AN ABSTRACT OF THE THESIS OF Ryan Seward for the degree of Master of Science in Mechanical Engineering presented on March 9, 2012. Title: Performance of a Thermally Activated Cooling System and Design of a Microchannel Heat Recovery Unit Abstract approved: Hailei Wang The performance of a combined vapor-compression cycle/ORC is evaluated using waste-heat from a diesel generator. A flat plate microchannel heat exchanger is employed to provide energy exchange between the diesel exhaust stream and an oil loop, which provides energy to a boiler. This study finds an increased diesel duty corresponds with an increased cooling capacity, for a maximum of 5 kW of cooling (with 13.5 kWe diesel load). System COP is reduced with a higher input power due to limitations in the cooling cycle. A number of solutions are identified to increase the COP and cooling capacity. A new microchannel heat exchanger to recovery heat is designed to increase performance compared to the previous version. © Copyright by Ryan Seward March 9, 2012 All Rights Reserved Performance of a Thermally Activated Cooling System and Design of a Microchannel Heat Recovery Unit by Ryan Seward A THESIS submitted to Oregon State University in partial fulfillment of the requirements for the degree of Master of Science Presented March 9, 2012 Commencement June 2012 Master of Science thesis of Ryan Seward presented March 9, 2012. APPROVED: Major Processor, representing Mechanical Engineering Head of the School of Mechanical, Industrial, and Manufacturing Engineering Dean of the Graduate School I understand that my thesis will become part of the permanent collection of Oregon State University libraries. My signature below authorizes release of my thesis to any reader upon request. Ryan Seward, Author ACKNOWLEDGEMENTS I would like to express my appreciation to Dr. Hailei Wang for providing support and encouragement during my time here; without his direction none of this would have been possible. Robbie Ingram-Goble has provided endless patients and help in not just the review of this document, but also throughout my college career. Kevin Harada offered me his insight regarding many aspects of engineering in the real world which proved to be a substantial contribution to my research. James Yih provided many hours of assistance. Without James’ excellent programming skills the quality of collected data would have suffered. Chris Ward did the initial groundbreaking on the heat recovery project and lent me his insights and findings, without which I would have started from scratch. I would also like to thank my family for always helping and guiding me to be the person I am today. Finally, I would like to thank Dr. Richard Peterson. During my undergrad time here he saw potential in me, and offered me the opportunity to further my education in engineering. Graduate school under his direction has led me into areas I never would have pursued otherwise, and for this I am eternally grateful. His guidance, support, and expertise will be greatly missed. 1 2 3 TABLE OF CONTENTS Introduction ........................................................................................................................ 1 Literature Review ............................................................................................................. 4 2.1 2.2 2.3 5 6 7 3.1 3.2 3.4 3.5 9 Diesel Particulate Filtration ................................................................................. 7 Microchannel Devices ............................................................................................. 9 Diesel Generator .................................................................................................... 16 Heat Recovery Device .......................................................................................... 17 Oil Loop ..................................................................................................................... 21 Thermally Activated Cooling System ............................................................. 24 Heat Transfer Fluid ............................................................................................... 26 Experimental Setup ...................................................................................................... 28 Data Reduction and Uncertainty Analysis ........................................................... 33 5.1 Calibration and Uncertainty .............................................................................. 33 5.1.1 5.1.2 5.1.3 TACS Instrumentation ................................................................................ 33 HRU Instrumentation .................................................................................. 34 Calculations ..................................................................................................... 36 Performance Analysis and Discussions ................................................................ 38 6.1 6.2 6.3 Heat Recovery Unit Performance .................................................................... 39 TACS Performance – Power Side ..................................................................... 44 TACS Performance – Cooling Side ................................................................... 49 Second Generation HRU .............................................................................................. 53 7.1 7.2 7.3 8 Power Cycles .............................................................................................................. 4 System Overview ........................................................................................................... 15 3.3 4 Page 7.4 7.5 Air Shim Design ...................................................................................................... 57 Oil Shim Design....................................................................................................... 61 Header Design ......................................................................................................... 63 Plenum Design ........................................................................................................ 68 Final Design ............................................................................................................. 70 Conclusion ........................................................................................................................ 73 Works Cited ..................................................................................................................... 75 Figure LIST OF FIGURES Page Figure 2.1 - Types of fluids shown in a T-s diagram. Notice the slope of the right leg of all the curves dictates the type of fluid [22]. ............................................ 6 Figure 2.2 - Chemical etching process [8:14]. .............................................................. 12 Figure 3.1 - System Overview consisting of the oil loop (top left), Organic Rankine Cycle (top right), and vapor compression cycle (bottom). ................... 16 Figure 3.2 - Kubota SQ-14 13.5 kW diesel generator. ............................................... 17 Figure 3.3 - Two pass cross-counter flow heat exchanger...................................... 18 Figure 3.4 - Picture of HRU manufactured and tested. ............................................. 19 Figure 3.5 - Side view of HRU showing air channels with rounded features... 19 Figure 3.6 - Oil Loop layout. ................................................................................................ 23 Figure 3.7 – Experimental dynamic viscosity and density versus temperature for Duratherm 600 and Paratherm NF at operating conditions during steady state. Values were taken from manufacturer technical documents. ................... 27 Figure 4.1 – Piping and Instrumentation diagram (P&ID) for the HRU and oil loop. .............................................................................................................................................. 29 Figure 4.2 - Modified diesel exhaust manifold............................................................. 30 Figure 4.3 - Full HRU assembly inside the diesel generator housing. ................ 31 Figure 4.4 - Insulation of HRU/oil loop. ......................................................................... 32 Figure 5.1 - Catch and weigh experimental setup for calibration of the oil turbine flow meter.................................................................................................................. 35 Figure 6.1 - Typical duty of the HRU during testing. ................................................. 40 Figure 6.2 – Typical back pressure as measured at the exhaust manifold. ...... 40 Figure 6.3 - Effect of back pressure with respect to duty. ....................................... 41 Figure 6.4 - Oil duty as a function of ORC working fluid mass flow rate. .......... 42 Figure LIST OF FIGURES (Continued) Page Figure 6.5 - HRU effectiveness and ORC working fluid mass flow rate. ............ 43 Figure 6.6 - Hydraulic power through HRU. ................................................................. 44 Figure 6.7 – The ratio of heat transferred from the HRU outlet of the oil side to that of the boiler inlet. The temperatures are recorded from the oil loop. ...... 46 Figure 6.8 – Expander work and rotational speed for a given expander mass flow rate. Work was determined from the mass flow rate and measured fluid conditions................................................................................................................................... 46 Figure 6.9 - Expander isentropic efficiency for a given mass flow rate. ............ 48 Figure 6.10 - Expander efficiency for each load and pressure ratio. .................. 49 Figure 6.11 - Cooling capacity and power flow rate. ................................................. 50 Figure 6.12 - System COP and power mass flow rate. A steady reduction in overall system COP is observed across the duty of the generator. ...................... 