Liebert® DSE™ System Design Manual–Downflow, 80-150kW, 23-43 Tons; Upflow, 80-85kW, 23-24 Tons; 60Hz TABLE OF CONTENTS 1.0 LIEBERT DSE COMPONENTS AND NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 1.1 Model Number Nomenclature - 25 Digit Configuration Number . . . . . . . . . . . . . . . . . . . . . . 3 2.0 AIR-COOLED PERFORMANCE DATA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 3.0 DIMENSIONS AND EQUIPMENT LAYOUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8 3.1 Floor Stand Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 4.0 PIPING SCHEMATICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 5.0 CONDENSERS—DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 6.0 PLENUM DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 6.1 Outdoor Equipment Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 7.0 DISASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 8.0 ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 8.1 Standard Electrical Field Connections, DA080 and DA085 Upflow and Downflow. . . . . . . 35 8.2 CANbus Electrical Connections, DA080 and DA085 Upflow and Downflow . . . . . . . . . . . . 35 8.3 Optional Electrical Field Connections, DA080 and DA085 Upflow and Downflow . . . . . . . 36 8.4 Optional Low-Voltage Terminal Package Field Connections, DA080 and DA085 Upflow and Downflow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 8.5 Liebert DSE Electrical Field Connection Descriptions, DA125 and DA150 Downflow Models Standard Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 8.6 Optional Electrical Connections, DA125 and DA150 Downflow Models. . . . . . . . . . . . . . . . 39 8.7 Optional Low- Voltage Terminal Package Connections, DA125 and DA150 Downflow Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42 i ii Liebert DSE Components and Nomenclature 1.0 LIEBERT DSE COMPONENTS AND NOMENCLATURE Figure 1 Downflow model component locations 3 2 1 8 11 4 10 6 9 7 5 1. Liebert iCom Control Display 2. Electric Box 3. Filters Plenum (not shipped with unit) 4. Evaporator Coil 5. Fan Modules (internal position) 6. Compressor Section 7. Infrared Humidifier (optional) 8. Disconnect (optional) 9. Condensate Pump (optional) 10. Smoke Sensor (optional) 11. THD Assembly (575V units only) DPN002402 Rev. 0 1 Liebert® DSE™ Liebert DSE Components and Nomenclature Figure 2 Upflow model component locations 10 5 7 11 2 1 Typ. 3 1. Liebert iCOM Control Display 2. Electric Box 3. Filters (not shown for clarity) 4. Evaporator Coil 5. Compressor Section 6. Infrared Humidifier (optional) 7. Disconnect (optional) 8. Condensate Pump (optional) 9. Smoke Sensor (optional) 10. EC Fans 11. Plenum (Front Discharge Shown) Liebert® DSE™ 4 8 6 9 2 DPN003010 Rev. 0 Liebert DSE Components and Nomenclature 1.1 Model Number Nomenclature - 25 Digit Configuration Number Model #** Part 1/2 Model Details 1 2 3 4 5 6 7 8 9 10 11 12 13 D A 1 2 5 D A 1 A T H A 0 Digits 1-2 - Product Family DA = Liebert DSE Digits 3-5 - Cooling Capacity, kW Nominal Sensible Capacity, kW Digit 6 - Air Discharge D = Downflow U = Upflow Digit 7 - System Type A = Air-Cooled P = Air-Cooled, Econ-O-Phase Ready Digit 8 - Airflow (Fan Type) 1 = EC Plug Fans Digit 9 - Power Supply A = 460V / 3ph / 60Hz B = 575V / 3ph / 60Hz C = 208V / 3ph / 60Hz D = 230 / 3ph / 60Hz 2 = 380-415 / 3ph / 60Hz Digit 10 - Cooling System D = Digital Scroll, R-410A T = Tandem with Digital, R-410A Digit 11 - Humidification 0 = None H = Infrared Humidifier Digit 12 - Display D = Liebert iCOM Control with Large Display E = Liebert iCOM Control with Large Display with Supply Air Sensor Digit 13 - Reheat 0 = None 1 = Electric Reheat, 30kW Digit 14 - Air Filter 8 = MERV 8, 4" 9 = MERV 11, 4" A = MERV 13, 4" 6 = MERV 11, 2" plus MERV 8 prefilter, 2" C = MERV 13, 2" plus MERV 8 prefilter, 2" Digit 15 - Coil Options 1 = Non-Coated Coil, Indoor Unit 2 = Coated Coil, Indoor Unit Digit 16 - Enclosure Options 1 = Color standard 2 = Color Optional 6 = Color Standard W/Double-Skin Panels 9 = Color Optional W/Double-Skin Panels Model # Part 2 * 14 15 16 17 18 19 20 21 22 23 24 25 8 1 1 D 0 0 S P 1 2 3 S Digit 17 - High-Voltage Options 0 = No disconnect D = Non-Locking Disconnect L = Locking Disconnect 3 = No Disconnect, With Condensate Pump 4 = Non-Locking Disconnect, With Condensate Pump 5 = Locking Disconnect, With Condensate Pump Digit 18 - Option Packages 0 = None L = Option Package #1 - Low Voltage Terminal Package H = Reheat and Humidifier Lockout R = Remote Humidity Contact C = Option Package #1, Plus Reheat/Humidifier Lockout D = Option Package #1, Plus Remote Humidifier Contact E = Option Package #1, Plus Reheat/Humidifier Lockout, plus remote contact F = Remote Humidity Contact Plus Reheat/Humidifier Lockout Digit 19 - Monitoring Cards 0 = No Cards 1 = IS-WEBL Card 3 = IS-485L Card F = IS-IPBML Card C = IS-485EXI Card 5 = IS-WEBL & IS-485L Cards H = IS-WEBL & IS-IPBML Cards D = IS-WEBL & IS-485EXI Cards J = IS-485L & IS-IPBML Cards E = IS-485L & IS-485EXI Cards K = IS-IPBML & IS-485EXI Cards Digit 20 - Sensors 0 = None S = Smoke Sensor H = High-Temperature Sensor F = Smoke and High-Temperature Sensors C = Compressor Overload Sensors A = Compressor, High-Temperature Sensor D = Compressor, Smoke Sensor K = Compressor, High-Temperature, Smoke Sensors Digit 21 - Packaging P = Domestic Digit 22 - 24 Configuration Code — Digit 25 - Configuration Code A=1 S = SFA 3 = Color Standard & IBC/OSHPD Bracing 4 = Color Optional & IBC/OSHPD Bracing 8 = Color Standard, IBC/OSHPD, W/Double-Skin Panels A = Color Optional, IBC/OSHPD, W/Double-Skin Panels * The 14-digit model number consists of the first 10 digits and last four digits of the Configuration Number. 3 Liebert® DSE™ Air-Cooled Performance Data 2.0 AIR-COOLED PERFORMANCE DATA Table 1 Capacity data with and EC fans Model Size 80 85 125 150 Total, kW (BTUH) 88 (300) 100 (341) 146 (499) 170 (581) Sensible, kW (BTUH) Net Capacity Data kW (kBTUH) 95°F DB, 67.7°F WB, 52.3°F DP (35°C DB, 19.8.°C WB) 24% RH 84 (287) 94 (321) 146 (499) 170 (581) Net Full-Load SCOP (kW/kW) @ 95 Outdoor Ambient (Compressor Mode) 3.2 3.1 3.8 3.2 Net Full-Load SCOP (kW/kW) @ 35 Outdoor Ambient (Pump Mode) 10.5 10.1 17.5 13.0 90°F DB, 66.1°F WB, 52.3°F DP (32.2°C DB, 18.9°C WB) 28% RH Total, kW (BTUH) 86 (294) 98 (334) 138 (471) 162 (552) Sensible, kW (BTUH) 80 (273) 88 (300) 138 (471) 162 (552) Net Full-Load SCOP (kW/kW) @ 95 Outdoor Ambient (Compressor Mode) 3.1 3.0 3.6 3.1 Net Full-Load SCOP (kW/kW) @ 35 Outdoor Ambient (Pump Mode) 9.8 9.4 14.1 12.5 Total, kW (BTUH) 85 (290) 92 (314) 130 (444) 153 (522) Sensible, kW (BTUH) 77 (263) 83 (283) 130 (444) 153 (522) Net Full-Load SCOP (kW/kW) @ 95 Outdoor Ambient (Compressor Mode) 3.0 2.7 3.4 2.9 Net Full-Load SCOP (kW/kW) @ 35 Odor Ambient (Pump Mode) 9.1 8.7 12.2 12.0 Total, kW (BTUH) 83 (283) 89 (304) 123 (420) 145 (494) Sensible, kW (BTUH) 72 (246) 78 (266) 123 (420) 145 (494) Net Full-Load SCOP (kW/kW) @ 95 Outdoor Ambient (Compressor Mode) 2.8 2.6 3.3 2.7 Net Full-Load SCOP (kW/kW) @ 35 Odor Ambient (Pump Mode) 8.2 7.9 11.5 11.1 Total, kW (BTUH) 75 (256) 86 (294) 116 (396) 134 (457) Sensible, kW (BTUH) 85°F DB, 64.5°F WB, 52.3°FDP (29.4°C DB, 18.1°C WB) 32% RH 80°F DB, 62.8°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38% RH 75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45% RH 67 (229) 73 (249) 112 (382) 134 (457) Net Full-Load SCOP (kW/kW) @ 95 Outdoor Ambient (Compressor Mode) 2.6 2.4 3.0 2.4 Net Full-Load SCOP (kW/kW) @ 35 Outdoor Ambient (Pump Mode) 7.5 7.2 10.7 10.2 9,600 (16,310) 10,400 (17,670) 18,000 (30,582) 18,000 (30,582) 4.6 5.7 5.9 5.9 2 2 3 3 FAN SECTION - Downflow models Standard Air Volume - CFM (CMH) 0.2" external static Operating Fan kW, Total for All Fans Quantity of Fans 1. Capacity data is rated and factory certified per ASHRAE 127-2007 with a 5% tolerance 2. Some options or combinations of options may result in reduced air flow—consult factory for recommendations. Liebert® DSE™ 4 Air-Cooled Performance Data Table 2 Physical data—Air-cooled units Model Size 80 85 125 150 24.65 (2.3) 24.65 (2.3) 56.2 (5.2) 56.2 (5.2) 6 6 6 6 389.5 (2.0) 421.9 (2.2) 320.3 (1.6) 320.3 (1.6) EVAPORATOR COIL- A-Frame - Copper Tube/Aluminum Fin Face Area, sq. ft. (sq. m) Rows of Coil Face Velocity, FPM (m/s), STD Air Vol. REHEAT SECTION Electric - Three (3) Stage, Stainless Steel Fin Tubular, capacity does not include fan motor heat Capacity,- kW (KBTUH) - Std Selection 15 (51.20) 15 (51.20) 30 (102.4) 30.0 (102.4) Capacity, kW (KBTUH) - Opt Selection 10 (34.13) 10 (34.13) 10.0 (34.1) 10.0 (34.1) 22 (10) 22 (10) 22 (10) 22 (10) 25 x 20 25 x 20 21.5 x 24 21.5 x 24 4 4 10 10 7/8" 7/8" 7/8" 1-1/8" above 50ft. 1-1/8" 1-1/8" 1-3/8" 1-3/8" Infrared Humidifier,O.D. Copper 1/4" 1/4" 1/4" 1/4" Condensate Drain, FPT 3/4" 3/4" 1-1/8" 1-1/8" Condensate Drain w/opt Condensate Pump, OD 1/2" 1/2" 1/2 1/2 HUMIDIFIER SECTION Infrared Humidifier Capacity, lb./hr. (kg/h) FILTER SECTION - Disposable Type - Nominal Sizes and Quantities Nominal Size, inches Quantity Line Sizes Liquid Line, O.D. Copper (2/unit), up to 300 eq ft Hot Gas Line, O.D. Copper (2/unit), up to 300 eq ft. Table 3 Unit Voltage Rating 208V 230V 380V 460V 575V Electrical data - DA080 Reheat Options Electric, Std kW None Electric, Std kW None Humidifier Options Infrared Infrared None None FLA 119.2 119.2 97.1 92.6 WSA 128.5 128.5 116.8 101.9 OPD 150 150 125 125 FLA 114.8 114.8 94.6 92.6 WSA 124.1 124.1 113.7 101.9 OPD 150 150 125 125 FLA 74.8 74.8 62.6 62.6 WSA 81.4 81.4 69.2 69.2 OPD 100 100 90 90 FLA 59.6 59.6 48.0 48.0 WSA 64.6 64.6 57.6 53.0 OPD 80 80 70 70 FLA 46.6 46.6 35.8 35.0 WSA 50.2 50.2 43.2 38.6 OPD 60 60 50 50 5 Liebert® DSE™ Air-Cooled Performance Data Table 4 Unit Voltage Rating 208V 230V 380V 460V 575V Table 5 Unit Voltage Rating 208V 230V 380V * 460V 575V Electrical data - DA085 Reheat Options Electric, Std. kW None Electric, Std. kW None Humidifier Options Infrared Infrared None None FLA 152.2 152.2 125.6 125.6 WSA 165.6 165.6 139.0 139.0 OPD 200 200 175 175 FLA 147.8 147.8 125.6 125.6 WSA 161.2 161.2 139.0 139 OPD 200 200 175 175 FLA 74.8 74.8 62.6 62.6 WSA 81.4 81.4 69.2 69.2 OPD 100 100 90 90 FLA 61.0 61 49.4 49.4 WSA 66.2 66.175 58.5 54.575 OPD 80 80 70 70 FLA 50.8 50.8 39.2 39.2 WSA 54.9 54.9 45.775 43.3 OPD 70 70 50 50 Electrical data—DA125 Reheat Options Electric Std. kW None Electric Std. kW None Humidifier Options Infrared Infrared None None FLA 174.6 174.6 165.7 148 WSA 193.2 193.2 193.2 155.7 OPD 200 200 200 175 FLA 170.2 170.2 165.2 148 WSA 192.5 192.5 192.5 155.7 OPD 200 200 200 175 FLA 93.6 93.6 88.1 81.4 WSA 102.7 102.7 102.7 85.7 OPD 110 110 100 100 FLA 79.9 79.9 78.8 68.3 WSA 92.2 83.5 92.2 71.9 OPD 100 90 100 80 FLA 63.4 63.4 60.5 51.8 WSA 70.7 66.1 70.7 54.5 OPD 80 70 80 60 * 380V version of DA125 is not CSA- listed Full-load amperage values do not reflect operating amperage values. Liebert® DSE™ 6 Air-Cooled Performance Data Table 6 Unit Voltage Rating 208V 230V 380V * 460V 575V Table 7 Electrical data - DA150 Reheat Options Electric Std. kW None Electric Std. kW None Humidifier Options Infrared Infrared None None FLA 200.2 200.2 182.2 173.6 WSA 209.5 209.5 207.6 182.9 OPD 225 225 225 200 FLA 195.8 195.8 181.9 173.6 WSA 206.9 205.1 206.9 182.9 OPD 225 225 225 200 FLA 130.4 130.4 118.2 118.2 WSA 137.0 137 128.1 124.8 OPD 150 150 150 150 FLA 102.7 102.7 93.7 91.1 WSA 107.7 107.7 104.3 96.1 OPD 125 125 110 110 FLA 77.8 77.8 69.3 66.2 WSA 81.4 81.4 77.2 69.8 OPD 90 90 80 80 Electrical data—Liebert MC™ three- and four-fan, three-phase condensers Model MCL110 MCM160 MCL165 MCL220 Input Voltage FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD 208/230 11.4 12.8 15 9.2 9.8 15 17.1 18.5 20 22.8 24.2 25 460 5.6 6.3 15 5.6 6.0 15 8.4 9.1 15 11.2 11.9 15 1. FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Maximum Overcurrent Protection Device. 2. Must be connected to Wye 3-phase systems with solidly grounded neutral. 3. Source: 306258, Rev. 1 Table 8 Liebert MC™ shipping dimensions and weights Weights, Approximate lb. (kg) Model # # of Fans Dimensions, L x W x H in. (mm) MCL110 2 124-1/8 x 55-5/8 x 43-5/8 (3152 x 1413 x 1108) 605 (273) MCL165 3 180-1/4 x 55-5/8 x 43-5/8 (4578 x 1413 x 1108) 890 (404) MCL220 4 236-3/8 x 55-5/8 x 43-5/8 (6003 x 1413 x 1108) 1185 (538) MCM160 4 256 x 36 x 63 (650 x 91 x 160) 1425 (646) 7 Liebert® DSE™ Dimensions and Equipment Layout 3.0 DIMENSIONS AND EQUIPMENT LAYOUT Figure 3 Cabinet and floor planning dimensions—downflow, air-cooled, DA080, DA085, scroll and digital scroll compressor models Secondary Refrigerant Piping Entrance 80" (2032mm) Opening 33" (838mm) 35" (889mm) 24-5/8" (625mm) Opening AIR INLET OPENING Notes: Filters are accessible through top of unit only. Downflow electrical connections can be made from top or bottom of unit. 3/4" (19mm) Bezels Secondary Entrance High Volt Connection(s) TOP VIEW Secondary Entrance Low Volt Connections Minimum required for filter replacement "A" 5" (127mm) 76" (1930mm) 2" (51mm) Shaded area indicates a recommended minimum clearance for component access "B" DPN000925 Rev. 2 FRONT VIEW Model No. DA080 DA085 Air-Cooled 2200 (998) 2250 (1021) Dual-Cool N/A N/A Air-Cooled “A” 100 (2540) 100 (2540) Air Cooled “B” 99 (2515) 99 (2515) Weights, lb. (kg) Dimensions, in. (mm) Source: DPN000925, Rev. 2 Liebert® DSE™ 34" (864mm) 8 Dimensions and Equipment Layout Figure 4 Cabinet and floor planning dimensions—upflow, air-cooled, DA080U, DA085U, scroll and digital scroll compressor models Alternate Refrigerant Piping Entrance 33" (838mm) 35" (883mm) High-Voltage Connection(s) 3-1/4" (81mm) 3/4" (19mm) Bezels TOP VIEW Minimum required for blower replacement Low-Voltage Connection(s) 100" (2539mm) 24" (610mm) 76" (1929mm) 2" (50mm) 34" (864mm) 99" (2517mm) Shaded area indicates a recommended minimum clearance for component access FRONT VIEW Front air return unit shown. For rear return unit, in addition to front service area shown, also include 25" (635mm) on one side of unit for access to rear APPROXIMATE DRY WEIGHT, lb (kg) return filter box. See DPN001196. DA080U - DA085U: 2150 (977) 9 DPN002950 Rev. 0 Liebert® DSE™ Dimensions and Equipment Layout Figure 5 Cabinet and floor planning dimensions—downflow, air-cooled, DA125 and DA150, tandem scroll compressor models Filter Plenum (shipped separately) Filters are removed though the front of the plenum Secondary Refrigerant Piping Entrance 117-11/16" Opening (2989mm) 47" (1194mm) 48" (1219mm) 42" (1067mm) Opening 45" (1143mm) 3/4" (19mm) Bezels TOP VIEW Striated area indicates the recommended minmum clearance for component access. 