Catalog # Type

advertisement
Lumark
DESCRIPTION
The Vertimark II delivers horizontal and vertical footcandles to evenly
illuminate parking garage areas. The combination die-cast
reflector/ballast housing makes Vertimark II economical. Modular
assembly makes installation easy and quality construction ensures years
of consistent performance. U.L. listed and labeled for damp location. CSA
Certified. Durable construction and dependable performance make the
Vertimark II perfect for parking garages. Optional U.L. wet location listing
available.
Catalog #
Type
Project
Comments
Date
Prepared by
S P E C I F I C AT I O N F E AT U R E S
Construction
Optical
Mounting
HOUSING: Die-cast aluminum
housing has durable white
polyester powder coat finish.
REFRACTOR HINGE: Hinged
refractor permits relamping
without removal of refractor.
BALLAST COMPARTMENT:
Removable ballast compartment
cover provides easy internal
access.
REFLECTOR: Acrylic prismatic
refractor controls light for high
vertical and horizontal footcandles.
PENDANT MOUNTING: Standard
quick mounting plate for 3/4" IPS
conduit frees both hands to
complete wiring. OPTIONAL J-BOX
MOUNTING: Factory-installed
mounting bracket fits a standard 4"
J-Box for outlet box or surface
mounting.
BE
VERTIMARK II
100 - 250W
High Pressure Sodium
Pulse Start Metal Halide
Metal Halide
ALUMINUM LOW-BAY
DIMENSIONS
Surface
12 1/2”
[318mm]
Pendant
13 1/4”
[337mm]
T E C H N I C A L D ATA
EISA Compliant G
90°C Supply Wire Rating
17”
[432mm]
O P T I O N A L J - B OX
STA N DA R D E Z 1 2 3 M O U N T I N G
E N E R G Y D ATA
Reactor Ballast Input Watts
70W HPS NPF/HPF (82 Watts)
100W HPS HPF (118 Watts)
150W HPS HPF (175 Watts)
High-Reactance Ballast Input Watts
100W HPS HPF (130 Watts)
150W HPS HPF (190 Watts)
CWA Ballast Input Watts
175W MP HPF (198 Watts) G
200W MP HPF (227 Watts) G
250W MP HPF (283 Watts) G
3/4"
[19mm]
S H I P P I N G D ATA
Approximate Net Weight:
17 lbs. (8 kgs.)
r eadily accepts the mating
5 1/8”
[130mm]
C
2 9/16”
[654mm]
YS
ER
TEM
S
fixture is easily attached.
S
half of the hinge and the
D
Once in place, the EZ123
TIFIE
ADH082540
2015-12-02 10:01:56
BE VERTIMARK II
P H OTO M E T R I C S
90°
5
10
15
60°
20
25
30
35
40
45
50
CP/100
H P B E - 5 A - 1 5 0 H - 1 2 0 V- L L
150-Watt HPS
16,000-Lumen Clear Lamp
30°
Coefficients Of Utilization
Effective floor cavity reflectance = 20%
rc
80%
70%
rw
50 30 10
50 30
RCR
1
88 83 79
85 80
2
76 69 63
73 66
3
66 58 51
63 56
4
57 48 41
55 47
5
50 41 34
48 39
6
44 35 28
42 34
7
38 30 23
37 29
8
34 25 20
33 25
9
31 22 17
29 22
10
29 19 14
26 18
Spacing Criterion
1.6
Zone
%Lamp
Zone
0-30
11.67
0-90
0-40
19.95
90-180
0-60
53.54
Total
Eaton
1121 Highway 74 South
Peachtree City, GA 30269
P: 770-486-4800
www.eaton.com/lighting
Specifications and
dimensions subject to
change without notice.