52 Figure 7.1 - Aspect ratio definitions taken from a side view of a generic shim. B is etch depth, C is etch width, A is remaining material thickness, and D is the rib thickness. ............................................................................................................................. 56 Figure 7.2 - Surface area and the effects on total thermal waste heat recovery [9:34]. .......................................................................................................................................... 57 Figure 7.3 - Pressure drop and effectiveness for various etch widths in the air shim. Results are for a constant air etch depth, as well as a constant oil channel width and depth. .................................................................................................... 58 Figure 7.4 - Air shim with support and through ribs. ............................................... 60 Figure 7.5 - Air shim for second generation device. .................................................. 60 Figure 7.6 - Spacing between oil passes. ........................................................................ 61 Figure 7.7 - Oil shim for second generation device.................................................... 62 Figure 7.8 - Equivalent resistance network for simplified flow header and channel design [31:92]. ........................................................................................................ 64 Figure LIST OF FIGURES (Continued) Page Figure 7.9 - Header design to be studied. Variables Y and H will be adjusted to determine optimal configuration...................................................................................... 65 Figure 7.10 – The effect of H value on flow distribution of each channel. ........ 66 Figure 7.11- The effect of Y value on flow distribution of each channel. The H value was set to 0 for this figure. ...................................................................................... 67 Figure 7.12 - Oil shim inlet restriction. ........................................................................... 68 Figure 7.13 – Cross counterflow heat exchanger configurations. Fluid stream mixing varies [31:100]. ......................................................................................................... 70 Figure 7.14 - Filter box with removable door. ............................................................. 72 Figure 7.15 - Final HRU Generation 2 Design. ............................................................. 72 Table LIST OF TABLES Page Table 5.1 - Uncertainty in measurements for the oil loop and heat recovery device [31:61]. .......................................................................................................................... 37 Table 5.2 - Uncertainties in measurement for the thermally activated cooling system [34:19]. ........................................................................................................................ 37 Table 7.1 - Air shim dimensions. Refer to Figure 7.1 and Figure 7.4 for the location of these dimensions. ............................................................................................. 59 Table 7.2 – First generation and second generation HRU theoretical performance characteristics. .............................................................................................. 71 1 INTRODUCTION The continual use of fossil fuels and the increasing amount of energy required to drive devices in our technologically-driven lives has led to the need to increase the amount of available power. While creating more carbon-based fuel-consuming devices is one answer, the cost and environmental impact this has on the world of today and tomorrow suggests that other methods of power production must be utilized. Ideally, alternative energy systems would be used to meet this increasing demand, but the change in infrastructure needed to implement these technologies on the power production scale of fossil fuels has significant hurdles to overcome [1]. A potential solution that both increases usable power and decreases environmental waste is the incorporation of an additional attached cycle. In order to optimize current power cycles, heat recovery systems can be attached to utilize the waste-heat of the system. Internal combustion engines are one of the best candidates for this attached cycle approach, due to their propensity to waste (in the form of generated heat) approximately a third of their input energy [2], [3]. Mobile internal combustion (IC) cycles (cars, trucks, etc.) are an ideal choice for this attached cycle, but given the additional physical requirements for the machines (size, weight, etc.); a different system is considered for this study. Within the family of internal combustion engines, 2 diesel engines coupled with generators are a viable candidate for increasing the net power output of a system, due to their stationary nature, large amount of wasted heat, and a lack of space restrictions (compared to their mobile counterparts, where size and weight are common issues) [4]. Ways to recover waste-heat have been approached from many angles, including adsorption and absorption cooling systems, waste-heat airconditioning, and thermoelectric recovery [5]. However, Organic Rankine Cycles (ORC) are generally the most reliable and cost-effective method to recover low-grade waste-heat [6]. Due to their high level of safety and minimal amount of required maintenance, ORCs are regularly chosen to be used in conjunction with other power cycles to boost the usable power and efficiency. This study is a continuation of previous research done regarding the recovery of waste-heat to power a thermally activated cooling system [7–10]. A diesel generator and microchannel heat exchanger are used to transfer heat from the exhaust stream of the diesel engine to an oil loop. The oil loop provides energy to a boiler to produce shaft work within an ORC. The expander from the ORC is directly connected to a compressor in a vapor compression refrigeration cycle, driving the system. While the thermally activated cooling system and microchannel heat recovery design have been independently 3 tested in a laboratory setting, the purpose of this study is to determine the viability of these systems, used in unison, in a more realistic environment. The entire system will provide cooling power by utilizing the waste stream of a generator, thereby reducing the number of generators and amount of fuel consumption in the field. This reduction in required fuel and equipment has a ripple effect, further reducing the amount of energy needed that would otherwise transport these additional components. 4 2 LITERATURE REVIEW A literature review was performed to determine the current state of the various components used in the thermally activated cooling system (TACS) as well as technologies associated with the heat recovery unit (HRU) and diesel generator. 2.1 POWER CYCLES Internal combustion (IC) engines are an ideal source to perform heat recovery on due to their availability and large amount of recoverable heat offered; what remains is how best to harvest and utilize this thermal energy. While Organic Rankine Cycles (ORC) are generally used, others cycles such as the Kalina cycle, ammonia-water sorption cycles, and lithium bromide-water systems have also been utilized [4], [11]. ORCs have been shown to effectively generate useful power at temperatures as low as 100 °C [12], with low operating pressures relative to other bottoming cycles with the same power output [11]. ORCs are the preferred cycle due to their low maintenance, high safety, flexibility, and their effectiveness at utilizing waste-heat, which would otherwise be lost. The component that is the greatest factor in determining the efficiency of an ORC system is the expander [13]. Because expanders have not traditionally 5 demonstrated good efficiencies at smaller scales, ORCs generally required large expanders (dynamic, or turbo variety) to accompany the increased efficiency that typically comes with size [14]. Smaller scroll expanders (displacement, or volumetric type) have allowed current ORCs to shrink in size and thus become more applicable for heat recovery purposes; expander isentropic efficiencies have been shown as high as 0.85 [15]. In order to minimize entropy generation during the expansion and compression processes and to maximize efficiency, the intrinsic pressure ratio should be examined [7]. The increased efficiency at the isentropic pressure ratio comes from the lack of a discharge valve that would create throttling losses. The benefits of this scroll design begin to diminish compared to typical compressors when they are not operating at their ideal pressure ratio. Typically pressure ratios from approximately two to six are used, but are dependent upon the working fluid used [16]. Losses in efficiency and other disadvantages present themselves if an improper working fluid is chosen. To ensure that an ORC remains the best cycle for the given heat recovery application, safety and the characteristics of the fluid must be taken into account [17]. Much research has been done to determine which working fluid is best [12], [18–20]. According to Srinivasan et al. 6 Organic fluids can be classified as dry, wet, and isentropic depending on the slope of the saturation curve in the T-s diagram… a dry fluid has a positive slope; a wet fluid has a negative slope; while an isentropic fluid has infinitely large slopes. One of the reasons dry fluids show better thermal efficiencies is that they do not condense after the fluid goes through the turbine as opposed to wet fluids [18:3]. Figure 2.1 - Types of fluids shown in a T-s diagram. Notice the slope of the right leg of all the curves dictates the type of fluid [22]. A commonly used fluid for these power applications is R245fa, due to its inert environmental properties and its positive effect on cycle efficiency and performance. Others fluids may have traits not desirable for the given application [12]. 