Procurement Management Division On-Call Airport Communication Cabling Installation Services RFP #269-2016-042 Addendum #1 To: All Prospective Proposers Date: January 21, 2016 Subject: Addendum #1 – RFP # 269-2016-042 – On-Call Airport Communication Cabling Installation Services Please note the specification changes/modifications below for the RFP. Item # 1 Page # 44 Section # Specification(s) Change(s) Modification(s) Exhibit E CDIA Communications Infrastructure Standard Modification: The entire Exhibit E – CDIA Communications Infrastructure Standard can be found in Attachment 1 to this Addendum. In order to constitute a complete proposal response you must acknowledge receipt of this addendum with the Acknowledgement of Addenda found in Form 2, Section C. of the RFP in your Proposal. Any Service Provider not acknowledging receipt of an issued addendum may not be considered. In the event additional changes or clarifications to this RFP are warranted, all Service Providers are responsible for monitoring www.ips.state.nc.us or for additional addenda. We appreciate your interest in doing business with the City of Charlotte and look forward to receiving a proposal from your company. Sincerely, Philip Keller Procurement Officer cc: File Procurement Management Division Management and Financial Services/City of Charlotte 600 East Fourth Street Phone: 704/336-2256 Fax: 704/336-2258 1 Charlotte, NC 28202-2850 Attachment 1 Exhibit E – CDIA Communications Infrastructure Standard Procurement Management Division Management and Financial Services/City of Charlotte 600 East Fourth Street Phone: 704/336-2256 Fax: 704/336-2258 2 Charlotte, NC 28202-2850 Communications Infrastructure Standards May 31, 2010 Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 2 Contents GENERAL ................................................................................................................................................... 8 GENERAL: VERSION................................................................................................................................... 8 GENERAL: PURPOSE .................................................................................................................................. 8 GENERAL: SCOPE....................................................................................................................................... 8 GENERAL: STANDARD PRODUCTS ............................................................................................................. 8 GENERAL: COMMON TERMS ..................................................................................................................... 8 GENERAL: REFERENCED STANDARDS ....................................................................................................... 8 GENERAL: CONTRACTOR REQUIREMENTS AND RESPONSIBILITIES ........................................................ 10 General: Contractor Requirements and Responsibilities: Communications Contractor Responsibilities .................................................................................................................................... 10 General: Contractor Requirements and Responsibilities: Communications Contractor Requirements and Qualifications ............................................................................................................................... 10 General: Contractor Requirements and Responsibilities: Communications Contractor Additional Qualifications: ..................................................................................................................................... 11 General: Contractor Requirements and Responsibilities: Electrical Contractor Responsibilities ..... 11 TELECOMMUNICATION ROOMS ............................................................................................................... 11 Telecommunication Rooms : General.................................................................................................. 12 Telecommunication Rooms : Location ................................................................................................ 12 TELECOMMUNICATION ROOMS: SIZE ...................................................................................................... 12 Telecommunication Rooms: MDC ....................................................................................................... 12 Telecommunication Rooms: TR ........................................................................................................... 13 Figure 1. Telecommunications Room Clearances ............................................................................... 14 Figure 2. Main Data Center Room Clearances ................................................................................... 15 Telecommunication Rooms: Facilities ................................................................................................ 16 Telecommunication Rooms: Facilities: HVAC .................................................................................... 16 Telecommunication Rooms: Facilities: Back Board ........................................................................... 16 Telecommunication Rooms: Facilities: Electrical .............................................................................. 16 Telecommunication Rooms: Facilities: Data Outlets .......................................................................... 17 Telecommunication Rooms: Facilities: Equipment Cabinets .............................................................. 17 Telecommunication Rooms: Facilities: Ladder Racking ..................................................................... 17 Figure 3. Telecommunications ladder Racking Layouts .................................................................... 18 Telecommunication Rooms: Facilities: Ceiling .................................................................................. 18 Telecommunication Rooms: Facilities: Floor ..................................................................................... 19 Telecommunication Rooms: Facilities: Walls ..................................................................................... 19 Telecommunication Rooms: Facilities: Lighting ................................................................................. 19 Telecommunication Rooms: Facilities: Door ...................................................................................... 19 Telecommunication Rooms: Windows ................................................................................................. 19 TELECOMMUNICATIONS ROOMS: CABINET ASSEMBLIES ....................................................................... 19 Figure 4. Single Compartment Cabinet Configuration ....................................................................... 20 Figure 5. Two Compartment Cabinet Configuration .......................................................................... 21 Figure 6. Three Compartment Cabinet Configuration ........................................................................ 22 TELECOMMUNICATION ROOMS: COMPONENT PLACEMENT.................................................................... 23 Telecommunication Rooms: Component Placement: Floor Cabinets/Racks Descriptions and Placement ............................................................................................................................................ 23 Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 3 Telecommunication Rooms: Component Placement: Backboard mounted equipment Placement ..... 23 Telecommunication Rooms: Component Placement: CATV Placement ............................................. 23 Telecommunication Rooms: Component Placement: Paging Equipment Placement ......................... 23 TELECOMMUNICATION ROOMS: LABELING ............................................................................................ 23 TELECOMMUNICATION ROOMS: MINI-TR’S............................................................................................ 24 COMMUNICATIONS PATHWAYS ..................................................................................................... 25 PATHWAYS: ENTRANCE........................................................................................................................... 25 Pathways: Entrance: Material ............................................................................................................ 25 Pathways: Entrance: MINIMUM Size and Count ............................................................................... 25 Pathways: Entrance: Installation ........................................................................................................ 25 Pathways: Entrance: Firewall ............................................................................................................. 26 PATHWAYS: INTRA-BUILDING................................................................................................................. 26 Pathways: Intra-Building: Size and Count .......................................................................................... 26 Pathways: Intra -Building: Cable Tray ............................................................................................... 26 Pathways: Intra-Building: Cable Caddy Supports .............................................................................. 26 Pathways: Intra-Building: Conduit ..................................................................................................... 27 Pathways: Intra-Building: Non-Firewall Penetrations ....................................................................... 27 Pathways: Intra-Building: Firewall Penetrations ............................................................................... 27 PATHWAYS: INTER-BUILDING ................................................................................................................. 27 Pathways: Inter-Building: Conduit Between Buildings....................................................................... 27 PATHWAYS: HORIZONTAL ....................................................................................................................... 28 Pathways: Horizontal: General ........................................................................................................... 28 Pathways: Horizontal: Cable Caddy Supports .................................................................................... 28 Pathways: Horizontal: Cable Tray ...................................................................................................... 28 Pathways: Horizontal: Penetrations ................................................................................................... 29 Pathways: Horizontal: Penetrations: Firewalls .................................................................................. 29 Pathways: Horizontal: Metallic Conduit ............................................................................................. 29 Pathways: Horizontal: Flush Mounted Outlets ................................................................................... 29 Pathways: Horizontal: Surface Mounted Raceway with outlets.......................................................... 29 Pathways: Horizontal: Equipment Rooms Surface Mounted Raceway ............................................... 29 CABLING .................................................................................................................................................. 31 CABLING: GENERAL ................................................................................................................................ 31 CABLING: ENTRANCE CABLING .............................................................................................................. 31 Cabling: Entrance Cabling: Lightning Protection .............................................................................. 31 Cabling: Entrance Cabling: Installation ............................................................................................. 31 Cabling: Entrance Cabling: Termination............................................................................................ 31 Cabling: Entrance Cabling: Labeling ................................................................................................. 32 Cabling: Entrance Cabling: Testing.................................................................................................... 32 Cabling: Entrance Cabling: Grounding .............................................................................................. 32 CABLING: BACKBONE.............................................................................................................................. 32 Cabling: Backbone: General ............................................................................................................... 32 Cabling: Backbone: Installation.......................................................................................................... 32 Cabling: Backbone: Analog Voice and Paging ................................................................................... 33 Cabling: Backbone: Data Backbone ................................................................................................... 34 Cabling: Backbone: CATV Backbone.................................................................................................. 35 CABLING: HORIZONTAL .......................................................................................................................... 35 Cabling: Horizontal: General ............................................................................................................. 35 Cabling: Horizontal: Cable Type ........................................................................................................ 35 Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 4 Cabling: Horizontal: Color Coding .................................................................................................... 35 Cabling: Horizontal: Topology ........................................................................................................... 36 Cabling: Horizontal: Installation ........................................................................................................ 36 Cabling: Horizontal: Termination of Category 6 Data ....................................................................... 37 Cabling: Horizontal: Termination of Analog Voice and Paging......................................................... 37 Cabling: Horizontal: Termination of Voice and Paging: WAOs......................................................... 38 Cabling: Horizontal: Termination of CATV ........................................................................................ 38 CABLING: WORK AREA OUTLETS ........................................................................................................... 39 Cabling: Work Area Outlets: Detail .................................................................................................... 39 Cabling: Work Area Outlets: Location................................................................................................ 43 Cabling: Work Area Outlets: Labeling................................................................................................ 43 CABLING: TESTING .................................................................................................................................. 43 Cabling: Testing: Documentation ....................................................................................................... 