Nonmetallic NEMA 4X Zone 1, Division 2 EXPLOSION-PROTECTED DISTRIBUTION PANELS INTRODUCTION Cooper Crouse Hinds® now introduces the SpecOneTM D2Z family of corrosion-resistant, nonmetallic, NEMA 4X distribution panelboards approved worldwide for Class I, Zone 1 and Division 2 hazardous locations. Why choose SpecOne D2Z panelboards? • One product line that meets all worldwide codes and standards • Corrosion-resistant, nonmetallic, UV resistant, NEMA 4X, IP 66 construction • Power and ground-fault protection for lighting or heat-tracing circuits • Operate and view position of breakers without removing cover • Universal wiring for conduit or cable entries Technical Data Explosion Protection EEx de IIC T4, T6 AEx de IIC T4, T6 Ex de IIC T4, T6 Class I, Zone 1, Div. 2 Groups A, B, C, D 2 Certifications PTB - No. Ex-94.C.1037 UL, cUL Degree of Protection NEMA 4X IP 66 to IEC 529 UV Resistance ISO 4892 / EN 50 014 Enclosure Material Glass-reinforced polyester Temperature Ratings -55˚C to 55˚C Rated Voltage Up to 480 VAC Rated Current Max. 180 A E-mail inquiries to: d2zpanels@crouse-hinds.com KEY FEATURES 1 UL, cUL, PTB Certified for Class I, Zone 1, Division 2 hazardous areas. 2 Fiberglass-reinforced polyester enclosures: • Nonmetallic, corrosion-free. • Increased safety Ex-e protection. • Impact resistant. • NEMA 4X, IP 66 protection. • Enclosure meets UL 94-V0. • UV rated. 7 Clear, NEMA 4X window, hinged for actuation of breakers. 8 Double lockout on windows and breakers. 9 Brass plates for hub or cable gland entries. 10 Enclosures can be mounted on switchrack frames or walls. 11 Optional busbar distribution. 12 Optional pilot light indicator panel for breaker status. 13 Completely wired, ready for connection to terminal blocks. 3 Unique design allows for panels with more than 42 circuits. 4 Main disconnect switches 40, 80, 125, 180 A, or main breaker up to 100 A. 5 Optional flameproof Ex-d fusing of main disconnect. 6 Flameproof Ex-d encapsulated branch breakers: • Thermal-magnetic protection up to 40 A. • Auxiliary contacts (mechanical or electrical). • Lockout on components. • Prewired to Increase Safety Ex-e terminal blocks. • GFI branch breakers (EPDs). 10 12 11 6 3 2 4 1 8 7 13 5 9 2 3 4 6 7 CONTENTS 10 11 INTRODUCTION KEY FEATURES TECHNICAL DATA BUILDING D2Z PANELS ORDERING PROCEDURE TABLE OF BUILDING A CATALOG NUMBER COMPONENT & DIMENSION INFORMATION E-mail inquiries to: d2zpanels@crouse-hinds.com 3 TECHNICAL DATA Branch Circuit Breakers 1-pole, 2-pole, 3-pole, 4-pole; with EPD protection 1-pole + Neutral, 2-pole; 2, 6, 10, 16, 20, 25, 32 and 40 Amps Explosion Protection EEx de IIC T6 AEx de IIC T6 Class I, Zone 1, Div. 2 Groups A, B, C, D Certifications UL, cUL PTB - No. Ex-94.C.1035 U PTB 98 ATEX 1087 U • Large windows permit easy viewing and quick access to breakers without opening the enclosure. • Lockouts standard for both windows and breakers. • Up to 6 single-pole breakers can be installed under one window. • NEMA 4X, IP 66 protection. • Windows lock with 5/16" (8mm) Allen key. Rated Operating Voltage Up to max. 480 VAC Rated Current Up to 40 A, See Page 10 Rated Switching Capacity 10k AIC Tripping Characteristic “B” or “K” * Tripping Current for EPDs 30 mA (up to 300 mA on request) Enclosure Materials Fiberglass-reinforced polyester Optional Auxiliary/Signal Contacts** Rated Voltage 250 VAC Rated Current 5A * “B” Branch