7 2.2 DIESEL PARTICULATE FILTRATION Filtration of diesel exhaust is a concern due to back pressure limits and fouling of microchannel devices. The primarily used systems are diesel particulate filters (DPF), used in unison with a regenerative system to allow removing of filtered particulate matter. A temperature in excess of 500 °C is generally required to burn the particles in a regenerative system [23], but other methods can be used to lower this temperature. Active regeneration requires external energy, while passive makes use of a catalyst mixed in the fuel or filter that reduces the needed temperature to around 400 °C. This temperature is within the range of most IC exhaust gases [24]. While it is possible to increase the combustion temperature (which reduces the amount of particulate matter), doing so can lead to increases in NOx emissions, which can be much more difficult to reduce [25]. Porous ceramics are generally used in DPFs due to their favorable pressure drop and high filtration efficiency. The most popular porous ceramics are cordierite and SiC [26]. The initial filtration of a “fresh” filter is mainly driven by Brownian diffusion (or random particle movement) using a filter matrix with a pore size of 200 microns, which is much larger than the soot particles passing through. A “soot cake” is formed after particulate matter has been deposited. This “cake” further enhances the filtration process [27]. 8 Yang et al. [26] demonstrated with lab generated ammonium sulfate particles that the transition time from deep penetration to “cake” filtration was independent of flow rate and varied only with filtration material. Once the driving mechanism of filtration became a process driven by the cake formation, the filtration efficiency reached near unity for short (sub-25 minutes) tests, with minor efficiency reduction after that. Barhate and Ramakrishnaa [28] showed nanofibrous filtering media would provide benefits such as lower pressure drop and higher filtration efficiencies for a given operation time. Manufacturing techniques needed to manufacture strong enough nano-material to withstand significant impact are still far from commercial applicability. Nano materials could be used as an additive to current DPF to increase the aforementioned benefits, but uniformity of surface coating needs to be addressed. Size and cost restraints prohibited the use of the standard filtration media typically used when fouling is a concern. Due to its small size and low cost, 304 stainless steel mesh filters ranging from five to 190 microns were used during the initial testing stages, but an increase in back pressure over no filtration was observed. Stainless steel wool (Type 316) was used next without the mesh filter, but was found to contribute strands of wool to the clogging and reduced performance of the microchannel device. It was decided 9 that no filtration would be used during testing, which is further discussed in Section 6.1. 2.3 MICROCHANNEL DEVICES Microchannel devices were first proposed by Tuckerman and Pease [29] for heat dissipation with heat fluxes up to 790 W/cm2. By definition, the characteristic length of these devices is less than 1 mm. Using the definition of convective heat transfer: β = ππ’ π π π (2.1) Here h is the heat transfer coefficient οΏ½π2 βπΎοΏ½, Nu is the Nusselt number, k is π fluid’s thermal conductivity οΏ½πβπΎοΏ½, and d is the characteristic length. Given low Reynolds numbers such that flow is within the laminar regime, the Nusselt number becomes a constant. As the characteristic diameter of the channel decreases, the heat transfer coefficient increases. With an increase in the heat transfer coefficient, the overall heat transfer is increased, given a constant area and temperature difference between two points. This is expressed in Newton’s law of cooling: 10 πΜ = βπ΄Δπ (2.2) πΜ is the thermal energy (W), A is the area (π2 ), and Δπ is the temperature gradient between the device and the environment (K). π2 The higher surface area to volume ratio οΏ½π3 οΏ½ is another benefit of microchannel devices, allowing similarly capable systems to take place of their macro-scale counterparts within a much smaller footprint. Typical π2 scales for shell and tube heat exchangers show a value of 50-100 π3 , while π2 more compact heat exchangers approach a value of 1500 π3 . Microchannel devices can be reasonably manufactured with a surface area to volume ratio exceeding 1500 π2 π3 [30]. Pressure drop is a concern in microchannel devices and is dependent on scaling assumptions and other considerations [31]. While reducing the channel size increases the heat transfer coefficient, this reduction also increases pressure drop. ππ 2 πΏ Δπ = π 2 π· (2.3) 11 Here Δπ is the pressure gradient (Pa), π is the friction factor, π is the density ππ π οΏ½π3 οΏ½, V is the mean velocity οΏ½ π οΏ½, L is the length (m), and D is the diameter (m). Furthermore V is determined from the measured volumetric flow rate πΜ π3 οΏ½ π οΏ½ as shown: π= πΜ π΄ (2.4) It should be noted that minor losses (bends, restrictions, expansions) are not accounted for in Equation (2.3). To manufacture these devices in an economical fashion, flat plate heat exchanger designs are often used. Each shim is chemically etched in a fashion similar to that used in the microprocessor industry, which consists of creating a mask (beneath of which will “mask” the material so it will not be removed). The part is then soaked in a chemical bath to remove the desired material (the unmasked region). Once complete the part is cleaned of residue. 12 Figure 2.2 - Chemical etching process [8:14]. 13 Once all shims are etched, they are stacked in an alternating pattern then bonded by either diffusion brazing or diffusion bonding. The type of bonding or joining process chosen is a function of many factors, including the width of the material removed (or channel width) to that of material remaining (the material thickness minus the depth etched). If a ratio of approximately 10:1 is maintained (such that for a span of 10 units of width etched, 1 unit of material remains beneath that span), bonding can be used [32]. If much greater than this ratio, brazing must be used to ensure a usable part. This is due to the pressure which must be transferred throughout the device to ensure a proper seal. Brazing allows a lower temperature and pressure to be used since a coating is added to enhance grain growth. Bonding occurs at higher temperatures and pressures, and relies on the structural integrity of the device after etching to ensure proper bonding. Brazing may also be significantly cheaper and larger brazing furnaces are common. The possibilities of shim design have limitations that come into play when designing the features on a shim. While the actual tolerances vary slightly between companies, the restraints imposed by each etching manufacturer are similar [33–35]. Depending on whether the part requires a half-etch or a fulletch (which refers to whether the part is etched from one side or both), beveling will result. This bevel is a result of the acid bath eroding the side of the material as the rest of the desired material is removed. This is why 14 straight-walled holes will never result from chemical etching. Rectangular corners are also not a possibility with chemical etching, as etch radii is a function of the material thickness, and is usually equal to that of the provided material. Hole diameters (as with most features) are restricted by the etching material thickness and are required to be greater than 125% of the material thickness. For features such as ribs that separate channels, the minimum possible rib width is generally 90% of the material thickness. If less than 90% remains, undercutting of the walls or removal of the ribs altogether may occur. 15 3 SYSTEM OVERVIEW In order to power the thermally activated cooling system (TACS), waste-heat from a Kubota SQ-14 diesel generator was directed through a microchannel heat recovery unit (HRU). This exhaust was then rejected to the atmosphere as shown in Figure 3.1. Using a cross-counter flow configuration in the heat exchanger, the thermal energy from the high temperature waste-heat exhaust stream is transferred to the heat transfer oil. The heated oil flows through the boiler of an Organic Rankine Cycle (ORC) producing shaft work which is used to drive the compressor of the refrigeration cycle. 16 Heat Recovery Device Boiler Expander Integrated Microchannel Device Recuperator Oil Pump Power Condenser Cooling Condenser Compressor Expansion Valve Evaporator Figure 3.1 - System Overview consisting of the oil loop (top left), Organic Rankine Cycle (top right), and vapor compression cycle (bottom). 3.1 DIESEL GENERATOR The Kubota SQ-14 diesel generator is capable of providing power to devices at 120/240V, with a maximum current of 56.3 A. The maximum continuous electric power is 13.5 kWe, while for standby operation that number is 14.2 kWe. To minimize heat loss, the exhaust manifold was modified to allow for direct mounting of the HRU. The HRU and manifold were insulated. An analysis of the exhaust composition was done to determine its thermal properties. Assuming a standard diesel fuel chemical formula of πΆ12 π»23 and 17 full combustion with excess air, it was shown by Ward [9] that 20 kW of thermal energy was lost through the exhaust at full load. This energy could be recovered and utilized via the HRU to provide the required 10.6 kW of heat for the TACS. Figure 3.2 - Kubota SQ-14 13.5 kW diesel generator. 3.2 HEAT RECOVERY DEVICE A two pass cross-counter flow heat exchanger was integrated into the exhaust manifold outlet of the diesel generator. High back pressure for the diesel generator was a concern during design. A straight pass channel design was used on the exhaust side. For ease of manufacturability, space restrictions, and manufacturing constraints, a plate-type heat exchanger was designed and produced. 