44 Cabling: Testing: Backbone ................................................................................................................ 44 Cabling: Testing: Horizontal ............................................................................................................... 47 CABLING: MATERIALS ............................................................................................................................. 48 Cabling: Materials: Technology Preferred Vendors ........................................................................... 48 SYSTEMS .................................................................................................................................................. 52 SYSTEMS: CATV ..................................................................................................................................... 52 Systems: CATV: Incoming Signal ........................................................................................................ 52 Systems: CATV: Channels ................................................................................................................... 52 Systems: CATV: Components .............................................................................................................. 52 Systems: CATV: Design ....................................................................................................................... 52 Systems: CATV: Completeness ............................................................................................................ 52 Systems: CATV: Performance ............................................................................................................. 53 Systems: CATV: Testing ...................................................................................................................... 53 Systems: CATV: Training .................................................................................................................... 53 Systems: CATV: Warranty ................................................................................................................... 53 SYSTEMS: PAGING ................................................................................................................................... 53 Systems: Paging: Equipment ............................................................................................................... 53 Systems: Paging : Manufacturer of Choice ......................................................................................... 53 Systems: Paging : Documentation ....................................................................................................... 54 Systems: Paging : Authorized Installer ............................................................................................... 54 Systems: Paging : Warranty ................................................................................................................ 54 INSPECTIONS ......................................................................................................................................... 55 INSPECTIONS: SUBMITTALS ..................................................................................................................... 55 INSPECTIONS: PATHWAYS ....................................................................................................................... 55 INSPECTIONS: ROUGH INSTALLATION SUBSTANTIAL COMPLETION ....................................................... 55 INSPECTIONS: FINAL INSPECTION ............................................................................................................ 55 DOCUMENTATION................................................................................................................................ 56 WARRANTY............................................................................................................................................. 57 WARRANTY: ELECTRICAL ....................................................................................................................... 57 Warranty: Technology ......................................................................................................................... 57 Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 5 Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 6 Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 7 General General: Version This document is Version 2.0 of the Charlotte Douglas International Airport (CLT) Communications Infrastructure Standard, and supersedes all previous versions. General: Purpose This document is the CLT Communications infrastructure standard, providing Architects, Engineers, Project Managers, and Construction/Electrical/Communications Contractors with requirements for the Communications infrastructure within the Airport Campus. This Standard describes an infrastructure that offers high performance while meeting the needs of the Airports’ overall Communications demands, including maximum flexibility and longevity while minimizing the cost and scope of future adds, moves and changes. General: Scope This Standard is applicable to all new construction and renovation projects within CLT. General: Standard Products All products specified in this document reflect the standard products currently in use by CLT. Deviations from the specified products are not allowed without prior written approval from the CLT Technology Services Office. General: Common Terms The following common terms are utilized in this specification: TSO Charlotte Douglas International Airport Technology Services Office MDC Main Data Center TR Telecommunications Room WAO Work Area Outlet CATV Closed Circuit TV / Cable TV DSS Digital Surveillance System UTP Unshielded twisted pair RJ-45 8 pin modular jack MM Multimode Fiber Optic Cable SM SM Fiber Optic Cable General: Referenced Standards The following standards should be considered a part of this standard. In case of conflict between references, the more stringent requirements shall apply, unless specifically noted otherwise in the project Construction Documents. In the event any of the listed standards are superseded or updated, the most current version shall apply. Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 8 TIA/EIA-568-C, Commercial Building Telecommunications Cabling Standard The standard is comprised of four documents: 1. TIA 568-C.0 Generic Telecommunications Cabling (targeted to users/designers/installers). This document houses most information common to structured cabling in one place and becomes the foundation for future standards. This is where the minimum requirements for generic telecommunications cabling are specified such as cabling architecture, what applications the cabling is intended to support and over what distances, and other general requirements. The document thus serves two purposes - as a "default" standard for structured cabling in locations that are not office-oriented or covered by another standard, and as a foundation for future standards that can now focus on exceptions and allowances for that location rather than having to reconstruct all the generic information. 2. TIA 586-C.1 Commercial Building (Targeted to users/designers/installers). This document specifies the requirements for telecommunications cabling within and between commercial (office-oriented) buildings. This document builds on 568-C.0 and focuses on the requirements and guidance for office-oriented buildings. There are some technical changes to the information in 568-B.1 that are reflected in this document. These include the addition of: Category 6 balanced twisted-pair cabling Augmented category 6 twisted-pair cabling 850 nm laser-optimized 50/125 μm MM fiber Telecommunications enclosures (TEs) Centralized cabling A recommendation to select 850 nm laser-optimized 50/125 μm as the multimode fiber for commercial buildings Some information was also removed: 150-Ohm STP cabling Category 5 cabling 50-ohm and 75-ohm coaxial cabling Balanced twisted-pair cabling performance and test requirements (these are in the ANSI/TIA-568-C.2 document) 3. 568-C.2 Copper Cabling Components (Targeted to manufacturers). This standard includes component and cabling specifications for copper cabling, including testing requirements. The document incorporates Cat 3, Cat 5e, Cat 6 and Cat 6A. 4. TIA-568-C.3 Optical Cabling Components (Targeted to manufacturers). This document addresses component and cabling specifications for fiber optic cabling. The standard now includes all three types of multimode fiber (62.5-micron, 50-micron and 850nm laser-optimized 50-micron). TIA/EIA-569-C, Commercial Building Standard for Telecommunications Pathways and Spaces TIA/EIA-598-C, Optical Fiber Color Coding TIA/EIA-606-A, Administration Standard for Commercial Telecommunications Infrastructure TIA/EIA-758-A, Customer-Owned Outside Plant Telecommunications Cabling Standard J-STD-607-A, Commercial Building Grounding and Bonding Requirements for Telecommunications Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 9 BICSI, Telecommunications Distribution Methods Manual, current version BICSI, Outside Plant Design Reference Manual, current version BICSI, NECA/BICSI 568-2006, Installing Commercial Building Telecommunications Cabling STS-1000, North Carolina State Telecommunications Wiring Guidelines, current version (attached) NEC, National Electrical Code, current version UL, Underwriter’s Laboratories The above listed standards are available from BICSI (www.bicsi.org), or from HIS Global Engineering Documents (http://global.ihs.com). General: Contractor Requirements and Responsibilities General: Contractor Requirements and Responsibilities: Communications Contractor Responsibilities Unless otherwise noted in the Project Construction Documents, the Communications Contractor is responsible for providing materials and installation of all items in this Standard except: conduit, cable tray, electrical outlets, and electrical circuits. The Communications Contractor is responsible for providing all Communications Systems and equipment as described in the Project documentation . Coordination and communication between the Communications Contractor and the Electrical Contractor shall be maintained at all times. All installations must conform to this Standard, manufacturer’s specifications and all other applicable standards, codes and specifications. It is understood that the Communications Contractor shall furnish additional items not mentioned herein to meet requirements as specified without claim for additional payments. General: Contractor Requirements and Responsibilities: Communications Contractor Requirements and Qualifications The Communications Contractor must meet ALL requirements or employ sub-contractors to meet all requirements as applicable to the project infrastructure requirement. No more than one level of subcontractors is allowed. The Communications Contractor must provide all sub-contractor information and verification of requirements prior to acceptance of bid, or on demand by the Airport ITS Department or the Project Designer. Panduit Certified Installer capable of providing coverage under the Panduit Certification Plus System Warranty Program. Hubbell Certified Installer capable of providing coverage under the Hubbell Mission Critical System Warranty Program Corning Cable Systems Network of Preferred Installers. CommScope Certified Installer Program capable of provide Warranty coverage under the CommScope Uniprise/Systimax program Cisco Silver Business Partner Nortel Elite/Avaya Gold Business Partner All past work for CLT must be certified with no outstanding issues. 50% of the installation technicians on site must have completed BICSI ITS Installer, and Panduit/Hubbell/CommScope training (as applicable to the project) within two years prior to the start of the job, and hold current certifications for this training. Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 10 General: Contractor Requirements and Responsibilities: Communications Contractor Additional Qualifications: The Communications Contractor must meet the following criteria: Current, active, and valid State Contractors License. Provide a copy of Contractors License in the bid submission. Five, minimum, continuous years experience. Five, minimum, completed projects similar to scope and cost. Provide a list of projects, including references, in the bid submission. Technicians qualified for the work. Provide evidence in the bid submission of Technician qualifications. Evidence shall consist of current BICSI and manufacturer certifications, manufacturer training certificates, industry training, relevant project experience, etc. General: Contractor Requirements and Responsibilities: Electrical Contractor Responsibilities Unless otherwise specifically noted in the Construction Documents, the electrical contractor is responsible for pathways including but not limited to entrance, inter-building, intra-building, spillways, transitions, conduit bushings, cable tray and wire basket tray not in the Telecommunications rooms or equipment spaces. The electrical contractor is also responsible for fire stopping all penetrations, electrical outlets and electrical circuits described in this Standard. The electrical contractor is responsible for the demolition of the existing electrical systems and pathways where applicable as well as patching and painting. This demolition should not occur until the new communications system is up and running. Coordination and communication between the electrical contractor and the Communications Contractor shall be maintained at all times during the project. All installations shall conform and allow the Communications Contractor to conform to this Standard, project and manufacturer’s specifications, and all applicable standards. It is understood that the electrical contractor shall furnish additional items not mentioned herein to meet requirements as specified without claim for additional payments. The Communications Contractor shall be responsible for providing Ladder racking in Telecommunications spaces, Plywood Backboards, J-hooks, surface mounted raceway components (except where surface components are combined with electrical service; in which case the telecommunications faceplates and associated hardware only are the responsibility of the Communications Contractor. Multi-compartment raceway and all electrical related components are the responsibility of the Electrical Contractor.) The Telecommunications Grounding Bar in each equipment space and its connection to the building Telecommunications and Building Ground Systems shall be provided by the Electrical Contractor. Ground wires, entrance lightning protection and grounding connections to all necessary components shall be provided by the Communications Contractor. Equipment Ground Bars within cabinets, racks and other communications equipment enclosures shall be provided by, and connected to the Telecommunications Grounding system by the Communications Contractor. Telecommunication Rooms Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 11 Telecommunication Rooms : General The telecommunication rooms provide a transition between the horizontal, backbone, and entrance pathways and provide space for telecommunications systems components. The TRs and MDC shall provide adequate space for cable terminations (horizontal and backbone), active and passive equipment, cross-connection wiring and hardware, and any other materials or equipment associated with the building technology systems. The TRs and MDC shall be dedicated to the telecommunications related systems and associated support systems, and shall not be shared with electrical or other