Room Controller - Private Office Switching with BMS Output Summary Basic code compliance requires automatic turn-off of lighting as well as a method for manual and/or automatic control within the space. Office spaces 250 sq. ft. or less must have automatic off within 30 minutes of vacancy. Providing manual and bi-level control of lighting can provide up to 66% energy savings. Including BMS/ HVAC control based on occupancy status further provides additional energy savings opportunities. The Room Controller QuicKit is shipped preconfigured to work out-of-the-box minimizing installation and setup time, while ensuring maximum energy savings. Using this design guide to specify your room with a Room Controller QuicKit catalog number will guarantee that after installation the lighting control system will work immediately as defined on this application guide. Half Lights Full Lights Raise Lower All Off Room Controller Sample room layout (10ʹ x 10ʹ) Half Lights Full Lights Raise Lower AllHalf Off Lights Full Lights Raise Lower RC3DE All Off Room Controller QuicKit Half Lights Full Lights Raise Lower All Off Half Lights Full Lights RCQK-OS-OS1-W1-B-W Raise Lower Half Lights All Off Full Lights Raise Product Legend Lower RC3DE All Off OCC-RJ45 (BMS Output/Egress Control) Normal power connection RC3DE RC3DE Half Lights Full Lights Raise OCC-RJ45 (Connection to any Greengate sensor) RC3 (3 Relay) Lower All Off RC3DE Half Lights RC3DE Full Lights Half Lights Full Lights All Off RC-3TLB-OS1-* (Pre-engraved Wallstation) RC3 Qty1: RC3 3 On/Off relays Raise Lower OAWC-DT-120W (Wall Corner Occupancy Sensor) All Off RC3DE Qty1: RC-3TlB-OS1-W Half lights, full lights, all off Qty1: OAWC-DT-120W Wall Corner vacancy sensor RC3DE Qty1: OCC-RJ45 Occupancy sensor RJ45 connector Load 1 Qty1: OCC-RJ45 BMS/HVAC Occupancy output Qty1: GGRJ45-10-G Quickconnect cable 10’ Qty2: GGRJ45-50-G Quickconnect cable 50’ Single box packaging with wiring detail and installation Entry Lighting All Off Load 3 Load 2 Recessed Fixtures Entry Lighting All Off For guaranteed compatibility refer to preferred Cooper lighting fixture information below. Entry Lighting All Off Entry Lighting RC3D All Off Entry Lighting All Off Entry Lighting All Off RC3D General Exam Entry Lighting Reading Control sequence All Off All Off • Manual On/Automatic Off or Automatic On (50%)/Automatic Off RC3D Entry Lighting TV CHANNEL VOLUME cc RC3D 1 2 All Off 4 • Providing users with wall-based manual controls to adjust the lighting levels to meet their needs 3 5 7 6 8 9 0 PREV SLEEP MUTE OPTION 2 1 3 ALL ON/OFF Half lights 1. Preset - Load 1 On, Load 2 Off RC3D General Exam RC3D Reading • Provides automatic 30 minute Off after the space is vacant Full lights • After-hours warn Offs and timers to ensure maximum efficiency and savings All Off All Off 2. Preset - Load 1, 2, 3 On General Whiteboard Quiet Time • A/V Mode Raise Lower RC3D 3. All Loads Off General Exam Reading • Occupancy based BMS integration for HVAC control UL924 UL924 TV All Off CHANNEL VOLUME cc 1 2 3 General 4 5 6 Exam 7 8 9 Reading 0 PREV MUTE All Off SLEEP OPTION 2 1 3 ALL ON/OFF RC3D UL924 RC-3TLB-OS1 General Exam ReadingTV CHANNEL VOLUME cc All Off 1 2 3 General 4 5 Exam 6 7 8 9 Reading 0 PREV MUTE TV All Off CHANNEL SLEEP VOLUME OPTION 2 1 cc 3 1 2 ALL ON/OFF 4 3 5 7 6 8 9 0 PREV SLEEP MUTE OPTION 2 1 3 ALL ON/OFF Cooper Lighting Guaranteed Compatible Fixtures Integrated capabilities General Exam TV Reading General CHANNEL VOLUME cc All Off Whiteboard 1 2 3 Quiet Time • 4 5 6 7A/V 8Mode 9 1 Metalux LED TV CHANNEL 0 Raise PREV VOLUME MUTE cc SLEEP OPTION Lower 2 1 2 3 4 ALL ON/OFF 3 5 Room Controller Office Lighting Layouts 7 6 8 9 0 PREV SLEEP MUTE OPTION 2 General 1 3 ALL ON/OFF Exam Reading All Off Metalux LFL Room Controller Office Lighting Layouts General TV CHANNEL VOLUME Whiteboard cc Quiet Time 1 •2 A/V Mode4 3 5 7 6 8 Raise General 0 Lower Whiteboard 2 PREV SLEEP 9 MUTE OPTION Corelite LED Room Controller Office Lighting Layouts Corelite LFL Room Controller Office Lighting Layouts 1 3 Quiet Time • ALL ON/OFF A/V Mode Raise Lower CHANNEL TV VOLUME cc 1 2 4 3 5 7 6 8 0 PREV 9 General SLEEP MUTE OPTION 2 1 Whiteboard 3 ALL ON/OFF Quiet Time • Occupancy/Vacancy Sensing Manual Control Integration A/V Mode Raise General