breakers are used for all general applications such as lighting and heat-tracing. Type “K” breakers are used for MOVs and portable power. Contact factory for other applications. ** Aux contacts indicate mechanical or electrical tripping. Signal contacts indicate only electrical tripping and are used primarily on heat-tracing circuits. Branch breakers with signal contacts require next larger breaker enclosure. Main Disconnect Switch 40, 80, 125, 180 A, 4-pole Explosion Protection EEx de IIC T6 AEx de IIC T6 Class I, Zone 1, Div. 2 Groups A, B, C, D Certifications 40-180 A UL, cUL PTB 98 ATEX 1031 U • Main Switch • 40 A main switch, 4-pole, optional fusing in enclosure with window(s). • 80, 125 and 180 A main switch, 4-pole, optional fusing in enclosure. PTB - No. Ex-93C.1028 U 80 A PTB - No. Ex-85B.1055 U 125/180 A PTB - No. Ex-86B.1048 U Rated Operating Voltage Up to 690 VAC Motor Switching Capacity AC 3* Type 230 V 400 V 500 V 690 V 40 A 40 A 40 A 40 A 32 A 80 A 80 A 80 A 80 A 80 A 125 A 125 A 125 A 125 A 125 A 180 A 180 A 180 A 150 A 125 A * See IEC 947-4-1: 1990. 4 40 A E-mail inquiries to: d2zpanels@crouse-hinds.com Main Breaker Explosion Protection CIass I, Zone 1, Div. 2, Groups C, D Explosionproof CIass II, Div. 2, Groups F, G CIass III NEMA 3; 7 C, D; 12 Certifications UL, cUL Rated Current 30 to 100 A • Main Breaker Single, 3-phase Rated Voltage 120/240 VAC Main Fuse, 3-pole Explosion Protection EEx de IIC T4, T6 AEx de IIC T4, T6 Class I, Zone 1, Div. 2 Groups A, B, C, D Certifications UL, cUL PTB - No. Ex-86.B.1065 U Rated Operating Voltage Up to max. 500 VAC Rated Current Current Temperature Class 25 A T6 35 A T5 50 A T4 63 A T4 80 A T4 100 A T4 125 A T4 • Main Fuse, type NH Recommended manufacturer: Cooper Bussman type NH ØØG fuses for general use or NH ØØM for motor applications. Specify Amperage. (Fuses not provided) Pending UL certification, panels supplied with fuses PTB certified only. Standard Entries Brass gland plate with Zone 1 Myers adapter hubs: (STM series) Main Supply Branches Metric Entries (remove hubs) (1) 2" + (3) 1" (1) M 63 + (3) M 32 (9) 3/4" (9) M 25 • Universal Wiring – Zone 1 Myers® adapter hubs for conduit or Terminator™ cable glands. • Stainless Steel Hubs – available upon request. E-mail inquiries to: d2zpanels@crouse-hinds.com 5 HOW TO BUILD D2Z DISTRIBUTION PANELS Example of D2Z distribution panel with built-in components under the window. (available mounting width = 213 mm) D2Z panel with 3 mounting spaces 4 5 1 6 2 7 8 3 10 9 1 Mounting Space - 190 mm 2 Mounting Space - 190 mm 3 Mounting Space - 190 mm 4 (2) 4 pole breakers - width 106 mm ea. 5 (3) 3 pole breakers - width 70 mm ea. 6 (4) 2 pole breakers- width 53 mm ea. 7 (6) 1 pole breakers - width 35 mm ea. 8 40 A main switch, 4-pole. 1 mounting space required 9 Main fuse. 1 mounting space required in place of 1 window } available mounting width - 213 mm 10 6 Window E-mail inquiries to: d2zpanels@crouse-hinds.com ORDERING PROCEDURE STEP 1: WINDOW Determine the number of windows required from the following chart based on the number of branch breakers. Multiply breaker space by number of breakers. Round the sum total to the next highest whole number to determine required windows. i.e. For (8) 1-pole and (2) 2-pole breakers: (8 x 0.16) + (2 x 0.25) = 1.78 ➔ 2 windows required. Max. No. Per Window Branch Circuit Breakers Space Required For Each