GridAdvisor Reference Information GridAdvisor Smart Sensor Series II Communications R1150-20-1 Communications Point Data Base for Communications Protocol DNP3 For Use With Eaton’s Cooper Power Systems GridAdvisor Smart Sensor Series II December 2013 • New Issue GridAdvisor Series II smart sensor Device Profile Data Dictionary GridAdvisor Series II smart sensor DNP3 Map Points October 11, 2013 v1.0 THE INFORMATION CONTAINED IN THIS DOCUMENT IS THE PROPERTY OF COOPER INDUSTRIES, INC. UNAUTHORIZED REPRODUCTION OR MODIFICATION IS PROHIBITED. Document 1.00 Date 10/11/2013 Description Initial Release Page 1 Cover Page GridAdvisor Series II smart sensor Device Profile Data Dictionary INPUT SUBSYSTEM Binary Inputs Description Battery Charger State Charging Status Power Flow Direction Fault Direction Loss of Current Detect Momentary Fault Detect Sustained Fault Detect Overcurrent Detect Overcurrent Reset Detect V Swell Alarm V Sag Alarm V in Window Alarm Entering Normal Mode Entering Low Power Mode Default Static Variation Obj 01 Var 1 Binary Input – Packed format Index Hex Index Default Event Class 00 01 02 03 04 05 06 07 08 09 10 11 12 13 00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Page 2 Default Event Variation Obj 02 Var 2 Binary Input Event – With absolute time Binary Inputs GridAdvisor Series II smart sensor Device Profile Data Dictionary INPUT SUBSYSTEM Analog Inputs Description Battery Voltage Temperature Nominal Current Unfiltered Nominal Current Filtered Not Used Fault Current Demand Current Nominal Voltage EC/I0 RSSI Serial Number Low Serial Number High Nominal Current Hi-Res Unfiltered Nominal Current Hi-Res Filtered Demand Current Hi-res Default Static Variation Obj 30, see table for variation Index Hex Index 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E Default Event Variation Obj 32, see table for varation Default Division Event Scale Factor Class 2 0 2 2 0 0 0 2 0 0 0 0 2 2 0 1000 100 10 10 1 10 10 10 1 1 1 100 100 100 Units Obj 30 Default Variation Obj 32 Default Variation Volts °C Amps Amps Amps Amps kV dB dBm Amps Amps Amps 2 2 2 2 2 2 2 2 2 3* 3* 3* 3* 3* 2 2 2 2 2 2 2 2 2 3* 3* 3* 3* 3* * Values overrange for 16-bit variations; device will always respond with 32-bit variations. Page 3 Analog Inputs GridAdvisor Series II smart sensor Device Profile Data Dictionary INPUT SUBSYSTEM Counters Description Total Fault Counts Momentary fault counts Sustained fault counts AC loss counts AC restore counts di/dt counts Default Static Variation Obj 20 Var 2 Counter – 16-bit with flag Index Hex Index Default Event Class 00 01 02 03 04 05 00 01 02 03 04 05 1 1 1 1 1 1 Page 4 Default Event Variation Obj 22 Var 2 Counter Change – 16-bit with flag Counters GridAdvisor Series II smart sensor Device Profile Data Dictionary OUTPUT SUBSYSTEM Analog Outputs Description AC Loss Cycles AC Inrush Delay Fault Delay Time Demand Interval UNS Reporting Interval didt Trip Level FCI OverCurrent Alarm Threshold FCI Reset OverCurrent Alarm Threshold Voltage Swell Alarm Threshold Voltage Sag Alarm Threshold Fault LED Indication Period Minimum Current Threshold CBM OverCurrent Alarm Threshold CBM Reset OverCurrent Alarm Threshold Default Static Variation Obj 40 Var 2 Analog Output Status – 16-bit with flag Index Hex Index Division Scale Factor Units 00 01 02 03 04 05 06 07 08 09 10 11 12 13 00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Cycles Seconds Seconds Minutes Minutes Amps Amps Amps % % Hours Amps Amps Amps Page 5 Default Event Variation None Supported Analog Outputs GridAdvisor Series II smart sensor Device Profile Data Dictionary OUTPUT SUBSYSTEM - Control Output Relay Block Operations and Status Description Index Hex Index Obj Var Desc Operation Type Latch ON/OFF, Null Pulse ON, Null Pulse ON, Null Pulse ON, Null Pulse ON, Null Pulse ON, Null Pulse ON, Null Pulse ON, Null Pulse ON, Null Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output 00 01 02 03 04 05 06 07 08 00 01 02 03 04 05 06 07 08 12 12 12 12 12 12 12 12 12 01 01 01 01 01 01 01 01 01 CROB CROB CROB CROB CROB CROB CROB CROB CROB Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output 00 01 02 03 04 05 06 07 08 00 01 02 03 04 05 06 07 08 10 10 10 10 10 10 10 10 10 02 02 02 02 02 02 02 02 02 Status Status Status Status Status Status Status Status Status Description DNP Unsolicited Reporting Enable Clear Counters Update Firmware Copy Current Image to Backup Restore To Backup Image Remote Reed Switch Reset Targets Force OTASP Force Sleep (Shelf) Mode DNP Unsolicited Reporting Enable Clear Counters Update Firmware Copy Current Image to Backup Restore To Backup Image Remote Reed Switch Reset Targets Force OTASP Force Sleep (Shelf) Mode Page 6 CROB GridAdvisor Smart Sensor Series II Communications Protocol DNP3 ©2013 Eaton. All Rights Reserved. Eaton and Cooper Power Systems are valuable trademarks of Eaton in the U.S. and other countries. You are not permitted to use Eaton trademarks without the prior written consent of Eaton. One Cooper | www.cooperpower.com | Online 2300 Badger Drive Waukesha, WI 53188