Room Controller - Conference Room w/Daylight Dimming and BMS Output

advertisement
Room Controller - Conference Room
w/Daylight Dimming and BMS Output
Summary
Proper lighting that emphasizes daylighting with natural light provides a more focused meeting environment. This application illustrates how conference rooms can
use basic dimming in conjunction with natural light entering the space, while providing Scene Control/Automatic Off to achieve energy savings up to 60% and achieve
higher quality lighting. Providing optional control of individual lighting zones and HVAC output will allow for even greater energy savings.
The Room Controller QuicKit is shipped preconfigured to work out-of-the-box minimizing installation and setup time, while ensuring maximum energy savings. Using this design guide to specify your room with a Room Controller QuicKit catalog number will guarantee that after installation the lighting control system will work
immediately as defined on this application guide.
Room Controller Sample room layout (10ʹ x 10ʹ)
Half Lights
Full Lights
Room Controller QuicKit
Raise
Lower
Half
Lights
All Off
Full Lights
Half Lights
Raise
Full Lights
Lower
Raise
All Off
Lower
All Off
RCQK-OS3E-CR2-ZAD-W1-D1-B-W
RC3DE
Half Lights
Full Lights
OCC-RJ45
(BMS output/Egress Control)
RC3DE
(3 Relay + 3 Dimmer +
Normal Power 1 Emergency)
Raise
Half Lights
Lower
Full
Lights
All
Off
Product Legend
Qty1: RC3DE
3 On/off relays + 3 dimmers + 1 Emergency Relay
Raise
General
Zone 1 UP
Meeting
Zone 1 DN
Whiteboard
Zone 2 UP
Presentation
Zone 2 DN
All Off
Zone 3 UP
Zone 3 DN
Connection
OCC-RJ45
(Connection to any Greengate sensor)
Lower
RC3DE
RC3DE
All Off
General
Meeting
Whiteboard
Presentation
RC-6TSB-ZAD-*
(Pre-engraved Wallstation)
RC3DE
All Off
OAWC-DT-120W
(Wall Corner Occupancy Sensor)
Half Lights
Half Lights
Full Lights
Full Lights
Raise
Raise
Lower
Lower
All Off
All Off
RC3DE
RC3DE
Half lights
Full lights
RC-6TSB-CR2-*
(Pre-engraved Wallstation)
Half Lights
Full Lights
All Off
Raise
Lower
All Off
RC3DE
RC3DE
Half Lights
Full Lights
Raise
Lower
All Off
Load 3
RC3DE
Dimmer 3
RC3DE
Qty1: RC-5TsB-CR2-W
General, Meeting, whiteboard, presentation, all off)
Qty:1 RC-6tsb-zad-W
Zone 1 UP, Zone 1 DN, Zone 2 UP, Zone 2 DN, Zone 3 UP,
Zone 3 DN
Qty1: DSRC-FMOIR
Daylight Sensor
Qty1: OAWC-DT-120W
Wall Corner mount vacancy sensor
Qty1: OCC-RJ45
Occupancy sensor RJ45 connector
Load 2
Qty1: OCC-RJ45
BMS or egress connector
Dimmer 2
Qty1: GGRJ45-03-G
Quickconnect cable 3’
Entry
Lighting
All Off
Qty2: GGRJ45-10-G
Quickconnect cable 10’
Load 1
Dimmer 1
Qty2: GGRJ45-25-G
Quickconnect cable 25’
DSRC-FMOIR
(Multi-zone Daylight Sensor)
RC3D
Single box packaging with wiring detail
and installation
Entry
Lighting
Entry
Lighting
All Off
All Off
Recessed Fixture
General
Entry
Exam
Lighting
Reading
All Off
For guaranteed compatibility refer to preferred
Cooper lighting fixture information below.
