Instruction Leaflet IL032010EN Effective December 2015 Version 2.0 105U-G-5W wireless gateway installation guide Figure 1. Antenna Installation Antenna* 1 Wavelength (minimum) Wavelengths: 360 MHz = 32.7" (83 cm) 512 MHz = 22.8" (58 cm) Stress Relief Loop Weatherproof Connections (recommended: 3M™ 23 selfbonding tape) NOTE Refer to the user manual for important regulatory and safety information before installing and using this product. Coaxial Cable 105U-G-5W Mast CAUTION ELPRO Wireless Gateway 105U-G-5W Ethernet For continued protection against risk of fire, replace the module fuse only with the same type and rating. RX Serial TX RX Radio TX GND GND SUP2 SUP1 DIO 8 Earth Conductor at least 5 AWG (16 mm2) BAT+ GND DIO 6 OK DIO 7 DIO 4 DIO 5 DIO 2 DIO 3 DIO 1 ACT Surge Arrestor (recommended) Statutory requirements EC: Unlicensed operation limits the radio power. High gain aerials may only be used to compensate for cable losses. Antenna installation Use Figure 1 as a guide for installing an antenna and attaching it to the module. *For maximum range, install above local obstructions GND at least 11 AWG (4 mm2) Earth Stake Provide good ground connection to mast, module, and surge arrestor. If ground conditions are poor, use more than one stake. Instruction Leaflet IL032010EN 105U-G-5W wireless gateway installation guide EATON_105U-G-5W Install Guide Effective December 2015 Version 2.0 Installation Figure 2. Wiring Diagram Choose a power supply option: • 12–24 Vac, 1.5A CSA certified Class 2 * • 15–30 Vdc, 1.5A CSA certified Class 2 * • 11–15 Vdc, 2.0A • Solar panel with battery Host Protocol Connection After choosing a power supply option, wire the module as shown in Figure 2. ELPRO Wireless Gateway NNote: All I/O must be SELV. DIO channels can be wired as inputs or outputs. 105U-G-ET1 Ethernet *Backup battery must be used if radio power is set to 2W or higher. RX When the wiring is completed, connect the module to a computer (PC) and configure it using the configuration software. For details, refer to the user manual. Serial TX RX Radio TX Before operating the module, read the sections on operation and configuration in the user manual to take advantage of all product features. ACT OK BAT+ GND SUP2 SUP1 GND DIO 8 DIO 7 DIO 6 DIO 5 DIO 4 DIO 3 DIO 2 DIO 1 GND SUP1 SUP2 SUP1 Do not disconnect while circuit is live unless area is known to be non-hazardous. GND WARNING EXPLOSION HAZARD 2A – + DC Supply 9–30 Vdc, 16 Vac To Earth Connection Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton’s wireless business www.eaton.com/wireless – + – + AC Supply 12–24 Vac Do not earth SUP1 or SUP2 connection. 12V Backup Battery (optional; up to 100 Ah) Digital Input Voltage-Free Contact or Transistor Device To Earth Connection + – Digital Output Max. 30 Vdc, 500 mA DC Relay Supply © 2014 Eaton All Rights Reserved Printed in USA Publication No. IL032010EN December 2015 Eaton is a registered trademark. All other trademarks are property of their respective owners.