Room Controller - Private Office Switching with BMS Output

advertisement
Room Controller - Private Office
Switching with BMS Output
Summary
Basic code compliance requires automatic turn-off of lighting as well as a method for manual and/or automatic control within the space. Office spaces 250 sq. ft. or
less must have automatic off within 30 minutes of vacancy. Providing manual and bi-level control of lighting can provide up to 66% energy savings. Including BMS/
HVAC control based on occupancy status further provides additional energy savings opportunities.
The Room Controller QuicKit is shipped preconfigured to work out-of-the-box minimizing installation and setup time, while ensuring maximum energy savings.
Using this design guide to specify your room with a Room Controller QuicKit catalog number will guarantee that after installation the lighting control system will work
immediately as defined on this application guide.
Half Lights
Full Lights
Raise
Lower
All Off
Room Controller Sample room layout (10ʹ x 10ʹ)
Half Lights
Full Lights
Raise
Lower
AllHalf
Off Lights
Full Lights
Raise
Lower
RC3DE
All Off
Room Controller QuicKit
Half Lights
Full Lights
Raise
Lower
All Off
Half Lights
Full Lights
RCQK-OS-OS1-W1-B-W
Raise
Lower
Half Lights
All Off
Full Lights
Raise
Product Legend
Lower
RC3DE
All Off
OCC-RJ45
(BMS Output/Egress Control)
Normal power
connection
RC3DE
RC3DE
Half Lights
Full Lights
Raise
OCC-RJ45
(Connection to any Greengate sensor)
RC3
(3 Relay)
Lower
All Off
RC3DE
Half Lights
RC3DE
Full Lights
Half Lights
Full Lights
All Off
RC-3TLB-OS1-*
(Pre-engraved Wallstation)
RC3
Qty1: RC3
3 On/Off relays
Raise
Lower
OAWC-DT-120W
(Wall Corner Occupancy Sensor)
All Off
RC3DE
Qty1: RC-3TlB-OS1-W
Half lights, full lights, all off
Qty1: OAWC-DT-120W
Wall Corner vacancy sensor
RC3DE
Qty1: OCC-RJ45
Occupancy sensor RJ45 connector
Load 1
Qty1: OCC-RJ45
BMS/HVAC Occupancy output
Qty1: GGRJ45-10-G
Quickconnect cable 10’
Qty2: GGRJ45-50-G
Quickconnect cable 50’
Single box packaging with wiring detail
and installation
Entry
Lighting
All Off
Load 3
Load 2
Recessed Fixtures
Entry
Lighting
All Off
For guaranteed compatibility refer
to preferred Cooper lighting fixture
information below.
Entry
Lighting
All Off
Entry
Lighting
RC3D
All Off
Entry
Lighting
All Off
Entry
Lighting
All Off
RC3D
General
Exam
Entry
Lighting
Reading
Control sequence
All Off
All Off
• Manual On/Automatic Off or Automatic On (50%)/Automatic Off
RC3D
Entry
Lighting
TV
CHANNEL
VOLUME
cc
RC3D
1
2
All Off
4
• Providing users with wall-based manual controls to adjust the lighting levels to
meet their needs
3
5
7
6
8
9
0
PREV
SLEEP
MUTE
OPTION
2
1
3
ALL
ON/OFF
Half lights
1. Preset - Load 1 On, Load 2 Off
RC3D
General
Exam
RC3D
Reading
• Provides automatic 30 minute Off after the space is vacant
Full lights
• After-hours warn Offs and timers to ensure maximum efficiency and savings
All Off
All Off
2. Preset - Load 1, 2, 3 On
General
Whiteboard
Quiet Time •
A/V Mode
Raise
Lower
RC3D
3. All Loads Off
General
Exam
Reading
• Occupancy
based BMS integration for HVAC control
UL924
UL924
TV
All Off
CHANNEL
VOLUME
cc
1
2 3
General
4
5
6
Exam
7
8
9
Reading
0
PREV
MUTE
All Off
SLEEP
OPTION
2
1
3
ALL
ON/OFF
RC3D
UL924
RC-3TLB-OS1
General
Exam
ReadingTV
CHANNEL
VOLUME
cc
All Off
1
2 3
General
4
5
Exam 6
7
8
9
Reading
0
PREV
MUTE
TV
All Off
CHANNEL
SLEEP
VOLUME
OPTION
2
1
cc
3
1
2
ALL
ON/OFF
4
3
5
7
6
8
9
0
PREV
SLEEP
MUTE
OPTION
2
1
3
ALL
ON/OFF
Cooper Lighting Guaranteed Compatible Fixtures
Integrated capabilities
General
Exam
TV Reading
