Kyle Padmount Switchgear Type PST 15kV through 38kV, 600 Amps Continuous, 12,000 Amp Fault Protection SI Tap S II Kyle® Type PST ™ Switchgear Automatic source transfer and threephase fault protection in a compact, self-contained, deadfront design! Features: • Deadfront Design • Low Profile • Self Contained; Self Powered • Vacuum Interruption • Three-Phase Overcurrent Protection • Three-Phase Switching • Automatic or Manual Operation • SCADA Operable The Kyle Type PST (Padmount Source Transfer Switchgear package) is a self contained load transfer device, which provides both automatic load transfer and circuit fault protection, in a single padmount switchgear unit. The PST represents the union of several timeproven Kyle products: the S control, which detects loss of voltage and automatically transfers the load between the preferred and alternate sources; the ETC electronic trip control, which provides fault detection; and the CI vacuum fault interrupter, which performs three-phase switching and threephase fault interruption. Kyle Type PST— Automatic Source Transfer Product Description HINGED COVER AND DOORS, provide easy access to connections and controls. The Padmount Source Transfer (PST) package provides both lossof-voltage and overcurrent protection for critical loads. It features deadfront source and tap cable compartments, and a sealed tank, which houses the switching and fault interrupting components. Source Compartment CONTROL SOURCE I The source compartment houses the preferred and alternate source cable connections, the controls, and handles for manual operation. SOURCE II (either source can be the preferred) Tank Automatic Source Transfer All electrical distribution systems are subject to service interruptions and outages; however, there are many critical loads which cannot tolerate prolonged service interruptions. For such applications, a load-transfer scheme is used to minimize outage times. In a load transfer scheme, power is normally supplied from a preferred source and is automatically switched to an alternate source, if preferred source voltage is lost for any reason. Upon restoration of preferred source voltage the load can automatically be switched back, in either a parallel-return mode (preferred-source switch closes before alternate source switch opens) or a non-parallel return mode (alternate-source switch opens before preferred-source switch closes). Page 2 The parallel-return transfer mode eliminates an outage when switching back to the preferred source; however, the sources must be in phase. PUSH-PULL HANDLES, for manual charging of the stored energy switch operators. CONTACT POSITION, and SPRING STATUS INDICATORS The PST tank contains: Six potential transformers, which provide input to the S-Control to sense loss-of-voltage; Six current transformers, which provide input to the electronic trip control, to sense overload and fault conditions; Two, three-phase, Type CI inter- MANUAL TRIP/ CLOSE LEVERS, lockable in the open position. OPERATIONS COUNTERS, one for each switch. Resettable “Three-Phase” Fault Interruption! rupters, which perform the threephase switching and fault interruption; And, insulating oil, which serves as the dielectric medium. ETC CONTROL, monitors load to detect overcurrent conditions. Tap Compartment The Model-6 tap compartment houses the tap cables and connections. Optional Configuration The PST is designed in the industry-standard Model-6 configuration; however, occasionally two critical loads must be served, each independently, from the same source. To accommodate this need, the PST can optionally be designed in a Model-9 configuration. In the Model-9 configuration the Electronic Trip Control (ETC) is replaced with two Kyle TriPhase controls, which are located in the tap-side compartment, each control operates a separate threephase interrupting VFI. This arrangement of two Tri-Phase controls, operating VFI interrupters, provides independent overcurrent and fault protection for the critical loads serviced by each tap. Kyle Technology Kyle CI Interrupter Switching and fault interruption are both accomplished with Kyle’s, motor-operated, Type CI interrupters. The CI interrupters feature Kyle’s long-life, maintenance free, vacuum interrupters, which assure many years of trou- TEST TERMINALS, provide electrical access to latch relay to determine control status in the event of voltage loss from both sources. SWITCH STATUS INDICATORS, provide visual reference as to the status of each switch. SOURCE PREFERENCE AND RETURN MODE SWITCH, provides an easy means of programming a transfer scheme; settings can be locked. ble free performance. When energized, a motor winds the CI interrupter mechanism to charge the opening and closing springs; this provides quick-open and quick-close operation of the vacuum interrupters. Each CI interrupter can also be operated manually, should control power be lost. A hot-stick operable lever can be operated to manually close or trip the CI, while a hot-stick operable push-pull handle can be operated for manual charging of TIME DELAY RELAYS, synchronous-motor type, provide accurate time delay, will reset to zero if voltage is restored. MANUAL OPERATION CONTROLS, provide manual control over each switch. CONTROL MODE, provides a convenient override