18 As shown in Figure 3.3, hot exhaust air enters from the diesel engine on the right. This exhaust flow continues through the HRU, and exhausts into the atmosphere. The heat transfer oil enters at its coolest temperature and passes next to the coolest exhaust temperature. That oil continues into an open plenum to allow mixing, then enters into the upstream portion of the HRU, which comes into contact with the hottest exhaust. This design was chosen due to its relative easiness to implement compared to a fully inverted configuration. If a fully inverted configuration were utilized, both fluids would fully invert between passes and would require more complicated headers. The first generation heat recovery unit is shown in Figure 3.4 and Figure 3.5. In Figure 3.4 the Swagelok NPT fittings are shown installed, with the lower portion of the image designated as the oil inlet, and the upper as the oil outlet. Figure 3.3 - Two pass cross-counter flow heat exchanger. 19 Figure 3.4 - Picture of HRU manufactured and tested. Figure 3.5 - Side view of HRU showing air channels with rounded features. 20 The HRU was designed by Ward [9]. Once revisions were finalized, drawings were sent out to Vacuum Processes Engineering Incorporated (VPEI) for diffusion brazing of the device. VACCO engineering was subcontracted by VPEI to chemically etch the shims. From Ward [9], the channel geometry as well as the overall dimensions of the device varied from ideal. The height was found to be 1.5% less than ideal, while the channels cross sections in the lamina displayed a rounded characteristic from the chemical etching process. A phase-shifting profilometer was used to measure unbounded sample lamina. The deviation from ideal oil and air cross sectional area were on average 8% and 15% less than specified, respectively. In a controlled laboratory environment the HRU was tested by varying the load of the generator and the flow rate of oil. Pressure drop was recorded within both fluid streams, and the effect of filtration on pressure drop within the exhaust stream was analyzed. While running an 11.4 kWe load, the HRU showed an increase in the upstream air side pressure from 4 kPa at a rate of 1 kPa per hour. During this time the measured duty of the engine showed no variation in the arithmetic mean. Variations of flow rate within the oil loop have little effect on the performance of the HRU. 21 Performance was shown to match the theoretical model well. However air side pressure drop was nearly double of what was expected (3.6 kPa compared to 5.7 kPa). This deviation may be accounted for by the channel discrepancies from the ideal model and the manufactured, chemically-etched shims. Duty was less, with a theoretical recovery of 11.3 kW of heat and an average of 10.7 kW of heat recovered. Simplifications (made in the model and measurement uncertainty) account for this. Other values such as oil inlet and outlet temperature, flow rate, and effectiveness were only slightly less than predicted, again likely due to simplifications in the model and measured error and uncertainty. The use of filtration upstream of the HRU resulted in gradual back pressure increase, but did not affect the overall heat transfer that occurred during testing. 3.3 OIL LOOP The oil pump chosen was a Liquiflo 45-series external gear pump. The pump was chosen based upon the expected fluid temperature, viscosity, flow rate, and pressure drop. Liquiflo pumps offered the most desirable characteristics for the system. The maximum operating temperature for the pump was 260 °C, with a maximum pressure differential of 690 kPa (100 psi). A Baldor ¼ horsepower motor was used to drive the pump with a Baldor 90V DC motor controller. It was observed that the maximum flow rates advertised were not 22 achievable. This discrepancy was a result of slipping between the gears, as well as the high rate of speed which the gears experienced. A more powerful motor and larger pump head would provide better flow rate capabilities, as the voids within the gears would have more time to fill with fluid if the rotational speed was reduced. The oil loop heat transfer fluid was modified from its original configuration due to pressure buildup. Investigation of removed pipe sections exposed thermal degradation buildup within the closed oil loop. A cleaning fluid was used (Duraclean Ultra) to remove deposited sludge and Paratherm heat transfer fluid from the system. The cleaning procedure improved later performance of the system, with a high side pressure reduced from 620 kPa to 275 kPa. Between this buildup and potential contamination that may have slipped into the system from open-to-atmosphere locations, an in-line oil filter was added to reduce the negative effects on system performance due to contamination. An open to atmosphere reservoir was added to the high point of the system, above the suction line of the oil pump. The reservoir enhanced the process of degasification. As the system ran open, there was noticeable bubble formation. The amount of bubbles slowly decreased to the point where no further bubbles were observed. Condensation, water deposits from previous 23 use of the piping, and air trapped during the manufacturing and assembly process was thought to be the cause of the bubble formation. POI T T TOI P P HRU Turbine Flowmeter TOO To thermally activated cooling system Open Reservoir QO TPO PPO T T Oil Filter POO TPI P P Gear Pump Figure 3.6 - Oil Loop layout. PPI 24 3.4 THERMALLY ACTIVATED COOLING SYSTEM The TACS was developed by Wang et al. [7]. During laboratory testing the TACS demonstrated 4.4 kW of cooling capacity given an oil inlet temperature of 200 °C and a system COP of 0.48, which is a function of the heat provided by the boiler and the heat absorbed by the evaporator . Power and duty were calculated via working fluid mass flow rates and enthalpies found from temperature and pressure measurements at the specific cycle locations. Further correlations are found in Wang et al. [7]. πΆπππ π¦π π‘ππ = ππ πΆπππΆππππππ ππ = (3.1) πΜππ₯ππππππ − πΜππ’ππ πΜππππππ (3.2) πΜππ£ππππππ‘ππ πΜπππππππ π ππ (3.3) πΆπππππππππ = The system was designed to reach 5.3 kW of cooling capacity, but is dependent upon the indoor and outdoor air temperature. These temperatures are important because they provide the needed outdoor compressor temperature and indoor evaporator temperature to maximize the flow rate for the system to operate at its design point. 25 The early laboratory tests were performed with a hot oil circulator to simulate a waste-heat source. While designed with the intent of an outdoor condenser air temperature of 48.9 °C and indoor evaporator air temperature of 32 °C, the TACS was tested in a laboratory setting of 22 °C for both temperatures. Typical flat plate heat exchangers were used in place of custom microchannel devices for the boiler and recuperator due to internal leaks from the manufacturing process. The scroll expander reached an isentropic efficiency of 84% at a pressure ratio of 3.3, with efficiency decreasing with a further increase in pressure ratio. The power side ORC first law efficiency was calculated to be 10% at a pressure of 2 kPa. Increases in pressure led to greater efficiencies due to the higher saturation temperature. The vapor compression cycle results were below expected due to the aforementioned air temperatures, which affected the mass flow rate in a negative way. The measured cooling capacities varied between 3.5 and 4.5 kW; well off the design point of 5.3 kW. Additional losses occurred due to the underperforming plate recuperator, which maintained an efficiency of 75%; 10% less than modeled. Designed to utilize low-to-medium-grade waste-heat, the working fluid for the ORC is HFC-245fa. This ORC working fluid is vaporized in the boiler then flows through the scroll expander to produce shaft work. The sensible heat remaining after going through the scroll expander is then used to preheat the 26 entering fluid going into the boiler via a recuperator, which boost cycle efficiency. While the shaft work could be utilized to power other devices directly, the current setup has the compressor shaft directly coupled to the expander shaft to minimize loses that would otherwise occur if an electric motor and generator were used. The scroll compressor used in the vapor compression cycle pushes the fluid through a standard condensing and evaporating process before returning to the compressor. Due to its wide acceptance in other mobile air-conditioning systems and the cycle efficiency at these temperatures, HFC-134a was used as the working fluid on the compression side. 3.5 HEAT TRANSFER FLUID Paratherm NF was initially used as the heat transfer fluid. This heat transfer fluid was picked due to its low maintenance and relatively low viscosity for easy startup when cold. The thermal properties also aligned well with the overall goals of the thermal system. However, NF lacks oxidation inhibitors. After inspection of the fluid it appeared as though oxidation and thermal degradation occurred, resulting in decreased TACS and oil loop performance. Duratherm 600 was used to replace Paratherm after these observations were made. Duratherm has similar properties to Paratherm, but has the added benefit of oxidation inhibitors, as well as a higher film temperature. 27 As the dynamic viscosity approaches that of water (0.001 Pa-s, or 1 cPs), slippage can occur around the gears within a gear pump. Given the higher viscosity at all temperatures, Duratherm 600 allowed for a higher flow rate (less slippage) in addition to better heat transfer characteristics. Figure 3.7 Paratherm Viscosity Duratherm Viscosity Paratherm Density Duratherm Density 10 850 9 830 8 810 7 790 6 770 5 750 4 730 3 710 2 690 1 670 Density [kg/m3] Dynamic Viscosity [cPs] shows this comparison between fluids for density and dynamic viscosity. 650 0 100 120 140 160 180 200 220 240 Temperature [°C] Figure 3.7 – Experimental dynamic viscosity and density versus temperature for Duratherm 600 and Paratherm NF at operating conditions during steady state. Values were taken from manufacturer technical documents. 28 4 EXPERIMENTAL SETUP The oil loop is powered by a Liquiflo 45-series gear pump, with a ¼ horsepower motor. The pump allows for a high temperature of 260 °C, with a maximum rated flow rate 11 LPM. Due to the large change in viscosity of the heat transfer oil used and the range of operating temperature, the gears were “trimmed”, or specially designed to allow for thermal expansion. A DC controller provides control of the flow rate, while a high point inlet and low point outlet provide the ability to add and drain oil. The piping and instrumentation diagram (P&ID) shown in Figure 4.1 shows the layout of the instrumentation. 