Whiteboard Refer to these Cooper Lighting data sheets for lighting layouts and illuminance value information. Lower Quiet Time • A/V Mode Raise Lower General Whiteboard Quiet Time • A/V Mode Raise Lower General Whiteboard Quiet Time • A/V Mode www.coopercontrol.com 1 Raise Lower Room Controller - Private Office Switching with BMS Output Room Controller and Smart Devices use Click & Go technology The RC3 will automtically recognize any smart device connected with the QuickConnect cable (provided) and start working immediately upon power up with no programming required. The RC3 defaults to Manual On/Automatic Off vacancy sensor mode for maximum energy savings. Office stations provide On/Off control of the Yellow, Red and Purple loads. *Refer to Room Controller website for more information on other integral no programming required benefits like Demand Response, Solatube Control, Egress Control, BMS Output, Alert Mode, Emergency Lighting Control, and Slider Stations available in other Room Controller models. WHT/ORG or WHT/BLK Neutral BLACK - Hot (120/277 VAC) YELLOW Lighting Load (1) RED Lighting Load (2) PURPLE Lighting Load (3) BLUE - Relay In (120/277 VAC) BMS/ Egress Output: Occupancy status output to the Building Management System or other 3rd party system require no programming of the Room Controller and occurs when ever there is occupancy in the room regardless of light output status. Allows connection to any Greengate Occupancy/Vacancy Sensor (OCC-RJ45) (OCC-RJ45) Quick connect cables are pre-terminated and included in the Room Controller QuicKit and measured to fit typical room layouts Half Lights Dual Technology Wall Corner Occupancy/Vacancy Sensor (OAWC-DT-120W) *Defaults to vacancy sensor mode Manual On/Automatic Off (all loads) for maximum energy savings Button 1: Load (1) On, Load (2) Off Full Lights Button 2: Load (1), (2), (3) On All Off Button 3: Load (1), (2), (3) Off Cooper Controls 203 Cooper Circle Peachtree City, GA 30269. USA RC-3TLB-OS1-* Office Station Tel: +1-800-553-3879 Fax: +1-800-954-7016 Email: controls@cooperindustries.com Website: www.coopercontrol.com Room Controller - RC3 Three Relay Wiring Diagram Drawing Name: RC3-Office-BMS.dwg www.coopercontrol.com 2 Drawing Date: 1/10/2013 Room Controller - Private Office Switching with BMS Output Mounting The Room Controller The Room Controller mounts above the ceiling in the space it is controlling, typically above the door to the room. The Room Controller includes breakouts for direct conduit connection limiting the need for additional junction boxes. Mount the Room Controller using the keyhole slots at the top and secure to the wall using the holes at the bottom of the Room Controller. Connect conduit to the line voltage breakout connections and connect the line and load wires. Connect low voltage cables either through the low voltage breakout openings or by connecting low voltage conduit to the breakouts on the low voltage side of the Room Controller. Sample Placement Diagram (for example purposes only) Room Controller (above entry door) Wall/Corner Mount Occupancy Sensor Entry Wallstation General On Window Off Wiring Diagram Occupancy sensor Coverage Diagram (OAWC-DT-120W) 24’ (7.3 mm) 20’ (6 mm) Room Controller Normal Power OCC-RJ45 (Above Entry Door) (Line In & Load Out) 24’ (7.3 mm) (BMS/ Egress Output) 20’ (6 mm) 12’ (3.7 mm) (low voltage, class 2) Minor Motion, IR 8’ (2.4 mm) 0 8’ (2.4 mm) OCC-RJ45 Major Motion, IR Minor Motion, Ultrasonic 12’ (3.7 mm) 12’ (3.7 mm) 8’ (2.4 mm) 0 8’ (2.4 mm) Major Motion, Ultrasonic Minor Motion, IR Major Motion, IR Maximum coverage area may Minor Ultrasonic varyMotion, somewhat according to room shapeMotion, and theUltrasonic presence of obstacles. Major 12’ (3.7 mm) (Any Greengate Occupancy Sensor) The NEMA WD 7 Guide and robotic method coverage were utilized verify Maximum areatomay coverage patterns. vary somewhat according to room shape and the presence of obstacles. 