GND 905U ANT PROVIDE GOOD GROUND CONNECTION TO MAST, MODULE AND SURGE ARRESTOR COAXIAL CABLE MAST EARTH STAKE IF GROUND CONDITIONS ARE POOR, INSTALL MORE THAN ONE STAKE STRESS RELIEF LOOP Power supply: Choose option and wire as shown (D) Solar panel with solar battery (C) Supply battery or 11-15VDC (B) 15-30VDC 1.5 Amp CSA certified Class 2 (A) 12-24VAC 1.5 Amp CSA certified Class 2 905U-1, 105S-1 I/O Installation ANTENNA INSTALLATION Antennas should be installed by experienced Contractors. INSTALL AERIAL ABOVE LOCAL OBSTRUCTIONS SURGE ARRESTOR (OPTIONAL) WEATHERPROOF CONNECTORS WITH “3M 23” TAPE COLINEAR ANTENNA 1m minimum CAUTION! For continued protection against risk of fire, replace the module fuse only with the same type and rating All I/O must be SELV Analog Outputs are either Loop Powered or Externally Powered - Output Loops are sink to earth (not floating). DC Load, use Bypass Diode. AC Load use 10nF 250V Surge Capacitor. AC Supply 12-24VAC min 15VAC for Battery Charging. Do not earth SUP1 or SUP2 connections 12V Solar Panel Supply max 20VDC max 30W panel 2 3 xxxx-1 OUTPUTS + - To +24V loop supply + – Analog Outputs See Note 2. 4 + - 2 3 INPUTS 4 Loop Powered Analog Transducer + - To Com Ext. Powered AnalogTransducer + - + - Output Counter Ext. DC Supply 30VDC, 500mA max © ELPRO Technologies Pty. Ltd. 2002 Rev. 1.9 Digital Input Voltage Free Contact OR Transistor Device To Earth Connection DC Supply 15-30VDC min 17VDC for Battery Charging 1 RADIO TELEMETRY MODULE 1 DO 1 GND Aerial Installation SUP2 Digital Outputs are Relay contacts. For ratings refer to User Manual. SOL NOTES DO 2 DI 1 THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS 1 DIVISION 2 GROUPS ABC AND D OR NON HAZARDOUS LOCATIONS ONLY DI 2 2A - + DI 3 This device complies with Part 15.247 of the FCC Rules. Operation is subject to the following two conditions: 1) This device may not cause harmful interference and 2) This device must accept any interference received, including interference that may cause undesired operation + - AC Relay Supply DI 4 FCC Notice GND DC Relay Supply DO 3 11-15VDC Supply or Optional 12V Backup Battery to 12 Amphour for AC/DC to 100 Amphour for Solar DO 4 COM DO NOT DISCONNECT WHILE CIRCUIT IS LIVE UNLESS AREA IS KNOWN TO BE NON -HAZARDOUS SUP1 BAT+ SUP1 Digital Outputs See Note 1. +24V Installation Guide SUP2 +24V +AI 1 EXPLOSION HAZARD SOL AO 1 - 905U-1, 105S-1 GND AO 2 +AI 2 WARNING! PO -