24" (610mm) Shaded area indicates the required minimum clearance below the unit to lower the fans into the floor. Fans may remain in their shipped position. 144" (3658mm) 18" (457mm) 45" (1143mm) Plenum 94" (2388mm) Total Height 76" (1930mm) Base Unit 142" (3607mm) FRONT VIEW Dry Weights DA125: 3465lb (1572kg) DA150: 3565 (1617kg) Liebert® DSE™ 1" (25mm) Typical 10 45" (1143mm) 47" (1194mm) DPN002311 Rev. 2 Dimensions and Equipment Layout 3.1 Floor Stand Dimensions Figure 6 Floor stand and floor planning dimensions, DA080, DA085 A B Piping Access Area 3/4" (19mm) 32" (813mm) Center Feet 31-1/2" (800mm) C Support Feet Centers 3/4" (19mm) 32-3/4" (832mm) D 3/4" (19mm) 7/8" (23mm) See Note 4 3" (76mm) 33" (838mm) 1" (25mm) E 1. This floor stand should be used when EC fans are intended to be lowered under a raised floor. The standard Liebert DS floor stand can be used if the fans are to remain in their original raised position. 2. Right side of paneled unit is flush with right side of floorstand. All other paneled sides overhang floor stand 1" (25mm). 3) The floor stand used with EC units is not symmetrical and its orientation to the Liebert DSE is critical for lowering the EC fans. Unless the floor stand is installed in the correct position, the blowers will not lower into the floor stand. 4. Jack and jack support are shipped loose and are intended to be placed into position under each fan and utilized to lower or raise that fan as needed. F* 35" (889mm) Overall Depth DPN002151 Rev. 1 * Leveling feet are provided with ±1-1/2" (38mm) adjustment from nominal height C. Dimensions, In. (mm) Model # A B C D E DA080, DA085 Air-Cooled Digital Scroll Models 99 (2515) 17 (432) 97.5 (2477) 99 (2515) 100.5 (2553) Height, F In. (mm) 24 (610) 30 (762) 36 (914) 42 (1067) Source: DPN002151, Rev. 1 48 (1219) 11 Liebert® DSE™ Dimensions and Equipment Layout Figure 7 Floor stand dimensions—downflow, DA125 and DA150 models C + 1-1/2" (38mm) (with feet) C D 46-1/2" (1181mm) With Feet Typ 43-1/2" (1105mm) Center Feet Typ 43" (1092mm) 59-1/4" Center Feet (1505mm) 118-1/2" Center Feet (3010mm) 120-3/4" Center Feet (3067mm) 1" (25mm) Typical 45" (1143mm) Typical 3/4" (19mm) Typical A* 7/8" (23mm) Typical 47" (1194mm) Typical 3" (76mm) Typical 1. This floor stand should be used when EC fans are intended to be lowered into the floor stand. The standard Liebert floor stand can be used if the fans are to remain in their original raised position. 2. All paneled sides of unit overhang floor stand 1" (25mm). 3. The floor stand used with EC units is not symmetrical and proper orientation required for lowering the blowers. Unless the floor stand is installed in the correct position, the blowers will not lower into the floor stand. 4) Jack and jack support are shipped loose and are intended to be placed into position under each fan and used to lower or raise that fan as needed individually. 5) Jack to lower blowers not provided with 18" floor stand. * Leveling feet are provided with ±1-1/2” (38mm) adjustment from nominal height A. Height, in. (mm) A* B* 24 (610) — 30 (762) — 36 (914) 5 (127) 42 (1067) 11 (279) 48 (1219) 17 (432) Dimensions, in. (mm) C D Air-Cooled 142 (3607) 21 (533) Water/Glycol Cooled 164" (4166mm) 43" (1092mm) Source: DPN002315, Rev. 2 Liebert® DSE™ 12 B DPN002315 Rev. 2 Piping Schematics 4.0 PIPING SCHEMATICS Figure 8 Primary connection locations—downflow, air-cooled DA080 and DA085, scroll compressor models NOTE: Drawing not to scale. Tolerance on all piping dimensions is ±1/2" (13mm). All dimensions from rear corner of unit including panels A A FRONT VIEW SECTION A-A X O Y R 5" (127mm) BLOWER OUTLET L1 L2 G1 G2 35" (889mm) 15" (379mm) ECS ECR B1 E1 E2 HUM LV1 LV2 LV3 FRONT OF UNIT 100" (2540mm) DPN002182 Rev. 2 Point Description X, in. (mm) Y, in. (mm) Connection Size / Opening in. (mm) R Refrigerant Access 81-3/4 (2076) 14-3/4 (374) 12-3/16 x4 (310 x 102) R Refrigerant Access 82-7/8 (2105) 13-11/1 (348) 15 x 5 (379 x127) L1 Liquid Line System 1 94-11/16 (2405) 16-3/4 (425) 1/2" / 5/8" Cu Sweat L2 Liquid Line System 2 91-7/8 (2334) 16-3/4 (425) 1/2" / 5/8" Cu Sweat G1 Hot Gas Discharge 1 88-3/4 (2254) 16-3/8 (416) 7/8" / 1-1/8" Cu Sweat G2 Hot Gas Discharge 2 85-9/16 (2173) 16-3/8 (416) 7/8" / 1-1/8" Cu Sweat CD Condensate Drain (Infrared Humidifier or No Humidifier) * 68-3/8 (1737) 31-3/8 (797) 3/4" FPT W/ Optional Pump 68-3/8 (1737) 31-3/8 (797) 1/2" Cu Sweat Hum Humidifier Supply Line 76-1/2 (1943) 29 (736) 1/4" Cu Sweat HS Hot Water Reheat Supply Consult Factory HR Hot Water Reheat Return Consult Factory E1 Electrical Connection (High-Voltage) 78-1/2 (1994) 31-1/8 (790) 2-1/2" E2 Electrical Connection (High-Voltage) 75-3/8 (1915) 31-1/8 (790) 2-1/2" LV1 Electrical Connection (Low-Voltage) 2 (51) 29 (737) 7/8" LV2 Electrical Connection (Low-Voltage) 2 (51) 30-7/8 (784) 7/8" LV3 Electrical Connection (Low-Voltage) 2 (51) 32 (813) 7/8" B1 Blower Outlet 4-1/2 (114) 33 (838) 58-3/8 x 30 (1483 x 762) * Field pitch Condensate Drain line a minimum of 1/8" (3.2mm) per foot (305mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water; select appropriate drain system materials. The drain line must comply with all local codes. Source: DPN002182, Rev. 2 13 Liebert® DSE™ Piping Schematics Figure 9 Primary connection locations—downflow, air-cooled, DA125, scroll compressor models A A FRONT VIEW NOTE: Drawing not to scale. Tolerance on all piping dimensions is ±1/2" (13mm). All dimensions from rear corner of unit including panels SECTION A-A X O 3-3/8" (86mm) G1 G2 L1 L2 R Y 19" (483mm) 41" (1041mm) Typical AIR DISCHARGE AREA CD 47" (1193mm) 29-5/16" (744mm) Typical AIR DISCHARGE AREA LV1 LV2 LV3 E1 E2 HUM B FRONT EDGE OF UNIT 144" (3657mm) * Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. DPN002312 Opening for conduit chase, E1 and E2 are openings for conduit for connections to 2-1/2", 1-3/4" and Pg. 1, Rev. 4 1-3/8" knockouts at electric panel DX Only Point Description DX with Liebert EconoPhase™ X inches (mm) Y inches (mm) Connection Size/ Opening, inches (mm) 19 x 3-3/8 (483 x 86) 19 x 3-3/8 (483 x 86) R Refrigerant Access 122-5/16 (3106) 12-1/8 (333) L1 Liquid Line System 1 127-7/8 (3248) 13-3/4 (348) 7/8 Cu Sweat 7/8 Cu Sweat L2 Liquid Line System 2 124-13/16 (3170) 13-3/4 (348) 7/8 Cu Sweat 7/8 Cu Sweat G1 Hot Gas Discharge 1 140 (3554) 14 (355) 1-1/8 Cu Sweat 1-3/8 Cu Sweat G2 Hot Gas Discharge 2 136-11/16 (3471) 14 (355) 1-1/8 Cu Sweat 1-3/8 Cu Sweat 110 (2794) 35-1/16 (891) 1-1/8 FPT 1-1/8 FPT Condensate Drain * (infrared humidifier or no humidifier) CD Condensate Drain (steam generating humidifier) * W/ Optional Pump HUM Humidifier Supply Line Consult Factory 110 (2794) 35-1/16 (891) 1/2 Cu Sweat 1/2 Cu Sweat 101-1/4 (2572) 43 (1091) 1/4 Cu Sweat 1/4 Cu Sweat HS Hot Water Reheat