3/8” stainless steel tubing and Swagelok fittings was used for the construction of the oil loop. 29 HRU Exhaust Manifold THO PHO PHI T P POI T T TOI P P Exhaust Ducting P Turbine Flowmeter TPO PPO T TEI T TOO To thermally activated cooling system T Oil Filter Filter P POO Open Reservoir QO PFI TPI P P PPI E-3 Figure 4.1 – Piping and Instrumentation diagram (P&ID) for the HRU and oil loop. Minimization of heat loss and space constraints resulted in the need to mount the HRU within the diesel generator housing. A custom exhaust manifold is used to enable this internal mounting to occur. As shown in Figure 4.2, the standard exhaust manifold was removed from the diesel engine and modified to allow direct mounting to the surface. 30 Figure 4.2 - Modified diesel exhaust manifold. The HRU is then placed in-line with the filter plate, air side exhaust elbow, and finally a flexible hose to the exhaust outlet of the diesel generator (Figure 4.3). 31 Figure 4.3 - Full HRU assembly inside the diesel generator housing. Various forms of insulation were used around the exhaust manifold and HRU to ensure a slower rate of heat transfer to the surroundings. One inch foam sheet as well as fiberglass insulation was used to increase the resistance of heat vented to the atmosphere within the ORC and vapor compression cycle. 32 Figure 4.4 - Insulation of HRU/oil loop. 33 5 DATA REDUCTION AND UNCERTAINTY ANALYSIS EES was used with the collected pressure and temperature data to determine state properties for the working fluids (HFC-134a, HFC-245fa) within the thermally activated cooling system (TACS), the oil loop (Duratherm 600), and the exhaust stream (combusted exhaust-air). The majority of uncertainty for the devices can be attributed to the bias error within the instrumentation itself. The random error during experimentation was averaged out over many data points and time. The Kline McClintock method of error propagation (using a root-sum-squared methodology) was used to determine the effect of all sources of error within each calculated value. 5.1 CALIBRATION AND UNCERTAINTY 5.1.1 TACS Instrumentation The TACS was comprised of Omega K-type thermocouples special limits of error material, resulting in an uncertainty of ± 1.1 °C. The mass flow rate measurements for both power and cooling within the TACS were made by AW Company turbine flow meters, with an accuracy of± 1%. Further details can be found in Wang et al [7]. 34 5.1.2 HRU Instrumentation Temperature measurement systems in the HRU were comprised of Omega K- type thermocouples with limits of error of 2.2 °C. The Omega pressure transducers had an accuracy of ±0.25%, which were then calibrated with a digital pressure gauge with an accuracy of ±0.05%. These pressure transducers were used in both the TACS and HRU. During testing, pressure, temperature, flow rate, and load were recorded. The latter value was recorded manually from the visual reading of a Simplex Swift-E Plus load bank. Pressure, temperature, and flow rate were recorded via LabView. Using a National Instruments CDAQ-9172 chassis with current and voltage DAQs NI 9203 and NI 9211, respectively, samples were taken at a frequency of 100 Hz and were average every second. Using the heat transfer fluid Duratherm 600, temperatures and pressures were recorded to determine fluid properties. These properties were linearly interpolated if needed to determine values at the measured state points [36]. 35 An Omega turbine flow meter (FTB-901T) with signal conditioner (FLSC62A) was calibrated with a catch and weigh method described by Doebelin [37] with fluid temperatures that varied from 85 °C to 140 °C to an uncertainty of 7.72E-7 m3/s. The open loop consisted of a reservoir, heater, pump, and fluid return bucket with a scale below it, as shown in Figure 5.1. Fluid bucket (rejection) Fluid Reservoir Stopwatch Heater Scale T T TPO PPO P P Turbine Flowmeter TPI PPI Gear Pump Figure 5.1 - Catch and weigh experimental setup for calibration of the oil turbine flow meter. Omega K-type thermocouples manufactured with standard limits of error material contain an uncertainty of 2.2 °C or 0.75% over the range from 200 °C to 1250 °C were used in the oil loop. The pressure transducers manufactured by Cole Palmer used in the oil loop have a maximum rating of 100 and 50 psig with an accuracy of ±0.25% full scale. The Omega turbine 36 flow meter (model FTB-901T) has a range from 0.5 to 2.5 GPM, with a linearity of 0.3% full scale, while the signal conditioner used in conjunction with it had an accuracy of 0.5% readability. 5.1.3 Calculations With mass flow rate calculated from the volumetric flow rate as: πΜ = πΜ β π (5.1) The heat transfer from the oil side can be calculated: πΜ = πΜπππ ππ (πππ’π‘ − πππ )πππ (5.2) With no losses to the environment, the mass flow rate of the exhaust side is: πΜππ₯βππ’π π‘ = πΜπππ ππ (πππ’π‘ − πππ )πππ ππ (πππ − πππ’π‘ )ππ₯βππ’π π‘ (5.3) This results in an oil side effectiveness of: π= ππ (πππ − πππ’π‘ )ππ₯βππ’π π‘ πππ,ππ₯βππ’π π‘ − πππ,πππ (5.4) π½ With πΜπππ as the mass flow rate οΏ½ π οΏ½ and ππ of oil as the specific heatοΏ½ππβπΎοΏ½. 37 Table 5.1 - Uncertainty in measurements for the oil loop and heat recovery device [31:61]. Parameter Uncertainty πΜExhaust πΜOil Duty ΔP πΜ flow ε 1.8E-3 kg/s 6.1E-4 kg/s 293 W 1.7 kPa 0.17 W 0.015 The uncertainties for the thermally activated cooling system were found in a similar manner and resulting in the uncertainties shown in Table 5.2. Table 5.2 - Uncertainties in measurement for the thermally activated cooling system [34:19]. Parameter Uncertainty ηexp 2.50% ηp 2.50% ηp,II 2.50% εrecp πΜ evap 2.80% COPs 2.20% 3.50% 38 6 PERFORMANCE ANALYSIS AND DISCUSSIONS The oil’s viscosity was heavily dependent upon the temperature of the oil, which affected the flow rate of the oil. Previous testing showed a weak correlation between the oil flow rate and the heat transferred. Thus the decision was made to allow the oil to flow at the maximum rate the pump would allow for the given operating conditions. The ORC working fluid flow rate had a much stronger effect on the performance of the system than the heat transfer oil. By controlling the ORC working fluid flow rate, the effects of heat transfer and system performance could be observed. The goal of the TACS was to produce 5.3 kW of cooling capacity with a heat input rate of 10.6 kW and system COP of 0.5, so only the upper limits of diesel generator duty were tested. The duty of the generator is controlled by an electric load bank. The electric loads used were 11.1 kWe, 12.1 kWe, and 13.5 kWe. Testing of the performance of the HRU and the TACS occurred at different times. Hence Chapter 6.1 numbers will vary from the remainder of the Analysis section. Error bars are a function of the measured uncertainty as described in Table 5.1 and Table 5.2. 39 6.1 HEAT RECOVERY UNIT PERFORMANCE The system ran without the TACS operating to verify the effect of duty with that of pressure drop. To replace the role of the TACS to dissipate heat from the oil side, a tube and shell heat exchanger was used. The tube and shell heat exchanger used cool water from a faucet to exchange heat with the oil. The HRU was cleaned with compressed air before operation. A load bank was used to control the load on the diesel generator. Operating with a load bank at full load resulted in 10.2 kW of heat recovered (Figure 6.1). The back pressure as measured at the exhaust manifold rose steadily without any filtration in line as shown in Figure 6.2, but duty remained nearly constant despite the back pressure increase. As the diesel generator load was increased, the back pressure showed a significant increase (Figure 6.3). A greater load produces more diesel particulate and mass flow rate, increasing the density of the exhaust fluid. When the system was later run with the TACS absorbing the heat, similar back pressure values were observed. 40 12000 10000 Duty [W] 8000 6000 4000 2000 0 0 1000 2000 3000 4000 5000 Time [s] Figure 6.1 - Typical duty of the HRU during testing. 10 Back Pressure [kPa] 9 8 7 6 5 4 0 500 1000 1500 2000 Time [s] Figure 6.2 – Typical back pressure as measured at the exhaust manifold. 41 11.1 kWe 12.1 kWe 13.5 kWe Manifold Pressure [kPa] 26 21 16 11 6 1 10 10.5 11 11.5 12 12.5 13 13.5 14 Duty [kW] Figure 6.3 - Effect of back pressure with respect to duty. The oil duty increases as the ORC working fluid mass flow rate increases. An increase in mass flow rate in the ORC results in the boiler duty increasing. By carrying away more heat the outlet on the oil side of the boiler decreases. This results in a larger temperature rise across the oil side of the HRU, feeding more power to the boiler. This relationship is shown by: πΜ = πΜπππ ππ οΏ½ππππ,ππ’π‘ − ππππ, ππ οΏ½π»π π (6.1) 42 11.1 kWe 12.1 kWe 13.5 kWe 12000 Oil Duty [W] 11000 10000 9000 8000 7000 6000 0.025 0.030 0.035 0.040 0.045 0.050 0.055 0.060 ORC Power Cycle Working Fluid Mass Flow Rate [kg/s] Figure 6.4 - Oil duty as a function of ORC working fluid mass flow rate. Effectiveness of the HRU decreases slightly due to the decrease in NTU resulting from an increase πΆπππ value. 