INS # Overview Application Note

advertisement
INS #
Application Note
Joining multiple Room Controllers via the keypad interface
Overview
The Room Controller Wallstation interface provides +24 VDC power for up to twelve wall mounted switch
stations. Each wallstation can support multiple pre-configured control functions. These include zone (load)
toggles, or preset scene trigger commands. This also allows multiple wallstations to use the same interface
port on a Room Controller. Wallstations can also share the same control function in different locations
creating a multi-way control scenario.
Adjustable Skylights
QuickConnect Cables
Switchpack
Receptacle
BMS/Out
Sensors
Sensors
Slider
Station
Wallstations
+
+
+
+
Alert
Mode
Time
Clock
6
5
3
2
1
Not Used
Occupancy
Occ
Vac (default)
3
4
Energy
Options
1 2
Reset
Demand Response
High End
Energy Options DIP Switch
Default 10%
20%
30%
40%
Status
0-10V Gain
Adjustment
0-10V Dimming Outputs
+ + + Dimmer 3
Control Sequence: Wallstations can be shared
between up to four Room Controllers. Button
presses will perform the same function in all
connected Room Controllers.
Uniquely connected occupancy sensors and
daylight sensors will control the Room Controller
they are connected to only. This can allow for
wallstations to be shared over a large area and
occupancy and daylight sensors to control
smaller zones.
4
Integration Controls
Green
A/V
Mode
Demand
Response
Low End
Red - Load 2 Out
Purple - Load 3 Out
Blue - Load In
Yellow - Load 1 Out
Black
Integration Controls
CAUTION: Bonding between conduit connections is not automatic and must be provided as part of the installation.
White
Red
Blue - EM Line In
Blue - EM Loads Out
Black - Line In
White/Black - 120V N
White/Orange - 277V N
Adjustable Skylights
Lighting control scenarios can take further advantage of this method by connecting one or more
wallstations to up to four Room Controllers. The wallstation is equipped with two RJ45 connectors to
allow the signals to pass through to another wallstation. Each connector on a wallstation can then be
connected to a different wallstation or Room Controller for simultaneous control of both panels via any of
the wallstations. This is depicted in Figure 1 below.
Dimmer 2
Dimmer 1
-
Dimmer 3
+
-
Dimmer 2
+
-
Dimmer 1
+
Adjustable Skylights
QuickConnect Cables
Switchpack
Receptacle
BMS/Out
Sensors
Sensors
Slider
Station
Wallstations
+
+
+
+
Alert
Mode
Time
Clock
6
5
4
Integration Controls
Green
A/V
Mode
Demand
Response
2
4
Dimmer 2
Status
GGRC-SPLITTER
(1 to 2 Cable Splitter)
0-10V Gain
Adjustment
0-10V Dimming Outputs
+ + + Dimmer 3
Dimmer 1
-
Dimmer 3
+
-
Dimmer 2
+
-
Dimmer 1
+
Sensors
Sensors
Wallstations
Demand
Response
Alert
Mode
Time
Clock
+
+
+
+
Adjustable Skylights
Receptacle
BMS/Out
Slider
Station
A/V
Mode
4
2
1
Status
0-10V Gain
Adjustment
0-10V Dimming Outputs
+ + + Dimmer 2
QuickConnect Cable
(Class 2)
Reset
4
Energy
Options
3
High End
Not Used
Occupancy
Occ
Vac (default)
Dimmer 3
1
3
Low End
1 2
Additional Wallstation Additional Wallstation
(Back)
(Back)
6
Energy Options DIP Switch
Demand Response
Default 10%
20%
30%
40%
Additional Wallstation
(Back)
5
Integration Controls
Adjustable Skylights
Switchpack
QuickConnect Cables
Green
Integration Controls
Blue - Load In
Yellow - Load 1 Out
Red
Blue - EM Line In
Blue - EM Loads Out
Black - Line In
White/Black - 120V N
White/Orange - 277V N
White
CAUTION: Bonding between conduit connections is not automatic and must be provided as part of the installation.