Supply Consult Factory HR Hot Water Reheat Return Consult Factory E1 Electrical Connection (High-Voltage) 113 (2870) 42-1/2 (1080) 2-1/2 2-1/2 E2 Electrical Connection (High-Voltage) 110 (2794) 42-1/2 (1080) 2-1/2 2-1/2 LV1 Electrical Connection (Low-Voltage) 2-1/2 (64) 36 (914) 7/8 7/8 LV2 Electrical Connection (Low-Voltage) 2-1/2 (64) 37-1/2 (952) 7/8 7/8 LV3 Electrical Connection (Low-Voltage) 2-1/2 (64) 39 (991) 7/8 7/8 Blower Outlet 5-1/8 (131) 44 (1117) 93 x 41 (2362 x 1041) 93 x 41 (2362 x 1041) B Source: DPN002312, Rev. 4, Pg. 1 Liebert® DSE™ 14 Piping Schematics Figure 10 Primary connection locations—downflow, air-cooled, DA150, scroll compressor models A A All dimensions from rear corner of unit including panels X FRONT VIEW NOTE: Drawing not to scale. Tolerance on all piping dimensions is ±1/2" (13mm). SECTION A-A O 3-3/8" (86mm) L1 L2 G1 G2 R Y 19" (483mm) CD 41" (1041mm) Typical AIR DISCHARGE AREA 29-5/16" (744mm) Typical AIR DISCHARGE AREA 47" (1193mm) LV1 LV2 LV3 E1 E2 HUM B FRONT EDGE OF UNIT 144" (3657mm) * Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. DPN002312 Opening for conduit chase, E1 and E2 are openings for conduit for connections to 2-1/2", 1-3/4" and Pg. 2, Rev. 4 1-3/8" knockouts at electric panel DX Only Point Description DX with Liebert EconoPhase™ X inches (mm) Y inches (mm) Connection Size/ Opening, inches (mm) 19 x 3-3/8 (483 x 86) 19 x 3-3/8 (483 x 86) R Refrigerant Access 122-5/16 (3106) 12-1/8 (333) L1 Liquid Line System 1 140 (3554) 14 (355) 1-1/8 Cu Sweat 1-1/8 Cu Sweat L2 Liquid Line System 2 136-11/16 (3471) 14 (355) 1-1/8 Cu Sweat 1-1/8 Cu Sweat G1 Hot Gas Discharge 1 127-7/8 (3248) 13-3/4 (348) 1-3/8 Cu Sweat 1-3/8 Cu Sweat G2 Hot Gas Discharge 2 124-13/16 (3170) 13-3/4 (348) 1-3/8 Cu Sweat 1-3/8 Cu Sweat 110 (2794) 35-1/16 (891) 1-1/8 FPT 1-1/8 FPT Condensate Drain * (infrared humidifier or no humidifier) CD Condensate Drain (steam generating humidifier) * W/ Optional Pump HUM Humidifier Supply Line HS Consult Factory 110 (2794) 35-1/16 (891) 1/2 Cu Sweat 1/2 Cu Sweat 101-1/4 (2572) 43 (1091) 1/4 Cu Sweat 1/4 Cu Sweat Hot Water Reheat Supply Consult Factory HR Hot Water Reheat Return E1 Electrical Connection (High-Voltage) 113 (2870) 42-1/2 (1080) 2-1/2 2-1/2 E2 Electrical Connection (High-Voltage) 110 (2794) 42-1/2 (1080) 2-1/2 2-1/2 LV1 Electrical Connection (Low-Voltage) 2-1/2 (64) 36 (914) 7/8 7/8 LV2 Electrical Connection (Low-Voltage) 2-1/2 (64) 37-1/2 (952) 7/8 7/8 LV3 Electrical Connection (Low-Voltage) 2-1/2 (64) 39 (991) 7/8 7/8 5-1/8 (131) 44 (1117) 93 x 41 (2362 x 1041) 93 x 41 (2362 x 1041) B Blower Outlet Consult Factory Source: DPN002312, Rev. 4, Pg. 2 15 Liebert® DSE™ Piping Schematics Figure 11 Primary connection locations—upflow, DA080U and DA085U 15-7/16" (392mm) NOTES 1. Drawing not to scale. 2. Tolerance on all piping dimensions is ± 1/2" (13mm). 3. Field-routed alternatives for refrigerant gas and liquid line connection points. 4. See submittal page DPN002748 for plenum dimensions. 3. 35" (889mm) O X R1 4" (102mm) 5" (127mm) All dimensions from rear corner of unit including panels R2 HUM CPD L1L2G1G2 4. Y 14-15/16" (379mm) 3. LV1 LV2 LV3 E1 E2 6" (152mm) 100" (2540mm) TOP VIEW Front of Unit R3 17-3/16" (437mm) 3 CGD* 14-1/4" (362mm) 3-7/8" (98mm) 14-1/8" (359mm) 15-7/8" (403mm) L1L2G1G2 Factory Location Left Side Section View of Unit Front Section View of Unit (Left Front Panel Not Shown) CGD* * Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. Point R1 Description 3 Refrigerant Access (Top) R2 3 Refrigerant Access (Bottom) R3 3 Refrigerant Access (Side) L1 X inches (mm) Y inches (mm) DPN002951 Rev. 0 Connection Size/ Opening, inches (mm) 83-5/8 (2124) 1-7/8 (48) 15-7/16 x 4 (392 x 102) 82-15/16 (2106) 13-5/8 (346) 14-15/16 x 5 (379 x 127) — — 6 x 17-3/16 (152 x 437) Liquid Line System 1 94-9/16 (2402) 16-3/4 (425) 5/8 Cu Sweat L2 Liquid Line System 2 91-7/8 (2334) 16-3/4 (425) 5/8 Cu Sweat G1 Hot Gas Discharge 1 88-7/8 (2257) 16-7/16 (418) 1-1/8 Cu Sweat G2 Hot Gas Discharge 2 85-5/8 (2175) 16-7/16 (418) 1-1/8 Cu Sweat — — 3/4 FPT CGD Condensate Gravity Drain CPD Condensate Pump Discharge (Optional) 79-5/16 (2015) 11-7/8 (302) 1/2 Cu Sweat HUM Humidifier Supply Line 79-5/16 (2015) 9-7/8 (251 1/4 Cu Sweat E1 Electrical Connection (High Voltage) 78-1/8 (1984) 30 (762) 2-1/2 E2 Electrical Connection (High Voltage) 74-3/8 (1889) 30 (762) 2-1/2 LV1 Electrical Connection (Low Voltage) 2-5/8 (66) 28-9/16 (726 7/8 LV2 Electrical Connection (Low Voltage) 2-5/8 (66) 30 (762) 7/8 LV3 Electrical Connection (Low Voltage) 2-5/8 (66) 31-7/16 (799) 7/8 Source: DPN002951, Rev. 0 Liebert® DSE™ 16 Piping Schematics Figure 12 Piping schematic—air-cooled, tandem compressor models, DA0805, DA085 Optional Liebert EconoPhase Unit Differential Check Valve 1-3/8" Liquid from Condenser See Note 2 LIEBERT MC CONDENSER Check Valve 7/8" Liquid to Indoor Unit See Note 2 LIEBERT DSE RECEIVER Ball Valve Includes Factory traps. No external trap required Differential Check Valve HOT GAS DISCHARGE DA080 and DA085 Solenoid Valve Ball Valve 1-1/8" Hot Gas Discharge from Indoor Unit See Note 2 LIQUID EVAPORATOR COIL Service Valve For rises over 25ft. (7.6m), trap every 20ft. (6m) or evenly divided* SUCTION Field-installed relief valves required for 50Hz EU CE units rated maximum 650PSIG (45bar) Check Valve Trap at base of risers over 5ft. (1.5m)* *Full Ported Ball Valve See Note 4 Service Valve Check Valve HOT GAS DISCHARGE See Note 2 LIQUID RETURN See Note 2 Electronic Expansion Valve *Full Ported Ball Valve See Note 4 Differential Check Valve (Required) REFRIGERANT PIPING * Components are not supplied by Liebert but are required for FIELD PIPING proper circuit operation and SERVICE/SCHRADER (ACCESS) CONNECTION, NO VALVE CORE maintenance. SERVICE/SCHRADER (ACCESS) CONNECTION, WITH VALVE CORE 1. Two refrigeration circuits provided. Single refrigeration circuit shown for clarity. 2. Circuit 1 must be maintained between indoor unit, condenser and Liebert EconoPhase unit. Circuit 2 must be maintained between indoor unit, condenser and Liebert EconoPhase unit. 3. Schematic representation shown. Do not use for specific connection locations. 4. Port in ball must be the same diameter as the piping I.D. 5. Length of piping between condenser and indoor unit shall be no greater than 300 ft (91.4 m) (Maximum equivalent length of 450 ft [137.2 m]). 6. Vertical height of condenser above indoor unit must be no greater than 60ft (18.3m). 7. All indoor and outdoor field refrigerant piping must be insulated, 1/2" minimum thickness. All outdoor insulation must be UV- and ozone-resistant. 