G ARWOOD LABORATORIES, INC.
Your Most Trusted
Name in Testing
Since 1954.
EARTHQUAKE RESISTANCE
TEST REPORT
for
COOPER B-LINE
Model: SB-852 Series Seismic Rack
Page: 1 of 41
GARWOOD LABORATORIES, INC.
TESTING AND ENGINEERING SERVICES
?
Earthquake Resistance Testing
Report for:
COOPER B-LINE
Model:
SB-852 Series Seismic Rack
Prepared For: COOPER B-Line
13755 Stead Blvd.
Reno, NV 89506
Prepared By: Garwood Laboratories, Inc
7829 Industry Avenue
Pico Rivera, CA 90660
Issued: March 25, 2005
Page: 2 of 41
GARWOOD LABORATORIES, INC.
“EXCELLENCE BUILT
ON INTEGRITY”
7829 Industry Avenue, Pico Rivera, CA 90660
®
Testing Services
Since 1954
Report No: 26328
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
RESPONSIBLE S IGNATURES
This report is intended for the use by the organization to whom it is addressed, and will not be made
available to any other parties without the expressed written consent of the aforementioned
organization. This report shall not be reproduced, except in full, without the written approval of
Garwood Laboratories, Inc.
WRITTEN B Y:
REVIEWED B Y:
Don Bennett
Director of Telecom Compliance
William Flower
Quality Assurance Manager
Document History
Revision
N/C
Date: March 25, 2005
Issue Date
Affected
Page(s)
Description Of
Modifications
Revised
By
Approved
By
Initial release
EUT: Model SB-852 Series Seismic Rack
Page: 3 of 41
Test Report #: 26328
TABLE OF CONTENTS
PREAMBLE:
PROGRAM SCOPE .................................................................................................................. 6
EXECUTIVE SUMMARY ............................................................................................................... 6
TEST DOCUMENTATION:
ADMINISTRATIVE DATA...................................................................................................... 9
ENVIRONMENTAL CRITERIA ............................................................................................ 9
GR-63 EARTHQUAKE, ZONE 4 (§ 4.0)……………………………………………………..9
Earthquake, Zone 4 Criteria (§ 4.1)………………………………………………………….9
APPENDIX A:
TEST DATA ...............................................................................................................................A
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 4 of 41
Test Report #: 26328
?
PREAMBLE
to the
Earthquake Resistance Test Report
for
COOPER B-LINE
Model:
SB-852 Series Seismic Rack
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 5 of 41
Test Report #: 26328
TESTS PERFORMED:
TEST
PERFORMED
YES
NO
X
ENVIRONMENTAL CRITERIA:
EARTHQUAKE, ZONE 4
EXECUTIVE S UMMARY
Introduction
All test equipment used for this program was checked prior to testing to assure that it is in calibration,
and that the parameters being measured are appropriate for the range on the measuring instrument.
Calibration is performed and checked on a routine basis using standards traceable to the National
Institute of Standards and Technology (NIST). Calibration of equipment is performed in accordance
with the Garwood Laboratories, Inc quality program and satisfies the requirements of ISO 10012-1.
A list of test equipment used and verification of the suitability of the measuring instrument is included
in this report and documents the type of equipment, accuracies, and calibration due dates as a
minimum.
Test Results Summary
Testing of Cooper B-Line’s SB-852 Series Seismic Rack was performed at Garwood Laboratories Inc.
in Pico Rivera, CA on March 21, 2005. All observations are entered on test log sheets. The rack
under test was loaded with ten (10) 100 pound weights distributed evenly throughout the rack, totaling
to 1,000 lbs. An additional 50 lbs. was added to the top of the rack to simulate overhead cable weight.
Test activities are summarized in this report. This report includes, but is not limited to, test details,
Garwood Laboratories observations, test results (including the summarized table listed below), test
photographs, and a test equipment list. Refer to the appropriate section of the test report for specific
test results.
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 6 of 41
Test Report #: 26328
?
TEST DOCUMENTATION
Earthquake Resistance Test Report
for
COOPER B-LINE
Model:
SB-852 Series Seismic Rack
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 7 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
®
Testing Services
Since 1954
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
ADMINISTRATIVE DATA
REFERENCES
GR-63-CORE, Network Equipment Building System (NEBS) Requirements: Physical Protection, Issue
2, April 2002
Garwood Laboratories, Inc’s Quote Number 200501-104, January 24, 2005
ISO/IEC 17025, General Requirements of the Competence of Calibrating Test Laboratories, 1999.
ANSI/NCSL Z540-1: 1994, Calibration Laboratories and Measuring and Test Equipment – General
Requirements
CALIBRATION D ETAILS
All test equipment used for this program is checked prior to testing to assure that it was in calibration
and that the parameters being measured are appropriate for the range on the measuring instrument.