10
50%
50 30 10
30%
50 30 10
10%
50 30 10
0%
0
76
61
50
40
33
28
23
19
16
13
78
67
58
51
47
39
324
30
27
24
72
62
54
47
41
36
31
28
25
22
66
57
50
43
37
33
29
25
23
20
58
47
39
31
26
21
17
14
12
9
74
62
52
44
37
32
27
23
20
17
71
57
47
38
31
26
22
18
16
13
69
58
49
41
35
30
25
22
19
16
66
54
44
36
30
25
20
17
15
12
64
54
45
38
32
28
23
20
18
15
62
50
42
34
28
23
19
16
14
11
Candlepower
Degree CP
0
2113
5
1888
15
1748
25
35
45
55
65
75
2308
2003
2329
3855
1964
1020
85
90
845
787
%Lamp
77.41
14.83
92.23
ADH082540
2015-12-02 10:01:56
BE VERTIMARK II
ORDERING INFORMATION
Sample Number: HPBE-5A-100H-MT-LL
Lamp Type
MP=Pulse Start Metal 1
Halide
MH=Metal Halide1, 2
HP=High Pressure 3, 4
Sodium
Options 11
C3=3' Cord with no plug (Specify Voltage)12, 13
__=Normal Power
Factor
PC3=3' Cord with NEMA Plug (120V-L5-15P,
208V-L6-15P, 347V-L37-20P, AND
480V-L8-20P) Other cord lengths are
available by specifying length (PC6 for 6'
Cord) Requires FH-1 or FL-1, or SHK.
Example: PC3-120V Use with
TPPH-NEMA. Specify Voltage.
Voltage 6
120V=120V
Series
BE=Vertimark II
208V=208V
240V=240V
PHC-NEMA=Power Cord and NEMA Plug (18"
Power Cord and 20 AMP NEMA plug
configuration). Must be used with FL-1
and TPPH-NEMA (Thru-Way Pendant
Power Hook).
480V=480V7
MT=Multi-Tap, wired8
277V
5A=Type V Lens
5
2P=Type II
Polycarbonate
Lens
TT=Triple-Tap, wired 9
347V
5
FH-1=Die-cast Aluminum Fixture Hook (with 3/4"
threads for easy installation)
Lamp Included
LL=Lamp Included
Lamp Wattage
FL-1=Malleable Iron Plated Fixture Loop (with 3/4"
threads for easy installation)
__=Lamp Not Included
SHK=Die-cast Aluminum Fixture Hook (with safety
screw and 3/4" threads for easy installation)
Socket
10
OR=Open Rated
Socket for Metal
Halide Lamps
F1=Single Fuse (120, 277 or 347V only)
F2=Double Fuse (208, 240 or 480V only)
MP
100=100W
175=175W
200=200W
250=250W
MH
SCF=3' Aircraft Safety Cable secures Housing to 12
Ceiling (Alternative lengths available.
Example: SCF6 = 6' Cable)
__=Non Applicable
(HPS or Not
compatible with OR
Socket)
1, 2
175=175W
250=250W
Q=Quartz Restrike (Hot Strike Only)15
EM=Quartz Restrike with ''Delay Relay'' (Quartz 15
lamp strikes at both hot and cold starts)
HP
EM/SC=Emergency Separate Circuit15
100=100W
150=150W
Notes: 1
12, 13
PHC=Power Cord and Plug (18" Power Cord and 14
Non-NEMA plug configuration. Must be used
with FL-1 and TPPH (Thru-Way Pendant
Power Hook). Must specify single voltage.
277V=277V
347V=347V
Lens Type
2A=Type II Lens
5P=Type V
Polycarbonate
Lens
Ballast
H=High Power Factor
L/TCB=Less Top Connector Box (Housing shipped
less top connector box. (Specify when using
TWMBS accessory)
Open Rated socket and lamp must be used.
2
MH available in non-U.S. markets only.
3
150W maximum.
4
Not available in 175, 200, 320 and 350W.
5
Not recommended for use with Metal Halide lamps due to rapid yellowing typical of
polycarbonate material.
6
Products also available in non-US voltages and 50HZ for international markets. Consult
your Cooper Representative for availabiltiy and ordering information. 88% Efficient
EISA Compliant MP Fixtures not available in 347V and TT Voltages.
7
Not available with 200W or 250W Pulse Start Metal Halide.
8
Multi-Tap ballast 120/208/240/277V wired 277V.
9
Triple-Tap ballast 120/277/347V wired 347V.