to block automatic return to the preferred source. the springs. Viewing ports provide access to the contact position indicators and operation counters for each interrupter. Type ETC Control (Model-6 Configuration) The PST switchgear package can optionally be equipped with a Kyle Type ETC control to monitor the three-phase load. If a fault or other overcurrent condition is detected, the ETC control issues a trip signal to the CI interrupter, Page 3 PST-6 Tap-Side TAP-SIDE BUSHINGS, provide threephase 200A or 600A bushing wells, conforms to ANSI/IEEE Standard 386. Kyle Tri-Phase Control OIL SIGHT GAUGE, provides visual indication of oil level within tank. which simultaneously interrupts all three phases of the load. When properly coordinated, with upline devices, the ETC control can detect and isolate tap-side faults without causing nuisance operations of the source-side protective devices. The ETC control can be ordered with a remote operation accessory, for connection to a SCADA system. In addition, the ETC can be configured to respond to local input from other transformer protective devices (thermal sensors, smoke detectors, sudden pressure relays and secondary ground fault relays). Type S Control Kyle’s Type S control provides the timing and control logic required to perform the automatic load transfer. The S control is a time-proven user-friendly control. Simple relay logic and analog timers assure reliable operation, ease of installation and quick troubleshooting. The face of the control provides visual indication of the status of each CI interrupter, control settings and manual operation capabilities. FAULT PROTECTION, Tri-Phase controls coupled with VFI vacuum fault interrupters provide independent fault protection for each tap. The PST switchgear package can optionally be supplied in a Model-9 configuration, with two independent fault protected taps. Each tap is protected by a Kyle VFI interrupter, operated by a Kyle Tri-Phase control. Sensing CT‘s, mounted internally on each phase, are used by the Tri-Phase control to monitor line current. If the current monitored is greater than the minimum trip level, the control begins a user-selected time-current-curve (TCC) delay sequence. At completion of the programmed TCC delay, a signal is issued to trip the VFI. The Tri-Phase control is powered by the current transformers; no external voltage supply or battery backup is required. Since the Tri-Phase control is powered by sensing CT‘s, it is not affected by system voltage conditions such as overvoltage transients. THREE-PHASE TRIP, all three phases trip simultaneously. PST-9 Tap-Side TAP-SIDE BUSHINGS, provide threephase 200A bushing wells for each tap, conforms to ANSI/IEEE Standard 386. Page 4 Dimensional Information PST-6 kV Dim. Tap Cabinet Source Cabinet All Cabinets 48" High 30" E A B C D E 84 62 36 16 32 90 62 36 22 32 78 62 30 16 32 35 A B C D E 92 70 40 20 32 98 70 40 26 32 86 70 34 20 32 Source / Tap 600A / 200A Source / Tap 600A / 600A Source / Tap 200A / 200A PST-9 15 & 25 A B C D E 95 70 36 16 43 101 70 36 22 43 89 70 30 16 43 35 A B C D E 103 70 40 20 43 109 70 40 26 43 97 70 34 20 43 30" Specifications Additional Product Information Electrical Ratings Nominal Voltage Rating Source / Tap 200A / 200A B D A Source / Tap 600A / 600A 15 & 25 kV Dim. C Source / Tap 600A / 200A 15kV 25kV 35kV BIL (kV) 95 Interrupting Current (Symmetrical) (kA) 12 Load Break and Continuous Current Rating (Symmetrical) (A) 600 125 150 12 12 600 600 ANSI Ratings The Type PST padmount source transfer package meets ANSI C37.72 for manually-operated, deadfront padmount switchgear with load interrupting switches, and ANSI C37.60 for automatic circuit reclosers and fault interrupters. For additional product information, refer to the following catalog sections: Type S Control ............Catalog Section .. 260-75 Type CI Interrupter ...Catalog Section .. 275-10 Type VFI and TriPhase Control ....Bulletin ................. 91041 Ordering Information For ordering information, or additional product and application information, contact your local Cooper Power Systems sales representative, or write to: Cooper Power Systems PO Box 2850 Pittsburgh, PA 15230 Phone: (412) 269-6700 Page 5 “Kyle Quality” Type PST Schematic Diagrams PST-6 PST-9 Features: • Deadfront Design • Sealed Construction • Low Profile • Vacuum Interruption • Self Contained; Self Powered • Flexible Control Options • Time-proven “Kyle Quality” ©1991 Cooper Power Systems, Inc. KYLE® is a registered Trademark of Cooper Industries, Inc. Bulletin 91049 • December1991 Reference 285 Benefits: ✔ Safest Equipment Available — Complies with ANSI C37.72 ✔ Virtually Maintenance Free ✔ No exposure to airborne contaminants ✔ No exposure to live conductors ✔ Aesthetically Pleasing, ideal for commercial applications ✔ Long Life, Maintenance Free ✔ Resettable, three-phase load and fault interruption ✔ Eliminates user supplied PTs & CTs ✔ Reduces installation time ✔ Source transfer functions can be field tailored to fit application. ✔ No fuses ✔ Field selectable Phase and Ground Trip TCCs ✔ Can be coordinated with “up-line” and “down-line” overcurrent protective devices ✔ Provides reliable and economical means of supplying an automatic source transfer PO Box 1640 Waukesha, WI 53187