Calibration is performed and checked on a routine basis using standards traceable to the National
Institute of Standards and Technology (NIST). Calibration of equipment is performed in accordance
with the Garwood Laboratories quality program and satisfies the requirements of the above referenced
standards.
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 8 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
®
Testing Services
Since 1954
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
ENVIRONMENTAL CRITERIA
GR-63 E ARTHQUAKE, ZONE 4 (S EC. 4.0)
Earthquake Environment and Criteria (§ 4.1)
Earthquake Environment (§ 4.1.1)
During an earthq uake, telecommunications equipment is subjected to motions that can over-stress
equipment framework, circuit boards, and connectors. The amount of motion and resulting stress
depends on the structural characteristics of the building and framework in which the equipment is
contained, and the severity of the earthquake. Refer to Figure 4-2 of GR-63-CORE for the map of
Earthquake Risk Zones. Zone 4 corresponds to the highest risk areas, Zone 3 the next highest, and so
on. Geographic areas designated as Zone 0 present no substantial
earthquake risk. Equipment to be used in earthquake risk Zones 1 through 4 shall be tested to
determine the equipment’s ability to withstand earthquakes. No earthquake requirements are provided
for Zone 0.
Section 5.4.1 of GR-63 details earthquake test methods. A frame level test configuration is used for
network equipment supplied with a framework, or equipment that is greater than 36” in height. A
shelf level configuration is used for equipment supplied as a single shelf to be installed in framework
by the purchaser. The equipment tested is expected to meet physical and functional performance
requirements. All framework and concrete expansion anchors used in network facilities shall meet the
criteria of Section 4.4.2
Telecommunications equipment shall be earthquake tested using a prescribed waveform. The test
procedure subjects equipment to follow the prescribed motion of the synthesized waveform by means
of the shaker table.
Shaking shall be applied to the equipment being tested in each of three (3) orthogonal directions of the
framework. This simulates conditions that would be encountered in service when building floors
apply earthquake motions to the equipment.
Sine Surveys and Earthquake, Zone 4 test conditions sha ll be applied sequentially in the horizontal,
transverse and vertical axes. Seismic testing shall be performed at the following levels:
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 9 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
®
Testing Services
Since 1954
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
Sine Survey:
1 to 50 Hz at 0.2 g’s
peak
1 octave per minute
1 sweep up
Earthquake:
Zone 4
Physical Performance Criteria (§ 4.1.2)
Permanent structural damage is defined to be deformation of any load-bearing element of the
equipment being tested, or any connection failure. Typical examples of permanent structural damage
are bent or buckled uprights, deformed bases, cracks, and failed anchors or fastening hardware.
Mechanical damage is defined to be any dislocation or separation of components. Examples of
mechanical damage are disengaged circuit cards and modules, and opened (including partially) doors,
drawers, or covers.
R4-46
[110] All equipment shall be constructed to sustain the waveform testing of Section 5.4.1
without permanent structural or mechanical damage.
During frame- level testing, the physical performance of the equipment shelves, framework, and
fastening hardware are considered. Permanent structural or mechanical damage of any of these
elements constitutes a test failure. During shelf- level testing, only the equipment shelf’s physical
performance is considered.
(Permanent structural or mechanical damage of the framework or its fastening hardware would not
constitute a failure, but may invalidate the test.)
Repairs or replacements that can be made without interrupting service are acceptable. An example of
such a repair is an anchor that has loosened but can be retightened.
R4-47
[111] Frame level equipment shall be constructed so that during the waveform testing of
Section 5.4.1, the maximum single-amplitude deflection at the top of the framework, relative
to the base, does not exceed 75 mm (3 in.).
R4-48
[112] Frame level equipment shall have a natural mechanical frequency greater than 2.0 Hz
as determined by the swept Sine Survey of Section 5.4.1.
O4-49
[113] Frame level equipment should have a natural mechanical frequency greater than 6.0
Hz as determined by the swept Sine Survey of Section 5.4.1.
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 10 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
Testing Services
Since 1954
®
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
Functional Performance (§ 4.1.3)
R4-50
[114] All equipment shall be constructed to meet applicable functionality requirements
immediately before and after each axis of waveform testing of Section 5.4.1. The equipment
shall sustain operation without replacement of components, manual rebooting, or human
intervention.
O4-51
[115] All equipment should be constructed to meet applicable functionality requirements
continuously during waveform testing of Section 5.4.1. These functionality criteria shall
demonstrate that the equipment has sustained operation without loss of service during the
testing.
The criteria for assessing functionality depend on the service provided by the equipment being tested.
