IAQ Check List

advertisement

Building: Seth Paine Elementary School

Date: May 15, 2013

Building Inspection Performed by: Lyle Erstad

Report Compiled by: Lyle Erstad

Check List

1.

Ground Level Indoor Inspection a.

Univents are on and air discharge grills are free of obstructions.

If false, send email to building principal and facilities director asking staff to be instructed to keep vents clear at all times. Record locations here:

2.

Ground Level Outdoor Inspection (weather permitting) a.

Univent air intakes are free of obstructions.

If false, record locations here: b.

Filters i.

Medium efficiency filters are installed in all univents.

If false, list locations and create work orders to initiate corrective action.

ii.

High efficiency filters are installed in the air handling units.

If false, list locations and create work orders to initiate correction action. iii.

Filters are being changed every six months and the installed date is written on the outer filter casing.

If filter is older than 6 months, list locations and create work orders to initiate corrective action. c.

Insects, bird nests, or droppings are not evident near outdoor air intakes.

If false, indicate locations here: d.

Trash dumpsters are located away from doors, windows, and outdoor air intakes. e.

Potential sources of air contaminants do not exist near the building. (e.g. chimneys, stacks, industrial plants, exhaust from nearby buildings) f.

Trucks and buses are not allowed to keep their engines idling near the building.

IAQ Check List

IAQ Check List

True False N/A

Page 1 of 9

Revised 3/7/2011 AMJ

Created 11/2010

Building: Seth Paine Elementary School

Date: May 15, 2013

Building Inspection Performed by: Lyle Erstad

Report Compiled by: Lyle Erstad

Check List g.

No evidence of drainage problems exist. Water drains away from the building including roof downspouts. h.

Sprinklers do not spray directly toward the building or into outdoor air intakes. i.

Grass clippings from mowers are directed away from the building air intakes.

The landscaper is reminded of this.

j.

Clean walk-off mats are present at exterior entrances.

Steam cleaning will occur as a summer project.

3.

Roof (Inspections conducted weather permitting) a.

Roofing consultant has not found any issues requiring immediate repair.

Most recent roofing inspection date/company: 5-year roofing plan completed 5/25/2010 with C. E.

Crowley & Associates. b.

There is no evidence of water ponding on the roof. c.

Intake ventilation units are operating properly and free of debris. d.

All exhaust fans are operating properly and free of debris. e.

Air intake dampers are set to allow air flow even at minimum setting. f.

Insects, birds, animal nests or droppings are not evident near outdoor air intakes. g.

Plumbing stacks and exhaust vents are located away from air intakes.

4.

Attic a.

There is no evidence of roof or plumbing leaks.

No Attic

Page 2 of 9

IAQ Check List

IAQ Check List

True False N/A

Revised 3/7/2011 AMJ

Created 11/2010

Building: Seth Paine Elementary School

Date: May 15, 2013

Building Inspection Performed by: Lyle Erstad

Report Compiled by: Lyle Erstad

Check List b.

There is no evidence in attic of insects, birds, animals, or nests.

No Attic

5.

General Considerations a.

Classrooms, offices and/or common areas appear recently cleaned.

If examples of poor housekeeping are found, record locations below: b.

Only vacuums with HEPA filters are being used. c.

All supply and exhaust ventilation units are working properly. d.

Occupied space temperatures and relative humidity levels are within the standards listed below. i.

Temperature range:

Winter temperatures 70-73 degrees.

 Summer temperatures 74-80 in air-conditioned spaces and 74-85 in non-air-conditioned spaces.

Outdoor air temperature: 58.1; 55.5; 72.2; 91 degrees.

Highest temperature – Location: 108; 209; 104;104 ; Reading of 75.1; 74.3; 81.8; 86.3 degrees.

Lowest temperature – Location: 110/Gym; 200; 305 ; Reading of 69.6; 67.3; 75.3 degrees. ii.

Relative humidity range is 30% to 60%.

 Non-air-conditioned spaces may be higher on rainy or humid summer humid days.

 All spaces may be less than 30% when the out-door air temperature is less than 32 degrees.

Outdoor relative humidity: 44.2; 51.5; 47.5; 27; %

Highest relative humidity – Location: Gym; 200; 305; 104; ; Reading of 41.4; 51.9; 45.4; 35.2

%

Lowest relative humidity – Location: LL2; 210; 104 ;Reading of 34.8; 40.1; 36; %

Readings not within acceptable standards will result in the creation of a work order, requesting maintenance to address. (Readings are noted on the attached test data sheet)

Page 3 of 9

IAQ Check List

IAQ Check List

True False N/A

Revised 3/7/2011 AMJ

Created 11/2010

Building: Seth Paine Elementary School

Date: May 15, 2013

Building Inspection Performed by: Lyle Erstad

Report Compiled by: Lyle Erstad

Check List e.

