COOPER LIGHTING - LUMARK ® DESCRIPTION The LumaWatt controller accepts inputs from up to four remote-mounted motion detectors and provides a 24 volt DC low-voltage output capable of controlling up to 25 fixtures. It switches connected fixtures from low intensity to high, providing maximum light when an area is occupied and lowered energy usage when the area is empty. U.L. listed and CSA certified. Use in conjunction with LumaWatt-equipped Lumark indoor industrial fixtures. Type Catalog # Project Date Comments Prepared by SPECIFICATION FEATURES A ... 24 Volt DC Output Low voltage output controls up to 25 LumaWatt-equipped fixtures. D ... Remote Switch Input Input terminal allows use of user-supplied dry-contact switch. Switch overrides motion sensors, putting system into high brightness mode. In absence of motion detectors, switch provides manual high-low control. Consult Technical Services for 1000W applications. B ... Control #2 Output Allow daisy-chaining of multiple controllers. C ... Motion Detector Inputs Terminal block provides input connections for one to six passive infrared motion sensors. A B E ... Transformer Standard transformer accepts 120V or 277V user-configurable input. 208V, 240V, 347V and 480V are also available. F ... LED Indicator Lights Three front panel lights show system status: amber indicates that the controller is receiving power, red indicates that output from the controller is at full brightness and green indicates that output is at low brightness. G ... Bi-Level Function Switch Front panel switch provides same function as remote dry-contact switch. H ... Initializing Timer CMOS timer maintains system in full brightness mode for a 15 minute warm-up period when power is applied. D C CML INDUSTRIAL HID DIMMING SYSTEM Controls all LumaWatt Equipped Lumark HID Industrial Luminaires E CONTROL MODULE Output – 2 + Control #2 – 2 + Aux. Controller + + Aux. Controller + + Dry Contact – 2 + T E C H N I C A L D AT A 55 Degree C Maximum Ambient E N E R G Y D AT A G CWA Ballast High/Low Input Watts 150W HPS HPF (196/118 Watts) 250W HPS HPF (300/151 Watts) 2 13/32" [61mm] 4 5/8" [117mm] 3 3/4" [95mm] 8 23/32" [221mm] 400W HPS HPF (465/215 Watts) 1000W HPS HPF (1100/616 Watts) 175W MH HPF (210/101 Watts) 250W MH HPF (295/162 Watts) 400W MH HPF (455/238 Watts) 1000W MH HPF (1080/666 Watts) Consult your representative for additional options and finishes. T EM S Specifications and Dimensions subject to change without notice. YS ER C 7 15/16" [202mm] 8 7/8" [225mm] D F S DIMENSIONS TIFIE ADH041467 06/25/2007 2:59:57 PM SYSTEM CONFIGURATION CML LUMAWATT CONTROLLER Output #2 #1 # 25 Maximum Control #2 RED Detector Input BLACK BLUE RED Detector Input BLACK BLUE Dry Contact Wiring Chart Maximum distance between LumaWatt Control Module and the first luminaire, based upon total number of fixtures controlled. Number of Fixtures #16 AWG #18AWG 1 7500 4700 2 3700 2300 3 2500 1600 4 1900 1200 5 1500 900 6 1200 800 7 1100 700 8 900 600 9 800 500 10 700 500 11 700 400 12-13 600 400 14-16 500 300 17-18 400 300 19-21 400 200 22-25 300 200 Master Controller Optional Motion Detector Modules (Maximum 6 ) LumaWatt Lamp Input Watts Wattage High (HW) Low Change (PC) Metal Halide Output Control #2 1000W 1080 666 38% 400W 455 238 48% 250W 295 162 45% 175W 209 101 52% 44% High Pr essure Sodium Detector Input Detector Input #2 #1 1000W 1100 616 400W 465 215 54% 250W 300 151 50% 150W 196 118 40% # 25 Maximum Dry Contact Additional Control Module(s) (required to control subsequent groups of fixtures up to 25 each) Auxiliary Controller HL FIXTURE MODULE ORDERING INFORMATION Sample Number: CML-120/277 Product Family 1, 2 CML=LumaWatt Control Module Input Voltage 3 120/277=User selectable 120V or 277V input voltage 208V=208V 240V=240V 347V=347V 480V=480V Notes: 1 System utilizes a 30 second time delay in switching between power levels. 2 See separate cutsheet for full details on control module. 3 Products also available in non-US voltages and 50HZ for international markets. Consult factory for availabiltiy and ordering information. OTHER LUMAWATT COMPONENTS Fixture Module (add as suffix to any Lumark indoor industrial fixtures) HL=Allows low voltage control wire to be daisey-chained between fixtures outside AC conduit run similar to low voltage intercoms, fire alarms and phone systems. HC=Low voltage leads pulled out of top connection box for areas requiring all wiring to be installed in conduit. Motion Detectors (order separately) IRMD-N-24V=Passive infrared motion detector with narrow coverage pattern 3 IRMD-W-24V=Passive infrared motion detector with wide coverage pattern 3 IRMD-A-24V=Passive infrared motion detector for aisleway coverage 3 Specifications and Dimensions subject to change without notice. Lumark • Customer First Center • 1121 Highway 74 South • Peachtree City, GA 30269 • TEL 770.486.4800 • FAX 770.486.4801 ADH041467 06/25/2007 2:59:57 PM