General
CHANNEL
VOLUME
cc
All Off
Whiteboard
1
2
3
Quiet Time •
4
5
6
7A/V 8Mode
9
1
Metalux LED
TV
CHANNEL
0
Raise
PREV
VOLUME
MUTE
cc
SLEEP
OPTION
Lower
2 1
2
3
4
ALL
ON/OFF
3
5
Room Controller Office Lighting Layouts
7
6
8
9
0
PREV
SLEEP
MUTE
OPTION
2
General 1
3
ALL
ON/OFF
Exam
Reading
All Off
Metalux LFL
Room Controller Office Lighting Layouts
General
TV
CHANNEL
VOLUME
Whiteboard cc
Quiet Time
1 •2
A/V Mode4
3
5
7
6
8
Raise
General 0
Lower
Whiteboard
2
PREV
SLEEP
9
MUTE
OPTION
Corelite LED
Room Controller Office Lighting Layouts
Corelite LFL
Room Controller Office Lighting Layouts
1
3
Quiet Time •
ALL
ON/OFF
A/V Mode
Raise
Lower
CHANNEL
TV
VOLUME
cc
1
2
4
3
5
7
6
8
0
PREV
9
General
SLEEP
MUTE
OPTION
2
1 Whiteboard
3
ALL
ON/OFF
Quiet Time •
Occupancy/Vacancy
Sensing
Manual
Control
Integration
A/V Mode
Raise
General
Whiteboard
Refer to these Cooper Lighting data sheets for lighting layouts and illuminance value information.
Lower
Quiet Time •
A/V Mode
Raise
Lower
General
Whiteboard
Quiet Time •
A/V Mode
Raise
Lower
General
Whiteboard
Quiet Time •
A/V Mode
www.coopercontrol.com
1
Raise
Lower
Room Controller - Private Office
Switching with BMS Output
Room Controller and Smart Devices use Click & Go technology
The RC3 will automtically recognize any smart device connected with the QuickConnect cable (provided) and start working immediately upon power up with no
programming required. The RC3 defaults to Manual On/Automatic Off vacancy sensor mode for maximum energy savings. Office stations provide On/Off control of
the Yellow, Red and Purple loads.
*Refer to Room Controller website for more information on other integral no programming required benefits like Demand Response, Solatube Control, Egress
Control, BMS Output, Alert Mode, Emergency Lighting Control, and Slider Stations available in other Room Controller models.
WHT/ORG or WHT/BLK
Neutral
BLACK - Hot
(120/277 VAC)
YELLOW
Lighting Load (1)
RED
Lighting Load (2)
PURPLE
Lighting Load (3)
BLUE - Relay In
(120/277 VAC)
BMS/ Egress Output:
Occupancy status output to the Building
Management System or other 3rd party
system require no programming of the
Room Controller and occurs when ever
there is occupancy in the room
regardless of light output status.
Allows connection to
any Greengate
Occupancy/Vacancy
Sensor
(OCC-RJ45)
(OCC-RJ45)
Quick connect cables are
pre-terminated and included
in the Room Controller
QuicKit and measured to fit
typical room layouts
Half Lights
Dual Technology
Wall Corner
Occupancy/Vacancy Sensor
(OAWC-DT-120W)
*Defaults to vacancy sensor mode
Manual On/Automatic Off (all loads)
for maximum energy savings
Button 1: Load (1) On, Load (2) Off
Full Lights
Button 2: Load (1), (2), (3) On
All Off
Button 3: Load (1), (2), (3) Off
Cooper Controls
203 Cooper Circle
Peachtree City,
GA 30269. USA
RC-3TLB-OS1-*
Office Station
Tel: +1-800-553-3879
Fax: +1-800-954-7016
Email: controls@cooperindustries.com
Website: www.coopercontrol.com
Room Controller - RC3
Three Relay Wiring Diagram
Drawing Name:
RC3-Office-BMS.dwg
www.coopercontrol.com
2
Drawing Date:
1/10/2013
Room Controller - Private Office
Switching with BMS Output
Mounting The Room Controller
The Room Controller mounts above the ceiling in the space it is controlling, typically above the door to the room. The Room Controller includes breakouts for direct
conduit connection limiting the need for additional junction boxes. Mount the Room Controller using the keyhole slots at the top and secure to the wall using the
holes at the bottom of the Room Controller.