Occupied space readings of carbon monoxide (CO) levels are less than 9.0 PPM.

Outdoor Air CO Reading: 0

Highest CO Location: 0 Reading: All Rooms

Lowest CO Location: Reading:

If the CO level is greater than 9.0 PPM in any space as measured with a handheld device or “leave-in” monitor, the space must be cleared of all occupants and steps taken to correct the problem. The issue will be immediately addressed by maintenance and the Fire Department. (Readings are noted on the attached test data sheet) f.

CO2 levels in any occupied space are below threshold limits. i.

Perform CO2 check with Gray Wolf or other portable device. Measure four times yearly or more often if needed. Measure only in fully occupied rooms. Reading should be less than 700 PPM plus outside air CO2 PPM.

700 PPM + 365; 355; 330; 384 PPM = 1065; 1055; 1050; 1084 PPM

Assume outside CO2 is 350 if temperature is below 41 degrees and air is not stagnant with no- wind.

Record all occupied space CO2 levels on forms provided. Provide the outdoor CO2 level as well as the high and low CO2 extremes below:

Outdoor reading: 365; 355; 330; 384 PPM

Highest CO2 reading – Location: 204; 305; 104; 104 ; Reading of 1015; 1354;1172; 922

PPM

Lowest CO2 reading – Location: Gym; 200; 309W ; Reading of 521; 696; 878 PPM ii.

If reading is above threshold, check univent and air handling dampers to ensure a value is set to provide at least 15 cfm of fresh air intake per student based on average space occupancies. If reading is consistently elevated, then use data logging to monitor CO2 concentrations over time and look for other sources of problems.

Page 4 of 9

IAQ Check List

IAQ Check List

True False N/A

Revised 3/7/2011 AMJ

Created 11/2010

Building: Seth Paine Elementary School

Date: May 15, 2013

Building Inspection Performed by: Lyle Erstad

Report Compiled by: Lyle Erstad

Check List

Work orders were written to address adequate outside air.

iii.

CO2 levels were checked three months ago. iv.

CO2 levels on “leave-in” devices, where present, where checked.

No leave-in devices g.

Offensive odors are not apparent.

If false, list problem areas: h.

Water damage is not evident.

Check for roof leaks, pipe leaks, spills, stained ceiling tiles, etc, visually and with moisture meter. Look for the source of any water leaks and schedule repairs. Discard porous items such as ceiling tiles if wet for more than 24 hours. For carpeting, if less than 9 square feet of wet area, shampoo with germicide and fan dry. For areas greater than 9 square feet, replace carpet with tile in reasonable timeframe. If carpet is over ACM tile, replace during next unoccupied break time (winter break, spring break, summer).

If false, record findings and locations here: i.

Mold or mildew growth is not evident.

If false, record findings and locations here: j.

All pest management issues are being handled by Integrated Pest Management. k.

No other unresolved concerns or complaints by building personnel are known.

If false, list any pending issues not previously mentioned in this report here: l.

There are no incomplete HVAC preventative maintenance (PM) work requests.

If false, list any incomplete HVAC work request here:

6.

Bathrooms and General Plumbing a.

All locker or restroom exhaust fans are working.

Inoperable or malfunctioning fans are listed as follows:

Location: Problem:

Page 5 of 9

IAQ Check List

IAQ Check List

True False N/A

Revised 3/7/2011 AMJ

Created 11/2010

Building: Seth Paine Elementary School

Date: May 15, 2013

Building Inspection Performed by: Lyle Erstad

Report Compiled by: Lyle Erstad

Check List b.

All of the following drain-trap maintenance procedures are being conducted according to the frequency indicated.

If false, indicate all deviations and locations: i.

Water is poured into floor drains once per week (approximately 1 quart of water) or water and a teaspoon of cooking oil poured into the drain once a month.

The Custodial staff is reminded of this regularly.

ii.

Water is poured into sinks at least once per week (about 2 cups of water). iii.

Toilets are flushed at least once per week.

7.

Lab Chemicals & Maintenance Supplies a.

Lab chemicals are used with exhaust fans turned on. b.

Lab chemical storage areas have been inspected yearly by ROE and Fire Department.

Record last inspection dates below:

ROE: 9/2012

LZFD: 9/2012 c.

Flammables are not stored with igniters. d.

All chemicals that may react or produce toxic or explosive by-products are separated and maintained in approved containers stored in approved storage. (e.g. lockable, with appropriate ventilation). e.

Chemical disposal records for all lab chemicals are available for review. f.