17 DPN002615 Rev. 4 Liebert® DSE™ Piping Schematics Figure 13 Piping schematic—air-cooled, tandem compressor models, DA125 and DA150 Liebert DSE Receiver Ball Valve Includes Factory Traps No External Trap Required DA125: 7/8" DA150: 7/8" or 1-1/8" Liquid to Indoor Unit Depending on length of line See Note 2 Check Valve 1-3/8" Liquid Line from Condenser See Note 2. Liebert MC Condenser Differential Check Valve Optional EconoPhase Unit Differential Check Valve 1-3/8" Hot Gas Discharge from Indoor Unit See Note 2. Hot Gas Discharge DA125 and DA150 Solenoid Ball Valve Valve Liquid Evaporator Coil Service Valve For rises over 25ft. (7.6m), trap every 20ft. (6m) or evenly divided Suction Field-installed relief valves required for 50Hz EU CE units rated maximum 650 PSIG (45 Bar) Check Valve * Trap at Base of Risers Over 5ft. (1.5m) *Full Ported Ball Valve See Note 4. Service Valve Check Valve Hot Gas Discharge See Note 2. Liquid Return See Note 2. Electronic Expansion Valve Refrigerant Piping Field Piping Service/Schrader (Access) Connection, No Valve Core Service/Schrader (Access) Connection, With Valve Core 18 Differential Check Valve (Required) * Components are not supplied by Emerson but are required for proper circuit operation and maintenance. 1. Two refrigeration circuits provided. Single refrigeration circuit shown for clarity. 2. Circuit 1 must be maintained between indoor unit, condenser and EconoPhase unit. Circuit 2 must be maintained between indoor unit, condenser and EconoPhase unit. 3. Schematic representation shown. Do not use for specific connection locations. 4. Port in ball must be the same diameter as the piping I.D. 5. Length of piping between condenser and indoor unit must be no greater than 300 ft (91.4 m) [Maximum equivalent length of 450 ft (137.2 m)]. 6. Vertical height of condenser above indoor unit shall be no greater than 60ft (18.3m). 7. All indoor and outdoor field refrigerant piping must be insulated, 1/2" minimum thickness. All outdoor insulation must be UV- and ozone-resistant Liebert® DSE™ *Full Ported Ball Valve See Note 4. DPN002340 Rev. 7 Condensers—Dimensions 5.0 CONDENSERS—DIMENSIONS Figure 14 Cabinet and anchor dimensions, MCM040, MCM080, MCM160 Emerson recommends a clearance of 36" (915mm) on each side for proper operation and component access Height to Top of Fan Guard Eyebolts for Lifting Condenser Provided on Four-Fan Models H G A* A B F 575V Transformer Enclosure Option 13/16" (21mm) 2-1/2" (64mm) C 1-7/8" (48mm) 2-1/2" (64mm) 46" (1168mm) 3-5/8" (93mm) 1/2" x 1" 12.7mm x 25.4mm) Obround 1-7/8" (48mm) TYPICAL FOOTPRINT ANCHOR PLAN E Electric Box End D Provided On Four-Fan-models 39-5/16" 999mm) 44-3/8" (1127mm) DPN002172 Rev. 5 A Liebert No. Model No. Fans in. (mm) A* (575V) in. (mm) B C D E in. (mm) in. (mm) in. (mm) in. (mm) Leg Height F1 in. (mm) G H in. (mm) in. (mm) MCM040 1 57-3/16 (1453) 65 3/8 (1661) -- 48 (1219) 46-5/16 (1177) -- 18 (457) 31-5/8 (803) 39-5/8 (1006) MCM080 2 105-1/4 (2674) 113-7/16 (2882) -- 96-1/16 (2440) 94-7/16 (2398) -- 36 (914) 49-5/8 (1260) 57-5/8 (1464) MCM160 4 202-7/16 (5142) 210-5/8 (5350) 113-1/2 (2883) 192-1/4 (4883) 94-7/16 (2398) 96-3/16 (2444) 48 (1219) 61-5/8 (1565) 69-5/8 (1768) 60 (1524) 73-5/8 (1870) 81-5/8 (2073) 1. Cross-bracing required for legs longer than 18" (457mm). Quantity varies according to the model and options selected. 2. Source: DPN002172, Rev. 5 19 Liebert® DSE™ Condensers—Dimensions Figure 15 Liebert MC™ cabinet and anchor dimensions, MCL110, MCL165 and MCL220 Height to Top of Fan Guard Emerson recommends a clearance of 36" (915mm) on each side for proper operation and component access Eyebolts for Lifting Condenser Provided on 3&4 Fan Models H G A* A B F 575V Transformer Enclosure Option 13/16" (21mm) 3-5/8" (93mm) 2-1/2" (64mm) C 1-7/8" (48mm) 2-1/2" (64mm) 1/2"x1" (12.7mm x 25.4mm) Obround 3-5/8" (93mm) 55-1/2" (1409mm 1-7/8" (48mm) TYPICAL FOOTPRINT ANCHOR PLAN E Electric Box End D Provided on 3- and 4-Fan Models 53-7/8" (1368mm) 48-3/4" (1238mm) DPN002416 Rev. 4 Table 9 Cabinet and anchor dimensions, MCL110, MCL165 and MCL220 Dimensions, In. (mm) Liebert Model # # of Fans MCL055 A A* (575V) 1 68 (1727 MCL110 2 MCL165 MCL220 Leg Height F1 G H B C D E 76-1/8 (1935) — 56 (1423) 54-3/8 (1381) — 18 (457) 35-7/8 (911) 43-5/8 (1108) 124-1/8 (3152) 132-1/4 (3360) — 112-1/8 (2848) 110-1/2 (2806) — 36 (914) 53- 7/8 (1368) 61-5/8 (1565) 3 180-1/4 (4578) 188-3/8 (4786) 73-7/16 (1866) 168-1/4 (4274) 110-1/2 (2806) 56-1/8 (1425) 48 (1219) 65-7/8 (1673) 73-5/8 (1870) 4 236-5/16 (6003) 244-1/4 (6211) 129-9/16 (3291) 224-3/8 (5699) 110-1/2 (2806) 112-1/4 (2851) 60 (1524) 77-7/8 (1978) 85-5/8 (2175) 1. *Cross-bracing required for legs longer than 18" (457mm). Quantity varies per model and options selected. 2. Source: DPN002416, Rev. 4 Liebert® DSE™ 20 Condensers—Dimensions Figure 16 Typical receiver mounting MCL110, MCL165, MCL220 units, left-side mounting outlet receiver Receiver Mounting Holes Single Circuit DETAIL A Typically 4 Places 4, 3, 2 Trim piping as needed 1 16 15 3 A 1 7 13 12 14 2 8 11.13" (282.6mm) 3 Notes 64.3" (1383.1mm) 36" (914.4mm) Clearance required for viewing sight glass Cross-Bracing Not Shown 1. Use Items 15 and 16 as needed for mounting Item 1. 2. Item 12 to be used on MCL165 units. Item 13 to be used on MCL220 units. 3. Small receiver shown. Actual receiver DPN002554 Pg. 1, Rev. 4 size may vary. 1 Receiver and Bracket Assembly 1 2 Cap Screw HXDIN933M8-1.25x25A2 8 3 Fender Washer DIN9021 M8x24 A2 12 4 Lock Nut, Hex Nylon Insert, M8 8 7 90-degree Elbow FTGXC 7/8" Copper 1 8 Copper Formed Tube 1-1/8" 1 12 Coupling, Copper 1-1/8" 1 13 Reducer, Copper CXC 1-3/8"x1-1/8" 1 14 Reducer, Copper CXC 1-1/8"x7/8" 1 15 Support Leg 1 16 Fastener Assembly: Cap Screw, Lock Washer, Fender Washer 4 Source: DPN002554, Page 1, Rev. 4 21 Liebert® DSE™ Condensers—Dimensions Figure 17 Typical receiver mounting MCL110, MCL165, MCL220 units, right-side mounting outlet receiver Receiver Mounting Holes Single Circuit Trim piping as needed 12 13 2 DETAIL B Typ. 4 Places 4, 3, 2 8 B 7 15 16 1 14 9 1 3 5 6 11.13" (282.6mm) 3 64.3" (1383.1mm) 36" (914.4mm) Clearance required for viewing sight glass Cross-Bracing Not Shown Notes 1. Use Items 15 and 16 as needed for mounting Item 1. 2. Item 12 to be used on MCL165 units. Item 13 to be used on MCL220 units. 3. Small receiver shown. Actual receiver size may vary. DPN002554 Pg. 2, Rev. 4 Item # Description Quantity 1 2 3 4 5 6 7 8 9 12 13 14 15 16 Receiver and Bracket Assembly Cap Screw HXDIN933M8-1.25x25A2 Fender Washer DIN9021 M8x24 A2 Lock Nut, Hex, Nylon Insert, M8 Clamp Omega 1-1/8" Screw, Self-Drilling, HWH YZ 10-16 x 5/8 90-degree Elbow FTGXFTG 7/8" Copper Copper Formed Tube 1-1/8" Copper Formed Tube 1-1/8" Coupling, Copper 1-1/8" Reducer, Copper CXC 1-3/8"x1-1/8" Reducer, Copper CXC 1-1/8"x7/8" Support Leg Fastener Assembly: Cap Screw, Lock Washer, Fender Washer 1 8 12 8 7 2 1 1 2 1 1 2 1 4 Source: DPN002554, Page 2, Rev. 4 Liebert® DSE™ 22 Condensers—Dimensions Figure 18 Required receiver mounting MCM160 units, left-side mounting outlet receiver Receiver mounting holes Single circuit DETAIL A Typically 4 Places 2 34 15 16 1 1 A 7 Trim piping as needed 8 11.23" (285.3mm) 1 1. Small receiver shown. Actual receiver size may vary 36" (914.4mm) Clearance required for viewing sight glass 54.45" (1383.1mm) Cross Bracing Not Shown DPN002383 Pg. 1, Rev. 5 Item # Description Quantity 1 Receiver and Bracket Assembly 1 2 Cap Screw HXDIN933M8-1.25x25A2 8 3 Fender Washer DIN9021 M8x24 A2 12 4 Lock Nut, Hex Nylon Insert, M8 8 7 90-degree Elbow FTGXC 7/8" Copper 2 8 Copper Formed Tube 7/8" 1 