All Off
Entry
Lighting
All Off
TV
CHANNEL
VOLUME
cc
1
2
4
3
5
7
6
8
9
0
PREV
SLEEP
MUTE
OPTION
2
Entry
Entry
Lighting
Lighting
1
3
ALL
ON/OFF
All Off
All Off
Control sequence
RC3D
RC3D
• Scene Control/Automatic Off
1. All On, Dimmers set to: 100%,
80%, 100%
Entry
Lighting
All Off
1. Press and hold raise lighting 5%
General
Whiteboard
• Individual Zone Raise/Lower control
Quiet Time •
A/V Mode
Raise
RC3D
Lower
General
2. All On, DimmersRC3D
set to: 80%, 20%, 100%
Entry
Lighting
Zone 1 UP
All Off
• Occupancy based HVAC or Egress control
Meeting
Whiteboard
• Automatic multi-zone daylight dimming out-of-the-box
Presentation
Zone 1 DN
Zone 2 UP
3. All On, Dimmers set to: RC3D
RC3D
50%, 100%, 25%
Zone 2 DN
General
Exam
General
Reading
2. Press and hold lowers lighting 5%
3. Press and hold raise lighting 5%
4. Press and hold lowers lighting 5%
Exam
All
Off
• Automatic Demand Response 10%-40% reduction based on input
All Off
Zone 3 UP
Reading
All Off
4. All On, Dimmers set to: 30%, 0%, 25%
• High-end trim/tuning to define target light levels
UL924
5. All Off
UL924 warn Offs and timers to ensure maximum efficiency and • After-hours
UL924
RC-5TSB-CR2-W
savings
Conference Room Wallstation
5. Press and hold raise lighting 5%
6. Press and hold lowers lighting 5%
RC3D
General
Exam
TV
CHANNEL
VOLUME
Reading
cc
All
1 Off2
CHANNEL
TV 3
General
VOLUME
4 cc
5 6
7 Exam
8 9
1
2 3
Reading
0
4
5 6
PREV
MUTE
SLEEP
OPTION
7 All
28Off 9
1
3
0
PREV
MUTE
ALL
ON/OFF
SLEEP
OPTION
2
1
3
ALL
ON/OFF
RC3D
General
TV
General
Exam cc
Exam
1
Reading
2 3
Reading
6
All4Off 5
7 All8Off 9
CHANNEL
VOLUME
TV
CHANNEL
1
RC-6TSB-ZAD-W
Individual Dimming Wallstation
VOLUME
0 cc
PREV
SLEEP
MUTE
OPTION
12
2
3
5
4
ALL
ON/OFF
7
3
6
8
9
0
PREV
SLEEP
Integrated capabilities
Zone 3 DN
MUTE
OPTION
2
Cooper Lighting Guaranteed Compatible Fixtures
1
3
ALL
ON/OFF
General
General
Whiteboard
Exam
General
Quiet
Time •
Reading
TV
Whiteboard
All Off
A/V
Mode
CHANNEL
TV
VOLUME
cc
CHANNEL
VOLUME
Quiet Time
Raise
cc •
1
2
3
Metalux LED
A/V Mode
1
2
Lower
4
5
4
7Raise8
7
Lower
0
PREV
SLEEP
1
3
6
5
9
8
6
9
MUTE
0
PREV
MUTE
OPTION
2
SLEEP
3
2
1
OPTION
3
ALL
ON/OFF
ALL
ON/OFF
Room Controller Office Lighting Layouts
General
Exam
Metalux LFL
Reading
UL924
All Off
General
Room Controller Office Lighting Layouts
Whiteboard
TV
CHANNEL
VOLUME
Quiet Time •
cc
A/V Mode
1
2 3
General
Raise4
5 6
Whiteboard
7
8 9
Lower
Quiet Time
•
0
Corelite LED
PREV
MUTE
SLEEP
A/V Mode
2
1
Raise
OPTION
3
ALL
ON/OFF
Room Controller OfficeLighting Layouts
Lower
Corelite LFL
CHANNEL
TV
VOLUME
cc
1
2
5
6
8
9
0
PREV
SLEEP
Occupancy/Vacancy
Sensing
Daylighting
Control
Manual
Control
Integration
3
4
7
ALL
ON/OFF
Refer to these Cooper Lighting data sheets for lighting layouts and illuminance
value information.
