to 3 amps continuous.
PRODUCT ADVANTAGES
Regain local switch control of your
designated emergency fixtures powered
from a generator or inverter
Promotes energy savings by eliminating
the need for always-on fixtures
Full light output
SPECIFICATIONS
Input Voltage............................................................................ (Dual) 120/277V, 60Hz
Input Current................................................................................................... 250 mA
Maximum Switching Voltage............................................................. 3 Amps @ 120V
3 Amps @ 277V
Circuit Protection.......................................................................... 3A on Control Input
3A on Neutral and 120/277V Outputs
Emergency Operation.............................................. The ETS allows operation of any
lamp type in the designated fixture for
the duration of the auxiliary supply
Compatible with LED loads up to 3 amps
continuous in accordance with NEMA 410
FEATURES
Shunts local switch devices in the emergency
mode allowing for full lumen output
Rated for LED loads up to 3 amps continuous
per NEMA 410 standards
Galvanized steel case
Initial Illumination..................................................... The ETS allows operation of the
designated load at full light output
Dual Voltage 120/277V 60hz
Operating Temp ......................................................................................... 0° to 50° C
Available in flex or non-flex configuration
Weight.............................................................................................................. 1.0 lbs.
Rated for use in plenum fixtures
Approval................................................................................................ UL 924 Listed
Meets or exceeds all NEC, IBC, and Life Safety
Code Emergency Lighting Requirements
RoHS Compliant
5-Year Warranty. See Warranty Page
for details.
DIMENSIONS
8.0″ x 1.18″ x 1.125″ (mounting center 7.5″)
FLEX (ETS-R ONLY)
24”
IOTA REV 050416
IOTA ENGINEERING PO BOX 11846 TUCSON, AZ 85734
TEL: 1-800-866-IOTA (4682) FAX: (520) 741-2837 WEB: www.iotaengineering.com
EM CONTROLS / ACCESSORIES
MODEL NO:
ETS
3-AMP EMERGENCY LIGHTING CONTROL DEVICE
OPTIONS
CONFIGURATION
ETS (NO FLEX)
ETS-R (W/ 24″ FLEX)
WIRING DIAGRAMS
TYPICAL GENERATOR APPLICATION
TYPICAL BALLAST/GENERATOR APPLICATION
WHITE
NEUTRAL
BLU/WHT (NORMAL COMMON)
CONTROL
DEVICE
NORMAL
POWER
ORG (277V)
BLK (120V)
N
HOT
BLUE (NORMAL LINE)
÷
NORMAL
PANEL
EMERGENCY
PANEL
RED (EMERGENCY LINE)
HOT
RED/WHT (EMERGENCY COMMON)
NEUTRAL
G
EMERGENCY
POWER
ETS EMERGENCY
CONTROL DEVICE
YELLOW
WHT/BLK
NEUTRAL
BLK/ORG
120/277 VDC
AC DRIVER / BALLAST
RED LED
NORMAL POWER INDICATOR
(OPTIONAL)
YELLOW/WHITE
NORMAL POWER SENSE
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
ETS1_MOD_REDESIGN
TYPICAL
DIMMING
BALLAST/GENERATOR
TYPICAL
GENERATOR
APPLICATION
REV 020916
APPLICATION
WHITE
WHITE
NEUTRAL
BLU/WHT (NORMAL COMMON)
BLUE (NORMAL LINE)
YELLOW
BLUE (NORMAL LINE)
RED
3 WIRE
DIMMING
CONTROL
HOT
NORMAL
POWER
ORG (277V)
BLK (120V)
÷
ORG (277V)
BLK (120V)
N
BLK
NORMAL
PANEL
EMERGENCY
PANEL
÷
RED (EMERGENCY LINE)
HOT
RED (EMERGENCY LINE)
NEUTRAL
RED/WHT (EMERGENCY COMMON)
G
EMERGENCY
POWER
YELLOW
YELLOW/WHITE
RED LED
NORMAL POWER INDICATOR
(OPTIONAL)
ETS EMERGENCY
CONTROL DEVICE
WHT/BLK
NEUTRAL
BLK/ORG
BLACK
AC DRIVER / BALLAST
BLACK
NORMAL POWER SENSE.
SELECT PROPER VOLTAGE
LEADS. CAP UNUSED LEADS.
CONNECT THE PROPER VOLTAGE
LEADS BEFORE DIMMER CONTROL
ON THE NORMAL POWER LINE.
BLK/ORG
ETS EMERGENCY
CONTROL DEVICE
WHT/BLK
RED/WHT
YELLOW
YELLOW/WHT
BLU/WHITE
2
2
CAP UNUSED LEADS.
ETS1_MOD_REDESIGN
REV 020916
IOTA REV 050416
IOTA ENGINEERING PO BOX 11846 TUCSON, AZ 85734
TEL: 1-800-866-IOTA (4682) FAX: (520) 741-2837 WEB: www.iotaengineering.com
Download