All cleaning products used in building contain no/low VOC.

Page 6 of 9

IAQ Check List

IAQ Check List

True False N/A

Revised 3/7/2011 AMJ

Created 11/2010

Building: Seth Paine Elementary School

Date: May 15, 2013

Building Inspection Performed by: Lyle Erstad

Report Compiled by: Lyle Erstad

Check List

List any exceptions: g.

Increased ventilation is considered when installing new carpets, cleaning upholstered furniture, shampooing carpets, etc. h.

Exhaust ventilation systems in chemical and trash storage areas are turned on and functioning properly. i.

Portable fuel containers are properly closed. j.

Power equipment, like snow blowers and lawn mowers, have been serviced and maintained according to manufacturers’ guidelines. k.

Oil based paints are stored in approved storage cabinets.

No oil based paint allowed in District.

l.

Green Cleaning products and processes are used in this building.

8.

Combustion Appliances a.

Combustion analysis is performed at the start of the heating season on all boilers. Adjustments are made to the burners to correct any abnormalities and improve efficiency.

Barr Mechanical performed combustion analysis on 1-9-13.

b.

In rooms that contain combustion appliances, there is no evidence of combustion gas or fuel odors.

If false, record locations here: c.

No leaks, disconnections, and/or deterioration were found on exhaust hoods. d.

Flue components are clean and free of soot. e.

All combustion appliances have flues or exhaust hoods and vent NO2. i.

If false, inspect cooking hoods, chemical hoods. Assure that cooking stoves and appliances are correctly installed, used, and maintained according to manufacturers’ specifications.

Page 7 of 9

IAQ Check List

IAQ Check List

True False N/A

Revised 3/7/2011 AMJ

Created 11/2010

Building: Seth Paine Elementary School

Date: May 15, 2013

Building Inspection Performed by: Lyle Erstad

Report Compiled by: Lyle Erstad

Check List ii.

If not vented, ensure that “leave-in” CO monitors are placed in room. Record locations here: NONE

IAQ Check List

IAQ Check List

True False N/A iii.

CO levels in rooms with combustion appliances are measured and recorded with an IAQ monitor. CO readings outside of normal CO range will result in an immediate response by maintenance to reduce

CO level or vacating the room/building, if necessary.

Record locations here:

9.

Other a.

Paint

No peeling and/or flaking paint found.

If planned building renovation will damage paint or if peeling paint is discovered, lead testing may be necessary. If peeling paint is found, send email to the building Principal and the Facilities Director alerting them of the problem. Staff and teachers need to pick up any flakes of paint to prevent children from being exposed. The Facilities Director will advise the Facilities Coordinator (a Certified

Lead Paint Renovator) to test the paint for lead. Lead paint was discontinued in 1978. Buildings built after 1978 are exempt from lead paint testing.

If lead is present, required repairs should be done immediately using lead-safe methods and, if necessary, a licensed lead contractor.

Location(s) of known peeling paint in building: b.

The following preventive measures are being taken to reduce lead exposure. i.

Play areas and toys are cleaned nightly. ii.

Floors are mopped nightly. iii.

Dust at least weekly. c.

Radon testing is recommended by IEMA every 5 years. Last testing date listed below:

Date: 12/16/2011 - 12/19/2011 ; Reading of (Highest) 1.0 pCi/L in Room 104.

National concern level: 4.0 pCi/L or above

Page 8 of 9

Revised 3/7/2011 AMJ

Created 11/2010

Building: Seth Paine Elementary School

Date: May 15, 2013

Building Inspection Performed by: Lyle Erstad

Report Compiled by: Lyle Erstad

Check List d.

The IAQ testing equipment used for this inspection was calibrated and is in good working order.