General
Whiteboard
Quiet Time •
A/V Mode
Raise
www.coopercontrol.com
Lower
General
Whiteboard
Quiet Time •
A/V Mode
1
Room Controller Office Lighting Layouts
MUTE
OPTION
2
General1
3
General
Whiteboard
Whiteboard
Quiet Time •
Quiet Time •
A/V Mode
A/V Mode
Raise
Raise
Lower
Lower
Demand
Response
Raise
Lower
Room Controller - Conference Room
w/Daylight Dimming and BMS Output
Room Controller and Smart Devices use Click & Go technology
The RC3D will automtically recognize any smart device connected with the QuickConnect cable (provided) and start working immediately upon power up with no
programming required. The RC3D defaults to Manual On/Automatic Off vacancy sensor mode for maximum energy savings. Office stations provide On/Off control
of the Yellow, Red and Purple loads as well as manual Raise/Lower of all dimmers.
The daylight sensor will automatically provide multi-zone daylight dimming in the space. (Remote adjustments can be made later.)
*Refer to Room Controller website for more information on other integral no programming required benefits like Demand Response, Solatube Control, Egress Control, BMS Output, Alert Mode, Emergency Lighting Control, and Slider Stations.
WHT/ORG or WHT/BLK
Neutral
BLACK - Hot
(120/277 VAC)
YELLOW
Lighting Load (1)
RED
Lighting Load (2)
PURPLE
Lighting Load (3)
BLUE - Relay In
(120/277 VAC)
Requires 0-10V
dimming ballasts
Violet - Dimmer 1
Gray - Dimmer 1
Violet - Dimmer 2
Gray - Dimmer 2
Violet - Dimmer 3
Gray - Dimmer 3
0-10V Dimming Zone Note:
The 0-10V dimming zones within the
Room Controller can be wired and
controlled independent of the connected
loads. This allows a each load to have a
dedicated 0-10V dimming zone or a single
load to have up to three 0-10V dimming zones.
QuickConnect coupler
(GGRC-COUPLER)
BMS/ Egress Output:
Occupancy status output to the Building
Management System or other 3rd party
system require no programming of the
Room Controller and occurs when ever
there is occupancy in the room
regardless of light output status.
(OCC-RJ45)
Adjustable daylight
sensor dome
Quick connect cables are
pre-terminated and included
in the Room Controller
QuicKit and measured to fit
typical room layouts
Daylight sensor
(DSRC-FMOIR)
*Immediately provides multi-zone
daylight dimming upon powerup
Allows connection to
any Greengate
Occupancy/Vacancy
Sensor
(OCC-RJ45)
Button 1: Load (1), (2), (3) ON, Dimmer 1: 100%,
Zone 1 UP
General
Dimmer 2: 80%, Dimmer 3: 100%
Button 1: Press and hold increase Zone 1 lighting 5%
Meeting
Zone 1 DN
Button 2: Press and hold decrease Zone 1 lighting 5%
Button 2: Load (1), (2), (3) ON, Dimmer 1: 80%,
Whiteboard
Zone 2 UP
Button 3: Press and hold increase Zone 2 lighting 5%
Dimmer 2: 20%, Dimmer 3: 100%
Presentation
Zone 2 DN
Button 4: Press and hold decrease Zone 2 lighting 5%
Button 3: Load (1), (2), (3) ON, Dimmer 1: 50%,
Zone 3 UP
All Off
Button 5: Press and hold increase Zone 3 lighting 5%
Dimmer 2: 100%, Dimmer 3: 25%
Zone 3 DN
Button 6: Press and hold decrease Zone 3 lighting 5%
Button 4: Load (1), (2), (3) ON, Dimmer 1: 30%,
Dimmer 2: 0%, Dimmer 3: 25%
Button 5: Load (1), (2), (3) OFF
RC-5TSB-CR2-*RC-6TSB-ZAD-*
Office Station Office Station
Dual Technology
Wall Corner
Occupancy/Vacancy Sensor
(OAWC-DT-120W)
*Defaults to vacancy sensor mode
Manual On/Automatic Off (all loads)
for maximum energy savings
Cooper Controls
203 Cooper Circle
Peachtree City,
GA 30269. USA
Tel: +1-800-553-3879
Fax: +1-800-954-7016
Email: controls@cooperindustries.com
Website: www.coopercontrol.com
Room Controller - RC3D
Three Relay + Three Dimmers Wiring Diagram
Drawing Name:
RC3D-Conference-BMS.dwg
www.coopercontrol.com
2
Drawing Date:
1/10/2013
Room Controller - Conference Room
w/Daylight Dimming and BMS Output
Mounting The Room Controller
The Room Controller mounts above the ceiling in the space it is controlling, typically above the door to the room. The Room Controller includes breakouts for
direct conduit connection limiting the need for additional junction boxes. Mount the Room Controller using the keyhole slots at the top and secure to the wall using
the holes at the bottom of the Room Controller.
