HRCII-C Current-Limiting Fuses CGL 600 Volt, 1 to 600 Amps Bussmann

advertisement
Bussmann®
HRCII-C Current-Limiting Fuses
CGL
600 Volt, 1 to 600 Amps
Dimensional Data
0.22"
0.81"
0.22"
(20.64mm)
(5.56mm) (5.56mm)
0.06"
2.0"
(50.8mm)
(1.59mm)
0.34"
2.80"
0.94"
(8.73mm)
(23.81mm)
(71.04mm)
3.31"
(84.14mm)
CGL 1-30
0.22"
0.81"
0.22"
(20.64mm)
(5.56mm) (5.56mm)
0.06"
2.0"
(50.8mm)
(1.59mm)
0.50"
2.80"
1.06"
(12.7mm)
(71.04mm)
(26.92mm)
3.5"
(88.9mm)
CGL 40-50
Catalog Symbol: CGL
Current-Limiting
Ampere Rating: 1 to 600 Amperes
Voltage Rating: 600 Volts AC (or less)
1 to 30 Amps, 250 Volts DC (or less)
Interrupting Rating: 200,000A RMS Sym.
40,000A DC (1 to 30A)
Agency Approval:
CSA Certified, C22.2106, Class 1422, File 53787
General Information:
TRON® HRC FORM II Class C Fuses
• TRON® HRCII-C fuses are designed to withstand inrush
currents on typical motor start-ups while offering high
current limitation in the short-circuit region.
• The TRON® HRCII-C fuses can be sized close to the motor
nameplate rating.
• Closer protection is offered for many motor sizes with the
availability of these additional fuse ratings.
• TRON® HRCII-C fuses have a high degree of current-limitation
greatly reducing the magnetic forces and thermal stresses
produced in today’s high capacity systems.
• TRON® HRCII-C fuses have an interrupting rating of 200,000
RMS symmetrical amperes at 600 volts.
• TRON® HRCII-C fuses are dimensionally interchangeable with
other Form II fuses on the market and can be used with the
same confidence as other High Quality Buss Fuses.
1.34"
0.343"
0.343"
(8.71mm)
(8.71mm)
2.39"
(60.72mm)
3.64"
(34.04mm)
0.09"
(2.29mm)
0.75"
1.375"
(19.05mm)
(34.93mm)
(92.47mm)
4.31"
(109.54mm)
CGL 70-100
0.343"
(8.71mm)
0.343
(8.71mm)
0.125"
3.00"
(3.18mm)
0.75"
(76.2mm)
(19.05mm)
4.30"
(109.22mm)
1.50"
(38.1mm)
5.31"
(134.87mm)
CGL 125-200
0.19"
(4.76mm)
1.0"
0.38"
(25.4mm)
(9.53mm)
1.0"
(25.4mm)
3.0"
2.38"
(76.2mm)
(60.33mm)
5.25"
(133.35mm)
8.19"
(207.96mm)
CGL 225-400
1.0"
0.41"
(25.4mm)
(10.32mm)
1.0"
(25.4mm)
.60"
3.0"
(76.2mm)
5.25"
(133.35mm)
8.19"
(15.24mm)
0.375"
(9.53mm)
3.00"
(76.2mm)
(207.96mm)
CGL 450-600
5-02-01
SB01155
Form No. CGL
Page 1 of 3
BIF Doc #4125
Bussmann®
HRCII-C Current-Limiting Fuses
CGL
600 Volt, 1 to 600 Amps
500
600
150
80
300
400
350
450
200
250
100
125
60
40
1,000
25
30
AMPERE
RATING
1,000
50
CGL - Minimum Melt
6
8
10
15
20
3
4
2
1
CGL - Minimum Melt
AMPERE
RATING
100
100
10
TIME IN SECONDS
TIME IN SECONDS
10
1
1
.1
1,000
10
1
.01
100
.1
20,000
10,000
1000
40
.01
100
CURRENT IN AMPERES
CURRENT IN AMPERES
5-02-01
SB01155
Form No. CGL
Page 2 of 3
BIF Doc #4125
Bussmann®
HRCII-C Current-Limiting Fuses
CGL
600 Volt, 1 to 600 Amps
B
AMPERE
RATING
400,000
100,000
600
400
200
100
60
10,000
30
200,000
10,000
1,000
100,000
A
1,000
INSTANTANEOUS PEAK LET-THROUGH CURRENT IN AMPS
CGL LIMITRON
PROSPECTIVE SHORT-CIRCUIT CURRENT
SYMMETRICAL RMS AMPS
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained
in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
5-02-01
SB01155
Form No. CGL
Page 3 of 3
BIF Doc #4125
Download