43 HRU effectiveness 11.1 kWe 0.95 0.94 0.93 0.92 0.91 0.90 0.89 0.88 0.87 0.86 0.85 0.025 0.030 0.035 12.1 kWe 0.040 13.5 kWe 0.045 0.050 0.055 0.060 ORC Power Cycle Working Fluid Mass Flow Rate [kg/s] Figure 6.5 - HRU effectiveness and ORC working fluid mass flow rate. The power required to pump the heat transfer oil also increases with an increase in ORC working fluid mass flow rate. As explained previously, the outlet temperature of the boiler on the oil side decreases. The temperature reduction results in an increase in both density and viscosity. Since the pump is the next component after the outlet from the TACS, the pump has to work harder to provide the same mass flow rate. This relationship is shown below: π€Μπ»π π = πΜπππ (πππ − πππ’π‘ )πππ (6.2) 44 Hydraulic Power Required [W] 11.1 kWe 33 32 31 30 29 28 27 26 25 24 23 0.025 0.030 0.035 12.1 kWe 0.040 13.5 kWe 0.045 0.050 0.055 0.060 ORC Power Cycle Working Fluid Mass Flow Rate [kg/s] Figure 6.6 - Hydraulic power through HRU. 6.2 TACS PERFORMANCE – POWER SIDE The effects of the flow rate of R245fa and boiler heat duty in the ORC power cycle on the cooling capacity of the Rankine Heat Pump were analyzed. R245fa flow rate in the ORC was adjusted for each duty cycle to ensure the fluid remained in the superheat regime at the inlet of the expander for the duration of testing at each interval. Temperatures at the inlet and outlet of both the HRU and ORC power cycle boiler were measured on the oil side and compared. As shown in Figure 6.7, three distinct trends are shown. From left to right the generator electric loads 45 are 11.1 kWe, 12.1 kWe, and 13.5 kWe. As this flow rate increases the boiler absorbs more heat from the oil loop for a given diesel generator duty, shown in Equation (5.2). This results in a lower return temperature for the oil. The lower incoming temperature of the oil increases the temperature difference further allowing the HRU to transfer more heat to the oil to be carried to the boiler. An efficiency of sorts can be developed comparing the temperature rise across the HRU to that of the temperature drop across the boiler. An increase power cycle working fluid mass flow rate results in a smaller difference between these two temperature changes, resulting in a higher efficiency. This relationship is shown in Figure 6.7. Figure 6.8 shows the expander work and the mass flow rate of the ORC for the given RPM. Since the scroll expander is a positive displacement type device, the higher RPM and flow rate raise the available work from the expander. 46 ΔTratio 11.1 kWe 0.97 0.96 0.95 0.94 0.93 0.92 0.91 0.9 0.89 0.88 0.87 0.020 0.025 0.030 12.1 kWe 0.035 0.040 13.5 kWe 0.045 0.050 0.055 0.060 ORC Power Cycle Working Fluid Mass Flow Rate [kg/s] Figure 6.7 – The ratio of heat transferred from the HRU outlet of the oil side to that of the boiler inlet. The temperatures are recorded from the oil loop. Expander Speed Linear (Expander Speed) 1800 4100 1700 3900 1600 3700 1500 3500 1400 3300 1300 3100 1200 2900 1100 2700 1000 0.020 0.025 0.030 0.035 0.040 0.045 0.050 0.055 Speed [RPM] Wexp [W] Expander Work 2500 0.060 ORC Power Cycle Working Fluid Mass Flow Rate [kg/s] Figure 6.8 – Expander work and rotational speed for a given expander mass flow rate. Work was determined from the mass flow rate and measured fluid conditions. 47 The expander isentropic efficiency of the expander decreases as the flow rate is increased (Figure 6.9). The isentropic efficiencies as well as the work values at the expander are rough estimates. Using the temperature and pressure values measured at the inlet and outlet are not as accurate as measuring the mechanical power. Measurement of the mechanical power was not possible due to a faulty torque sensor. The expander isentropic efficiency was calculated using the enthalpies that correspond with the given temperature and pressure at the measurement points of the ORC working fluid. πππ₯π,ππ ππ = βππ₯π,πππππ‘ − βππ₯π,ππ’π‘πππ‘ βππ₯π,πππππ‘ − βππ₯π,ππ’π‘πππ‘,ππ ππ πππ₯π = πΜπππ€ππ (βππ₯π,ππ − βππ₯π,ππ’π‘ ) (6.3) (6.4) 48 11.1 kWe 12.1 kWe 13.5 kWe 1 0.95 0.9 ηexp 0.85 0.8 0.75 0.7 0.65 0.6 0.020 0.025 0.030 0.035 0.040 0.045 0.050 0.055 0.060 ORC Power Cycle Working Fluid Mass Flow Rate [kg/s] Figure 6.9 - Expander isentropic efficiency for a given mass flow rate. The isentropic expander efficiency is shown in Figure 6.10. The highest isentropic efficiency is located around the 5.2 range. The expander ratio was controlled by providing more heat to the boiler, in addition to increasing the flow rate of the ORC power cycle working fluid. The higher ORC power cycle working fluid flow rate decreased the ratio of pressure across the expander. 49 11.1 kWe 12.1 kWe 13.5 kWe 100% 95% 90% ηexp 85% 80% 75% 70% 65% 60% 4.0 4.5 5.0 5.5 6.0 6.5 Expander Pressure Ratio Figure 6.10 - Expander efficiency for each load and pressure ratio. 6.3 TACS PERFORMANCE – COOLING SIDE The effect of power cycle mass flow rate and cooling capacity are shown in Figure 6.11. As the duty of the generator and mass flow rate of the power cycle increased, the amount of cooling available also increased. The increase in mass flow rate in the ORC drove an increase in expander power. This increased the power to the condenser, increasing the mass flow rate, which increases the evaporator cooling capacity. πΜ ππ£ππ = πΜπππππππ (βππ’π‘ − βππ )ππ£ππ (6.5) 50 11.1 kWe 12.1 kWe 13.5 kWe Cooling Capacity [kW] 5.5 5.0 4.5 4.0 3.5 3.0 0.0200 0.0250 0.0300 0.0350 0.0400 0.0450 0.0500 0.0550 0.0600 ORC Power Cycle Working Fluid Mass Flow Rate [kg/s] Figure 6.11 - Cooling capacity and power flow rate. The outliers circled above are a result in an increase in the fan speed. For the 12.1 kWe case, the increase in fan speed resulted in more cooling taking place. The fan speed decreased the temperature and pressure of the evaporator inlet. This decrease in state conditions also resulted in a slight decrease in compressor outlet conditions, which increased the amount of subcooling available in the vapor compression cycle (VCC). This means the condenser removed a greater amount of heat, and the evaporator increased the amount of heat absorbed. 51 The 13.5 kWe cases also had their fan speed increased. While the thermal expansion valve (TXV) tried to reduce the flow rate to allow for superheating of the VCC working fluid at the outlet of the evaporator, it was observed that the pressure drop across the device was so large that further reduction in VCC mass flow rate was not possible. This resulted in a slight amount of liquid still available at the outlet of the evaporator. Since testing occurring off the design point, a large enough thermal gradient was not present. For the given conditions, if the surface area was increased, or spring tension was adjusted further on the TXV, proper superheat out of the evaporator would occur. Further increasing the ORC working fluid mass flow rate allowed for more power to the expander/compressor, but since it could not properly utilize this power, a stagnate cooling capacity was observed for the highest load bank/ORC working fluid mass flow rate conditions. The HRU is attempting to provide addition power, but the boiler cannot use it since the demand from the compressor does not increase. Looking at the overall system performance of the TACS gives a similar result. As the flow rate and cooling capacity increased, a steady trend of the reduction in the system COP is observed (in Figure 6.12). More power is being produced for the cooling cycle than is able to be efficiently utilized. 52 From a performance standpoint, the lower flow rate and duty result in higher performance. This is due to the larger enthalpy drops driven by a larger change in temperature and pressure at these lower rates. Again, increasing the air flow rate or replacing air with another fluid (such as water) to remove the heat would result in increased COP. 11.1 kWe 12.1 kWe 13.5 kWe 0.60 COP (system) 0.55 0.50 0.45 0.40 0.35 0.30 0.0200 0.0250 0.0300 0.0350 0.0400 0.0450 0.0500 0.0550 0.0600 ORC Power Cycle Working Fluid Mass Flow Rate [kg/s] Figure 6.12 - System COP and power mass flow rate. A steady reduction in overall system COP is observed across the duty of the generator. 53 7 SECOND GENERATION HRU To further increase the efficiency and minimize negative aspects of the initial design of the heat recovery device, a second generation device was designed. While the majority of the ground work has been covered by Ward [9], modifications were done as testing was carried out and problems arose. The chief concerns to be addressed include pressure drop in the fluid streams, size, weight, and fluid distribution. The basics principles of the model for the HRU are as follows. For complete process details, refer to Ward [9]. To properly model a single pass microchannel heat exchanger, an energy balance was conducted. Assuming no phase change, steady flow, constant specific heats of the fluid, and negligible changes in potential and kinetic energy, the heat transfer from one fluid to another can be expressed as follows: πΜ = πΜβ ππ,β (πβ,π − πβ,π ) (7.1) πΜ = πΜπ ππ,π (ππ,π − ππ,π ) (7.2) The unknowns are found via an effectiveness-NTU method, with πΆπππ being the smaller value of heat capacity of the oil and exhaust (exhaust is smaller in this case). 54 πππ = ππ΄ πΆπππ (7.3) An order of magnitude analysis was carried out to determine which resistances play the largest roles. It was determined between the convective and conductive resistances within and between the two fluid streams, only the convective resistances of the two fluid streams play a significant role (fouling was not considered for this design). Effectiveness was determined from empirical correlations for a cross-flow heat exchanger, as shown in below: π= πΜ πΜ max 1 π = 1 − exp οΏ½οΏ½ οΏ½ (πππ)0.22 {ππ₯π[−πΆπ (πππ)0.78 ] − 1}οΏ½ πΆπ πΆπ = πΆπππ πΆπππ₯ (7.4) (7.5) (7.6) The pressure drop through the channels is calculated from the Darcy- Weisbach equation (2.3). 55 Modeling of a two pass heat exchanger was done in an iterative scheme in MATLAB to determine the temperatures between passes and within each stream outlined by Ward [9]. The shim size was fixed for the air and oil shim with material thicknesses of 0.99 mm and 0.30 mm, respectively. The material used was316L stainless steel, which was selected for its manufacturability and bonding characteristics. Two different ratios are of interest during the design and manufacturing process, the aspect ratio and fin aspect ratio. The aspect ratio is define as πΆ πΌ = π΅. This ratio affects the performance characteristics of the device. If πΌ becomes too large, it is possible to etch through the device. The fin aspect πΆ ratio, defined as = π΄ , is important during the manufacturing process. Having too large a fin aspect ratio could result in bonding problems and a leaking device. Using the restraints outlined in Section 2.3 and correspondence with VACCO [39], maximum values were obtained for this specific heat exchanger design to optimize desired characteristics without compromising the manufacturability of the device. 