SURE-LITES FBP-2-40 HU INSTALLATION INSTRUCTIONS - Universal Input ! IMPORTANT SAFEGUARDS ! WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS BE FOLLOWED, INCLUDING THE FOLLOWING: READ AND FOLLOW ALL SAFETY INSTRUCTIONS 1. To prevent high voltage from being present on red & yellow output leads prior to installation, inverter connector must be open. Do not join inverter connector until installation is complete and AC power is supplied to the emergency ballast. 2. This product is for use with most 2' through 8' (17 W - 215 W) single pin or bipin fluorescent lamps, including standard, energy saving, HO, VHO, circline, U-shaped and rapid-start (4-pin) long compact fluorescent lamps. 3. Make sure all connections are in accordance with the National Electrical Code and any local regulations. 4. To reduce the risk of electric shock, disconnect both normal and emergency power supplies and inverter connector of the emergency ballast before servicing. 5. This emergency ballast is for factory or field installation in either the ballast channel or on top of the fixture. 6. This product is suitable for damp locations where the ambient temperature is 0°C minimum, +50°C maximum. Product is also suitable for installation in sealed and gasketed fixtures. Product is not suitable for heated air outlets and wet or hazardous locations. 7. An unswitched AC power source is required (120 through 277 VAC, 50/60 Hz). 8. Do not install near gas or electric heaters. 9. Do not attempt to service the battery. A sealed, no-maintenance battery is used that is not field replaceable. Contact the manufacturer for information on service. 10. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition. 11. Do not use this product for other than intended use. 12. Servicing should be performed by qualified service personnel. SAVE THESE INSTRUCTIONS CONTAINS NICKEL-CADMIUM RECHARGEABLE BATTERY. MUST BE RECYCLED OR DISPOSED OF PROPERLY. Ni - Cd 02/21/12 Lighting COOPER Sure-Lites • Customer First Center • 1121 Highway 74 South • Peachtree City, GA 30269 • 770-486-4800 • Fax 770-486-4801 75000048P 443529060611 INSTALLATION WARNING: TO PREVENT HIGH VOLTAGE from being present on red and yellow output leads prior to installation, inverter connector must be open. do not join inverter connector until installation is complete and ac power is supplied to the emergency ballast. NOTE: Make sure the necessary branch circuit wiring is available. An unswitched source of power is required. The emergency ballast must be fed from the same branch circuit as the AC ballast. 1. Disconnect AC power from the fixture. Remove the ballast channel cover and install the emergency ballast either in the ballast channel (see Illustrations 1 & 2) or on top of the fixture* (see Illustration 3). 2. Select the appropriate wiring diagram to connect the emergency ballast to the AC ballast and lamp. Make sure all connections are in accordance with the National Electrical Code and any local regulations. ILLUSTRATION 1 ILLUSTRATION 2 ILLUSTRATION 3 *For installation on top of the fixture, wire bundle covers may be required by state or local codes. These covers are available from the manufacturer as an accessory kit and must be ordered separately. Call your local distributor or the factory for complete infomation. 