15 Support Leg 1 16 Fastener Assembly: Cap Screw, Lock Washer, Fender Washer 4 Source: DPN002383, Page 1, Rev. 5 23 Liebert® DSE™ Condensers—Dimensions Figure 19 Required receiver mounting MCM160 units, right-side mounting outlet receiver Receiver Mounting Holes Single circuit DETAIL A Trim Piping As Needed 8 A 3 Typically 4 Places 24 15 16 7 56 9 1 1 11.23" (285.3mm) 1 54.49" (1384.1mm) 36" (914.4mm) Clearance required for viewing sight glass Cross Bracing Not Shown 1. Small receiver shown. Actual receiver size may vary DPN002383 Pg. 2, Rev. 5 Item # Description 1 Receiver and Bracket Assembly 1 2 Cap Screw HXDIN933M8-1.25x25A22 8 3 Fender Washer DIN9021 M8x24 A2 12 4 Lock Nut, Hex Nylon Insert, M8 8 5 Clamp Omega 7/8" 1 6 Screw, Self-Drilling, HWH YZ 10-16 x 5/8 2 7 90-degree Elbow FTGXC 7/8" Copper 1 8 Copper Formed Tube 7/8" 1 9 Copper Formed Tube 7/8" 1 15 Support Leg 1 16 Fastener assembly: Cap Screw, Lock Washer, Fender Washer 4 Source: DPN002383, Page 2, Rev. 5 Liebert® DSE™ Quantity 24 Plenum Dimensions 6.0 PLENUM DIMENSIONS Figure 20 Plenum dimensions—downflow, DA080 and DA085, air-cooled digital scroll models 80-1/2" (2045mm) Return air inlet opening Height, in. (mm) 32-1/8" (816mm) Opening 7/8" (22mm) Typical H 20 (508) 24 (610) 36 (914) 34" (864mm) 82-1/4" (2089mm) Plenum Hinged door for filter access 12" (305mm) 1" (25mm) H 76" (1930mm) Liebert DSE Unit DPN001107 Pg. 2, Rev. 2 25 Liebert® DSE™ Plenum Dimensions 6.1 Outdoor Equipment Dimensions Figure 21 Plenum dimensions—upflow, DA080U and DA085U, 53-77kW (15-22 tons), EC fans Top duct flanges on plenum top for supply air ducting when solid panel plenum is used. D 0.88" (22.2mm) C H I G J Both top duct opening and grilles shown. See specification sheet for specific application. 0.88" (22.2mm) E A F B DPN002748 Rev. 1 Liebert® DSE™ 26 Plenum Dimensions Figure 22 Liebert EconoPhase™ pump box dimensions, typical Electric Box End of Unit 42" (1067mm) Minimum Clearance Pump Access Typical Both Sides 36" (914mm) Minimum Clearance 36" (914mm) Minimum Clearance 21-3/8" (543mm) ISOMETRIC VIEW 1-3/8" Liquid Line from Condenser 4-13/16" (122mm) 36-15/16" (939mm) B 42-1/8" (1071mm) System Circuit 2 Liquid In System Circuit 1 Liquid In System Circuit 2 Liquid Out System Circuit 1 Liquid Out 40-1/8" (1019mm) Ø 7/16" (11mm) typical 8 places for unit mounting 9-3/8" (238mm) Ø 7/16" (11mm) Typical 8 Places for unit mounting 40-11/16" (1033mm) 4-13/16" (123mm) 7/8" Liquid to Indoor Unit LEFT SIDE VIEW 21-5/16" (541mm) 40" (1016mm) REAR VIEW (PIPING END) 39-3/8" (1000mm) 36-3/16" (919mm) Unit Voltage, Hz 208/230, 460V 60Hz 380/400, 575V 60Hz 415V 50Hz Approximate Weight lb (kg) 340 lb.(154kg) 390 lb. (177kg) 347 lb. (157kg) 5/8" (16mm) 2-15/16" (56mm) 35-7/8" (911mm) A DETAIL B FRONT VIEW DPN002326 Rev. 4 A 27 12-15/16" (328mm) 22-15/16" (582mm) 32-15/16" (836mm) 35-7/8" (911mm) SECTION A-A Liebert® DSE™ Plenum Dimensions Figure 23 Condenser and Liebert EconoPhase™ unit locations, typical unit arrangement diagram layout Top View Circuit 1 Circuit 2 Air-Cooled Condenser Top View Liebert EconoPhase Unit Entering Hot Gas Line CIRCUIT 1 42" (1067mm) Minimum Clearance Air-Cooled Condenser Liquid Line to Liebert EconoPhase from Bottom of Receiver Entering Hot Gas Line CIRCUIT 2 *Liquid line from Condenser 1-3/8". Do Not Trap Line. Slope toward Liebert EconoPhase unit. * Liquid Line from Condenser 1-3/8" Do Not Trap Line Slope down 2" per 10' (51mm per 3m) toward Liebert EconoPhase unit * Liquid from Condenser 1-3/8" Do Not Trap Line Slope down 2" per 10' (51mm per 3m) toward Liebert EconoPhase unit CIRCUIT 1 CIRCUIT 2 60" (1524mm) 60" leg height Typical; see Note 1. Factory-supplied, Field-installed Field Piping 1. For proper pump function, a minimum elevation difference of 60” (1524 mm) must be maintained between the bottom of condenser box to the bottom of Liebert EconoPhase unit. 2. All indoor and outdoor field refrigerant piping must be insulated, 1/2" minimum. All outdoor insulation must be UV- and ozone-resistant. Liebert® DSE™ 28 *Components are not supplied by Emerson but are recommended for proper circuit operation and maintenance. **Components supplied by Emerson and must be field-installed. DPN002324 Rev. 3 Disassembly 7.0 DISASSEMBLY Figure 24 Liebert DSE disassembly downflow air-cooled 53-77kW and DA080, DA085 with EC fans Filter & Electric Box Assembly 39" (991mm) Forward curved blowers shown. DA units only available with EC blowers, optional on DS. Compressor Assembly Blower & Coil Assembly 76" (1930mm) Assembled Height 76" (1930mm) 59-7/16" (1509mm) 37" (940mm) DS053-DS077 = 15" (381mm) DA080,DA085 = 17" (432mm) 82" (2083mm) 33" (838mm) NOTE: Drawing views are simplified with panels removed to show over all dimensions. See disassembly and handling instructions in installation manual. Assembled Length DS053-DS077 = 97" (2464mm) DA080,DA085 = 99" (2515mm) 29 DPN000927 Rev. 5 Liebert® DSE™ Disassembly Figure 25 Liebert DSE disassembly dimensions, downflow air-cooled DA125 and DA150 models Filter Assembly 18" (457mm) Electric Box Assembly 40-11/16" (1034mm) Compressor Assembly Blower & Coil Assembly 94" (2388mm) Assembled Height 74-3/16" (1884mm) 76" (1930mm) 35" (889mm) 45" (1143mm) 22" (558mm) 120" (3048mm) 142" (3607mm) Assembled Length Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions. Table 10 Approximate dry weight, lb (kg), includes panels Component DA125 DA150 Compressor Assembly 630 (286) 739 (335) Electric Box Assembly 417 (189) 417 (189 2218 (1006) 2218 (1006) 200 (91) 200 (91) Blower and Coil Assembly Filter Assembly Source: DPN002420, Rev. 0 Liebert® DSE™ 30 DPN002420 Rev. 2 Disassembly Figure 26 Liebert DSE disassembly dimensions, upflow air-cooled 53-77kW (15-22 tons) and DA080U-DA085U Blower & Electric Box Assembly 31-1/4" (794mm) Compressor Assembly Filter & Coil Assembly 76" (1930mm) Assembled Height 76" (1930mm) 45-13/16" (1163mm) 33" (838mm) VS053-VS077 = 15" (381mm) DA080,DA085 = 17" (432mm) NOTE: Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual. 82" (2083mm) Assembled Length VS053-VS077 = 97" (2464mm) DA080,DA085 = 99" (2515mm) 31 DPN001210 Rev. 2 Liebert® DSE™ Electrical Connections 8.0 ELECTRICAL CONNECTIONS Figure 27 Electrical field connections Premium Efficiency Control, three-fan models Condenser #1 Connect this wire only to Condenser #1 70 Fan #3 12 13 70 71 230 C1 71 C2 230 Fan #2 Condenser #2 Liebert Indoor Unit 12 13 70 71 230 Connect this wire only to Condenser #2 Fan #1 DETAIL A ON 123 45678 CAN DETAIL B (DIPswitch 1 Setting Position) Electrical Service Connection Terminals with factory-supplied disconnect Factory-Installed Contactors Factory-Installed Fuse Blocks Factory-Installed Disconnect Earth Ground Connection Connection terminal for fieldsupplied earth grounding wire See Note 4 B A Earth Ground Bar Connection terminals with factory ground from each high voltage component for field-supplied earth grounding wire. Factory-wired to GND to the fans. . Electrical Service Entrance Remote shutdown Remote Shutdown (See Note 3) Alarm Connections Factory-Installed Transformer 7/8 in. (22.2mm) diameter holes in 1-1/8 in. (28.6mm) knockouts provided in bottom of electric box Field-wired SPD Field-installed CANbus Electrical Service (Optional) communication with indoor Not by Emerson unit. (See Note 2) NOTE: 1. Refer to specification sheet for full load amp and wire size amp ratings. 