Connect conduit to the line voltage breakout connections and connect the line and load wires. Connect low voltage cables either through the low voltage breakout
openings or by connecting low voltage conduit to the breakouts on the low voltage side of the Room Controller.
Sample Placement Diagram
(for example purposes only)
Room Controller
(above entry door)
Wall/Corner Mount
Occupancy Sensor
Entry
Wallstation
General On
Window
Off
Wiring Diagram
Occupancy sensor
Coverage Diagram (OAWC-DT-120W)
24’ (7.3 mm)
20’ (6 mm)
Room Controller
Normal Power
OCC-RJ45
(Above Entry Door)
(Line In & Load Out)
24’ (7.3 mm)
(BMS/ Egress
Output)
20’ (6 mm)
12’ (3.7 mm)
(low voltage, class 2)
Minor Motion, IR
8’ (2.4 mm)
0
8’ (2.4 mm)
OCC-RJ45
Major Motion, IR
Minor Motion, Ultrasonic
12’ (3.7 mm)
12’ (3.7 mm)
8’ (2.4 mm)
0
8’ (2.4 mm)
Major Motion, Ultrasonic
Minor Motion, IR
Major Motion, IR
Maximum coverage area may
Minor
Ultrasonic
varyMotion,
somewhat
according to room
shapeMotion,
and theUltrasonic
presence of obstacles.
Major
12’ (3.7 mm)
(Any Greengate
Occupancy Sensor)
The NEMA WD 7 Guide and robotic
method coverage
were utilized
verify
Maximum
areatomay
coverage
patterns.
vary somewhat
according
to room
shape and the presence of obstacles.
24’ (7.3 mm)
20’ (6 mm)
10 ft
(3 mm)
Wallstation
(Entry)
10 ft
(3 mm)
24’ (7.3 mm)
24 ft
6 ft
15 ft
20’ (6 mm)
(1.7 mm) (4.6 mm) (7.3 mm)
50 ft
(15.3 mm)
The NEMA WD 7 Guide and robotic
method were utilized to verify
coverage patterns.
Half Lights
Full Lights
24 ft
6 ft
15 ft
(1.7 mm) (4.6 mm) (7.3 mm)
Raise
Lower
All Off
50 ft
(15.3 mm)
Connections
OCC-RJ45
(Occupancy Coupler)
(Class 2)
BMS System
Connect the OCC-RJ45 Coupler to the BMS system. Closure
will be made across the Blue and Red wire locations. Connect
a QuickConnect cable between the Receptacle/BMS Out
Click & Go portion on the Room Controller and to one of the
ports on the OCC-RJ45 ports.
Black
Brown
Model: OCC-RJ45
Occupancy Sensor Coupler
Blue
Red
Room Controller and Smart Devices
use Click & Go Connections
QuickConnect Cable
(Class 2)
Closure to
BMS System
Receptacle
BMS/Out
Sensors
Sensors
Slider
Station
Adjustable Skylights
Switchpack
QuickConnect Cables
4
Time
Clock
Integration Controls
+
2
1
Energy
Options
4
High End
3
Reset
Not Used
Occupancy
Occ
Vac (default)
Low End
1 2
0-10V Dimming Outputs
+ + + Dimmer 3
5
3
Energy Options DIP Switch
Demand Response
Default 10%
20%
30%
40%
1
6
5
Wallstations
+
+
+
Alert
Mode
Status
Red - Load 2 Out
Purple - Load 3 Out
Blue - Load In
Yellow - Load 1 Out
Black - Line In
White/Black - 120V N
White/Orange - 277V N
Click & Go
Ports
Green
A/V
Mode
Demand
Response
0-10V Gain
Adjustment
Red
Blue - EM Line In
Blue - EM Loads Out
Blue
White
Red
Black
Integration Controls
45 ler
RJ up
C- Co
OC or
el: Sens
Mod ncy
pa
cu
n
ow
k
Br
ac
Bl
ler
d
Bro
Re
el:
cy OCC
Se -R
ns J4
or 5
Co
n
up
w
ck
Bla
ue
Bl
d
CAUTION: Bonding between conduit connections is not automatic and must be provided as part of the installation.
