PDF FILE - Emergency Lighting

advertisement
IOTA ENGINEERING
ETS
PRODUCT SPECIFICATION SHEET
EMERGENCY TRANSFER SWITCH FOR GENERATOR SUPPLIES
MODEL NO:
TYPE:
PROJECT:
COMMENTS:
LAMPS OPERATED
Will operate any lamp in the designated circuit
for the duration of the generator supply.
DESCRIPTION:
PRODUCT ADVANTAGES
The IOTA ETS Emergency Transfer Switch allows the use of auxiliary generator power
on a switched fluorescent fixture in power failure situations. The ETS senses the loss
of normal AC power and switches the AC ballast to the auxiliary generator supply. The
ETS will operate the lamps at full light output for as long as the generator is able, and
will work in conjunction with any lamp type and fixture on the generator circuit. Dimming
ballasts require one ETS for each hot lead.
Full Light Output
Allows Auxiliary generator power on a
switched fixture
TECHNICAL SPECIFICATIONS
Input Voltage.............................................................. (Dual) 120/277V, 60Hz
FEATURES
Input Current......................................................................................250 mA
Maximum Switching Voltage................................................ 3 Amps @ 120V
3 Amps @ 277V
UL Listed
Will cold start and operate all specified lamps
Circuit Protection........................................................... 3A on Control Input
3A on Neutral and 120/277V Outputs
Galvanized steel case
Emergency Operation................................... The ETS will operate any lamp
type in the designated fixture for
the duration of the generator supply
Available in flex or non-flex configuration
Initial Illumination................................................... The ETS will operate the
designated lamp at full light output
Weight............................................................................................... 1.0 lbs.
Approval......................................................................................... UL Listed
Dual Voltage 120/277V 60hz
Meets or exceeds all National Electrical Code
and Life Safety Code Emergency Lighting
Requirements
5-Year Warranty. See Warranty Page for
details.
CASE DIMENSIONS
8.0″ x 1.18″ x 1.125″ (mounting center 7.5″)
HEIGHT 1.125"
LENGTH 8"
MOUNTING CENTER 7.5"
WIDTH
1.18"
P.O. BOX 11846 TUCSON, AZ 85734
(520) 294-3292 • FAX (520) 741-2837
www.iotaengineering.com
IOTA REV 080709
ETS
EMERGENCY TRANSFER SWITCH
WIRING DIAGRAMS
OPTIONS
TYPICAL BALLAST/GENERATOR APPLICATION
CONFIGURATION
TYPICAL GENERATOR APPLICATION
■ ETS (NO FLEX)
ETS-R (W/ FLEX)
WHT/BLK
WHITE
BLK/ORG
BLACK
AC BALLAST
ORG (277V)
ETS
EMERGENCY
TRANSFER
SWITCH
BLK (120V)
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
�
WHITE
NEUTRAL
BLU/WHT
(NORMAL COMMON)
HOT
BLUE
(NORMAL HOT)
NORMAL
POWER
WALL
SWITCH
TRANSFER
SWITCH
NORMAL
PANEL
EMERGENCY
PANEL
HOT
RED
(GENERATOR HOT)
RED/WHT
(GENERATOR COMMON)
NEUTRAL
YELLOW
GENERATOR
POWER
RED LED
NORMAL POWER INDICATOR
(OPTIONAL)
YELLOW/WHITE
ETS1_MOD
REV 051109
TYPICAL
BALLAST/GENERATOR
DIMMING
BALLASTDIMMING
AND GENERATOR
APPLICATION
WHT/BLK
BLK/ORG
APPLICATION
WHITE
WHT/BLK
BLACK
ORANGE
ETS
EMERGENCY
TRANSFER
SWITCH
BLUE
AC BALLAST
BLK/ORG
RED
RED/WHT
YELLOW
YELLOW/WHT
WHITE
BLU/WHITE
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
ORG (277V)
BLK (120V)
ORG (277V)
BLK (120V)
ETS
EMERGENCY
TRANSFER
SWITCH
CAP UNUSED LEADS.
➀
WHITE
NEUTRAL
BLU/WHT
(NORMAL
COMMON)
YEL
BLUE
RED
(NORMAL HOT)
LUTRON
3 WIRE
DIMMER
CONTROL
HOT
TRANSFER
SWITCH
EMERGENCY
PANEL
RED
(GENERATOR HOT)
RED/WHT
(GENERATOR COMMON)
YELLOW
YELLOW/WHITE
NORMAL
POWER
BLK
NORMAL
PANEL
HOT
NEUTRAL
GENERATOR
POWER
RED LED
NORMAL POWER INDICATOR
(OPTIONAL)
ETS_2_MOD
REV 050509
IOTA REV 080709
IOTA ENGINEERING PO BOX 11846 TUCSON, AZ 85734
TEL: 1-800-866-IOTA (4682) FAX: (520) 741-2837 WEB: www.iotaengineering.com