10
Not applicable for HPS.
11
Must be listed in the order shown and separated by a dash.
12
Other lengths are available.
13
Requires FH-1or FL-1or SHK.
14
Requires FL-1 and TPPH.
15
Quartz lamp wattage is 100W maximum.
16
Not available with PC3, C3, PHC or MWS. Not available with single circuit MWS
special order.
17
Fixtures must be same wattage and voltage and without hooks, loops or plugs.
18
Requires FL-1 and PHC.
19
Requires FL-1 and PHC-XXXV-NEMA.
Accessories
C3=3' Cord-No Plug - Requires FH-1, FL-1, or SHK12, 13
12, 13
PC3=3' Cord with NEMA Plug - (120V-L5,
208V-L6-15P, 347V-L37-20P and
480V-L8-20P) Other cord lengths are
available by specifying length (PC6 for 6'
cord). Requires FH-1 or FL-1, or SHK. Use
14
PHC=Power Hook Cord and Non-NEMA plug
configuration. Must be used with FL-1 and TPPH
(Thru-Way Pendant Power Hook)
PHC-NEMA=Power Cord and NEMA plug - 18" Power
Cord and 20 Amp NEMA plug configuration.
Must be used with FL-1 and TPPH-NEMA
(Thru-Way Pendant Power Hook)
MBT=Twin Mount Bracket (Fixtures must be same17
voltage and without hooks, loops or plugs.)
TPPH=Thru-Way Pendant Power Hook. Requires FL-1 18
and PHC. Specify Voltage.
TPPH-F=Thru-Way Pendant Power Hook Single Fuse, 18
120, 277 or 347 Volt. Requires FL-1 and PHC.
Specify Voltage.
TPPH-F2=Thru-Way Pendant Power Hook - Double 18
Fused, 208, 240, or 480 Volt. Requires FL-1
and PHC. Specify Voltage.
TPPH-F-QD=Thru-Way Pendant Power Hook Single 18
Fuse, Quick Disconnect. Requires FL-1
and PHC. Specify Voltage (120, 277, or
347V)
TPPH-F2-QD=Thru-Way Pendant Power Hook Double 18
Fuse, Quick Disconnect. Requires FL-1
and PHC. Specify Voltage (208, 240, or
480V)
19
TPPH-NEMA=Thru-Way Pendant Power Hook.
Requires FL-1 and PHC-XXXV-NEMA.
(Specify Voltage).
FH-1=Fixture Hook
FL-1=Fixture Loop
SHK=Hook with Safety Screw
IA1025=Bracket for Surface Mounting to 4'' J-Box
P=Mounting Bracket for Surface or 4'' J-Box
W/MWS=MWS Industrial components attached to
the fixture at the factory. (Standard cord
length is 3 ft. 6 ft. and 11 ft. also available.
Please refer to MWS Modular Wiring
System section for additional information.
16
HC=LumaWatt Fixture Control Module (Low
voltage leads pulled out of top connection box
for areas requiring all wiring to be installed in
conduit)
HL=LumaWatt Fixture Control Module (Allows low
voltage control wire to be daisy-chained between
fixtures outside AC conduit run similar to low
voltage intercom's, fire alarms and phone
systems)
WLB=UL Labeled for Wet Locations with Die-Cast
Box for 3/4'' Conduit
LAMP TYPE
WATTAGE
Pulse Start Metal Halide (MP)
100, 175, 200, 250W
Metal Halide (MH)
175, 250W
High Pressure Sodium (HPS)
100, 150W
WLD=UL Labeled for Wet Locations with Quick
Disconnect
WLP=UL Labeled for Wet Locations Suitable for
Surface or 4'' J-Box Mounting
VOLTAGE CHART
MT=Multi-Tap
120/208/240/277 (wired 277V)
TT=Triple-Tap
120/277/347 (wired 347V)
Eaton
1121 Highway 74 South
Peachtree City, GA 30269
P: 770-486-4800
www.eaton.com/lighting
Specifications and
dimensions subject to
change without notice.
ADH082540
2015-12-02 10:01:56
Download