The criteria are determined by applying appropriate Telcordia’s generic requirements or, if none
exists, by the supplier’s or purchaser’s own performance specifications.
Framework and Anchor Criteria (§ 4.1.4)
The following criteria apply to all framework and concrete expansion anchors used in network
facilities. They are intended to ensure minimum limits for structural performance in earthquake
environments are met.
O4-52
[116] Framework should be of welded construction.
R4-53
[117] Framework shall be constructed for base mounting to the floor without auxiliary
support or bracing from the building walls or ceilings.
O4-54
[118] For framework used in earthquake risk zones, the static pull testing procedures of
Section 5.4.1.4 should be followed, meeting these objectives:
?
The maximum single amplitude deflection at the top of the framework should not exceed
75 mm (3 in).
?
The top of the framework should return to its original position, within 6 mm (0.24 in.)
when the load is removed.
?
The framework should sustain no permanent structural damage during static framework
testing.
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 11 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
Testing Services
Since 1954
®
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
R4-55
O4-56
[119] Concrete expansion anchors used to base mount framework to the floor shall meet the
following requirements:
?
Maximum embedded depth of 90 mm (3.5 in.).
?
Maximum bolt diameter of 13 mm (0.5 in.).
[120] Concrete expansion anchors used to base mount the framework to the floor should be
suitable for earthquake (dynamic) applications, as specified by the manufacturer.
Note: typical concrete anchors are not designed for dynamic loads, such as earthquakes. The above
criteria specify that the selected anchors should be designed to meet the dynamic loads specified in
this document.
O4-57
[121] Concrete expansion anchors should use steel construction to minimize creep.
Concrete expansion anchors used for waveform testing must conform to the physical performance
requirements of Section 4.4.1. If substitute fasteners are used in place of concrete expansion anchors
during testing, the peak fastener load measured during the tests must not exceed the preload specified
for the concrete expansion anchors by the manufacturer.
Earthquake Environment and Criteria - Comments
When subjected to the Earthquake Resistance criteria, the Cooper B- Line’s SB-852 Series Seismic
Rack sustained no physical deterioration or functional degradation. Cooper B-Line’s SB-852 Series
Seismic Rack conformed to the requirements of GR-63 CORE listed above. The results of the sine
survey and the displacement measured during the earthquake test are as follows:
AXIS
RESONANCE
G - LEVEL
Front to Back
Side to Side
5.91 Hz.
7.7 Hz.
3.47 g
0.99 g
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
MAX. DISPLACEMENT
(SINGLE AMPLITUDE)
2.12 inches
2.34 inches
Page: 12 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
®
Testing Services
Since 1954
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
EARTHQUAKE RESISTANCE PHOTOS
Vertical Direction
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 13 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
®
Testing Services
Since 1954
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
Side to Side Direction
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 14 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
®
Testing Services
Since 1954
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
Front to Back Direction
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 15 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
®
Testing Services
Since 1954
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
Test Equipment List-Earthquake Resistance
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 16 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
®
Testing Services
Since 1954
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
Test Data and Log Sheets -Earthquake Resistance
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 17 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
®
Testing Services
Since 1954
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 18 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
®
Testing Services
Since 1954
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 19 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
®
Testing Services
Since 1954
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 20 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
®
Testing Services
Since 1954
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 21 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
®
Testing Services
Since 1954
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 22 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
®
Testing Services
Since 1954
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 23 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
®
Testing Services
Since 1954
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 24 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
®
Testing Services
Since 1954
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 25 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
®
Testing Services
Since 1954
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 26 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
®
Testing Services
Since 1954
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 27 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
®
Testing Services
Since 1954
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 28 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
®
Testing Services
Since 1954
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 29 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
®
Testing Services
Since 1954
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 30 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
®
Testing Services
Since 1954
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 31 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
®
Testing Services
Since 1954
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 32 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
®
Testing Services
Since 1954
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 33 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
®
Testing Services
Since 1954
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 34 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
®
Testing Services
Since 1954
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 35 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
®
Testing Services
Since 1954
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 36 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
®
Testing Services
Since 1954
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 37 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
®
Testing Services
Since 1954
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 38 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
®
Testing Services
Since 1954
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 39 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
®
Testing Services
Since 1954
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 40 of 41
GARWOOD LABORATORIES, INC.
7829 Industry Avenue, Pico Rivera, CA 90660
®
Testing Services
Since 1954
“EXCELLENCE BUILT
ON INTEGRITY”
Report No: 26328
www.garwoodtestlabs.com
EARTHQUAKE RESISTANCE TEST REPORT FOR COOPER B-LINE
Date: March 25, 2005
EUT: Model SB-852 Series Seismic Rack
Page: 41 of 41