3. Install the test switch through the ballast channel cover of a troffer or through the side of a strip fixture. Drill a 1/2" hole and install the switch as shown (see Illustration 1 & 2). Refer to the wiring diagrams section and wire the test switch so it removes AC power from the unswitched hot line to the emergency ballast. 4. Refer to Illustration 4 and install the charging indicator light so that it will be visible after the fixture is installed. NOTE: After installing the charging indicator light and test switch, mark each with the appropriate label. If a detached charging indicator light is used, connect by matching wire colors and install as shown in Illustration 4. 5. In a readily visible location, attach the label “CAUTION–This Unit Has More Than One Power Connection Point. To Reduce The Risk Of Electric Shock, Disconnect Both The Branch Circuit-Breakers Or Fuses And Emergency Power Supplies Before Servicing.” 2 ILLUSTRATION 4 troffer style fixture strip style fixture Fixture Fixture Charging Indicator Light Charging Indicator Light Violet (+) Violet (+) Brown (–) 5/8" Black Bushing 1/2" White Bushing Brown (–) 1/2" White Bushing 5/8" Black Bushing 1/2" Punch NOTE: After installing the charging indicator light and test switch, mark each with the appropriate label. 6. After installation is complete, supply AC power to the emergency ballast and join the inverter connector. 7. A short-term discharge test may be conducted after the emergency ballast has been charging for one hour. Charge for 24 hours before conducting a long-term discharge test. Refer to OPERATION. OPERATION When AC power is applied, the charging indicator light is illuminated, indicating the battery is being charged. When power fails, the emergency ballast automatically switches to emergency power, operating one or two lamps at reduced illumination. When AC power is restored, the emergency ballast returns to the charging mode and delays AC ballast operation for approximately three seconds to prevent false-tripping of AC ballast (end-of-lamp-life) shutdown circuits. This emergency ballast will operate the rated lamp load for a minimum of 90 minutes. MAINTENANCE Although no routine maintenance is required to keep the emergency ballast functional, it should be checked periodically to ensure that it is working. The following schedule is recommended: 1. Visually inspect the charging indicator light monthly. It should be illuminated. 2. Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds. Either one or two lamps should operate at reduced illumination. 3. Conduct a 90-minute discharge test once a year. Either one or two lamps should operate at reduced illumination for at least 90 minutes. Refer any servicing indicated by these checks to qualified personnel. WIRING DIAGRAMS The following diagrams are typical schematics only. May be used with other ballasts. Consult the factory for other wiring diagrams. Emergency Ballast and AC Ballast must be fed from the SAME BRANCH CIRCUIT. BROWN CONNECTOR OPEN IMPORTANT TEXT: REFER TO TABLE 1 REGARDING BROWN CONNECTOR Table 1 BROWN CONNECTOR CLOSED LAMP BASE TYPE T8,T9,T10,T12 Single or Bipin (DIAMETER) BROWN BROWN JUMPER WIRE BROWN (1”, 1¼”, 1½”) BROWN LONG COMPACT 4-PIN (2G11) WATTAGE (Length) 17 - 40 W (2'-4') 40 - 215 W (5' -8') 18 - 39 W 40 - 55 W 3 NO. of LAMPS (EMERGENCYMODE) BROWN CONNECTOR 1 CLOSED 2 OPEN 1 OPEN 1 CLOSED 2 OPEN 1 CLOSED EMERGENCY BALLAST AND AC BALLAST MUST BE FED FROM THE SAME BRANCH CIRCUIT TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLASTS. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS. WIRING DIAGRAM for 1-LAMP emergency operation FIG A ONE (1) LAMP RAPID START BALLAST FIG B ONE (1) LAMP INSTANT START BALLAST WALL SWITCH WALL SWITCH HOT WHT/RED B L K RED INVERTER CONNECTOR TEST SWITCH E M E R G E N C Y WHITE VIOLET (+) CHARGING INDICATOR B L K BROWN BROWN (-) BLACK WHITE WHT/BLK COMMON B A L L A S T HOT WARNING: Refer to Table 1 before connecting BROWN RED YELLOW YEL/BLK BLU/WHT BLUE LAMP BLUE BLUE WHT/RED B L K INVERTER CONNECTOR TEST SWITCH CHARGING INDICATOR B L K RED RED BROWN RED E M E R G E N C Y WHITE VIOLET (+) BROWN (-) BLACK 1 LAMP RAPID START BALLAST COMMON WHITE WHT/BLK BLACK WHITE FIG C TWO (2) LAMP RAPID START BALLAST FIG D BROWN RED INVERTER CONNECTOR E M E R G E N C Y WHITE VIOLET (+) CHARGING INDICATOR B L K BROWN (-) BLACK WHITE WHT/BLK COMMON TWO (2) LAMP INSTANT START BALLAST B A L L A S T HOT WARNING: Refer to Table 1 before connecting BROWN RED YELLOW YEL/BLK LAMP 1 (EMERGENCY) BLU/WHT BLUE BLUE BLUE RED RED 2 LAMP RAPID START BALLAST WHT/RED B L K INVERTER CONNECTOR TEST SWITCH CHARGING INDICATOR B L K LAMP 2 BROWN RED E M E R G E N C Y WHITE VIOLET (+) BROWN (-) BLACK COMMON YELLOW YELLOW WHITE WHT/BLK WARNING: Refer to Table 1 before connecting BROWN B A L L A S T RED YELLOW YEL/BLK BLU/WHT BLUE BLACK WHITE FIG F THREE (3) LAMP RAPID START BALLAST WHT/RED CHARGING INDICATOR BROWN RED INVERTER CONNECTOR B L K E M E R G E N C Y WHITE VIOLET (+) BROWN (-) BLACK WHITE WHT/BLK COMMON B A L L A S T HOT WARNING: Refer to Table 1 before connecting BROWN RED YELLOW YEL/BLK BLU/WHT BLUE LAMP 1 BLUE BLUE BLU/WHT YELLOW YELLOW 3 LAMP RAPID START BALLAST WHT/RED B L K (EMERGENCY) INVERTER CONNECTOR TEST SWITCH CHARGING INDICATOR B L K LAMP 2 COMMON LAMP 3 WHT/RED BROWN RED INVERTER CONNECTOR E M E R G E N C Y WHITE VIOLET (+) CHARGING INDICATOR BROWN (-) BLACK WHITE WHT/BLK COMMON FIG H BROWN (-) WHITE WHT/BLK YELLOW YEL/BLK BLU/WHT LAMP 1(EMERGENCY) BLUE BLUE BLUE 3 LAMP INSTANT START BALLAST BLUE LAMP 2 LAMP 3 RED FOUR (4) LAMP INSTANT START BALLAST B A L L A S T HOT WARNING: Refer to Table 1 before connecting BROWN RED YELLOW YEL/BLK BLU/WHT RED YELLOW BLUE RED YELLOW 4 LAMP RAPID START BALLAST BLU/WHT BLU/WHT WHT/RED B L K LAMP 1 (EMERGENCY) BLACK WHITE FIG I VIOLET (+) RED WALL SWITCH HOT B L K RED WARNING: Refer to Table 1 before connecting BROWN B A L L A S T BLACK WHITE WALL SWITCH TEST SWITCH E M E R G E N C Y RED RED FOUR (4) LAMP RAPID START BALLAST B L K BROWN RED WHITE BLACK BLU/WHT BLACK WHITE FIG G 2 LAMP INSTANT START BALLAST LAMP 2 WALL SWITCH HOT TEST SWITCH BLUE THREE (3) LAMP INSTANT START BALLAST WALL SWITCH B L K LAMP 1(EMERGENCY) BLUE BLACK WHITE FIG E 1 LAMP INSTANT START BALLAST WALL SWITCH WHT/RED TEST SWITCH LAMP