Occ M
up od
an
Re
Oc
e
Blu
Adjustable Skylights
Press Here
Dimmer 2
Dimmer 1
-
Dimmer 3
+
-
Dimmer 2
+
-
Dimmer 1
+
0-10V Dimming
(Supports 9-36 VDC @
10 mA from BMS System)
www.coopercontrol.com
3
2
5
34
6
1. Wallstations (up to four)
2. Slider Station Connection (one)
3. Occupancy Sensors (up to two)
4. Daylight Sensor (one)
5. Receptacle Control or BMS Output
6. Switchpack (controlled with Load 1 for
alternate voltage)
Room Controller - Private Office
Switching with BMS Output
Ordering
RCQK
-
OS
-
OS1
-
W1
-
B
-
Room Controller
Options
QuicKit
P - Plug Load
B - BMS/Egress
W
Office Stations (Choose up to 4)
Types of Space
and Control
OS1 - Half Lights, Full Lights, All Off
(3 Large Buttons)
OS2 - Half Lights, Full Lights, Raise, Lower, All Off †
(5 Small Buttons)
OS3 - Half Lights, Full Lights, Under Cabinet, Raise, Lower, All Off †
(6 Small Buttons)
OS4 - All On, All Off (2 Large Buttons)
CR1 - General, Meeting, Whiteboard, Presentation, Raise, Lower
(6 Small Buttons - Scenes)
SS1 - Slider Station ††
OS - Office Switching (RC3)
OS2 - Office 2 Zone Dimming (RC3D2)
OS3 - Office 3 Zone Dimming (RC3D)
OS3E - Office 3 Zone Dimming and
and Emergency Relay (RC3DE)
Occupancy Sensor
Station Color
C1 - Ceiling DT 2000 sq. ft.
C2 - Ceiling PIR 1500 sq. ft.
C3 - Ceiling DT 1000 sq. ft.
W1 - Wall Corner DT
W2 - Wall Corner PIR
W3 - Hallway PIR
W - White
G - Gray
V - Ivory
B - Black
*Catalog number automatically includes low voltage
connection cable, wallplates and connectors based on room
type and configuration.
Pre-defined Wallstation Model numbers
Half Lights
Half Lights
All On
Half lights
Full lights
Full Lights
Full Lights
Raise
Undercabinet
Lower
Raise
All Off
Lower
All Off
All Off
All Off
RC-3TLB-OS1
RC-5TSB-OS2
RC-6tsb-OS3
RC-2tlb-OS4
*For site specific engraving, please see the Room Controller
Wallstation custom engraving form on the Cooper Controls
website
Applications
Office Application Button Functionality
Function
(Unless a target level is indicated, the dimmer output
will default to daylight sensor control)
Program
No.
Button Text
Control
Type
9
Half Lights
Preset
Load 1 (yellow) ON, Load 2 (red) OFF
All Dimmers 50%
Solatube Open (RC3DE only)
10
Full Lights
Preset
Load 1 (yellow) ON, Load 2 (red) ON, Load 3 (purple) ON
All Dimmers 100%
11
Undercabinet
Toggle
Load 3 (purple) ON and OFF
6
Raise
Raise
Raise All Dimmers
7
Lower
Lower
Lower All Dimmers
†
†
16
All On
Preset
Load 1 (yellow) ON, Load 2 (red) ON, Load 3 (purple) ON
All Dimmers 100%
8
All Off
Preset
Load 1 (yellow) OFF, Load 2 (red) OFF, Load 3 (purple) OFF
Solatube Closed (RC3DE only)
Slider
Raise and Lower All Dimmers
Slider
††
Catalog #
Type
Project
†
These dimming wallstations can only be used with dimming Room Controllers (RC3D, RC3D2, RC3DE)
†† Slider stations can not be used if a wallstation with Raise/Lower buttons are used
Comments
Prepared by
www.coopercontrol.com
4
ACC130074