Connect conduit to the line voltage breakout connections and connect the line and load wires. Connect low voltage cables either through the low voltage breakout
openings or by connecting low voltage conduit to the breakouts on the low voltage side of the Room Controller.
Sample Placement Diagram
Daylight Sensor Ceiling Location
(for example purposes only)
1. Mount the daylight sensor one to two times the window height from the window wall.
2. Position the sensor so its arrow is pointed toward
the nearest window.
3. Ensure the daylight sensor is not obstructed or
looking directly at electric light.
4. For narrow spaces mount the daylight sensor near
the window facing into the space.
Sample Placement Diagram
(for example purposes only)
Room Controller
(above entry door)
Wall/Corner Mount
Occupancy Sensor
Additional
Wallstation
General On
AV Mode
Whiteboard
Quiet Time
Raise
Lower
Entry
Wallstation
General On
Off
Window
Daylight
Sensor
60°
Area viewed by
daylight sensor
Occupancy sensor
Coverage Diagram (OAWC-DT-120W)
24’ (7.3 mm)
Wiring Diagram
20’ (6 mm)
OCC-RJ45
Room Controller
Normal Power
(BMS/ Egress
Output)
(Above Entry Door)
(Line In & Load Out)
24’ (7.3 mm)
20’ (6 mm)
12’ (3.7 mm)
RC3D
Minor Motion, IR
8’ (2.4 mm)
0
8’ (2.4 mm)
(low voltage, class 2)
Major Motion, IR
Minor Motion, Ultrasonic
12’ (3.7 mm)
12’ (3.7 mm)
8’ (2.4 mm)
0
8’ (2.4 mm)
OCC-RJ45
Major Motion, Ultrasonic
Minor Motion, IR
Major Motion, IR
Maximum coverage area may
Minor
Ultrasonic
varyMotion,
somewhat
according to room
shapeMotion,
and theUltrasonic
presence of obstacles.
Major
12’ (3.7 mm)
0-10V Dimmer Wiring
(Dimming Models Only)
The NEMA WD 7 Guide and robotic
method coverage
were utilized
verify
Maximum
areatomay
coverage
patterns.
vary somewhat
according
to room
shape and the presence of obstacles.
24’ (7.3 mm)
(Any Greengate
Occupancy Sensor)
20’ (6 mm)
10 ft
(3 mm)
Wallstation
10 ft
(3 mm)
(Entry)
24’ (7.3 mm)
24 ft
6 ft
15 ft
20’ (6 mm)
(1.7 mm) (4.6 mm) (7.3 mm)
50 ft
(15.3 mm)
The NEMA WD 7 Guide and robotic
method were utilized to verify
coverage patterns.
Half Lights
24 ft
6 ft
15 ft
(1.7 mm) (4.6 mm) (7.3 mm)
Full Lights
Raise
Lower
50 ft
(15.3 mm)
All Off
Connections
Room Controller and Smart Devices
use Click & Go Connections
Room Controller 0-10V Dimming Connections
Dimmer 1: Near the Window
Dimmer 2: Middle of Room
Dimmer 3: Far from Window
-
Dimmer 3
+
-
Dimmer 2
+
-
Dimmer 1
+
The daylight sensor will automatically provide multi-zone daylight dimming based on this wiring configuration
0-10V Dimming
1
0-10V Gray (-)
0-10V Violet (+)
www.coopercontrol.com
3
2
5
34
6
1. Wallstations (up to four)
2. Slider Station Connection (one)
3. Occupancy Sensors (up to two)
4. Daylight Sensor (one)
5. Receptacle Control or BMS Output
6. Switchpack (controlled with Load 1 for
alternate voltage)
Room Controller - Conference Room
w/Daylight Dimming and BMS Output
Ordering
RCQK
-
OS3E
- CR2 - ZAD
-
W1
-
D1
-
B
-
W
Room Controller
Daylight
Station Color
QuicKit
D1 - Multi-zone Daylight Sensor
DH - Multi-zone Daylight Sensor w/
Handheld Remote
W - White
G - Gray
V - Ivory
B - Black
Office Stations (Choose up to 4)
Types of Space
and Control
OS - Office Switching (RC3)
OS2 - Office 2 Zone Dimming (RC3D2)
OS3 - Office 3 Zone Dimming (RC3D)
OS3E - Office 3 Zone Dimming and
and Emergency Relay (RC3DE)
OS1 - Half Lights, Full Lights, All Off
(3 Large Buttons)
OS2 - Half Lights, Full Lights, Raise, Lower, All Off †
(5 Small Buttons)
OS3 - Half Lights, Full Lights, Under Cabinet, Raise, Lower, All Off †
(6 Small Buttons)
OS4 - All On, All Off (2 Large Buttons)
CR1 - General, Meeting, Whiteboard, Presentation, Raise, Lower
(6 Small Buttons - Scenes)
CR2 - General, Meeting, Whiteboard, Presentation, All Off (5 Small Buttons - Scenes)
SS1 - Slider Station ††
ZAD - Zone 1 UP, Zone 2 DN, Zone 3 UP, Zone 3 DN
(6 Small Buttons - Scenes)
Occupancy Sensor
C1 - Ceiling DT 2000 sq. ft.