24’ (7.3 mm) 20’ (6 mm) 10 ft (3 mm) Wallstation (Entry) 10 ft (3 mm) 24’ (7.3 mm) 24 ft 6 ft 15 ft 20’ (6 mm) (1.7 mm) (4.6 mm) (7.3 mm) 50 ft (15.3 mm) The NEMA WD 7 Guide and robotic method were utilized to verify coverage patterns. Half Lights Full Lights 24 ft 6 ft 15 ft (1.7 mm) (4.6 mm) (7.3 mm) Raise Lower All Off 50 ft (15.3 mm) Connections OCC-RJ45 (Occupancy Coupler) (Class 2) BMS System Connect the OCC-RJ45 Coupler to the BMS system. Closure will be made across the Blue and Red wire locations. Connect a QuickConnect cable between the Receptacle/BMS Out Click & Go portion on the Room Controller and to one of the ports on the OCC-RJ45 ports. Black Brown Model: OCC-RJ45 Occupancy Sensor Coupler Blue Red Room Controller and Smart Devices use Click & Go Connections QuickConnect Cable (Class 2) Closure to BMS System Receptacle BMS/Out Sensors Sensors Slider Station Adjustable Skylights Switchpack QuickConnect Cables 4 Time Clock Integration Controls + 2 1 Energy Options 4 High End 3 Reset Not Used Occupancy Occ Vac (default) Low End 1 2 0-10V Dimming Outputs + + + Dimmer 3 5 3 Energy Options DIP Switch Demand Response Default 10% 20% 30% 40% 1 6 5 Wallstations + + + Alert Mode Status Red - Load 2 Out Purple - Load 3 Out Blue - Load In Yellow - Load 1 Out Black - Line In White/Black - 120V N White/Orange - 277V N Click & Go Ports Green A/V Mode Demand Response 0-10V Gain Adjustment Red Blue - EM Line In Blue - EM Loads Out Blue White Red Black Integration Controls 45 ler RJ up C- Co OC or el: Sens Mod ncy pa cu n ow k Br ac Bl ler d Bro Re el: cy OCC Se -R ns J4 or 5 Co n up w ck Bla ue Bl d CAUTION: Bonding between conduit connections is not automatic and must be provided as part of the installation. Occ M up od an Re Oc e Blu Adjustable Skylights Press Here Dimmer 2 Dimmer 1 - Dimmer 3 + - Dimmer 2 + - Dimmer 1 + 0-10V Dimming (Supports 9-36 VDC @ 10 mA from BMS System) www.coopercontrol.com 3 2 5 34 6 1. Wallstations (up to four) 2. Slider Station Connection (one) 3. Occupancy Sensors (up to two) 4. Daylight Sensor (one) 5. Receptacle Control or BMS Output 6. Switchpack (controlled with Load 1 for alternate voltage) Room Controller - Private Office Switching with BMS Output Ordering RCQK - OS - OS1 - W1 - B - Room Controller Options QuicKit P - Plug Load B - BMS/Egress W Office Stations (Choose up to 4) Types of Space and Control OS1 - Half Lights, Full Lights, All Off (3 Large Buttons) OS2 - Half Lights, Full Lights, Raise, Lower, All Off † (5 Small Buttons) OS3 - Half Lights, Full Lights, Under Cabinet, Raise, Lower, All Off † (6 Small Buttons) OS4 - All On, All Off (2 Large Buttons) CR1 - General, Meeting, Whiteboard, Presentation, Raise, Lower (6 Small Buttons - Scenes) SS1 - Slider Station †† OS - Office Switching (RC3) OS2 - Office 2 Zone Dimming (RC3D2) OS3 - Office 3 Zone Dimming (RC3D) OS3E - Office 3 Zone Dimming and and Emergency Relay (RC3DE) Occupancy Sensor Station Color C1 - Ceiling DT 2000 sq. ft. C2 - Ceiling PIR 1500 sq. ft. C3 - Ceiling DT 1000 sq. ft. W1 - Wall Corner DT W2 - Wall Corner PIR W3 - Hallway PIR W - White G - Gray V - Ivory B - Black *Catalog number automatically includes low voltage connection cable, wallplates and connectors based on room type and configuration. Pre-defined Wallstation Model numbers Half Lights Half Lights All On Half lights Full lights Full Lights Full Lights Raise Undercabinet Lower Raise All Off Lower All Off All Off All Off RC-3TLB-OS1 RC-5TSB-OS2 RC-6tsb-OS3 RC-2tlb-OS4 *For site specific engraving, please see the Room Controller Wallstation custom engraving form on the Cooper Controls website Applications Office Application Button Functionality Function (Unless a target level is indicated, the dimmer output will default to daylight sensor control) Program No. Button Text Control Type 9 Half Lights Preset Load 1 (yellow) ON, Load 2 (red) OFF All Dimmers 50% Solatube Open (RC3DE only) 10 Full Lights Preset Load 1 (yellow) ON, Load 2 (red) ON, Load 3 (purple) ON All Dimmers 100% 11 Undercabinet Toggle Load 3 (purple) ON and OFF 6 Raise Raise Raise All Dimmers 7 Lower Lower Lower All Dimmers † † 16 All On Preset Load 1 (yellow) ON, Load 2 (red) ON, Load 3 (purple) ON All Dimmers 100% 8 All Off Preset Load 1 (yellow) OFF, Load 2 (red) OFF, Load 3 (purple) OFF Solatube Closed (RC3DE only) Slider Raise and Lower All Dimmers Slider †† Catalog # Type Project † These dimming wallstations can only be used with dimming Room Controllers (RC3D, RC3D2, RC3DE) †† Slider stations can not be used if a wallstation with Raise/Lower buttons are used Comments Prepared by www.coopercontrol.com 4 ACC130074 Date