RED BLUE BLACK WHITE WALL SWITCH HOT B L K WARNING: Refer to Table 1 before connecting BROWN RED YELLOW YEL/BLK BLU/WHT BLUE B A L L A S T TEST SWITCH B L K LAMP 2 INVERTER CONNECTOR CHARGING INDICATOR E M E R G E N C Y VIOLET (+) BROWN (-) BLACK COMMON LAMP 3 BROWN RED WHITE WHITE WHT/BLK B A L L A S T WARNING: Refer to Table 1 before connecting BROWN RED YELLOW YEL/BLK BLU/WHT LAMP 1 (EMERGENCY) YELLOW BLUE BRN BRN BLUE BLACK WHITE BLUE BLUE BLUE 4 LAMP INSTANT START BALLAST RED FIG J LAMP 3 YELLOW RED LAMP 4 ONE (1) LAMP COMPACT RAPID START BALLAST LAMP 2 LAMP 4 TWO (2) LAMP COMPACT RAPID START BALLAST WALL SWITCH WHT/RED HOT B L K TEST SWITCH B L K RED INVERTER CONNECTOR CHARGING INDICATOR WHITE VIOLET (+) BROWN (-) BLACK COMMON WHITE WHT/BLK BROWN E M E R G E N C Y B A L L A S T BROWN RED YELLOW YEL/BLK BLU/WHT BLUE WALL SWITCH WARNING: Refer to Table 1 before connecting B L K LAMP BLUE BLUE BLACK WHT/RED HOT RED RED TEST SWITCH B L K 1 LAMP RAPID START BALLAST INVERTER CONNECTOR CHARGING INDICATOR WHITE VIOLET (+) BROWN (-) BLACK COMMON WHITE RED WHITE WHT/BLK BROWN E M E R G E N C Y B A L L A S T BROWN RED YELLOW YEL/BLK BLU/WHT BLUE WARNING: Refer to Table 1 before connecting LAMP 1 BLUE BLUE BLACK WHITE FIG K (EMERGENCY) YELLOW RED RED LAMP 2 TWO (2) LAMP RAPID START STEP DIMMING BALLAST COMMON WHT/RED INVERTER CONNECTOR CHARGING INDICATOR TEST SWITCH HOT 2 LAMP RAPID START BALLAST YELLOW BLK RED WHITE VIOLET (+) BROWN (-) WHITE BLACK BLK BROWN E M E R G E N C Y B A L L A S T WARNING: Refer to Table 1 before connecting BROWN RED YELLOW YEL/BLK BLU/WHT BLUE WHT/BLK S1 S2 The white/black lead must connect to the white lead of the step-dimming ballast associated with the emergency ballast only. Connections to other ballasts or fixtures could result in abnormal operation and cause product damage. LAMP 1 (EMERGENCY) BLUE BLUE WHITE BLACK BLACK 2 LAMP RAPID START STEP DIMMING BALLAST RED RED LAMP 2 YELLOW YELLOW 4 WIRING DIAGRAMS for 2-LAMP emergency operation (2´- 4´, 17- 40 W lamps only) Two-lamp emergency operation is not possible with all ballasts. Consult the factory for any ballast other than those shown. FIG L FIG M TWO (2) LAMP RAPID START BALLAST TWO (2) LAMP INSTANT START BALLAST WALL SWITCH WALL SWITCH HOT WHT/RED B L K TEST SWITCH B L K INVERTER CONNECTOR CHARGING INDICATOR E M E R G E N C Y WHITE VIOLET (+) BROWN (-) BLACK COMMON HOT BROWN RED WHITE WHT/BLK B A L L A S T WARNING: Do NOT connect brown connector BROWN YELLOW YEL/BLK RED LAMP 1 TEST SWITCH BLUE BLUE BLU/WHT BLUE WHT/RED B L K RED RED 2 LAMP RAPID START BALLAST B L K LAMP 2 RED INVERTER CONNECTOR WHITE VIOLET (+) CHARGING INDICATOR BROWN (-) BLACK WHITE WHT/BLK COMMON YELLOW YELLOW BROWN E M E R G E N C Y B A L L A S T BLUE THREE (3) LAMP RAPID START BALLAST FIG O WALL SWITCH WHT/RED B L K TEST SWITCH B L K INVERTER CONNECTOR CHARGING INDICATOR HOT BROWN RED E M E R G E N C Y WHITE VIOLET (+) BROWN (-) BLACK COMMON WHITE WHT/BLK WARNING: Do NOT connect brown connector BROWN B A L L A S T LAMP 1(EMERGENCY) BLUE BLUE BLU/WHT BLUE TEST SWITCH BLU/WHT BLU/WHT 3 LAMP RAPID START BALLAST YELLOW YELLOW WHT/RED B L K RED YELLOW YEL/BLK BLACK WHITE FIG P B L K B L K BROWN RED