Breaker 6 1-pole .16 4 2-pole 1-pole with EPD 1-pole with signal contact .25 3 3-pole 1-pole + Neutral with signal contact 2-pole with signal contact .33 2 4-pole 2-pole with EPD 3-pole with signal contact .50 (max 40 A) STEP 2: MAIN BREAKER OR DISCONNECT SWITCH If a main breaker or disconnect switch is required, select suffix from table. Amperage Main Breaker 3-Phase Single-Phase 30 to 100 A -3M100 -2M100 specify amperage i.e. 100 A i.e. 100 A Main Switch Disconnect 40 -3S*40 -2S*40 80 -3S*80 -2S*80 125 -3S*125 -2S*125 180 -3S180 – * Add F if fuses required. Fuses supplied by others. See page 5. * Pending UL certification, panels supplied with fuses PTB certified only. E-mail inquiries to: d2zpanels@crouse-hinds.com 7 STEP 3: PANEL SIZE Determine Panel Size Based on Windows Required Number of Windows Required Type Required Main Breaker or Disconnect 1, 2 A mini panel 40 A Disconnect – Integral 3 B panel Optional – Adjacent 4-6 C panel Optional – Adjacent 7-9 D panel Optional – Adjacent Mini Panels Type Quantity of A Ordering Information for Type A Mini Panels with Main Switch 819 mm 32.25" With 40 A Disconnect Switch 273mm 10.75" With 40 A Fused Switch 40 A 3-Phase 40 A Fused 3-Phase Quantity of Single Circuits D2Z A306 *XXXXX - 3S40 D2Z A306 *XXXXX - 3SF40 6 D2Z A308 *XXXXX - 3S40 8 D2Z A310 *XXXXX - 3S40 10 D2Z A312 *XXXXX - 3S40 12 Single Phase Single Phase Quantity of Single Circuits D2Z A106 *XXXXX - 2S40 D2Z A106 *XXXXX - 2SF40 6 D2Z A108 *XXXXX - 2S40 8 D2Z A110 *XXXXX - 2S40 10 D2Z A112 *XXXXX - 2S40 12 * See page 10 to complete catalog number Panel Type B Type D Type C Type B Type C Type D Main Breaker or Disconnect Switch If Required 546 mm 21.5" 819 mm 32.25" 1092 mm 43" 8 E-mail inquiries to: d2zpanels@crouse-hinds.com STEP 4: CONDUIT/CABLE ENTRIES Determine if additional entries are required on sides B and C. All panels are supplied with bottom entries (Side A), 1 main supply and remainder as branches. Example: Size D panels with disconnect switch, have 1 main supply and 3 branch plates as standard. Main Entries Type Main Supply Branches Entries Location (1) 2" + (3) 1" A (Standard) (9) 3/4" (B panel) A (Standard) (18) 3/4" (C panel) A (Standard) (27) 3/4" (D panel) A (Standard) (9) 3/4" (9) 3/4" Branches B (Optional) left side C (Optional) left side Side C Optional Side B Optional Side A Supply Side A Branch Terminal Wiring Supply Circuits Branch Circuits Amperage mm AWG Amperage mm2 AWG 40 16 6-18 10 4 12-22 80 35 2-6 15 4 12-22 125 70 8-2/0 20 10 6-14 180 95 6-3/0 40 16 6-18 2 E-mail inquiries to: d2zpanels@crouse-hinds.com 9 HOW TO BUILD A CATALOG NUMBER Panel Family Quantity Branch Panels D2Z C Phase Circuits Quantity/ poles/amp* 3 40EAX *06340 Class I, Div. 2, Groups A, B, C, D; Zone 1, AEx & Ex de IIC panelboards Panel Type – see step 3 (No. of enclosures) (A, B, C, or D) 1 – single-phase 3 – 3-phase Circuit Breaker Total: (see page 7) (12) single-pole = 12 circuits +(6) three-pole = 18 circuits +(2) single-pole EPD = 4 circuits +(5) single-pole = 5 circuits w/ Aux contacts 39 circuits 40 circuits If an odd number, round up to an even number. Add suffix if included: E for EPD, AX for auxiliary contacts, SC for signal contacts, K for MOVs and portable power Choose Circuit Breakers (2, 6, 10, 16, 20, 25, 32 or 40 Amp) (3-pole first – Options, then 2-pole then single-pole) a. Insert Asterisk * b. Quantity is 6: 06 (if