56 Figure 7.1 - Aspect ratio definitions taken from a side view of a generic shim. B is etch depth, C is etch width, A is remaining material thickness, and D is the rib thickness. Ward [9] showed the effects of total surface area for both the oil shim and the air shim on that of the recoverable duty. As shown in Figure 7.2, gains in surface area of the oil shim provide little benefit compared to the potential that exists with an increase in surface area on the exhaust shim. As πΆπππ increases due to an increase in mass flow rate and specific heat capacity (πΆπππ = πΜππ₯βππ’π π‘ ππ,ππ₯βππ’π π‘ ), the number of transfer units (NTU) decreases. This relationship is shown in Equation (7.3). 57 Figure 7.2 - Surface area and the effects on total thermal waste heat recovery [9:34]. 7.1 AIR SHIM DESIGN To decrease the pressure drop across the air side, a study was done to determine what affect the channel aspect ratio (while maintaining the channel depth) has on the pressure drop and heat transferred from the air fluid stream. 58 Using an iterative method and neglecting entrance and header effects, an optimal channel aspect ratio can be obtained. Figure 7.3 shows the effects of channel width on pressure drop and effectiveness from the HRU. Given the rate of decrease of effectiveness compared to the potential reduction in air pressure drop, the air aspect ratio could be increased to reduce the pressure drop while maintaining performance of the HRU. For this testing the etch depth was maintained at 0.80 mm and the rib width was held at 0.80 mm. Air Pressure Drop [Pa] 1.000 0.980 0.960 0.940 0.920 0.900 0.880 0.860 0.840 0.820 0.800 1800 1750 1700 1650 1600 1550 1500 1450 Air Pressure Drop [Pa] Effectiveness Effectiveness 1400 10 15 20 25 30 35 40 Air Fin Aspect Ratio (constant etch depth of 0.8 mm) Figure 7.3 - Pressure drop and effectiveness for various etch widths in the air shim. Results are for a constant air etch depth, as well as a constant oil channel width and depth. 59 Assurances were given on a best effort basis that with the chosen material and process control, a fin aspect ratio of 42 could be achieved if steps were taken to reduce the effective span across the inlet and outlet of the air shim. To accomplish this, a support rib was added (Figure 7.4). To minimize the pressure drop from this decrease of cross-sectional area from the addition of a support rib (denoted as A1 to A2 in Figure 7.4), the length of the support ribs were limited. Ideally an air aspect ratio as large as possible (for the given effectiveness) would be desired. However manufacturing constraints dictate a reasonable range of values that are practical for manufacturing. Due to the depth of etch required (80% of material thickness) and the required thickness of ribs to ensure proper bonding, only one support rib was placed between each through rib. This support rib is shown in Figure 7.4. The finalized dimensions of the air shim are shown in Table 7.1. Table 7.1 - Air shim dimensions. Refer to Figure 7.1 and Figure 7.4 for the location of these dimensions. Shim length Support rib width Support rib length Through rib width Channel width Etch depth Dimension [mm] 170 0.75 4 (2x at 2 mm each) 0.8 8 0.8 60 Figure 7.4 - Air shim with support and through ribs. Figure 7.5 - Air shim for second generation device. 61 7.2 OIL SHIM DESIGN The oil shim underwent a similar iterative analysis to determine the effect of channel aspect ratio on effectiveness and duty. The number of oil channels was increased to maximize the use of material. While on the first generation device there remained 14.75 mm of unetched material between passes, the second generation has a landing of only 3.6 mm between passes. Discussion with the manufacturer to ensure proper bonding and sealing resulted in 3.6 mm being sufficient width. Figure 7.6 - Spacing between oil passes. 62 Aspect ratios were examined from for value of eight up to a 24. It was shown that effectiveness was a weak function of oil channel aspect ratio. Given the low pressure drop and success bonding in the first generation device (with a ratio of eight), this value was chosen for the aspect ratio of the second generation device as well. Figure 7.7 - Oil shim for second generation device. 63 7.3 HEADER DESIGN Analytical models used to model headers have been shown to be in good agreement with CFD simulations according to Pan and Tang when dealing with right angle headers with small (less than 60) Reynolds numbers [40]. Right angled headers provide more uniform flow compared to obtuse header designs. Assuming a network of rectangular channels, the analytical model considers the frictional losses and velocity given by the Hagen-Poiseuille equation to determine the pressure drop in laminar flow within microchannels.: Δπ = 32ππΏπππΆ π = π π π π·π»2 (7.7) Where L is the length, π is the dynamic viscosity, U is the velocity, π π is the frictional resistance, and Δπ is the pressure drop. The hydraulic nominal diameter π·π» and the noncircular coefficient πππΆ are shown in (7.8) and (7.9), respectively. Note W is the microchannel cross-sectional width, and E is the height of the microchannel. π·π» = 2ππΈ π+πΈ (7.8) 64 πππΆ 3 οΏ½2οΏ½ = πΈ π 2 πΈ π 2 οΏ½1 − 0.351 min οΏ½π , πΈ οΏ½οΏ½ οΏ½1 + min οΏ½π , πΈ οΏ½οΏ½ (7.9) A simplified resistance model (Figure 7.8) is used which resembles an electrical network, consisting of resistances in each section as well as the flow rates. The pressure drops of two ends of a flow channel are equal. Rfi (1) Rji(1) Rfi(2) Rc(1) Rfo(1) Rji(2) Rc(2) Rjo(1) Rfi(j) Rc(j-1) Rfo(j-1) Rji(j) Rc(j) Rjo(j-1) Rfi(N) Rc(N-1) Rfo(N-1) Rji(N) Rc(N) Rjo(N-1) Rfo(N) Rjo(N) Figure 7.8 - Equivalent resistance network for simplified flow header and channel design [31:92]. Starting with the requirement for a right angle header design due to the recommendation from Pan and Tang, as well as the requirement of reducing overall HRU volume, an iterative approach was used to determine ideal header design for our case. The variables that were looked at include the distance from the inlet to the channel entrance (the Y dimension) and the distance from the far channel to the first bend, or H dimension. 65 Figure 7.9 - Header design to be studied. Variables Y and H will be adjusted to determine optimal configuration. The value of H (the lip size) was initially changed to determine the effects of flow distribution. It was found that decreasing this value down to 0 provided the lowest maldistribution for a given flow rate. As shown in Figure 7.10, as the lip size is decreased the amount of flow decreases near the inlet and slightly increases near the lip. 66 Normalized Flow Distribution 0mm 1mm 2mm 3mm 4mm 1.2 1.15 1.1 1.05 1 0.95 0.9 0 10 20 30 40 50 Channel Number Figure 7.10 – The effect of H value on flow distribution of each channel. The Y dimension was modified to determine the effects of maldistribution as well. As shown in Figure 7.11, increasing the Y value resulted in a decrease of flow near the closer channels, with an increase in flow near the far end of the channels (away from the inlet). This general trend was continued for large Y values. Due to size constraints a value of Y=17 mm was chosen to be manufactured. Larger values of Y would not allow the HRU assembly to fit within the diesel generator enclosure. 67 Normalized Flow Distribution 10mm 12mm 14mm 16mm 18mm 1.08 1.06 1.04 1.02 1 0.98 0.96 0 10 20 30 40 50 Channel Number Figure 7.11- The effect of Y value on flow distribution of each channel. The H value was set to 0 for this figure. While the reduction of pressure drop through the oil shim is beneficial, reducing the pressure drop through the array is not. To try and maintain a proper amount of resistance through the array, restrictions were added to the inlet, as shown here: 68 Figure 7.12 - Oil shim inlet restriction. 7.4 PLENUM DESIGN The configuration of the first generation HRU allowed for the mixing of heat transfer fluid between the first and second pass to minimize pressure losses and maintain good heat transfer characteristics. The second generation device uses a split header design to increase theoretical heat transfer and minimize the chances of oxidation. Baclic et al. [41] provided various configurations which could provide more beneficial heat transfer by employing various mixing schemes. While the first generation allowed mixing of the heat transfer fluid (Figure 7.13, Case 1), but not of the exhaust heat, the second generation will limit the mixing of the heat transfer oil and maintain the non- 69 mixing exhaust stream design, as shown in Case 2 in Figure 7.13. An ideal case could be realized if both fluid streams were fully inverted, but due to the complexity of both design and manufacturing, this case (Case 4) is not realistic for the given physical device requirements. Figure 7.13 shows a graphical representation of these flow configurations. From Ward it was shown that Case 2 offers a potential gain of 200 W from Case 1 (for the first generation HRU), while Case 3 and 4 offers an additional 100 W on top of Case 2. With the potential negatives such as increased pressure drop and complexity, the latter cases were not considered. 70 Case 1: 1 Generation HRU Case 2: Unmixed Passes Case 3: Inverted Oil Case 4: Both Fluids Inverted st Figure 7.13 – Cross counterflow heat exchanger configurations. Fluid stream mixing varies [31:100]. 