INVERTER CONNECTOR CHARGING INDICATOR E M E R G E N C Y WHITE VIOLET (+) BROWN (-) BLACK COMMON BROWN (-) BLACK WHITE WHT/BLK LAMP 3 WARNING: Do NOT connect brown connector BROWN B A L L A S T YELLOW RED LAMP 1 (EMERGENCY) YEL/BLK BLU/WHT BLUE BLUE BLUE BLACK WHITE RED RED FIG Q 3 LAMP INSTANT START BALLAST BLUE LAMP 2 (EMERGENCY) LAMP 3 RED FOUR (4) LAMP INSTANT START BALLAST WHITE WHT/BLK B A L L A S T HOT WARNING: Do NOT connect brown connector BROWN RED WHT/RED B L K YELLOW YEL/BLK LAMP 1 (EMERGENCY) BLU/WHT BLUE TEST SWITCH YELLOW YELLOW RED RED 4 LAMP RAPID START BALLAST BLU/WHT BLU/WHT B L K LAMP 2 (EMERGENCY) RED INVERTER CONNECTOR WHITE VIOLET (+) CHARGING INDICATOR BROWN (-) BLACK WHITE WHT/BLK COMMON LAMP 3 BRN BRN BLUE BLUE BLACK WHITE FIG R VIOLET (+) CHARGING INDICATOR BROWN E M E R G E N C Y WALL SWITCH WHT/RED TEST SWITCH WHITE COMMON WALL SWITCH B L K RED INVERTER CONNECTOR LAMP 2 (EMERGENCY) FOUR (4) LAMP RAPID START BALLAST HOT LAMP 2 2 LAMP INSTANT START BALLAST THREE (3) LAMP INSTANT START BALLAST WALL SWITCH HOT LAMP 1 RED BLUE BLUE BLACK WHITE BLACK WHITE FIG N WARNING: Do NOT connect brown connector BROWN RED YELLOW YEL/BLK BLU/WHT BROWN E M E R G E N C Y B A L L A S T BROWN RED YELLOW YEL/BLK BLU/WHT BLUE WARNING: Do NOT connect brown connector LAMP 1 (EMERGENCY) YELLOW BLUE BLACK WHITE BLUE 4 LAMP INSTANT START BALLAST RED LAMP 2 (EMERGENCY) LAMP 3 YELLOW RED LAMP 4 LAMP 4 TWO (2) COMPACT LAMP RAPID START BALLAST WALL SWITCH WHT/RED HOT B L K TEST SWITCH B L K INVERTER CONNECTOR CHARGING INDICATOR BROWN RED E M E R G E N C Y WHITE VIOLET (+) BROWN (-) BLACK COMMON WHITE WHT/BLK B A L L A S T BROWN RED YELLOW YEL/BLK BLU/WHT BLUE WARNING: DO NOT connect brown connector LAMP 1 BLUE BLUE BLACK WHITE YELLOW 2 LAMP RAPID START BALLAST YELLOW RED RED LAMP 2 WIRING DIAGRAMS for Emergency-Only fixtures FIG T FIG S ONE (1) LAMP WITHOUT AC BALLAST (16W-215W) HOT WHT/RED (CAP) B L K TEST SWITCH B L K INVERTER CONNECTOR VIOLET (+) CHARGING INDICATOR BROWN (-) BLACK WHITE WHT/BLK COMMON (CAP) FIG U B L K TEST SWITCH B L K BROWN E M E R G E N C Y B A L L A S T YELLOW YEL/BLK BLU/WHT BLUE HOT WARNING: Refer to Table 1 before connecting BROWN RED LAMP TEST SWITCH (CAP) B L K (CAP) RED WHITE VIOLET (+) CHARGING INDICATOR BROWN (-) BLACK COMMON (CAP) WHITE WHT/BLK INVERTER CONNECTOR BROWN E M E R G E N C Y B A L L A S T BROWN RED YELLOW YEL/BLK BLU/WHT BLUE BLACK WHITE WHT/BLK B L K LAMP TEST SWITCH (CAP) (CAP) B L K WARNING: Do NOT connect brown connector BROWN B A L L A S T WHT/RED INVERTER CONNECTOR RED WHITE VIOLET (+) CHARGING INDICATOR BROWN (-) BLACK COMMON (CAP) 5 BROWN E M E R G E N C Y RED YELLOW YEL/BLK BLU/WHT BLUE LAMP 1 (CAP) (CAP) LAMP 2 TWO (2) 4-PIN COMPACT LAMPS WITHOUT AC BALLAST (16W-39W) (CAP) HOT WARNING: Refer to Table 1 before connecting WHITE BROWN (-) (CAP) FIG V RED VIOLET (+) CHARGING INDICATOR COMMON WHT/RED INVERTER CONNECTOR WHT/RED (CAP) B L K ONE (1) 4-PIN COMPACT LAMP WITHOUT AC BALLAST (16W-55W) (CAP) HOT RED WHITE TWO (2) LAMPS WITHOUT AC BALLAST (17W-40W) WHITE WHT/BLK BROWN E M E R G E N C Y B A L L A S T BROWN RED YELLOW YEL/BLK BLU/WHT BLUE WARNING: Do NOT connect brown connector LAMP 1 (CAP) (CAP) LAMP 2