Equipment Used: Gray Wolf Last date of calibration: 1/8/13

IAQ Check List

IAQ Check List

True False N/A

Page 9 of 9

Revised 3/7/2011 AMJ

Created 11/2010

Site

Seth Paine

Seth Paine

Seth Paine

Seth Paine

Seth Paine

Seth Paine

Seth Paine

Seth Paine

Seth Paine

Location Date/Time

Outdoor Air 5/2/2013 10:52:01 AM

101 5/2/2013 12:07:36 PM

102 5/2/2013 11:30:08 AM

103 5/2/2013 12:05:44 PM

105 5/2/2013 12:03:32 PM

106 5/2/2013 11:27:29 AM

107 5/2/2013 12:00:10 PM

108 5/2/2013 12:11:10 PM

110 5/2/2013 10:58:42 AM

Seth Paine

Seth Paine

Seth Paine

Seth Paine

Seth Paine

Seth Paine

111 5/2/2013 11:00:49 AM

112 5/2/2013 11:02:56 AM

113 5/2/2013 11:04:56 AM

203 5/2/2013 11:36:53 AM

204 5/2/2013 11:38:39 AM

205 5/2/2013 11:40:13 AM

Seth Paine

Seth Paine

Seth Paine

207 5/2/2013 11:42:12 AM

306 5/2/2013 11:44:46 AM

307 5/2/2013 11:46:38 AM

Seth Paine

Seth Paine

308 5/2/2013 11:48:13 AM

310 5/2/2013 11:49:50 AM

Seth Paine

Seth Paine

Cafeteria 5/2/2013 11:53:28 AM

Faculty lounge 5/2/2013 11:09:44 AM

Seth Paine Gymnasium 5/2/2013 10:57:18 AM

Seth Paine Health Office Nurse 5/2/2013 11:07:20 AM

Seth Paine

Seth Paine

Seth Paine

LL2

Main office 100

Principal 100B

5/2/2013 11:56:23 AM

5/2/2013 11:06:18 AM

5/2/2013 11:16:58 AM

CO2 Formula: 700 + 365 = 1065

Seth Paine Spring 2013 IAQ Data

73.9

73.8

74.1

73.8

74.1

73.1

71

69.6

71.8

73.4

72

70.8

70.3

72.4

72.7

72.7

73.3

73.3

°F

58.1

74.8

72

74.8

74.4

71.7

73.9

75.1

69.6

%RH CO ppm CO2 ppm Occupant Window

44.2

0 365

38.2

39.4

38.7

38.1

0

0

0

0

848

774

932

819

19

14

19

18

Y

Y

39.9

38.3

38.9

41.3

0

0

0

0

873

863

850

621

19

18

17

19

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

38.5

36.2

37

35.9

35.1

35.5

40.3

41.4

40.8

34.8

40.1

37.2

38.9

40

40.1

39.4

39.9

38.8

666

745

833

900

1015

832

846

853

841

725

688

584

712

521

860

588

774

753

Y

Y

Y

Y

Y

20

9

3

2

1

55

2

17

1

6

29

22

18

18

21

19

20

19

Note

Site

Seth Paine

Seth Paine

Seth Paine

Seth Paine

Seth Paine

Seth Paine

Seth Paine

Seth Paine

Seth Paine

Seth Paine

Seth Paine

Seth Paine

Seth Paine

Seth Paine

CO2 Formula: 700 + 355 = 1055

Location Date/Time

Outdoor Air 5/3/2013 1:33:04 PM

104

200

5/3/2013 2:18:39 PM

5/3/2013 1:48:58 PM

201

202

208

209

5/3/2013 2:15:40 PM

5/3/2013 2:26:11 PM

5/3/2013 1:53:11 PM

5/3/2013 2:52:07 PM

210

211

301

305

309

309E

309W

5/3/2013 2:48:19 PM

5/3/2013 2:49:29 PM

5/3/2013 1:56:29 PM

5/3/2013 2:00:20 PM

5/3/2013 2:05:22 PM

5/3/2013 2:11:47 PM

5/3/2013 2:09:55 PM

Site

Seth Paine

Seth Paine

Seth Paine

Seth Paine

Seth Paine

Location Date/Time

Outdoor Air 5/14/2013 11:15:04 AM

305 5/14/2013 11:19:53 AM

309E 5/14/2013 11:16:31 AM

309W 5/14/2013 11:17:38 AM

104 5/14/2013 2:07:12 PM

CO2 formula: 700 + 350 = 1050

Site

Seth Paine

Seth Paine

Location

Outdoor Air

CO2 Formula: 700 + 384 = 1084

Date/Time

5/16/2013 2:44:44 PM

104 5/16/2013 2:47:42 PM

°F

55.5

72.1

67.3

71.4

74.3

68.1

74.3

73.9

74

68.8

70.5

71.2

71.3

71

%RH CO ppm CO2 ppm Occupant Window

51.5

0 355

45.9

51.9

0

0

1269

696

16

21

43.7

43.6

50.2

41.5

40.1

40.3

47.9

51

44.3

42.2

42.7

0

0

0

0

0

0

0

0

0

0

0

886

1042

782

907

867

869

746

1354

1047

1092

1082

5

21

7

17

19

21

3

21

5

1

2

Note

°F

77.2

75.3

76.7

75.8

81.8

%RH CO ppm CO2 ppm Occupant Window

47.5

0 330

45.4

40.1

0

0

899

915

19

3

Y

39.6

36

0

0

878

1172

3

18

Note

°F

91

86.3

%RH CO ppm CO2 ppm Occupant Window

27 0 384

35.2

0 922 18 Y

Note

Download