services, except for electrical and other systems serving that room. The TRs and MDC shall be left in a clean state at acceptance. The Communications Contractor is responsible for the cleaning of the TRs and MDC. Racks and equipment must be wiped free of dust. Cables shall be free of dust. No trash, wire pieces or other items shall be on the floor. Telecommunication Rooms : Location Each TR and MDC shall be placed as near as feasible to the center of the area served by that room. A TR shall not support multiple floors of a multi-story environment unless absolutely necessary. The maximum horizontal distance from any room to any WAO (cable distance via the horizontal pathway system) must be less than 90 meters (295 feet). Additional rooms shall be placed as appropriate to support this distance limitation. The TR rooms in a multistory building should be stacked vertically directly above one another to the maximum extent feasible. The TRs and MDC shall be placed such that no more than two walls are adjacent to non-movable building structures such as rest rooms, exterior walls, elevator shafts, elevator equipment rooms, etc. The TRs and MDC shall not have duct work, piping, etc. that is overhead or through the room, except as required for direct support of the room itself. No building structure or services shall block access to the room. Telecommunication Rooms: Size Telecommunication Rooms: MDC The MDC space should be sized to support all telecommunications related systems for the building served, including: backbone data, voice, DSS, paging and CATV cabling; horizontal data, voice, DSS, paging and CATV cabling; CATV and paging distribution equipment; Network electronics and Servers. The room sizes shown in Figure 1 are typical and minimum sizes for rooms that support all system types identified above. These room sizes assume the door opens outward. Larger rooms are required if the door opens inward due to clearance requirements. All wall or floor mounted equipment sizes and footprints anticipated to be installed in the room must be identified during the schematic phase of the design, and room sizes must be adjusted accordingly. Floor plans with proposed equipment layouts, including required clear space footprints, must be reviewed by CLT Technology Services Office (TSO) during the schematic design phase to confirm rooms are sized adequately. Refer to Figure 1. Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 12 Telecommunication Rooms: TR The TR rooms should be sized to support all telecommunications systems for the area served. The room sizes shown in Figure 2 are typical and minimum sizes for rooms that support horizontal cabling for data, voice, DSS and CATV services only, and do not include other special equipment (i.e., servers). These room sizes assume the door opens outward. Larger rooms are required if the door opens inward due to clearance requirements. All wall or floor mounted equipment sizes and footprints anticipated to be installed in the room must be identified during the schematic phase of the design, and room sizes must be adjusted accordingly. Rooms that include CATV Distribution systems, paging equipment or Network Servers, or any other equipment requiring 36” deep cabinets shall be sized per the MDC sizing requirements above. These room sizes assume the door opens outward. Larger rooms are required if the door opens inward due to clearance requirements. All wall or floor mounted equipment sizes and footprints anticipated to be installed in the room must be identified during the schematic phase of the design. Floor plans with proposed equipment layouts, including required clear space footprints, must be reviewed by CLT Technology Services Office (TSO) during the schematic design phase to confirm rooms are sized adequately. Refer to Figure 2. Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 13 Figure 1. Telecommunications Room Clearances Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 14 Figure 2. Main Data Center Room Clearances Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 15 Telecommunication Rooms: Facilities Telecommunication Rooms: Facilities: HVAC The TRs and MDC shall have HVAC service that is designed to dissipate the heat generated by electrically powered communications equipment. The control for the HVAC services shall be placed in each TR and the MDC at a height of at 72” AFF. Split units should be a cooling unit only. The MDC necessitates a unit that accommodates 12,200 to 12,600 BTUs or higher, as required by electrical demand. The TRs require service that accommodates 8,500 to 9,400 BTUs or higher, as required by the electrical demand. Telecommunication Rooms: Facilities: Back Board All walls of TR’s, and MDC’s, shall be covered with ¾” (trade size) grade AC fire rated plywood to support wall-mounted equipment. This plywood shall be a minimum of 8 feet 6 inches high, mounted 6” above the finished floor (AFF), and shall completely cover the walls. A minimum of 36" clearance plus a 12” allowance, minimum, for wall mounted equipment is required in front of the plywood for proper working space. The plywood shall be installed such that the fire rating stamps are visible. Telecommunication Rooms: Facilities: Electrical Telecommunication Rooms: Facilities: Electrical: Service Provide a minimum of one electrical panelboard, 100A minimum size, generator-backed, to serve all electrical outlets in the TR/MDC. This panelboard shall only be used to serve power loads within the TR/MDC. Telecommunication Rooms: Facilities: Electrical: Outlets TR One 20A,120V AC non-switched duplex outlet shall be installed on each wall of the TR at a height of 16” above the finished floor for test gear, tools, etc. These 4 outlets will share one circuit not shared with other outlets or other electrical devices. Equipment Racks: Two 20A 120V AC duplex outlets shall be installed per 19” equipment rack and shall be mounted in a single quad-outlet box (one duplex outlet per circuit) on the rear base plate of the rack. Power conduits shall be attached to the rear side of the vertical rack support. Conduits shall NOT be run on the front the rack, inside the rack, or in the vertical cable management for any reason. Equipment Cabinets: For multiple compartment cabinets, one 120V, 20A circuit shall be provided for each compartment with two duplex outlets per compartment. Provide two 120V, 20A circuits for single compartment cabinets, with one duplex outlet for each circuit, mounted in a single quad outlet box. Each compartment will be on a unique circuit not shared with other outlets or compartments. Provide two duplex receptacles in each Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 16 compartment. The electrical outlets shall be mounted inside equipment cabinets and enclosures. Refer to Figures 4, 5, and 6. All receptacles shall be labeled with the serving breaker panel and breaker number. MDC One 120 volt 20 amp AC quad outlet shall be installed every 5 feet on each wall of the MDC. A minimum of two quads shall be on each wall. The quad shall be at a height of 16” AFF. Each quad will be on a unique circuit not shared with other outlets or other electrical devices. Equipment Racks: Two 20A 120V AC duplex outlets shall be installed per 19” equipment rack and shall be mounted in a single quad-outlet box (one duplex outlet per circuit) on the rear base plate of the rack. Power conduits shall be attached to the rear side of the vertical rack support. Conduits shall NOT be run on the front the rack, inside the rack, or in the vertical cable management for any reason. Equipment Cabinets: For multiple compartment cabinets, one 120V, 20A circuit shall be provided for each compartment with two duplex outlets per compartment. Provide two 120V, 20A circuits for single compartment cabinets, with one duplex outlet for each circuit, mounted in a single quad outlet box. Each compartment will be on a unique circuit not shared with other outlets or compartments. Provide two duplex receptacles in each compartment. The electrical outlets shall be mounted inside equipment cabinets and enclosures. Refer to Figures 4, 5 and 6. All receptacles shall be labeled with the breaker panel and breaker number. Telecommunication Rooms: Facilities: Electrical: Grounding All items in the TR/MDC shall be grounded to the electrical panelboard as required by the National Electrical Code. Telecommunication Rooms: Facilities: Data Outlets The MDC shall have a standard data outlet located at the CATV Distribution System and at the telephone backboard adjacent to the telephone demarcation. Telecommunication Rooms: Facilities: Equipment Cabinets All Cabinets in each MDC/TR shall conform to the Standard one, two or three compartment cabinets as shown in Figures 4, 5 and 6. Telecommunication Rooms: Facilities: Ladder Racking Ladder racking shall be installed in the MDC and all TRs at a nominal height of 8-6”’ The ladder racking shall be sized such that a 40% or less fill capacity is maintained. The racking will not interfere with, or be placed within 12” of lighting fixture ballasts. Ladder racking mounting methods will include wall brackets for tray adjacent to a wall, and trapeze for racking not adjacent to a wall. Support must meet manufacturer’s recommendations to support a 150 lbs./foot load, minimum. The ladder rack shall have a minimum width of 12" and a minimum depth of 2”. It shall be routed over each row of equipment racks such that access is allowed to all cabinets/racks and pathways; and around the entire perimeter of the room for backboard access and cable routing. Provide ‘waterfall’ (spillways) bend radius managers for each cable dropout location. Each cabinet/rack must have direct access to the ladder rack without Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 17 traveling over other cabinet/racks or spaces. Appropriate spillways will be installed to accommodate any transitions to or from the ladder rack. The ladder rack shall have protective end caps. Affix any power conduits serving the cabinet/racks to the ladder rack support system. Do not affix conduits directly to ladder racking. Refer to Figure 3 . Figure 3. Telecommunications ladder Racking Layouts Telecommunication Rooms: Facilities: Ceiling The TR & MDC shall not have a suspended ceiling installed unless specifically noted otherwise by special circumstances. Ceiling protrusions (e.g. sprinkler heads, light fixtures, mechanical A/C units, etc.) shall be placed to assure a minimum height of 9’-0” AFF, have wire guards installed, and shall not be located above any racks, cabinets, or equipment. Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 18 Telecommunication Rooms: Facilities: Floor The floors shall be treated to eliminate dust. Floors may be covered in anti-static vinyl. Finishes shall be light in color. In existing buildings any carpet shall be removed and the floor cleaned and should be resurfaced in anti-static vinyl. Telecommunication Rooms: Facilities: Walls Walls shall be treated to minimize dust and painted with a light finish. Telecommunication Rooms: Facilities: Lighting Lighting shall be mounted a minimum of 9’ 6” above the finished floor, or a minimum of 12" above the ladder racking. It shall be mounted such that it does not interfere with the cable pathways in the room. Provide wire guards on lighting fixtures. Telecommunication Rooms: Facilities: Door The door shall be a minimum of 36" wide and 80" tall. Telecommunication Rooms: Windows Telecommunication rooms shall NOT have windows. In an existing building, if the MDC or a TR has windows, they shall be filled in and painted to match the existing color in the room Telecommunications Rooms: Cabinet Assemblies Refer to Figures 4, 5 and 6 for single, two- and three-compartment cabinet standard configurations. Each cabinet shall be provided complete as shown, including factory-installed conduits and outlet boxes for power wiring. The Electrical Contractor shall be responsible for providing receptacles, faceplates, wiring and all electrical power connections for these assemblies. Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 19 Figure 4. Single Compartment Cabinet Configuration Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 20 Figure 5. Two Compartment Cabinet Configuration Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 21 Figure 6. Three Compartment Cabinet Configuration Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 22 Telecommunication Rooms: Component Placement Telecommunication Rooms: Component Placement: Floor Cabinets/Racks Descriptions and Placement Floor mounted 19” racks shall be 84” in height, equipment cabinets shall have overall dimensions of 29”W x 30”/36”D x 84”H . Racks shall be located a minimum of 60”from center of rack to the wall directly behind. Clearance on the front side of the rack should be a minimum of 36” after placement of all wall mounted and rack mounted equipment. Refer to Figure 1 and Figure 2 for cabinet clearances. Specific cabinet/rack placement will be verified by CLT during schematic design. Installation will include bolting the racks to the floor and providing ladder racking from the rack to the wall. The ladder racking shall be attached to the equipment rack. There shall be a minimum of three cabinets/racks in a MDC and two cabinet/racks in each of the TRs. Racks will always be mounted side by side with the appropriate management between. Cabinets shall be mounted side-by-side, with internal sides and internal vertical wire management on both sides of each cabinet. All racks shall have one 8” wide Panduit vertical management panel, on the right and left side of the rack. Between 2 adjacent racks there shall be one 12” panel. The vertical management panels shall be doublesided to facilitate patch cable routing vertically in the front and cable routing in the rear of the rack. All racks shall have a 2u Panduit horizontal management panel below each fiber enclosure. Telecommunication Rooms: Component Placement: Backboard mounted equipment Placement Any equipment and/or connector blocks not installed in cabinets or racks will be installed on plywood back board. Specific locations not identified on the Construction Documents shall be approved at installation by the TSO. Telecommunication Rooms: Component Placement: CATV Placement CATV system equipment will be installed in specified cabinet, or on backboard as directed. Specific location shall be approved at installation by the TSO. The CATV equipment shall NOT be placed directly behind the floor racks, or in any location that interferes with required rack/cabinet clearances. Telecommunication Rooms: Component Placement: Paging Equipment Placement Paging System equipment will be installed in specified cabinet, or on backboard as required. Specific location shall be approved at installation by the TSO. The paging equipment shall NOT be placed directly behind the floor racks, or in any location that interferes with required rack/cabinet clearances. Telecommunication Rooms: Labeling Labeling of MDC and TR rooms shall be as directed by the TSO. Nameplate-style signs indicating the MDC and TR room and rack number identifier shall be placed on the center of the top crossbar of the racks or cabinet doors. As an example the second rack in a MDC would be labeled “MDC-A2” and the second rack in the “B” TR room would be labeled “TR-B2”. The Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 23 nameplate-style signs shall be a minimum of 1 ½” in height and consist of black letters on a white background. Nameplates shall be engraved phenolic nameplates. Hand written rack/cabinet nameplates are not acceptable. Telecommunication Rooms: Mini-TR’s Specified locations may have a separate ‘Mini-TR’ within the room for data cabling termination. The data cabling ONLY will be terminated in an enclosed wall mounted Hubbell Rebox cabinet part number RE-4 (32.2” H x 24.2” W x10” D) mounted such that the top of the Rebox is 72” AFF. The Rebox shall be mounted on a wall that will not be used for room expansion (i.e. a corridor wall, rest room wall, etc.). A minimum of 36" clearance is required in front of the Rebox for proper working space. The Rebox shall be grounded to building steel and the telecommunications ground system. The location of the Rebox unit will be identified by the TSO at the time of installation, unless shown on the Construction Documents. The Rebox shall be equipped with: a lockable front door, a standard 48 port patch panel (Panduit DP48688TP) and a six module surface mount box (Panduit CBXF6IW-A) with six inserts (CMSTEI) for the 6 strand ST terminated fiber. The surface mount box shall be mounted inside 1” from the top and side of the Rebox. A 15’ service loop shall be coiled and attached above the ceiling above the Rebox, away from any mounting structures. A 120 volt 20 amp duplex AC Power outlet, generator-backed, shall be provided within the Rebox. Outlet shall be placed at bottom left corner of Rebox. This outlet shall be served from a generatorbacked, Panelboard. The outlet shall be labeled with the breaker panel and breaker number Other wall mount enclosures may also be utilized. Mounting, power and other requirements shall be as for the Mini-TR. Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 24 Communications Pathways Pathways: Entrance Entrance pathways provide for the placement of cables between the utility demarcation point at the property line and the CLT provided entrance room within the building. The pathways shall comply with the EIA/TIA-569-B standard. Pathways: Entrance: Material Entrance pathways shall consist of PVC conduits, or as required by conditions. All penetrations shall be sealed. Pathways: Entrance: MINIMUM Size and Count The count and size of entrance pathways are dependent on the number of services being installed. All entrance conduit and sleeves should be specified according to the following table: Conduit Type From To Conduit Size Qty Service Supported PVC* Property Line Bldg. Entrance 4” 1 min. Copper, Fiber PVC* Property Line Bldg. Entrance 4” 2 Growth PVC* Property Line Bldg. Entrance 2” 1 CATV *- Entrance pathways shall consist of PVC conduits, or as required by conditions Entrance pathways shall be utilized as follows: Conduit 1 – Main (4”) telecommunications entrance conduit consisting of four (4) 1” flexible inner ducts, or one 4-cell Maxcell type innerduct. Conduits 2, 3 – Spare telecommunications entrance conduits shall be capped at both ends for future use with pull rope installed. Conduit 4 – Will be used by Time Warner for CATV. The two conduits (one 4” and one 2”) initially used shall be reamed and bushed to eliminate entrance cable damage. The spare 4” conduits shall be reamed and capped to eliminate gas, water, and vermin entrance. The contractor should provide and store the bushing for future use of this conduit. Pathways: Entrance: Installation The entrance pathways shall have the following attributes: conduits shall maintain a 40% or less fill capacity conduits shall be a minimum of 24” below grade conduits shall have a drain slope away from the building PVC conduits shall have a metallic tape placed 12” above the conduits conduits shall have no more than two 90 degree bends (radius a minimum of 40”) before a handhole or manhole is installed handholes or manholes shall not be shared with public utilities Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 25 conduits shall run no more than 500’ before a handhole or manhole is installed conduits shall extend 12” in the entrance room, and shall be no more than 2” from the nearest wall conduit ends shall be bushed, reamed and capped conduits, and all sub-ducts, shall have a pull string installed Conduits shall not be shared with other services, i.e., CATV, public utilities, etc. Pathways: Entrance: Firewall The penetration through firewalls to support entrance cabling shall be firestopped per code after installation of cabling, and after all cable additions. For new construction, firestopping materials shall be determined based on best fit to the building design. For existing buildings, the firestopping materials shall be finished to match existing wall finish. Pathways: Intra-Building Intra-building pathways shall provide for the placement of cables between building levels and/or between MDC and TRs within a building, and consist of trays, caddy supports, conduit, sleeves, surface mounted raceway, etc. The pathways shall comply with TIA/EIA-569-B standards. Pathways: Intra-Building: Size and Count The count and size of intra-building pathways are dependent on the number of services being installed and the number of WAOs the pathways support. Pathways: Intra -Building: Cable Tray Cable tray will have minimum dimensions of 12" wide x 4" deep. Cable tray will maintain a 40% or less fill capacity at installation. Backbone cable tray shall be installed above the corridor ceiling grids at nominal height of 1’ above the ceiling grid. The cable tray will not interfere with, or be placed within 12” of lighting fixture ballasts or duct work. Conduits pipes or sprinkler heads shall not run through the cable tray. Cable tray mounting methods will include wall brackets for tray adjacent to a wall and trapeze for tray not adjacent to a wall. All mounting methods must meet manufacturer’s recommendations and be sized and spaced according to load. Wire basket cable tray shall be installed to support a MINIMUM loading of 50 lbs./lineal foot. Cable tray will NOT penetrate walls, instead four 4” conduit sleeves shall be used to penetrate all walls. Pathways: Intra-Building: Cable Caddy Supports Erico Caddy Cablecat supports or equivalent shall be used to support cables instead of hooks. The placement caddy supports in the ceiling space shall facilitate the placement of cables, and shall be placed at a random distance between each support NOT TO EXCEED five feet to prevent uniform sag between cable supports which could have detrimental effects on the testing and transmission characteristics of the cabling. The caddy supports shall be attached to the structural support joists. The bottom of the supports should be between 8” and 12” from the ceiling grid. Multiple caddy support paths may be installed along a route if cable capacity requirements dictate. Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 26 The caddy supports shall be placed away from other services in the ceiling (HVAC, fire, electrical, etc.) to provide adequate working clearance for the technicians. The minimum horizontal clearance from the access side of the support is 12”, and must be maintained continuously between the supports. The caddy support and the intended cable pathway between supports shall have a minimum clearance of 12”, on all sides from any fluorescent lighting fixtures. Caddy supports shall maintain a 40% or less fill capacity at installation. Pathways: Intra-Building: Conduit Conduit pathways shall be installed according to the following: Conduits shall maintain a 40% or less fill capacity, 1 inch MINIMUM trade size. conduits shall have no more than two 90 degree bends (radius a minimum of 40”) before pull box is installed conduits shall run no more than 150’ before a pull box is installed conduit ends shall be bushed and reamed, and have an insulating bushing. conduits, and all sub-ducts, shall have a pull string installed Conduits shall not be shared with other services, i.e., CATV, public utilities, etc. Pathways: Intra-Building: Non-Firewall Penetrations Penetrations through non fire-rated walls will use 4” bushed and reamed sleeves as the transition through walls and cable tray runs. The number of sleeves will be dependent upon the quantity of cables to be supported while maintaining 40% or less fill capacity. 12” x 4” cable tray requires four 4” sleeves to penetrate walls without derating overall pathway capacity. Pathways: Intra-Building: Firewall Penetrations Firewall penetrations shall be made utilizing a fire-rated cable pathway, “Specified Technologies, Inc. EZ-Path Cable Pathway” or equivalent. The number of penetrations will be dependent upon the quantity of cables to be supported while maintaining a 40% or less fill capacity. Pathways: Inter-Building Inter-building pathways shall provide for the placement of cables between the MDC and TRs in unattached buildings and consist of underground or structure attached systems. The pathways shall comply with TIA/EIA-569-B standards. Pathways: Inter-Building: Conduit Between Buildings The backbone pathways between buildings shall be installed according to the following: conduits will maintain a 40% or less fill capacity conduits shall be a minimum of 24” below grade conduits shall have a drain slope away from the building PVC conduits shall have a metallic tape placed 12” above the conduits Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 27 conduits shall have no more than two 90 degree bends (radius a minimum of 40”) before a handhole or manhole is installed handholes or manholes shall not be shared with public utilities conduits shall run no more than 500’ before a handhole or manhole is installed conduits shall extend 4” AFF in the entrance room, and shall be no more than 2” from the nearest wall conduit ends shall be bushed and reamed conduits, and all sub-ducts, shall have a pull string installed Conduits shall not be shared with other services, i.e., CATV, public utilities, etc. Pathways: Horizontal Pathways: Horizontal: General Horizontal pathways shall consist of caddy supports, cable tray, metallic conduits, sleeves and surface mounted raceway. Sleeves and cable tray will be installed during construction, and other pathways phased in as construction evolves. Horizontal pathways will not be shared with any other service (e.g. electrical). All pathways shall comply with the EIA/TIA-569-B standard. Pathways: Horizontal: Cable Caddy Supports Erico Caddy Cablecat supports or equivalent will be used to support cables instead of hooks. Supports shall maintain a 40% or less fill capacity at installation. The placement of caddy supports in the ceiling space shall facilitate the placement of cables and shall be placed at a random distance between each support NOT TO EXCEED five feet to prevent uniform sag between cable supports which could have detrimental effects on the testing and transmission characteristics of the cabling. Smaller intervals may be used for facilitating turns and clearing obstructions. The supports shall be attached to the structural support joists. The bottom of the supports should be between 8 and 12” from the ceiling grid. Other intervals may be used for clearing obstructions. Multiple caddy support paths may be installed along a route if capacity requirements dictate. The supports shall be placed away from other services in the ceiling (HVAC, fire, electrical, etc.) to provide adequate working clearance for the technicians. The minimum horizontal clearance from the access side of the support is 12” and must be maintained continuously between the supports. The caddy support and the intended cable pathway between supports shall have a minimum clearance of 12”, on all sides, from any fluorescent lighting fixtures. Pathways: Horizontal: Cable Tray Horizontal cable tray shall be installed, according to manufacturer specifications, above the corridor ceiling grids at nominal height of 12” above the ceiling grid. Cable tray will maintain a 40% or less fill capacity at installation. The cable tray will not interfere with, or be placed within 12” of lighting fixture ballasts or duct work. Conduits, pipes or sprinkler heads are not to go through the cable tray. Cable tray mounting methods will include wall brackets for tray adjacent to a wall, and trapeze for tray not adjacent Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 28 to a wall. Cable tray will have minimum dimensions of 12" wide X 4" deep. Cable tray shall be installed to bear a load of 50 pounds per lineal foot, minimum. Pathways: Horizontal: Penetrations All wall and floor penetrations (non-firewall) for horizontal wiring will be made with metallic sleeves. All sleeves shall be reamed and bushed on both ends. Horizontal pathways through walls shall be sized according to the table below while maintaining a 40% or less fill capacity at installation: Number of Cables Sleeve Size 1–3 1.0" 4 –14 2.0" 15-50 4.0” * Note: Cable capacity is shown here is based on a cable diameter of 0.25”. Counts vary with cable diameter. Pathways: Horizontal: Penetrations: Firewalls All firewall penetrations will use utilize a fire-rated cable pathway, “Specified Technologies, Inc. EZ-Path Cable Pathway” or equivalent. All penetrations shall maintain a 40% or less fill capacity. Pathways: Horizontal: Metallic Conduit All conduit/sleeve ends shall have an insulating bushing ring installed on both ends to provide a smooth surface for cable pulling. All conduits shall have a gentle sweep into the cable tray in the direction of cable route so as to avoid sharp cable bends. All conduits shall maintain a 40% or less fill capacity. Pathways: Horizontal: Flush Mounted Outlets Flush mounted outlets will consist of a 4" x 4" x 2 1/8” outlet box with a single gang plaster ring. A 1” metallic conduit, bushed and reamed, will be stubbed from outlet box into the ceiling space, cable tray or serving TR . Pathways: Horizontal: Surface Mounted Raceway with outlets A 10’ section of non-metallic Panduit Twin-70 will be used. All raceway and faceplates will be International White. AC power can be run in the power channel provided. All electrical outlets in the raceway will be on a dedicated circuit separate from other outlets. In addition each electrical outlet shall be 120 volt 20 amp. Pathways: Horizontal: Equipment Rooms Surface Mounted Raceway Raceway in equipment rooms may be mounted on three walls around the perimeter of the room. Nonmetallic Panduit Twin-70 will be used. All raceway and faceplates will be International White. AC power can be run in the power channel provided. All electrical outlets in the raceway will be divided among dedicated 120 volt 20 amp circuits. Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 29 Pathways: Horizontal: Surface Mounted Raceway: Single Outlets in Existing Building The Contractor shall provide a vertical pathway from the ceiling space to the horizontal raceway and outlet utilizing nonmetallic raceway. PANDUIT Twin-70 shall be installed. All raceway and faceplates will be International White. The raceway shall be mounted 36” AFF to the bottom of the raceway. Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 30 Cabling Cabling: General Cabling: Entrance Cabling Entrance cabling will be provided by the Contractor or Service Provider, as required. Cabling: Entrance Cabling: Lightning Protection The utility provider is responsible for providing lightning protection on all entrance cabling. Protection will be solid-state and provide voltage clamping and other characteristics according to the manufacturer’s recommendations of the associated system. Cabling: Entrance Cabling: Installation The entrance cables shall be placed in the installed entrance pathway system between the property line and the building entrance rooms per the manufacturer’s guidelines on bend radii and maximum pulling tension. In the entrance rooms or spaces, the entrance cables will be routed neatly and shall be dressed as appropriate with Velcro wraps (suitable for air handing spaces). The cabling will be installed using standard industry procedures with regard to pulling methods and tension, cable bend radius, strain relief, etc. Fiber cables shall be indoor/outdoor, plenum rated, aluminum armored with an overall orange sheath, from the building entrance point to the fiber enclosure in the MDC. There shall be a fifteen-foot service loop for the fiber cable at each end and a ten-foot service loop for copper cable at each end. Cabling: Entrance Cabling: Termination Cabling: Entrance Cabling: Termination: Copper Multiple pair 24 AWG copper cable will be terminated on 66 blocks in the designated entrance room. The cable shall be terminated using standard industry procedures with regard to Termination order (color code), cable bend radius, strain relief, solid-state protection, etc. Cabling: Entrance Cabling: Termination: Fiber Fiber cables will be terminated on fiber enclosures located in the entrance room. The cable shall be Terminated using manufacturer and standard industry procedures with regard to cable cleaning, cable bend radius, strain relief, etc. Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 31 Cabling: Entrance Cabling: Termination: CATV The Time Warner entrance cable will be terminated on a wall mounted CATV tap in the designated entrance room. Cabling: Entrance Cabling: Labeling Each entrance cable will be tagged and labeled at each end point and pull point and note the Termination location. For example a copper voice entrance cable would be labeled “Telco Entrance to MDC”; a CATV entrance cable would be labeled “CATV Entrance to MDC”. Cabling: Entrance Cabling: Testing The service providers are responsible for testing the entrance cabling. Cabling: Entrance Cabling: Grounding The utility providers are responsible for grounding all entrance cabling. Cabling: Backbone Cabling: Backbone: General Backbone cabling shall consist of copper and fiber cable for voice and data applications and coax for CATV applications. All backbone cabling will be non-plenum or plenum rated depending upon the application. Cabling: Backbone: Installation The backbone cables shall be placed in the installed backbone pathway system between the TRs and MDC per the manufacturer’s guidelines on bend radii and maximum pulling tension. Cables shall not be tied to conduit, strung across ceiling grid, support joists, beams, girders, or otherwise installed outside the backbone pathway. In the TRs and MDC the backbone cables will be routed neatly in the ladder racking and shall be dressed as appropriate with Velcro wraps (suitable for air handing spaces). Installer will use standard industry procedures with regard to pulling methods and tension, cable bend radius, strain relief, etc. Fiber cables shall be continuous from the fiber enclosures in the TRs and the MDC through the backbone pathway. All fiber optics cable shall be indoor/outdoor rated, with interlocking flexible aluminum armor under an overall sheath. All fiber cables shall be plenum rated. There shall be a fifteen-foot service loop for fiber cable installed in the fiber enclosure, a ten-foot service loop for copper cable installed on the backboard and a fifteen-foot service loop for the CATV installed on the backboard. The fiber service loops in the MDC shall be 20 feet, minimum. Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 32 Cabling: Backbone: Analog Voice and Paging Cabling: Backbone: Analog Voice and Paging: Cable Type Voice and paging indoor backbone cable shall consist of multi-pair 24 AWG, solid conductor, Category 5e, non-plenum or plenum rated, depending upon the construction application. Voice and paging outdoor backbone cable for shall consist of multi-pair 24 AWG, solid conductor, Category 5e, with a water-proof fill and aluminum jacket (CALPETH or equivalent). Voice and paging backbone cable applications shall be sized for system requirements plus 20% growth. Cabling: Backbone: Analog Voice and Paging: Termination Multiple pair 24 AWG copper cable installed for use as backbone cable for voice and paging applications will be terminated on separate modular 66 blocks in all TRs and the MDC. Each backbone cable shall be terminated on its own unique modular 66 blocks. Mixing of backbone cables on the same modular 66 block is not permitted. The cable shall be terminated using standard industry procedures with regard to Termination order (color code), cable bend radius, strain relief, protection, etc. All outside plant copper cable will be terminated with solid-state protection clamped to 90 volts for analog. The installer is responsible for providing protectors on both ends of the backbone cable provided between buildings and for providing blanks for all unused spaces. Cabling: Backbone: Analog Voice and Paging: Labeling All labels shall be printed using a Brother P-touch labeler (or equivalent). Labels shall not be handwritten. Each backbone cable will be tagged and labeled at each end point and pull point. The label should include the buildings and/or rooms connected and indicate the type of cable and capacity. For example a 100 pair backbone cable from the MDC to TR-B would be labeled “MDC to TR-B 100-pair”. Voice and paging modular 66 block labeling in the MDC and TRs will use a numbering scheme starting with 001 for the first Termination on the first block, and continuing sequentially through the last Termination of the last block. A laminated sheet providing Termination information will be mounted on backboard near the modular 66 blocks. Each modular 66 block shall be labeled with a printed colored label consistent with the EIA/TIA-606 specification, which is as follows: Analog voice – purple Paging – red Horizontal Terminations – blue Intra Building backbone Terminations – white Interbuilding backbone Terminations – brown Miscellaneous circuits – yellow Service provider blocks - orange Customer side of demarc – green Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 33 Cabling: Backbone: Data Backbone Cabling: Backbone: Data Backbone: MDC and Distribution TRs The fiber cable for indoor/outdoor use shall be tight buffered, 8um/125um singlemode or 62.5/125um multimode (application dependent), constructed for indoor/outdoor inter-building applications, with water resistant features, rated for plenum environments, with interlocking flexible aluminum armor under an overall sheath. Cables shall be manufactured by CommScope or Corning. Cabling: Backbone: Data Backbone: Innerduct If flexible innerduct is used with unarmored fiber cabling in lieu of armored fiber, the each fiber cable shall be run in its own 1” fiber innerduct from termination rack to termination rack. Innerduct shall be continuous and have no gaps. Innerduct should be plenum or non-plenum rated depending on the application. The use of innerduct requires the prior written approval of the TSO. Cabling: Backbone: Data Backbone: Termination Fiber cables will be terminated in fiber enclosures located in the TRs and MDC, with ST connectors(multimode or type LC (singlemode) at both ends. The cable shall be terminated using manufacturer and standard industry procedures with regard to cable cleaning, cable bend radius, strain relief, etc. Fiber enclosure will be fitted with blanks on all unused termination points. Fiber strands will be terminated as listed in the table below. Strand 1 2 3 4 5 6 7 8 9 10 11 12 Color Blue Orange Green Brown Slate White Red Black Yellow Violet Rose Aqua Cabling: Backbone: Data Backbone: Labeling All labels shall be printed using a Brother P-touch labeler (or equivalent). Labels shall not be handwritten. Each backbone cable will be tagged and labeled at each end point and pull point. The label should include the buildings and/or rooms connected and the fiber type. For example the 12/6 strand multimode/singlemode fiber cable connecting TRB to the MDC would be labeled “MDC to TR-B 12MM/6SM”. In addition, each fiber pair shall be tagged and labeled at each end point. For example, the multimode fiber in the MDC going to TR-B would be labeled as such: B-1/2, B-3/4, B-5/6, B-7/8, B-9/10, B-11/12 with the letter indicating the TR and the numbers indicating the fiber strand. Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 34 Cabling: Backbone: CATV Backbone The CATV backbone (trunk cabling) will be run within the pathway system from the CATV service Entrance to the primary distribution point. Trunk cable will be run from the primary distribution point to each TR in each area. An individual trunk cable will then be run from designated TR down each corridor served. Cabling: Backbone: CATV Backbone: Cable Type The backbone cabling for the CATV Distribution System shall be plenum (CommScope P3500JACAR), coaxial cable. Cabling: Backbone: CATV Backbone: Termination Trunk cabling for CATV system in the MDC will be terminated on wall mounted taps. All taps will be mounted on the plywood backboard. Cabling: Backbone: CATV Backbone: Labeling All labels shall be printed using a Brother P-touch labeler (or equivalent). Labels shall not be handwritten. Each backbone cable will be tagged and labeled at each end point and pull point. The label should include the letter of the MDC or TR that it originates from followed by a number. The first backbone run would be number 1 and each run thereafter would be numbered sequentially. Labels will be put on a nylon marker tie and attached to the cable. Cabling: Horizontal Cabling: Horizontal: General The horizontal wiring consists of the wiring from the communications rooms (MDC or TR) to the WAO. The horizontal wiring design includes the wiring termination components in the telecommunications rooms, the horizontal wiring itself, and the termination components at the outlet. Cabling: Horizontal: Cable Type All horizontal cabling will be plenum rated. All data cabling shall be rated, tested and certified for Category 6 performance. All analog voice and paging cabling shall be rated, tested and certified for Category 5e. Category 6 cabling may be substituted for Category 5e cabling at no cost to the Owner. All jacks shall match the performance Category of the associated cable. All CATV horizontal coaxial cabling will be (CommScope F660BVR) plenum rated. Cabling: Horizontal: Color Coding All horizontal cabling run shall adhere to the following color code chart. Jack colors shall match cable color unless otherwise noted. Usage Cable Color Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 35 Tenant Data CLT Data FIDS Comnet Data TSA Data HMS/Host Data Critical DSS Phone TSA Phone Black Blue Green Pink Purple Red Blue with Orange jacks Grey White Cabling: Horizontal: Topology Horizontal wiring for data, voice and paging shall be configured in a star topology from the MDC or TRs. The maximum distance (cable run) between the outlet and the serving communications room shall be 90 meters (290 feet). Cable runs that exceed the 290 feet shall be submitted to the TSO in writing for a resolution. Cabling: Horizontal: Installation The horizontal cabling shall be placed in the installed horizontal pathway system (cable tray, hooks, and/or sleeves) between the communication rooms and the outlets. The cables shall not be tied to conduit in the ceiling, laid on duct work, strung across the ceiling grid, or otherwise be installed outside of the horizontal pathway system. In accordance with NEC 800-52(E), "Raceways shall be used for their intended purpose. Communication cables or wires shall not be strapped, taped, or attached by any means to the exterior of any conduit or raceway as a means of support." The cables shall be installed with a minimum of 12” clearance from fluorescent lighting fixtures. The cables shall have no more than 8” sag between hooks in the horizontal pathway system. The cables shall be dressed neatly and grouped in small bundles of 50 cables or less, of like purpose and color with loose Velcro wraps that are suitable for air handling spaces. For example, only data cables should be bundled together, only voice cables bundled together. All paging/intercom speaker cabling shall be run entirely in conduit to the serving TR. In the TRs and MDC, the horizontal cables will be routed via the ladder racking system and shall be dressed as appropriate with loose Velcro wraps (suitable for air handing spaces). A minimum 10 feet of slack shall be left in the ceiling space at the outlet conduit for future reterminations, repair, or repositioning of the outlet. The slack shall be placed in the cables in a “staggered” fashion. In the communications rooms, a service loop of minimum 10 feet of slack shall be placed in a “staggered” fashion on the cable tray. Any cables that are determined to be damaged should be removed from the patch panels and pulled out as opposed to being abandoned and a replacement cable(s) pulled according to specification. Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 36 All cables are full run. Splices or inline connectors are not allowed. Cabling: Horizontal: Termination of Category 6 Data Cabling: Horizontal: Termination of Category 6 Data: MDC & TRs Category 6 Data Horizontal Cables will be terminated in the MDC or TRs on 48 port high density modular patch panels. The patch panels shall be mounted in 19" racks or cabinets. In the MDC and any TR with 3 or more racks all data patch panels will be mounted in the center rack. In TRs with less than three racks data patch panels will be mounted in the rack closest to the wall. Patch panels used are 568B, 48 port, modular type, Category 6 (Panduit). The order for mounting enclosures, panels and management shall be as follows. The fiber enclosure shall be mounted at the top of the rack with a 2U horizontal front and rear management (Panduit WMPHF3) directly beneath. Data patch panels will be mounted next. Cables shall be routed from the pathway system to the rack via ladder racking. Cables of like purpose will be bundled with loose Velcro wraps (suitable for air handing spaces). Cables will turn down into the back of the vertical management. They will then turn and exit from the vertical management at the patch panel on which it is to be terminated. Cables for the left side of the patch panel will be routed on the left vertical management. Cables for the right side of the patch panel will be routed on the right vertical management. At no time shall cables cross the center point of the patch panel. Cables will be neatly dressed with loose Velcro wraps (suitable for air handing spaces). The installers shall observe the wiring practices described in EIA/TIA 568C and the cable manufacturer specifications. The amount of untwisting in any pair as a result of termination (ISO, patch panel, or block) shall not be greater than one-half (0.5) inch, and a minimum length of cable jacket shall be removed, no more than one-half (0.5) inch (only as much as is required to terminate on connecting hardware). The cable bend radii shall not be less than four-times the cable diameter for horizontal cable. Care should be exercised to minimize twisting of cabling during installation. Terminations will follow the T568B pattern for termination order. Cabling: Horizontal: Termination of Category 6 Data: WAOs Category 6 data cables will be terminated on the appropriately colored Category 6 RJ-45 jacks using the T568B pin-out (Panduit CJK688TP**). Cabling: Horizontal: Termination of Analog Voice and Paging Cabling: Horizontal: Termination of Analog Voice and Paging: MDC & TRs Voice and paging cabling Terminations and equipment shall be mounted to the plywood backboard. Voice and paging cabling Terminations shall NOT be installed directly behind or in interference with data racks. Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 37 The Termination method for Category 5e cable shall be distinct and separate 66 blocks for each application. Each application of Category 5e cabling (e.g. voice, paging) shall have individual modular blocks dedicated specifically for that particular application. Therefore, the analog voice cabling should have separate 66 blocks for voice terminations only, paging would have separate modular 66 blocks for paging only. Voice and paging modular block labeling in the MDC and TRs will use a numbering scheme starting with 001 for the first termination on the first block, and continuing sequentially through the last Termination of the last block. A laminated sheet providing termination information will be mounted on backboard near the blocks. Each modular block shall be labeled with a colored label consistent with the TIA/EIA-606A specification, which is as follows: Analog voice – purple Paging – red Horizontal Terminations – blue Intra Building backbone Terminations – white Interbuilding backbone Terminations – brown Miscellaneous circuits – yellow Service provider blocks - orange Customer side of demarc – green Analog voice and paging cross connects will utilize USOC patch cables. The patch cables should be gray for voice, and pink for paging. Cabling: Horizontal: Termination of Voice and Paging: WAOs Category 5e voice cables will be terminated on the appropriately colored Category 5e RJ-45 jacks using the T568B pin-out (Panduit CJ5E88TG**). Category 5e paging cables will be terminated on clips or screw type terminals on speakers mounted in the ceiling or on walls. Five feet of slack shall be coiled up with a Velcro wrap (suitable for air handing spaces) and laid on top of the speaker backbox. Cabling: Horizontal: Termination of CATV Cabling: Horizontal: Termination of CATV: MDC CATV Distribution components such as couplers and taps will be wall mounted. CATV distribution components shall be mounted on the plywood backboard and NOT be directly behind or in interference with data racks. Coax/fiber interfaces and other active CATV components may be either rack or backboard mounted, as required. Cabling: Horizontal: Termination of CATV: WAOs RG6 coax terminated with radial compression F connectors will be run from backbone tap to WAO. Each run should be a maximum of 150’. Coax will be labeled at each end with the same label as the WAO. Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 38 Cabling: Work Area Outlets Work Area Outlets (WAOs) shall consist of flush mount, surface mount raceway, or floor-box outlets and are of multiple types. All faceplates are the screw on type. The quantity and types of outlets are determined by the room type/function, i.e. classroom, lab, workroom, etc. Single gang, flush-mount, 4-port faceplates shall be installed for all outlets except for when outlets are placed in floor boxes or for the “J” outlet. For slab floorbox applications, the floorbox shall be Wiremold RFB4-CI-1 for raised floor applications Wiremold AF3-** with CIHT-GFI insert and Panduit CFG2IW insert. For applications requiring a power pole, the Panduit PCPA11R20IW (11’ length) or PCPA13R20IW (13’ in length) dual channel for power and communications should be used. It should be installed per manufacturer specifications by using mounting brackets and the faceplates should be the screw on type. The outlet types are as follows: Type A AD2 D2 D2R D4R D4 F2 F2R F4R F4 J JD2 K KD2 S Description Analog Voice Data/Analog Voice Data Only Data Only Data Only Data Only Data Only Data Only Data Only Data Only CATV CATV / Data CCTV CATV / Data Paging/Speaker Configuration 1 Voice (RJ45 Cat. 5e) 1 Voice (RJ45 Cat. 5e), 2 Data (RJ45 Cat. 6) 2 Data (RJ45 Cat. 6) 2 Data (RJ45 Cat. 6) cabled to REBOX 4 Data (RJ45 Cat. 6) cabled to REBOX 4 Data (RJ45 Cat. 6) 2 Data FIDS(RJ45 Cat. 6) 2 Data FIDS(RJ45 Cat. 6) cabled to REBOX 4 Data FIDS(RJ45 Cat. 6) cabled to REBOX 4 Data FIDS(RJ45 Cat. 6) 1 RG6 female F connector 1 RG6 female F connector, 2 Data (RJ45 Cat. 6) 1 RG6 female F connector 1 RG6 female F connector, 2 Data (RJ45 Cat. 6) 1 Paging (red Category 5e cable Terminated on a speaker with either clips or screw type Terminals) DS2 Data Only 2 Data (RJ45 Cat. 6) Camera Outlet for DSS system WD2 Data Only 2 Data (RJ45 Cat. 6) Access Point Outlet for Wireless system Note: Refer to Cable Color Code Chart for cable and jack color coding requirements. Cabling: Work Area Outlets: Detail Cabling: Work Area Outlets: Detail A “A” outlets will consist of a double gang deep outlet box with single gang opening, single gang four port flush mounted faceplate with one Category 5e cable terminated on a RJ-45 T568B jack in position A. Positions B, C & D shall be covered with a blank. These outlets will be installed at the same height as Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 39 electrical receptacles, typically 16” AFF unless in an office area where the mounting height will be 36”. All cables will be routed back to the appropriate MDC or TR. Cabling: Work Area Outlets: Detail AD2 “AD2” outlets will consist of a single gang, four port flush mounted faceplate mounted in the surface mounted raceway or double gang deep outlet box, with one Category 5e cable terminated on a RJ-45 T568B jack in position A for voice and with two Category 6 data cables terminated on RJ-45 T568-B jacks and placed in the C and D faceplate positions. Blanks shall be installed in the B position. A 120 volt 20 amp quad outlet is required within one foot of the outlet. For a slab floorbox application it will require a Wiremold RFB4-CI-1 floor box for raised floor applications Wiremold AF3-** with a Panduit CHI2MWG Bezel Adapter, one Category 5e cable terminated on a RJ-45 T568B jack in position A (voice) and two Category 6 data cables terminated on RJ-45 T568B data jacks and placed in the C, D positions of the faceplate. Two 120 volt 20 amp duplex outlets are required within the floor box. All cables will be routed back to the appropriate MDC or TR. Cabling: Work Area Outlets: Detail D2 “D2” outlets will consist of a single gang, four port flush mounted faceplate mounted in the surface mounted raceway or double gang deep outlet box, with two Category 6 data cables terminated on RJ-45 T568B jacks and placed in the C and D faceplate positions. Blanks shall be installed in the A and B positions. A 120 volt 20 amp quad outlet is required within one foot of the outlet. For a slab floorbox application it will require a Wiremold RFB4-CI-1 floor box for raised floor applications Wiremold AF3** with a Panduit CHI2MWG Bezel Adapter, with two Category 6 data cables terminated on RJ-45 T568B data jacks and placed in the C, D positions of the faceplate. Blanks shall be installed in the A and B positions. Two 120 volt 20 amp duplex outlets are required within the floor box. All cables will be routed back to the appropriate MDC or TR. Cabling: Work Area Outlets: Detail D2R “D2R” outlets will consist of a single gang, four port flush mounted faceplate mounted in the surface mounted raceway or double gang deep outlet box, with two Category 6 data cables terminated on RJ-45 T568B jacks and placed in the C and D faceplate positions. Blanks shall be installed in the A and B positions. A 120 volt 20 amp quad outlet is required within one foot of the outlet. For a slab floorbox application it will require a Wiremold RFB4-CI-1 floor box for raised floor applications Wiremold AF3** with a Panduit CHI2MWG Bezel Adapter, with two Category 6 data cables terminated on RJ-45 T568B data jacks and placed in the C, D positions of the faceplate. Blanks shall be installed in the A and B positions. Two 120 volt 20 amp duplex outlets are required within the floor box. All cables will be routed back to the appropriate to the serving REBOX. Cabling: Work Area Outlets: Detail D4R “D4R” outlets will consist of a single gang, four port flush mounted faceplate mounted in the surface mounted raceway or double gang deep outlet box, with four Category 6 data cables terminated on RJ-45 T568B jacks and placed in the A, B, C and D faceplate positions. A 120 volt 20 amp quad outlet is required within one foot of the outlet. For a slab floorbox application it will require a Wiremold RFB4CI-1 floor box for raised floor applications Wiremold AF3-** with a Panduit CHI2MWG Bezel Adapter, with four Category 6 data cables terminated on RJ-45 T568B data jacks and placed in the A, B, C, and D positions of the faceplate. Two 120 volt 20 amp duplex outlets are required within the floor box. All cables will be routed back to the appropriate to the serving REBOX. Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 40 Cabling: Work Area Outlets: Detail D4 “D4” outlets will consist of a single gang, four port flush mounted faceplate mounted in the surface mounted raceway or double gang deep outlet box, with four Category 6 data cables terminated on RJ-45 T568B jacks and placed in the A, B, C and D faceplate positions. A 120 volt 20 amp quad outlet is required within one foot of the outlet. For a slab floorbox application it will require a Wiremold RFB4CI-1 floor box for raised floor applications Wiremold AF3-** with a Panduit CHI2MWG Bezel Adapter, with four Category 6 data cables terminated on RJ-45 T568B data jacks and placed in the A, B, C, and D positions of the faceplate. Two 120 volt 20 amp duplex outlets are required within the floor box. All cables will be routed back to the appropriate MDC or TR. Cabling: Work Area Outlets: Detail F2 “F2” outlets are dedicated to the FIDS network. The outlet will consist of a single gang, four port flush mounted faceplate mounted in the surface mounted raceway or double gang deep outlet box, with two Category 6 data cables terminated on RJ-45 T568B jacks and placed in the C and D faceplate positions. Blanks shall be installed in the A and B positions. A 120 volt 20 amp quad outlet is required within one foot of the outlet. For a slab floorbox application it will require a Wiremold RFB4-CI-1 floor box for raised floor applications Wiremold AF3-** with a Panduit CHI2MWG Bezel Adapter, with two Category 6 data cables terminated on RJ-45 T568B data jacks and placed in the C, D positions of the faceplate. Blanks shall be installed in the A and B positions. Two 120 volt 20 amp duplex outlets are required within the floor box. All cables will be routed back to the serving MDC or TR. Cabling: Work Area Outlets: Detail F2R “F2R” outlets are dedicated to the FIDS network, and will consist of a single gang, four port flush mounted faceplate mounted in the surface mounted raceway or double gang deep outlet box, with two Category 6 data cables terminated on RJ-45 T568B jacks and placed in the C and D faceplate positions. Blanks shall be installed in the A and B positions. A 120 volt 20 amp quad outlet is required within one foot of the outlet. For a slab floorbox application it will require a Wiremold RFB4-CI-1 floor box for raised floor applications Wiremold AF3-** with a Panduit CHI2MWG Bezel Adapter, with two Category 6 data cables terminated on RJ-45 T568B data jacks and placed in the C, D positions of the faceplate. Blanks shall be installed in the A and B positions. Two 120 volt 20 amp duplex outlets are required within the floor box. All cables will be routed back to the appropriate to the serving REBOX. Cabling: Work Area Outlets: Detail F4R “F4R” outlets are dedicated to the FIDS network, and will consist of a single gang, four port flush mounted faceplate mounted in the surface mounted raceway or double gang deep outlet box, with four Category 6 data cables terminated on RJ-45 T568B jacks and placed in the A, B, C and D faceplate positions. A 120 volt 20 amp quad outlet is required within one foot of the outlet. For a slab floorbox application it will require a Wiremold RFB4-CI-1 floor box for raised floor applications Wiremold AF3** with a Panduit CHI2MWG Bezel Adapter, with four Category 6 data cables terminated on RJ-45 T568B data jacks and placed in the A, B, C, and D positions of the faceplate. Two 120 volt 20 amp duplex outlets are required within the floor box. All cables will be routed back to the appropriate to the serving REBOX. Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 41 Cabling: Work Area Outlets: Detail F4 “F4” outlets are dedicated to the FIDS network, and will consist of a single gang, four port flush mounted faceplate mounted in the surface mounted raceway or double gang deep outlet box, with four Category 6 data cables terminated on RJ-45 T568B jacks and placed in the A, B, C and D faceplate positions. A 120 volt 20 amp quad outlet is required within one foot of the outlet. For a slab floorbox application it will require a Wiremold RFB4-CI-1 floor box for raised floor applications Wiremold AF3-** with a Panduit CHI2MWG Bezel Adapter, with four Category 6 data cables terminated on RJ-45 T568B data jacks and placed in the A, B, C, and D positions of the faceplate. Two 120 volt 20 amp duplex outlets are required within the floor box. All cables will be routed back to the appropriate MDC or TR. Cabling: Work Area Outlets: Detail J “J” outlets are for CATV connection and will consist of a single gang, four port flush mounted faceplate mounted in the surface mounted raceway or double gang deep outlet box, with one Series 6 type coaxial cable terminated on one ‘F’ type radial clamp connector in position A, and blanks installed in positions B, C and D. Cable shall be run to tap in serving MDC or TR. Cabling: Work Area Outlets: Detail JD2 “JD2” outlets are for CATV and data connections and will consist of a single gang, four port flush mounted faceplate mounted in the surface mounted raceway or double gang deep outlet box, with one Series 6 type coaxial cable terminated on one ‘F’ type radial clamp connector in position A, two Category 6 data cables terminated on RJ-45 T568B jacks and placed in the C and D faceplate positions. Blanks shall be installed in the B position. A 120 volt 20 amp quad outlet is required within one foot of the outlet. All cables will be routed back to the appropriate MDC or TR. Cabling: Work Area Outlets: Detail K “K” outlets are for CCTV camera connection and will consist of a single gang, four port flush mounted faceplate mounted in the surface mounted raceway or double gang deep outlet box, with one Series 6 type coaxial cable terminated on one ‘F’ type radial clamp connector in position A, and blanks installed in positions B, C and D. Cable shall be run to tap in serving MDC or TR. Cabling: Work Area Outlets: Detail KD2 “KD2” outlets are for CCTV camera and data connections and will consist of a single gang, four port flush mounted faceplate mounted in the surface mounted raceway or double gang deep outlet box, with one Series 6 type coaxial cable terminated on one ‘F’ type radial clamp connector in position A, two Category 6 data cables terminated on RJ-45 T568B jacks and placed in the C and D faceplate positions. Blanks shall be installed in the B position. A 120 volt 20 amp quad outlet is required within one foot of the outlet. All cables will be routed back to the appropriate MDC or TR. Cabling: Work Area Outlets: Detail S “S” outlets will consist of a single red Category 5e cable terminated on a speaker with either clips or screw type Terminals. Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 42 Cabling: Work Area Outlets: Detail: DS2 “DS2” outlets will consist of a two-port surface mounted box, with two Category 6 data cables terminated on RJ-45 T568B jacks and placed in the A and B positions. All cables will be routed back to the DSS patch panel in appropriate MDC or TR. Cabling: Work Area Outlets: Detail: WD2 “WD2” outlets will consist of a two-port surface mounted box, with two Category 6 data cables terminated on RJ-45 T568B jacks and placed in the A and B positions. All cables will be routed back to the Wireless system mid-span Power Injector patch panel in appropriate MDC or TR. Cabling: Work Area Outlets: Location Specific outlet placement within each room is identified in the floor plan drawings. Cabling: Work Area Outlets: Labeling Each WAO shall have individual jack labels positioned on the faceplate on top and bottom directly over or under the individual jack. Jack icons shall be used. All labels shall be printed using a Brother P-touch labeler (or equivalent). Labels shall not be handwritten. The labeling system used is the following: For standard WAOs: WAO identifier (AB-XXX) where the “A” indicates the communications room/closet. The “B” indicates the jack usage, i.e. D = data, V = voice, T=CATV, C = CCTV, F=FIDS. The “XXX” indicates the patch panel port (data) or block cable pair number (voice) or CATV cable number (CATV). As an example, a typical outlet data jack cabled from TR-B patch panel port number 112 would be labeled as “BD-112”. A typical outlet voice jack cabled from TR-B block cable pair number 046 would be labeled as “BV-046”. A typical outlet CATV jack from TR-B CATV cable number 012 would be labeled as “BC-012”. For Paging Speaker WAOs: All speakers will have a label affixed to the outside surface that is visible without having to remove the speaker from the ceiling or the wall. All labels shall be printed using a Brother P-touch labeler (or equivalent). Labels shall not be handwritten. The WAO identifier (AS- XXX) would be used where the “A” indicates the TR, and where “S” indicates speaker. The “XXX” indicates the 66 block cable pair number (paging). As an example, a typical speaker cabled from TR-B 66 block cable pair number 031 would be labeled as “BS-031”. If the speaker is tied to a call button, as is the case in a classroom, the call button should have the same label as the speaker. Cabling: Testing For acceptance, 100% of the media must be tested and pass all testing requirements. When errors or defective components are found, the source of each error shall be determined, corrected, and the components re-tested at contractor's expense, following the testing procedures described in this document. Cable runs that fail due to distance are not acceptable and will be rerun at the contractor’s expense. Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 43 Cabling: Testing: Documentation Test documentation shall be provided to CLT Technology Services on CD-ROM and printed. The CD shall be clearly marked on the cover and on the CD itself with the words “Test Results”, the project name, and the date of completion (month and year). Testing must be performed within a 30 day window prior to the Final Inspection. Software required to read the test results shall be provided on the same CD. The information shall be indexed by major headings. The test equipment by name, manufacturer, model number and last calibration date shall also be provided at the end of the document. Unless the manufacturer specifies a more frequent calibration cycle, an annual calibration cycle is required on all test equipment used for this installation. Testing documentation shall include a printed description of the test method used and the specific settings of the equipment during the test. When repairs and re-tests are performed, the problem found and corrective action taken shall be noted, and both the failed and passed test data shall be co-located in the documentation. Cabling: Testing: Backbone Cabling: Testing: Backbone: Fiber The Communications Contractor shall provide all labor, materials, tools, field-test instruments and equipment required for the complete testing, identification and administration of the work. In addition to the tests detailed in this document, the contractor shall notify CLT of any additional tests that are deemed necessary to guarantee a fully functional system. The contractor shall carry out and record any additional measurement results at no additional charge. Testing shall be carried out in accordance with this document. This includes testing the attenuation and polarity of the installed cable plant with an optical loss test set (OLTS) and the installed condition of the cabling system and its components with an optical time domain reflectometer (OTDR). The condition of the fiber endfaces shall also be verified. Testing shall be performed on each cabling permanent link (connector to connector). All tests shall be documented and submitted to the TSO including OLTS dual wavelength attenuation measurements for multimode and singlemode links and OTDR traces and event tables for multimode and singlemode links. All testing procedures and field-test instruments shall comply with applicable requirements in the latest versions of: ANSI Z136.2, ANS for Safe Use of Optical Fiber Communication Systems Utilizing Laser Diode and LED Sources Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 44 ANSI/EIA/TIA-455-50B, Light Launch Conditions For Long-Length Graded-Index Optical Fiber Spectral Attenuation Measurements ANSI/TIA/EIA-455-59A, Measurement of Fiber Point Discontinuities Using an OTDR. ANSI/TIA/EIA-455-60A, Measurement of Fiber or Cable Length Using an OTDR. ANSI/TIA/EIA-455-61A, Measurement of Fiber or Cable Attenuation Using an OTDR. ANSI/TIA/EIA-526-7, Optical Power Loss Measurements of Installed Singlemode Fiber Cable Plant. ANSI/TIA/EIA-526-14-A, Optical Power Loss Measurements of Installed Multimode Fiber Cable Plant. TIA 568-C.0 Generic Telecommunications Cabling TIA 586-C.1 Commercial Building Cabling TIA-568-C.3 Optical Cabling Components Manufacturer specifications and recommendations Trained technicians who have successfully attended an appropriate training program, which includes testing with an OLTS and an OTDR and have obtained a certificate as proof thereof shall execute the tests. These certificates may have been issued by any of the following organizations or an equivalent organization: Manufacturer of the fiber optic cable and/or the fiber optic connectors. Manufacturer of the test equipment used for the field certification. Training organizations (e.g., BICSI, A Telecommunications Association headquarters in Tampa, Florida; ACP [Association of Cabling Professionals™] Cabling Business Institute located in Dallas, Texas) The TSO or their designated representative may select a random sample of 10% of the installed links. The TSO representative shall test randomly selected links and the results are to be stored in accordance with this document. The results obtained shall be compared to the results provided by the Communications Contractor. If more than 2% of the sample results differ in terms of the pass/fail determination, the Communications Contractor under supervision of the TSO representative shall repeat 100% testing of all fiber. The expense incurred to re-test will be borne solely by the Communications Contractor. Each cabling link shall be in compliance with the following test limits: Optical loss testing Backbone (multimode and singlemode) link The link attenuation shall be calculated by the following formulas as specified in ANSI/TIA/EIA-568-C.1. Link Attenuation (dB) = Cable_Attn (dB) + Connector_Attn (dB) + Splice_Attn (dB) Cable_Attn (dB) = Attenuation_Coefficient (dB/km) * Length (Km) Connector_Attn (dB) = number_of_connector_pairs * connector_loss (dB) Maximum allowable connector_loss = 0.75 dB Splice_Attn (dB) = number_of_splices * splice_loss (dB) Maximum allowable splice_loss = 0.3 dB The values for the Attenuation_Coefficient (dB/km) are listed in the table below: Type of Optical Fiber Wavelength (nm) Multimode 62.5/125 µm 850 Charlotte Douglas International Airport Attenuation coefficient (dB/km) 3.5 Wavelength (nm) 1300 Attenuation coefficient (dB/km) 1.5 Communications Infrastructure Standard, Version 2.0 Page 45 OTDR testing Reflective events (connections) shall not exceed 0.75 dB. Non-reflective events (splices) shall not exceed 0.3 dB. Magnified endface inspection Fiber connections shall be visually inspected for endface quality. Scratched, pitted or dirty connectors shall be diagnosed and corrected. All installed cabling links shall be field-tested and pass the test requirements and analysis as described. Any link that fails these requirements shall be diagnosed and corrected. Any corrective action that must take place shall be documented and followed with a new test to prove that the corrected link meets performance requirements. The final and passing result of the tests for all links and channels shall be provided in the test results documentation. The field-test instrument shall be within the calibration period recommended by the manufacturer. Optical loss test set (OLTS) Multimode optical fiber light source Provide dual LED light sources with central wavelengths of 850 nm (30 nm) and 1300 nm (20 nm) Output power of –20 dBm minimum. The light source shall meet the launch requirements of ANSI/EIA/TIA-455-50B, Method A. This launch condition can be achieved either within the field test equipment or by use of an external mandrel wrap (as described in ANSI/TIA/EIA-568-C.1) with a Category 1 light source. Singlemode optical fiber light source Provide dual laser light sources with central wavelengths of 1310 nm (20 nm) and 1550 nm (20 nm). Output power of –10 dBm minimum. Power Meter Provide 850 nm, 1300/1310 nm, and 1550 nm wavelength test capability. Power measurement uncertainty of 0.25 dB. Store reference power measurement. Save at least 100 results in internal memory. PC interface (serial or USB). Administration of the documentation shall include test results of each fiber link. The test result information for each link shall be recorded in the memory of the field-test instrument upon completion of the test. The test result records saved within the field-test instrument shall be transferred into a Windows™-based database utility that allows for the maintenance, inspection and archiving of these test records. These test records shall be uploaded to the PC unaltered, i.e., “as saved in the field-test instrument”. The file format, CSV (comma separated value), does not provide adequate protection of these records and shall not be used. The database for the complete project shall be stored and delivered on CD-ROM prior to Owner acceptance of the building. This CD-ROM shall include the software tools required to view, inspect, and print any selection of the test reports. Circuit IDs reported by the test instrument should match the specified label ID. The detailed test results documentation data is to be provided in an electronic database for each tested optical fiber and shall contain the following information: The identification of the customer site as specified by the end-user Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 46 The name of the test limit selected to execute the stored test results The name of the personnel performing the test The date and time the test results were saved in the memory of the tester The manufacturer, model and serial number of the field-test instrument The version of the test software and the version of the test limit database held within the test instrument The fiber identification number The length for each optical fiber Optionally the index of refraction used for length calculation when using a length capable OLTS Test results to include OLTS attenuation link and channel measurements at the appropriate wavelength(s) and the margin (difference between the measured attenuation and the test limit value). Test results to include OTDR link and channel traces and event tables at the appropriate wavelength(s). The length for each optical fiber as calculated by the OTDR. The overall Pass/Fail evaluation of the link-under-test for OLTS and OTDR measurements Optional: A picture or image of each fiber end-face A pass/fail status of the end-face based upon visual inspection. Cabling: Testing: Backbone: Voice and Paging The backbone copper cabling will be tested end-to-end for compliance with Category 5e performance specifications as stated in the TIA/EIA 568-C.2. The test equipment used will be in compliance with industry standard Level II test equipment, and the TIA/EIA 568C.2 test procedures. Test results must be provided the TSO in electronic and printed format. Cabling: Testing: Backbone: CATV Contractor will test the completed CATV riser and horizontal distribution system to verify compliance with the published design specifications. All testing will comply with National Cable Television Association Standards (NCTA) and/or Society of Cable Telecommunications Engineers Standards (SCTE) recommended practices. Coax cabling shall be tested for continuity and loss. Test results between the MDC and tap will be tested at 750mhz. Test results must provide the length of each run and the amount of loss with an acceptable loss not greater than 3.05db loss per 100 feet. Test results must be provided CLT Technology Services staff in electronic and printed format. Cabling: Testing: Horizontal Cabling: Testing: Horizontal: Category 6 Every cabling link in the installation shall be tested in accordance with the field test specifications defined in the most recent version of EIA/TIA 568-C.2. The installed twisted-pair horizontal links shall be tested from the TR to the WAO against the “Permanent Link” performance limits specification as defined in the CAT 6 Standard. 100% of the installed cabling links must be tested and must pass the requirements of the CAT 6 Standard and as described in the Standards. Any failing link must be diagnosed and corrected. The corrective action Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 47 shall be followed with a new test to prove that the corrected link meets the performance requirements. The final and passing result of the tests for all links shall be provided in the test results documentation. The test equipment (tester) shall comply with the accuracy requirements for the level III field testers as defined in the CAT 6 Standard. The tester including the appropriate interface adapter must meet the manufacturer specified accuracy requirements. The tester shall be within the calibration period recommended by the manufacturer. The tester interface adaptors must be of high quality and the cable shall not show any twisting or kinking. The Pass or Fail condition for the link-under-test is determined by the results of the required individual tests. And Fail or Fail* result yields a Fail for the link-under-test. In order to achieve an overall Pass condition, the results for each individual test parameter must be Pass or Pass*. The TSO or their designated representative may select a random sample of 10% of the installed links. The TSO representative shall test randomly selected links and the results are to be stored in accordance with this document. The results obtained shall be compared to the results provided by the Communications Contractor. If more than 2% of the sample results differ in terms of the pass/fail determination, the Communications Contractor under supervision of the TSO representative shall repeat 100% testing of all Category 5e cabling. The expense incurred to re-test will be borne solely by the Communications Contractor. Test results must be provided CLT Technology Services staff in electronic and printed format. Cabling: Testing: Horizontal: Category 5e Perform testing of Category 5e cables with a level IIe tester meeting EIA/TIA 568-C.2. Tests will include the following: Wire Map, Cable Length, Attenuation, NEXT, Power Sum NEXT, Power Sum ELFEXT, Propagation Delay, and Delay Skew. Cabling: Testing: Horizontal: CATV Contractor will test the completed CATV horizontal distribution system to verify compliance with the published design specifications. All testing will comply with National Cable Television Association Standards (NCTA) and/or Society of Cable Telecommunications Engineers Standards (SCTE). Coax cabling shall be tested for continuity. Test results between each tap and WAO will be tested at 750mhz. Test results must provide the length of each run and the amount of loss with an acceptable loss not greater than 6.15db loss per 100 feet. Cabling: Materials CLT preferred materials are listed here, and reflect the standard components currently in use. Preapproval by CLT Technology Services is required for all proposed substitutions. Cabling: Materials: Technology Preferred Vendors (This table is not meant to be an all inclusive parts list. If at any time you need assistance with determining the appropriate part or number please contact CLT Technology Services Office.) Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 48 Component Modular Jacks RJ 45 T568B pattern Categories 6 and 5e Faceplates 4 port flush faceplate kit Raceway 4 port Horizontal flush faceplate Manufacturer Panduit Panduit Panduit Patch Panels 48 Port Metal Modular Cat 6 with Panduit Strain Relief Mid-span Injector Panels 24 Port Mid Span Injector Panel with power supplies to Panduit provide full PoE Power (15.4W/Port) to each port. For use with the Wireless System cabling and other designated PoE applications. Cabling UTP Category 5e Plenum Rated Cabling per 1000’ CommScope UTP Category 6 Plenum Cabling per 1000’ CommScope Surface Mounted Raceway Twin-70 Base (8' Long) Panduit Cover (8' Long) Panduit Inside Corner Panduit Outside Corner Panduit Right Angle Panduit End Cap Panduit Tee (Divided) Panduit Entrance End Panduit Base Coupler Panduit Cover Coupler Panduit Device Bracket Panduit Wire Retainer Panduit Duplex Power Faceplate Panduit Power & Communications Pole 11Ft Panduit Power & Communications Pole 13Ft Panduit Power receptacle Addition Kit Panduit Termination Blocks withstand-off legs 66 Blocks Hubbell Communications Rooms 19” Equipment Rack, black 19” w x 84” H Panduit, CPI Chatsworth Rebox with lock, 36/42” H x 28” W x 10” D Panduit, Hubbell Wall Mount Equipment Cabinets, 24”W x 24”, 36” or 48” CPI/ChatsworthH, x 18” or 30” D. Provide with locking doors, fan kits, Cube-IT Series vertical wire management, surge suppressed power strips. Equipment Cabinet, black, single compartment, with Great Lakes vented Plexiglas locking front door, and fan equipped Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 49 solid split rear door, solid sides as required by placement. Provide surge suppressor outlet strip, internal vertical wire managers. Cabinet Dimensions: 29”W x 30”/36”D x 84” H Equipment Cabinet, black, two compartments, with Great Lakes vented Plexiglas locking front doors, and fan equipped solid split rear doors, solid sides as required by placement. Provide surge suppressor outlet strip in each compartment , internal top-load vertical wire managers for each compartment, on both sides. Cabinet Dimensions: 28”W x 30”/36”D x 84” H Equipment Cabinet, black, two compartments, with Great Lakes vented Plexiglas locking front doors, and fan equipped solid split rear doors, solid sides as required by placement. Provide surge suppressor outlet strip in each compartment , internal top-load vertical wire managers for each compartment, on both sides. Cabinet Dimensions: 28”W x 30”/36”D x 84” H Horizontal Cable Management Panel 4”x5” Front & Rear Panduit Vertical Wire Management System 8”x 8.5” x 84”H Panduit Vertical Wire Management System 12”x 12” x 84”H Panduit Vertical Wire Management System 8” Door Panduit Vertical Wire Management System 12” Door Panduit 19” Rack mount Surge Protector Horizontal/Vertical Geist 12” Ladder Tray 5’11” Section Homaco, CPI/Chatsworth Rack Mount UPS Units Backbone Cable Multimode - Indoor/outdoor, tight buffered, with water resistant features, with interlocking aluminum armor and overall plastic sheath, rated for plenum environments. Fiber shall be 62.5/125 um, graded index, FDDI rated. Singlemode - Indoor/outdoor, tight buffered, with water resistant features, with interlocking aluminum armor and overall plastic sheath, rated for plenum environments. Fiber shall be 9/125 um, Zero Water Peak, Dispersion Unshifted. Rack Mount Fiber Panels equipped with ST/LC Adapter panels and connectors 12 Adapter Panel Capacity Wall Mount Fiber Panels equipped with ST/LC panels and connectors 2, 4 or 8 Adapter Panels Fiber Panel Components Adapter Panel 6 ST with phosphor bronze split sleeves Adapter Panel 6 LC Duplex with phosphor bronze split sleeves Liebert GXT3 Series ST Fiber Optic Connector, Multimode, ceramic ferule, Panduit, Corning Charlotte Douglas International Airport CommScope, Corning, OCC CommScope, Corning, OCC Panduit Panduit Panduit Panduit Communications Infrastructure Standard, Version 2.0 Page 50 field polish LC Fiber Optic Connector, Singlemode, ceramic ferule, cam type ST field polish termination kits Raceway for Horizontal Pathways T70 Base (8’ or 10’ Long) T702 (Twin 70) Base TG-70 Base (8’or 10’ Long)* Base & Cover Included NOTE: For T70, T702 (Twin 70) and TG70 base, cover and divider wall part #s the last digit(s) indicates the length, whether 8’ or 10’.**Note With T702 no divider wall is needed Cover (8' or 10’ Long) T70 Raceway Divider Wall (8’ or 10’ Long) TG-70 Raceway Divider Wall (8’ or 10’ Long) Indoor Multi Pair Category 5 Copper Cable 25 Pair Plenum 25 Pair Non-Plenum Outdoor Multi Pair Category 5 Copper Cable 25 Pair Outdoor Rated Charlotte Douglas International Airport Panduit, Corning Panduit Panduit Panduit Panduit Panduit Panduit Panduit CommScope CommScope Superior ESSEX Communications Infrastructure Standard, Version 2.0 Page 51 Systems Systems: CATV The CATV installer should be level 3 SBCA certified. The CATV distribution system will consist of all equipment necessary to provide all channels of Time-Warner Cable to required areas of the building. Systems: CATV: Incoming Signal CLT will contract with the Time-Warner Cable to provide incoming CATV signal to the system. All designs should reference the current Time-Warner analog CATV channel lineup to insure compatibility. Systems: CATV: Channels Channel 1-79 Source Local Cable Feed Systems: CATV: Components Components of the system may include but not be limited to: Modular Headend system for modulators Modulators Demodulators Combiners Amplifiers Taps Low Pass Filter 70” Equipment rack, five shelves, power strips and other required hardware All CATV active components shall be provided by the CATV Service Provider. . Systems: CATV: Design Overall system design and installation is the responsibility of the CATV Service Provider. The Service provider shall submit a proposed system design to the TSO for approval prior to installation. Systems: CATV: Completeness The Communications Contractor / CATV Service provider shall provide all materials, components, etc. to provide a fully functional and operational system. Exceptions are items provided by CLT. These items will be provided by CLT, but are to be installed and tested by the Communications Contractor. Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 52 Systems: CATV: Performance The Communications Contractor shall provide all components and materials to consistently and comprehensively attain the appropriate signal strength throughout the CATV Distribution System within the Contractors’ Scope of Work. Acceptable signal strength is deemed to be 5-10db flat at all CATV outlets. The Communications Contractor/Service provider shall test all CATV outlets to certify the performance recorded according to the signal strength required above. Any CATV outlet that does not meet the signal strength requirements will be resolved by the vendor prior to acceptance by the TSO. All aspects of system including, but not limited to, camera broadcast and TV reception must be demonstrated to the TSO prior to acceptance. Systems: CATV: Testing Refer to sections D.6.2.3 and D.6.3.3 for physical cable test requirements. Signal strength testing should be performed on channels 4, 64, 80-84, and 89 on every CATV outlet. Results for each channel on each outlet should be provided to CLT in digital and printed form. Systems: CATV: Training The Communications Contractor shall thoroughly train all media center staff on how each component of the installed CATV system works as well as how the overall CATV system operates. They will also train personnel on how to setup the camera and broadcast from designated locations. Printed documentation must be provided to all trainees Systems: CATV: Warranty The CATV distribution system will be warranted by the Communications Contractor to be free from defects and workmanship for a period of one year following acceptance of the system by CLT. Materials, repairs, and adjustments will be performed at no cost to CLT. Systems: Paging Systems: Paging: Equipment The Communications Contractor shall furnish and install the following items, including, but not limited to, speakers, horns, speaker enclosures, speaker cabling, wire guards, microphone stations and other related items. Systems: Paging : Manufacturer of Choice Equipment supplied by Atlas Sound (speakers) and IED (microphone stations), shall be considered as meeting all specifications and as the base bid. CLT must approve alternate systems. Bidders supplying any other system shall make aware their intentions and provide all information, including catalog cuts, shop and working drawings, data sheets, and a demonstration of the proposed system features. The Communications Contractor is solely responsible for ensuring complete compatibility with the existing Paging System and must demonstrate this compatibility and functionality to the TSO. This information must be presented to the TSO as to allow sufficient time to review all material prior to acceptance of bid. Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 53 Systems: Paging : Documentation The Communications Contractor shall provide complete drawings detailing all interconnections, panel wiring diagrams, and specification sheets and any other pertinent documentation. Systems: Paging : Authorized Installer The installer shall be an authorized dealer and installer of the supplied equipment with full warranty privileges. Systems: Paging : Warranty The Communications Contractor shall provide a 2 year warranty of the installed system against defects in material and workmanship. All warranty material and labor will be provided at no expense. Warranty period shall begin on the date of CLT acceptance. Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 54 Inspections Inspections: Submittals All material and design submittals must be reviewed by the TSO for approval. Inspections: Pathways All pathways shall be inspected by the TSO prior to the installation of cabling. Inspections may be performed on a space-by-space basis if requested by the Electrical Contractor. Pathways which do not meet specifications will not be approved. Approval of pathways is required prior to cable installation. Inspections: Rough Installation Substantial Completion All cable plant and systems installations shall be inspected by the TSO prior to termination. Inspections may be performed on a space-by-space basis if requested by the Communications Contractor. Cabling that does not meet specifications will not be approved. All cabling issues must be resolved prior to acceptance. Inspections: Final Inspection All Work for the installation shall be completed prior to acceptance by the TSO. System performance must be fully demonstrated during this inspection. Inspections may be performed on a space-by-space basis if requested by the Communications Contractor. Work that does not meet specifications will not be approved. All communications project related issues must be resolved prior to acceptance by CLT. Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 55 Documentation The following documentation, at a minimum, will be provided to CLT Technology Services following the installation: As built floor plan identifying cable routing, outlet locations and identifications (include all outlet labels). A laminated copy of the as built of the area served will be mounted in each closet, or as otherwise directed by the TSO. As built site plan of the entire site showing the updated backbone pathways. A second laminated copy will be mounted in the MDC. An electronic AUTOCAD copy of the as built drawings. A paper copy of test results for each outlet cable and backbone cables of all types. A CD copy of test results for each outlet cable and backbone cables of all types. Software needed to read results shall be provided on the same CD. Copies of all warranty certificates i.e., Panduit, CommScope, Corning, etc. Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 56 Warranty Warranty: Electrical All electrical work referenced within the project specification will be warranted that all materials and equipment furnished under the contract are in good working order, free from defects, and in conformance with system specifications. All installations must conform to the manufacturer’s official published specifications. The warranty shall begin at the systems acceptance date and remain in effect for a period of 1 year from that date. The electrical contractor agrees to repair, adjust, and/or replace (as determined by the TSO to be in its best interest) any defective equipment, materials, or other parts of the system at the electrical contractor’s sole cost. CLT will incur no costs for service or replacement of parts during the warranty period. All third party warranties shall be passed through from the electrical contractor to CLT. The electrical contractor will warrant and supply evidence that the installation of materials and hardware will be made in strict compliance with all applicable provisions of the National Electric Code, the rules and regulations of the Federal Communications Commission, and state and/or local codes or ordinances that may apply, as well as the requirements of this document. The electrical contractor will warrant that the system will function as specified in the approved manufacturer’s Technical Description Guide. Warranty: Technology All technology work referenced within this specification will be warranted that all materials and equipment furnished under the contract are in good working order, free from defects, and in conformance with system specifications. All installations must conform to the manufacturer’s official published specifications. The warranty shall begin at the systems acceptance date and remain in effect for a period of twenty-five (25) years from that date for installed cabling and associated passive hardware, and 2 years for any and all active systems components. The Communications Contractor agrees to repair, adjust, and/or replace (as determined by the TSO to be in its best interest) any defective equipment, materials, or other parts of the system at the Communications Contractor’s sole cost. CLT will incur no costs for service or replacement of parts during the warranty period. All third party warranties shall be passed through from the Communications Contractor to CLT. The Communications Contractor will warrant and supply evidence that the installation of materials and hardware will be made in strict compliance with all applicable provisions of the National Electric Code, the rules and regulations of the Federal Communications Commission, and state and/or local codes or ordinances that may apply, as well as the requirements contained in this document. The Communications Contractor will warrant that the system will function as specified in the project construction documents, approved manufacturer’s Technical Description Guide, and this document. Charlotte Douglas International Airport Communications Infrastructure Standard, Version 2.0 Page 57