7.5 FINAL DESIGN The final layout of the device is similar to the first generation device. Other aspects were looked into and modified as seen fit to increase performance. The weight and size and been greatly reduced, and performance has 71 increased with no negative effects. Comparison between the first generation and second generation device are shown below. Table 7.2 – First generation and second generation HRU theoretical performance characteristics. Duty [W] 1st Gen 2nd Gen Oil Pressure Drop [Pa] Air Pressure Drop [Pa] Exhaust H.T. Area [m2] Oil H.T. Area [m2] 11571 0.88 32228 2373 0.77 0.62 12448 0.96 26890 1821 0.85 0.74 The mass has been reduced from 11.15 kg to 3.86 kg (as modeled). The length of the device has been reduced from 210 mm to 170mm. This reduction of space has allowed for a longer filter box to be placed in line with the HRU and exhaust manifold, allowing easier cleaning and easier testing of filter materials. Whereas before the whole assembly would need to be removed for maintenance to be performed on the device, the new filter box will have an easily accessible door which can be used with or without filter material. 72 Figure 7.14 - Filter box with removable door. Figure 7.15 - Final HRU Generation 2 Design. 73 8 CONCLUSION The first generation heat exchanger has proven to operate well when used in unison with a diesel generator and thermally activated cooling system at duties ranging from 11.1 to 13.5 kWe. The back pressure was determined to be a function of load on the diesel generator. A higher R245fa working fluid mass flow rate resulted in more work done by the expander, increasing the flow rate of the cooling cycle. A maximum efficiency of 92% was observed with a pressure ratio of 5.2. The efficiency is artificially high due to fluid properties used to compute work. A calibrated torque sensor would provide a more accurate measurement. Cooling capacity increased with flow rate, which is driven by the expander power. A maximum of 5 kW of cooling was observed at a generator duty of 13.5 kW with an R245fa working fluid mass flow rate of 0.056 kg/s. The system COP declined as the energy into the boiler exceeded the cooling capacity of the vapor compression cycle. Ability for dynamic charging, variable fan speed, or an increase in surface area for the condenser would allow for increased cooling capacity and system COP. If ambient temperatures were increased during testing, higher values of cooling capacity and COP for both system and cooling would be realized from a greater temperature differential. 74 The second generation heat recovery device has been modeling and outperforms the current HRU in all aspects, including size, weight, effectiveness, and overall performance. Restrictions and additional pressure drops from excess material have been removed, decreasing pressure drops throughout the HRU. Effectiveness is expected to increase from 0.88 to 0.96, and HRU duty is expected to see a theoretical increase from 11.6 to 12.4 kW for similar operating conditions. Oil pressure drop will decrease from a redesigned header and plenum area, and increased flow distribution will encourage more uniform temperature distribution across the fluid streams. 75 9 WORKS CITED [1] D. Pimentel, M. Herz, M. Glickstein, M. Zimmerman, R. Allen, K. Becker, J. Evans, B. Hussain, R. Sarsfeld, A. Grosfeld, and T. Seidel, “Renewable Energy: Current and Potential Issues,” BioScience, vol. 52, p. 1111, 2002. [2] J. Heywood, Internal combustion engine fundamentals, International ed. New York: McGraw-Hill, 1988. [3] H. Teng, G. Regner, and C. Cowland, “Waste Heat Recovery of Heavy-Duty Diesel Engines by Organic Rankine Cycle Part II: Working Fluids for WHR-ORC,” SAE International, Warrendale, PA, 2007-01-0543, Apr. 2007. [4] A. B. Little and S. Garimella, “Comparative assessment of alternative cycles for waste heat recovery and upgrade,” Energy, vol. 36, no. 7, pp. 4492–4504, Jul. 2011. [5] A. AktaΕ and A. DoΔu, “Recovery of waste heat energy from gasoline engine exhaust,” Journal of the Energy Institute, vol. 81, pp. 45–47, Mar. 2008. [6] T. C. Hung, T. Y. Shai, and S. K. Wang, “A review of organic rankine cycles (ORCs) for the recovery of low-grade waste heat,” Energy, vol. 22, no. 7, pp. 661–667, Jul. 1997. [7] H. Wang, R. Peterson, K. Harada, E. Miller, R. Ingram-Goble, L. Fisher, J. Yih, and C. Ward, “Performance of a combined organic Rankine cycle and vapor compression cycle for heat activated cooling,” Energy, vol. 36, no. 1, pp. 447–458, Jan. 2011. [8] J. Yih, “The Physical Characterization and Thermal Performance of a Microchannel Heat Exchanger for Diesel Engine Waste Heat Recovery,” Master’s Thesis, Oregon State University, 2011. [9] C. Ward, “Design and Performance of a Small Scale Waste Heat Recovery Unit,” Master’s Thesis, Oregon State University, 2011. [10] K. Harada, “Development of a Small Scale Scroll Expander,” Master’s Thesis, Oregon State University, 2010. [11] P. Bombarda, C. M. Invernizzi, and C. Pietra, “Heat recovery from Diesel engines: A thermodynamic comparison between Kalina and ORC cycles,” Applied Thermal Engineering, vol. 30, no. 2–3, pp. 212–219, Feb. 2010. [12] B. Saleh, G. Koglbauer, M. Wendland, and J. Fischer, “Working fluids for low-temperature organic Rankine cycles,” Energy, vol. 32, no. 7, pp. 1210–1221, Jul. 2007. [13] O. Badr, P. W. O’Callaghan, and S. D. Probert, “Performances of Rankinecycle engines as functions of their expanders’ efficiencies,” Applied Energy, vol. 18, no. 1, pp. 15–27, 1984. 76 [14] V. Lemort, S. Quoilin, C. Cuevas, and J. Lebrun, “Testing and modeling a scroll expander integrated into an Organic Rankine Cycle,” Applied Thermal Engineering, vol. 29, no. 14–15, pp. 3094–3102, Oct. 2009. [15] J. A. Mathias, J. Johnston, J. Cao, D. K. Priedeman, and R. N. Christensen, “Experimental Testing of Gerotor and Scroll Expanders Used in, and Energetic and Exergetic Modeling of, an Organic Rankine Cycle,” J. Energy Resour. Technol., vol. 131, no. 1, p. 012201–9, Mar. 2009. [16] A. Schuster, S. Karellas, E. Kakaras, and H. Spliethoff, “Energetic and economic investigation of Organic Rankine Cycle applications,” Applied Thermal Engineering, vol. 29, no. 8–9, pp. 1809–1817, Jun. 2009. [17] M. Wei, J. Fang, C. Ma, and S. N. Danish, “Waste heat recovery from heavy-duty diesel engine exhaust gases by medium temperature ORC system,” Science China Technological Sciences, vol. 54, pp. 2746–2753, Aug. 2011. [18] V. Maizza and A. Maizza, “Working fluids in non-steady flows for waste energy recovery systems,” Applied Thermal Engineering, vol. 16, no. 7, pp. 579–590, Jul. 1996. [19] S. Vijayaraghavan and D. Y. Goswami, “Organic Working Fluids for a Combined Power and Cooling Cycle,” J. Energy Resour. Technol., vol. 127, no. 2, pp. 125–130, Jun. 2005. [20] V. Maizza and A. Maizza, “Unconventional working fluids in organic Rankine-cycles for waste energy recovery systems,” Applied Thermal Engineering, vol. 21, no. 3, pp. 381–390, Feb. 2001. [21] K. K. Srinivasan, P. J. Mago, G. J. Zdaniuk, L. M. Chamra, and K. C. Midkiff, “Improving the Efficiency of the Advanced Injection Low Pilot Ignited Natural Gas Engine Using Organic Rankine Cycles,” J. Energy Resour. Technol., vol. 130, no. 2, p. 022201–7, Jun. 2008. [22] P. J. Mago, L. M. Chamra, and C. Somayaji, “Performance analysis of different working fluids for use in organic Rankine cycles,” Proceedings of the Institution of Mechanical Engineers, Part A: Journal of Power and Energy, vol. 221, no. 3, pp. 255 –263, May 2007. [23] K.-H. Choi, Y. Korai, and I. Mochida, “Combustion properties of particulate matter in diesel engine exhaust,” Combustion and Flame, vol. 137, no. 1–2, pp. 255–260, Apr. 2004. [24] C. Gorsmann, “Catalytic Coatings for Active and Passive Diesel Particulate Filter Regeneration,” Monatshefte fur Chemie - Chemical Monthly, vol. 136, pp. 91–105, Jan. 2005. [25] T. Martin, “Particulate Problems,” Aftermarket Business, vol. 116, no. 11, pp. 128–130, Nov. 2006. [26] J. Yang, M. Stewart, G. Maupin, D. Herling, and A. Zelenyuk, “Single wall diesel particulate filter (DPF) filtration efficiency studies using 77 laboratory generated particles,” Chemical Engineering Science, vol. 64, no. 8, pp. 1625–1634, Apr. 2009. [27] J. Adler, “Ceramic Diesel Particulate Filters,” International Journal of Applied Ceramic Technology, vol. 2, no. 6, pp. 429–439, Nov. 2005. [28] R. S. Barhate and S. Ramakrishna, “Nanofibrous filtering media: Filtration problems and solutions from tiny materials,” Journal of Membrane Science, vol. 296, no. 1–2, pp. 1–8, Jun. 2007. [29] D. B. Tuckerman and R. F. . Pease, “High-performance heat sinking for VLSI,” IEEE Electron Device Letters, vol. 2, no. 5, pp. 126–129, May 1981. [30] Anna Lee Tonkovich, “Microchannel Heat Exchangers: Applications and Limitations,” 09-Nov-2011. [31] J. Judy, D. Maynes, and B. W. Webb, “Characterization of frictional pressure drop for liquid flows through microchannels,” International Journal of Heat and Mass Transfer, vol. 45, no. 17, pp. 3477–3489, Aug. 2002. [32] B. K. Paul, P. Kwon, and R. Subramanian, “Understanding Limits on Fin Aspect Ratios in Counterflow Microchannel Arrays Produced by Diffusion Bonding,” J. Manuf. Sci. Eng., vol. 128, no. 4, pp. 977–983, Nov. 2006. [33] FotoFab, “FotoFab Design Guide,” Design Guide, 10-Sep-2001. [Online]. Available: http://www.fotofab.com/pdf/designguide.pdf. [Accessed: 10Sep-2001]. [34] Indiana Micro Metal Etching, “Design Guide,” Design Guide, 10-Sep2001. [Online]. Available: http://www.indymetaletching.com/micrometal-etching/design-guide/. [Accessed: 10-Sep-2001]. [35] Towne Technologies, Inc., “Design Restrictions for Chemical Machining,” Design, 10-Sep-2011. [Online]. Available: http://www.townetech.com/design.htm. [Accessed: 10-Sep-2011]. [36] Duratherm Extended Life Fluids, “Property vs. Temperature Charts,” 02Nov-2011. [Online]. Available: http://www.heat-transferfluid.com/pdf/productdata/heattransfer/duratherm-600-charts.pdf. [Accessed: 02-Nov-2011]. [37] Ernest Doebelin, Measurement systemsβ―: application and design, 4th ed. New York: McGraw-Hill, 1990. [38] H. Wang and R. B. Peterson, “Performance enhancement of a thermally activated cooling system using microchannel heat exchangers,” Applied Thermal Engineering, vol. 31, no. 14–15, pp. 2951–2962, Oct. 2011. [39] Ryan Seward, “Extra Shim,” 13-Jul-2011. [40] M. Pan, Y. Tang, H. Yu, and H. Chen, “Modeling of velocity distribution among microchannels with triangle manifolds,” AIChE Journal, vol. 55, no. 8, pp. 1969–1982, Aug. 2009. 78 [41] B. S. Baclic, F. E. Romie, and C. V. Herman, “The Galerkin Method for Two-Pass Crossflow Heat Exchanger Problem,” Chemical Engineering Communications, vol. 70, pp. 177–198, Aug. 1988.