Red - Load 2 Out
Purple - Load 3 Out
0-10V Dimming
Black
QuickConnect Cable
(Class 2)
Energy
Options
3
Reset
Not Used
Occupancy
Occ
Vac (default)
High End
1 2
QuickConnect Cable
(Class 2)
1
Energy Options DIP Switch
Demand Response
Default 10%
20%
30%
40%
QuickConnect Cable
(Class 2)
3
Low End
Red - Load 2 Out
Purple - Load 3 Out
Blue - Load In
Yellow - Load 1 Out
Black
Integration Controls
CAUTION: Bonding between conduit connections is not automatic and must be provided as part of the installation.
White
Red
Blue - EM Line In
Blue - EM Loads Out
Black - Line In
White/Black - 120V N
White/Orange - 277V N
Adjustable Skylights
0-10V Dimming
Dimmer 1
-
Dimmer 3
+
-
Dimmer 2
+
-
Dimmer 1
+
0-10V Dimming
Sensors
Sensors
Slider
Station
Wallstations
A/V
Mode
+
+
+
+
Demand
Response
Alert
Mode
Time
Clock
Adjustable Skylights
Receptacle
BMS/Out
3
2
Reset
Energy
Options
4
High End
3
Status
0-10V Gain
Adjustment
0-10V Dimming Outputs
+ + + Dimmer 3
Dimmer 2
* NOTE: Each cable lenght not to exceed
100ft. Total length not to exceed 400ft.
1
Not Used
Occupancy
Occ
Vac (default)
Low End
1 2
Dimmer 1
-
Dimmer 3
+
-
Dimmer 2
+
0-10V Dimming
-
Dimmer 1
+
QuickConnect Cable
(Class 2)
Entry Wallstation
(Back)
4
Energy Options DIP Switch
Demand Response
Default 10%
20%
30%
40%
GGRC-SPLITTER
(1 to 2 Cable Splitter)
6
5
Integration Controls
Adjustable Skylights
Green
Switchpack
QuickConnect Cables
Red
Black
Integration Controls
Blue - Load In
Yellow - Load 1 Out
Black - Line In
White/Black - 120V N
White/Orange - 277V N
Blue - EM Line In
Blue - EM Loads Out
White
CAUTION: Bonding between conduit connections is not automatic and must be provided as part of the installation.
Red - Load 2 Out
Purple - Load 3 Out
QuickConnect Cable
(Class 2)
QuickConnect Cable
(Class 2)
Additional Wallstation Additional Wallstation
(Back)
(Back)
Connect a QuickConnect cable between
the designated wallstation Click & Go
port on the Room Controller and to one
of the Click & Go ports on the Entry
wallstation. Connect up to twelve
wallstations using additional
QuickConnect cables to connect station
to station.
Figure 1. Joined Keypad Interfaces Between Four Room Controllers
Technical Details
The +24 VDC power for the wallstation will be supplied by at least one of the Room Controller wallstation ports. Each port
has a series diode for over-voltage protection of the power output, which allows two ports to be connected on the same
Cat5e cable without damage. However, one or both ports may supply power to the wallstations depending on the voltage
drops of the two diodes.
Up to twelve Room Controller Wallstations may be shared with up to four Room Controllers to provide large area control with
shared multi-way wallstation configurations.
The +24 VDC external power limit, which is approximately 90mA across all of the external ports, allows for multiple device
connections. The application note Room Controller accessory power allocation details the DC current usage of each Room
Controller accessory. Any combination of accessories may be connected to the sensor, keypad and slider RJ45 jacks as long
as the maximum current limit is not exceeded.
NNote: The Quiet Time LED on every Quiet Time button on any of the keypads, if equipped, will be illuminated when Quiet
Time Mode is entered on any of the keypads.
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, GA 30269
CooperControl.com
© 2014 Eaton
All Rights Reserved
Printed in USA
Publication No. ACC140064