C2 - Ceiling PIR 1500 sq. ft.
C3 - Ceiling DT 1000 sq. ft.
W1 - Wall Corner DT
W2 - Wall Corner PIR
W3 - Hallway PIR
Options
P - Plug Load
B - BMS/Egress
*Catalog number automatically includes low voltage
connection cable, wallplates and connectors based on room
type and configuration.
Pre-defined Wallstation Model numbers
Half lights
Half Lights
Half Lights
Full Lights
Full Lights
Raise
Undercabinet
Lower
Raise
All Off
Lower
All Off
Lower
All On
Full lights
All Off
RC-3TLB-OS1
RC-5TSB-OS2
All Off
RC-6tsb-OS3
RC-2tlb-OS4
General
General
Meeting
Meeting
Zone 1 DN
Whiteboard
Whiteboard
Zone 2 UP
Presentation
Presentation
Zone 2 DN
Raise
All Off
Zone 3 UP
Zone 1 UP
Zone 3 DN
RC-6tsb-cr1
RC-5tsb-cr2
RC-6tsb-ZAD
*For site specific engraving, please see the Room Controller
Wallstation custom engraving form on the Cooper Controls
website
Applications
Conference Room Application Button Functionality
Program
No.
Button Text
Control
Type
Function
(Unless a target level is indicated, the dimmer output
will default to daylight sensor control)
12
General
Preset
Load 1 (yellow) ON, Load 2 (red) ON, Load 3 (purple) ON
Dimmer 1: 100%, Dimmer 2 80%, Dimmer 3 80%
Solatube Open (RC3DE only)
13
Meeting
Preset
Load 1 (yellow) ON, Load 2 (red) ON, Load 3 (purple) ON
Dimmer 1: 80%, Dimmer 2 20%, Dimmer 3 100%
Solatube Open (RC3DE only)
14
Whiteboard
Preset
Load 1 (yellow) ON, Load 2 (red) ON, Load 3 (purple) ON
Dimmer 1: 50%, Dimmer 2: 100%, Dimmer 3: 50%
Solatube Closed (RC3DE only)
15
Presentation
Preset
Load 1 (yellow) ON, Load 2 (red) ON, Load 3 (purple) ON
Dimmer 1: 30%, Dimmer 2: 0%, Dimmer 3: 25%
Solatube Closed (RC3DE only)
6
Raise
Raise
Raise All Dimmers
7
Lower
Lower
Lower All Dimmers
16
All On
Preset
Load 1 (yellow) ON, Load 2 (red) ON Load 3 (purple) ON
All Dimmers 100%
8
All Off
Preset
Load 1 (yellow) OFF, Load 2 (red) OFF, Load 3 (purple) OFF
Solatube closed (RC3DE only)
Slider
Raise and Lower All Dimmers
Slider
†
†
††
Catalog #
Type
Project
†
These dimming wallstations can only be used with dimming Room Controllers (RC3D, RC3D2, RC3DE)
†† Slider stations can not be used if a wallstation with Raise/Lower buttons are used
Comments
Prepared by
www.coopercontrol.com
4
ACC130077
Date