2. For the Premium models, the CANbus wiring must be shielded cable that has at least one triad of 24-20AWG conductors plus a drain wire, similar to Belden Part #1348A or Alpha Wire Part # 6351. The cable must either be water resistant and sunlight resistant, or be run in conduit once it is outside the building. 3. 24V field-supplied control voltage wiring from Liebert indoor unit must be a minimum of 18 gauge (1.6mm) or not to exceed 1 volt drop in control line. Wire per local code. 4. If two condensers are used for one dual-circuit Liebert indoor unit, the condenser used for Circuit 2 must have CAN DIPswitch 1 set to the Off position. See Detail B. 306266 Rev. 3 Liebert® DSE™ 32 Electrical Connections Figure 28 Liebert EconoPhase™ pump box field electrical connections Field Connection From Condenser CANbus. Wire Per Local Codes Field Ground Connection. Wire Per Local Codes Field High Voltage Connection. Wire Per Local Codes. Optional Low-Voltage Field Wiring Connection 7/8" Knockout Optional High Voltage Field Wiring Connection 2" Knockout Optional LowVoltage Field Optional HighWiring Connections Voltage Field FRONT Wiring Connection 7/8" Knockout VIEW 1-18" Knockout DPN002327 Rev. 5 Optional High-Voltage Field Wiring Connections 1-1/8" Knockouts Input Voltage Full Load Amps, FLA Minimum Supply Circuit Ampacity Maximum Fuse Size 208/230, 60Hz 380 */400, 60Hz 460, 60Hz 575, 60Hz 415, 50Hz 13.8 8.4 7.0 5.6 7.4 15.5 9.4 7.9 6.3 8.3 20.0 15.0 15.0 15.0 15.0 Source: DPN002327, Rev. 5 33 Liebert® DSE™ Electrical Connections Figure 29 CANbus cable connections between indoor unit, Liebert MC™ and optional Liebert EconoPhase™ unit Factory wiring between control boards and terminal strip EconoPhase EconoPhase Control Board Control Board Dual Circuit Single Circuit (Factory Set) (Factory Set) CIRCUIT ONE CIRCUIT ONE 1 1 J6 4 J6 3 3 49-1 CANbus 49-3 Connections ON ON CAN SW6 CAN SW6 No Shield Connection CIRCUIT TWO 1 J6 3 DETAIL 4 CAN Cable Connection P80 CAN L TB50 P15 H 3 J4 TB49 L CONDENSER 2 3 3 1 2 3 C J6 J6 1 TB49 ON 1 INPUT CONDENSER 2 CONDENSER 2 D58 L CAN H Two Two Condensers Condensers With EconoPhase 1 1 Last Device on CANbus (If Present) 1 1 2 3 A 1 OUTPUT 1 1 11 B H TB50 Liebert EconoPhase ON CAN SW6 ON 3 J6 CAN SW6 CAN SW6 TB50 BOOTPSWD SYS APP CONDENSER 1 CONDENSER 1 OUT PU T 1 2 3 CA NH CA NL TB49 1 INPUT 2 3 1 1 J6 3 J6 3 3 ON ON ON CAN SW6 CAN SW6 DETAIL 3 CAN Cable Connection CAN SW6 CONDENSER 2 SH Low-voltage field entrance on bottom left of Condenser 2 enclosure 70 71 230 Factory wiring between Liebert MC control board and terminal strip H CONDENSER 1 TB50 OU TP UT 1 2 3 CA NH CAN L TB49 INPU T 1 2 3 B G 3 CONDENSER 1 SH Low-voltage field entrance on bottom left of Condenser 1 enclosure 70 71 230 Factory wiring between Liebert MC control board and terminal strip Remove Jumper F HEAT REJECTION INTERLOCK Component Notes: DETAIL 2 1. Component appearance, orientation and position may vary between product lines. Terminal names and callouts remain constant. Heat Rejection Interlock Cable Notes (A, B, C): 1. Field-supplied cable: ● shielded 70 71 230 ● 24-18AWG stranded tinned copper ● twisted pair (minimum 8 twists per foot) ● low capacitance (15pF/ft or less) ● must be rated to meet local codes and conditions. Shield ● examples Belden 89207 (plenum-rated), or Alpha Connection Wire 6454 Category 5, 5e or higher. 2. Do not run in same conduit, raceway or chase as highvoltage wiring. 3. Contact factory for CANbus network lengths greater SH than 350ft (107m). Wire Notes (F, G,H): 49-1 1. Field-supplied wire: 49-3 ● 18AWG or greater ● rated 600V 2. For single-circuit systems, run two wires from indoor unit to condenser(s). 3. For dual-circuit systems, run three wires from the indoor DETAIL 1 CAN Cable Connection unit to first condenser and one wire from first condenser Factory Wiring Between Liebert iCOM to second condenser (if present). A 24 51 38 50 55 56 230 70 71 237 1 INDOOR UNIT and Terminal Strip DPN002361 Rev. 4 Liebert® DSE™ 34 Electrical Connections 8.1 Standard Electrical Field Connections, DA080 and DA085 Upflow and Downflow Source: DPN000807, Revision 9; refer to Figures 30 and 31 1. Primary high-voltage entrance—2.5" (64mm); 1.75" (44mm); 1.375" (35mm) diameter concentric knockouts in bottom of box. 2. Secondary high-voltage entrance—2.5" (64mm); 1.75” (44mm); 1.375" (35mm) diameter concentric knockouts in top of box. 3. Primary low-voltage entrance—Three knockouts, each 1.375" (35mm) diameter, in bottom of unit. 4. Secondary low-voltage entrance—Three knockouts, each 1. 375" (35mm) diameter, in top of box. 5. Three-phase electrical service—Terminals are on main fuse block (disregard if unit has optional disconnect switch). Three-phase service not by Emerson. 6. Earth ground—Terminal for field supplied earth grounding wire. Earth grounding required for Liebert units. 7. Remote unit shutdown—Replace existing jumper between Terminals 37 and 38 with field supplied normally closed switch having a minimum 75VA, 24VAC rating. Use field-supplied Class 1 wiring. 8. Customer alarm inputs—Terminals for field-supplied, normally open contacts, having a minimum 75VA, 24VAC rating, between Terminals 24 and 50, 51, 55, 56. Use field-supplied Class 1 wiring. Terminal availability varies by unit options. 9. Common alarm—On any alarm, normally open dry contact is closed across Terminals 75 and 76 for remote indication. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring. 10. Heat rejection interlock—On any call for compressor operation, normally open dry contact is closed across Terminals 70 and 71 (Circuit 1), 230 (Circuit 2) to heat rejection equipment. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring. Three wires must connect Terminals 70, 71 and 230 of the indoor unit to Terminals 70, 71 and 230 of the Liebert MC series condenser. Liebert DSE units must be connected to Liebert MC series condenser with premium control. The jumper between Terminal 71 and Terminal 230 must be removed. Three wires must connect Terminals 70, 71 and 230 of the indoor unit to Terminals 70, 71 and 230 of the Liebert MC series condenser. 8.2 CANbus Electrical Connections, DA080 and DA085 Upflow and Downflow Source: DPN000807, Revision 98; refer to Figures 30 and 31 11. CANbus Connector—Terminal block with Terminals 49-1 (CAN-H) and 49-3 (CAN-L) + SH (shield connection). The terminals are used to connect the CANbus communication cable (provided by others) from the indoor unit to the Liebert MC – Premium Model and optional PRE unit. 12. CANbus Cable—CANbus cable provided by others to connect to the outdoor condenser. Cable must have the following specifications: a. Conductors—22-18AWG stranded tinned copper b. Twisted pair c. Braided shield or foil shield with drain wire d. Low-capacitance—15pf/ft or less e. UL-approved temperature rated to 167 (75°C) f. UL-approved voltage rated to 300V g. UV-resistant and moisture-resistant if not provided in conduit. h. Plenum-rated—NEC type CMP (if required by national or local codes.) 