less than 10, insert 0 before quantity) c. Three-pole: 3 d. Ampere Rating (max 40): 40 (if less than 10, insert 0 before amperage) Options “E” for EPD “AX” for auxiliary contacts “SC” for signal contacts “K” for MOVs and portable power Select main breaker or disconnect switch (see step 2, pg. 7) (3-phase, 4-pole Main Switch, Fused, 125 A) Branch Entries (Side A [bottom] standard) B – Side B left side C – Side C right side Example Order Number: D2Z C 3 40EAX * 06340 * 12120 * 02120E * 05110AX-3SF125-BC (6) 3-pole /40 A (12) single-pole /20 A (2) single-pole /20 A EPD (5) single-pole /10 A = *06340 = *12120 = *02120E = *05110AX w/ Aux contacts For other panels or options, consult factory. 10 E-mail inquiries to: d2zpanels@crouse-hinds.com Main -3SF125 Branch Entries -BC SPARE COMPONENT INFORMATION Please state rated current on order: 2 , 6, 10, 16, 20, 25, 32 or 40 A. Lighting Circuits Order Code 10 k AIC, max. 480 VAC 1-pole 2-pole 3-pole 4-pole 6/window 4/window 3/window 2/window SIA 001 SIA 002 SIA 003 SIA 004 Optional: Auxiliary contact – SAH 001 Signal contact – SAS 001 (In the case of branch breakers with signal contacts, the next largest component size is used.) Example: SIA 001-20 – SAH001 Single Pole, 20 A with auxiliary contacts Please state rated current on order: 6, 10, 16, 20, 25, 32 or 40 A. Heat-Tracing Order Code EPD with 10 k AIC, 30 mA leakage, max. 480 VAC 1-pole + N 2-pole 4/window 2/window FSS 002 FSS 004 DIMENSIONS Optional: With auxiliary contact – FSH 001 With signal contact in Size 4 component – FSS 001 Example: FSS 004 - 30 - FSS 001 EPD, 30 A, 30 mA with signal contact Dimensions in mm X = mounting dimensions 211 271 271 116 X 247 X 247 116 271 155 X 247 798 275 211 X 273 271 X 793 Note: Used only for fuses on 80,125 or 180 A disconnect switches. 817 271 X 247 254 11 136 116 11 Safety Switch X 520 544 Note: Used for main breaker Note: Used only for 80, 125 or 180 A disconnect switches without fuses. Note: Used for – 40 A switch with fuses and 1 window, or – 40 A switch and 2 windows, or – 3 windows of branch breakers. E-mail inquiries to: d2zpanels@crouse-hinds.com 11 Distributed by: For more information: If further assistance is required, please contact an authorized Cooper Crouse-Hinds Distributor, Sales Office or Customer Service Department: In the U.S.: In Australia: Cooper Crouse-Hinds P.O. Box 4999 Syracuse, NY 13221 (315) 477-5531 FAX: (315) 477-5179 crouse.customerctr@crouse-hinds.com Crouse-Hinds (Australia) Pty. Ltd. 61-29-743-7000 FAX: 61-29-743-7069 sales@crouse-hinds.com.au In Asia (Singapore): CEAG Crouse-Hinds Asia Pacific Pte. Ltd. 65-297-4849 FAX: 65-297-4819 sales@cchspore.com.sg In Canada: Cooper Crouse-Hinds Canada (905) 507-4187 FAX: (905) 501-4078 In Middle East (Dubai): In Mexico: CEAG Middle East LLC 971-4-342-578 FAX: 971-4-342-640 Crouse-Hinds Domex, S.A. de C.V. 52-5-804-4000 FAX: 52-5-804-4099 In India: In Latin America/Caribbean: CEAG Flameproof Control Gears Private Ltd. 91-22-492-6355 FAX: 91-22-495-0486 Cooper Crouse-Hinds (315) 477-5787 (USA) FAX: (315) 477-5118 For the latest in new products and services, visit our web site at: In Europe (Germany): www.crouse-hinds.com CEAG Sicherheitstechnik GmbH 49-6271-81-524 FAX: 49-6271-81-329 Solutions.Worldwide. TM 4684-0100 Crouse-Hinds is a registered trademark of Cooper Industries, Inc. © 2000 Cooper Industries, Inc. Printed in U.S.A.