R1150-20-1 Communications Point Data Base GridAdvisor

advertisement
GridAdvisor
Reference Information
GridAdvisor Smart Sensor Series II
Communications
R1150-20-1
Communications Point Data Base
for
Communications Protocol DNP3
For Use With Eaton’s Cooper Power Systems
GridAdvisor Smart Sensor Series II
December 2013 • New Issue
GridAdvisor Series II smart sensor Device Profile Data Dictionary
GridAdvisor Series II smart sensor DNP3 Map Points
October 11, 2013
v1.0
THE INFORMATION CONTAINED IN THIS DOCUMENT IS THE PROPERTY OF COOPER INDUSTRIES, INC.
UNAUTHORIZED REPRODUCTION OR MODIFICATION IS PROHIBITED.
Document
1.00
Date
10/11/2013
Description
Initial Release
Page 1
Cover Page
GridAdvisor Series II smart sensor Device Profile Data Dictionary
INPUT SUBSYSTEM
Binary Inputs
Description
Battery Charger State
Charging Status
Power Flow Direction
Fault Direction
Loss of Current Detect
Momentary Fault Detect
Sustained Fault Detect
Overcurrent Detect
Overcurrent Reset Detect
V Swell Alarm
V Sag Alarm
V in Window Alarm
Entering Normal Mode
Entering Low Power Mode
Default Static Variation
Obj 01 Var 1 Binary Input – Packed format
Index
Hex Index
Default
Event
Class
00
01
02
03
04
05
06
07
08
09
10
11
12
13
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Page 2
Default Event Variation
Obj 02 Var 2 Binary Input Event – With absolute time
Binary Inputs
GridAdvisor Series II smart sensor Device Profile Data Dictionary
INPUT SUBSYSTEM
Analog Inputs
Description
Battery Voltage
Temperature
Nominal Current Unfiltered
Nominal Current Filtered
Not Used
Fault Current
Demand Current
Nominal Voltage
EC/I0
RSSI
Serial Number Low
Serial Number High
Nominal Current Hi-Res Unfiltered
Nominal Current Hi-Res Filtered
Demand Current Hi-res
Default Static Variation
Obj 30, see table for variation
Index
Hex Index
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
Default Event Variation
Obj 32, see table for varation
Default
Division
Event
Scale Factor
Class
2
0
2
2
0
0
0
2
0
0
0
0
2
2
0
1000
100
10
10
1
10
10
10
1
1
1
100
100
100
Units
Obj 30 Default
Variation
Obj 32 Default
Variation
Volts
°C
Amps
Amps
Amps
Amps
kV
dB
dBm
Amps
Amps
Amps
2
2
2
2
2
2
2
2
2
3*
3*
3*
3*
3*
2
2
2
2
2
2
2
2
2
3*
3*
3*
3*
3*
* Values overrange for 16-bit variations; device will always respond with 32-bit variations.
Page 3
Analog Inputs
GridAdvisor Series II smart sensor Device Profile Data Dictionary
INPUT SUBSYSTEM
Counters
Description
Total Fault Counts
Momentary fault counts
Sustained fault counts
AC loss counts
AC restore counts
di/dt counts
Default Static Variation
Obj 20 Var 2 Counter – 16-bit with flag
Index
Hex Index
Default
Event
Class
00
01
02
03
04
05
00
01
02
03
04
05
1
1
1
1
1
1
Page 4
Default Event Variation
Obj 22 Var 2 Counter Change – 16-bit with flag
Counters
GridAdvisor Series II smart sensor Device Profile Data Dictionary
OUTPUT SUBSYSTEM
Analog Outputs
Description
AC Loss Cycles
AC Inrush Delay
Fault Delay Time
Demand Interval
UNS Reporting Interval
didt Trip Level
FCI OverCurrent Alarm Threshold
FCI Reset OverCurrent Alarm Threshold
Voltage Swell Alarm Threshold
Voltage Sag Alarm Threshold
Fault LED Indication Period
Minimum Current Threshold
CBM OverCurrent Alarm Threshold
CBM Reset OverCurrent Alarm Threshold
Default Static Variation
Obj 40 Var 2 Analog Output Status – 16-bit with flag
Index
Hex Index
Division
Scale Factor
Units
00
01
02
03
04
05
06
07
08
09
10
11
12
13
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Cycles
Seconds
Seconds
Minutes
Minutes
Amps
Amps
Amps
%
%
Hours
Amps
Amps
Amps
Page 5
Default Event Variation
None Supported
Analog Outputs
GridAdvisor Series II smart sensor Device Profile Data Dictionary
OUTPUT SUBSYSTEM - Control Output Relay Block Operations and Status
Description
Index Hex Index Obj Var
Desc
Operation Type
Latch ON/OFF, Null
Pulse ON, Null
Pulse ON, Null
Pulse ON, Null
Pulse ON, Null
Pulse ON, Null
Pulse ON, Null
Pulse ON, Null
Pulse ON, Null
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
00
01
02
03
04
05
06
07
08
00
01
02
03
04
05
06
07
08
12
12
12
12
12
12
12
12
12
01
01
01
01
01
01
01
01
01
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
00
01
02
03
04
05
06
07
08
00
01
02
03
04
05
06
07
08
10
10
10
10
10
10
10
10
10
02
02
02
02
02
02
02
02
02
Status
Status
Status
Status
Status
Status
Status
Status
Status
Description
DNP Unsolicited Reporting Enable
Clear Counters
Update Firmware
Copy Current Image to Backup
Restore To Backup Image
Remote Reed Switch
Reset Targets
Force OTASP
Force Sleep (Shelf) Mode
DNP Unsolicited Reporting Enable
Clear Counters
Update Firmware
Copy Current Image to Backup
Restore To Backup Image
Remote Reed Switch
Reset Targets
Force OTASP
Force Sleep (Shelf) Mode
Page 6
CROB
GridAdvisor Smart Sensor Series II Communications Protocol DNP3
©2013 Eaton. All Rights Reserved.
Eaton and Cooper Power Systems are valuable trademarks of
Eaton in the U.S. and other countries. You are not permitted to use
Eaton trademarks without the prior written consent of Eaton.
One Cooper | www.cooperpower.com | Online
2300 Badger Drive
Waukesha, WI 53188
Download