35 Liebert® DSE™ Electrical Connections 8.3 Optional Electrical Field Connections, DA080 and DA085 Upflow and Downflow Source: DPN000807, Revision 9; refer to Figures 30 and 31 13. Unit factory-installed disconnect switch, fuse block and main fuses—Two types of disconnect switches are available: locking and non-locking. The non-locking type consists of a non-automatic molded case switch operational from the outside of the unit. Access to the high-voltage electric panel compartment can be obtained with the switch in either the On or Off position. The locking type is identical except access to the high-voltage electric panel compartment can be obtained only with the switch in the Off position. Units with fused disconnects are provided with a defeater button that allows access to the electrical panel when power is On. The molded case switch disconnect models contain separate main fuses. Units with fused disconnect have main fuses within the disconnect. Only fused disconnects are used on dual disconnect options. 14. Secondary disconnect switch and earth ground 15. Three-phase electrical service—Terminals are on top of the disconnect switch. Three-phase service not by Liebert. 16. Smoke sensor alarm—Factory-wired dry contacts from smoke sensor are 91-common, 92-NO, and 93-NC. Supervised contacts, 80 and 81, open on sensor trouble indication. This smoke sensor is not intended to function as, or replace, any room smoke detection system that may be required by local or national codes. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring. 17. Reheat and humidifier lockout - Remote 24VAC required at terminals 82 and 83 for lockout of reheat and humidifier. 18. Condensate alarm (with condensate pump option)—On pump high water indication, normally open dry contact is closed across terminals 88 and 89 for remote indication. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring. 19. Remote humidifier - On any call for humidification, normally open dry contact is closed across Terminals 11 and 12 to signal field-supplied remote humidifier. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring. 20. Auxiliary cool contact—On any call for Econ-O-Coil operation, normally open dry contact is closed across Terminals 72 and 73 on dual-cool units only. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring. 8.4 Optional Low-Voltage Terminal Package Field Connections, DA080 and DA085 Upflow and Downflow Source: DPN000807, Revision 9; refer to Figures 30 and 31 21. Remote unit shutdown—Two additional contact pairs available for unit shutdown (labeled as 37B and 38B, 37C and 38C). Replace jumpers with field-supplied normally closed switch having a minimum 75VA, 24VAC rating. Use field-supplied Class 1 wiring. 22. Common alarm—On any alarm, two additional normally open dry contacts are closed across Terminals 94 and 95 and 96 and 97 for remote indication. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring. 23. Main fan auxiliary switch—On closure of main fan contactor, normally open dry contact is closed across Terminals 84 and 85 for remote indication. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring. 24. Liebert Liqui-tect® shutdown and dry contact—On Liebert Liqui-tect activation, normally open dry contact is closed across Terminals 58 and 59 for remote indication (Liebert Liqui-tect sensor ordered separately). 1A, 24VAC maximum load. Use field-supplied Class 1 wiring. NOTE Refer to specification sheet for total unit full load amps, wire size amps and maximum overcurrent protective device size. Liebert® DSE™ 36 Electrical Connections Figure 30 Electrical field connections, DA080, DA085, single molded case switch disconnect with main fuses Refer to Section 8.5 through 8.7 for keys to numbered items. 2 Liebert IntelliSlot Housing 4 OVERCURRENT PROTECTION DEVICES 15 A B C D Alternate Location P64 6 CONTACTORS 60Hz P67 CONTACTORS, RELAYS, & OVERLOAD PROTECTORS 13 E 5 1 Typical orientation of components shown. Component location varies by option and unit size. 17 18 82 83 88 89 9 22 16 19 B 23 58 59 84 85 C 11 75 76 94 95 96 97 91 92 93 80 81 11 12 A 24 3 Low-Voltage Section DA080/-85 6 21 37C 38C 37B 38B 7 8 10 20 12 37 38 24 50 51 55 56 70 71 23072 73 E D Item 12 Installation Conditions 1. Follow all local installation codes. 2. Do not run CAN cables in same conduit, raceway or chase as high-voltage wires (120-600V). 3. Separate high-voltage wires from CAN wires by 12 in. (305mm). 4. Contact factory for runs greater than 350ft. (107m). 37 DPN000807 Pg. 2, Rev. 9 Liebert® DSE™ Electrical Connections Figure 31 Electrical field connections, DA080 and DA085 models, dual-fused disconnect switches 4 14 2 A Overcurrent Protection Devices 15 6 Liebert IntelliSlot Housing B CD 60 Hz Alternate Location 15 P64 Contactors P67 SECONDAR Y PRIMARY 13 Contactors, Relays, & Overload Protectors E Low-Voltage Section DA080/-85 6 1 Note: Typical orientation of components shown. Component location varies by option and unit size. 18 22 9 16 11 19 SH 17 3 75 76 94 95 96 97 91 92 93 80 81 11 12 23 21 7 8 49-3 B A 24 49-1 82 83 88 89 20 10 12 58 59 84 85 37C38C37B38B 37 38 24 50 51 55 56 70 71 230 72 73 C E D Item 12 Installation Conditions 1. Follow all local installation codes. 2. Do not run CAN cables in same conduit, raceway or chase as high-voltage wires (120-600V). 3. Separate high-voltage wires from CAN wires by 12 in. (305mm). DPN000807 4. For runs greater than 350ft. (107m), contact Liebert factory. Pg. 3, Rev. 9 Liebert® DSE™ 38 Electrical Connections 8.5 Liebert DSE Electrical Field Connection Descriptions, DA125 and DA150 Downflow Models Standard Electrical Connections Source: DPN002318, Revision 4 (See Figure 33 for connection locations) 1. Primary high-voltage entrance—2.50" (64mm); 1.75" (44mm); 1.375" (35mm) diameter concentric knockouts located in bottom of box. 2. Primary low-voltage entrance—Three knockouts in bottom of unit, each 1.375" (35mm) in diameter. 3. Three-phase electrical service—Terminals are on top of the disconnect switch. Three-phase service not by Emerson. 4. Earth ground—Terminal for field-supplied earth grounding wire and component ground terminal strip. Earth grounding required for Liebert units. 5. Remote unit shutdown—Replace existing jumper between Terminals 37 and 38 with field-supplied normally closed switch having a minimum 75VA, 24VAC rating. Use field-supplied Class 1 wiring. 6. Customer alarm inputs—Terminals for field-supplied, normally open contacts, having a minimum 75VA, 24VAC rating, between Terminals 24 and 50, 51, 55, 56. Use field-supplied Class 1 wiring. Terminal availability varies by unit options. 7. Common alarm—On any alarm, normally open dry contact is closed across Terminals 75 and 76 for remote indication. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring. 8. Heat rejection interlock—On any call for compressor operation, normally open dry contact is closed across Terminals 70 and 71 (Circuit 1), 230 (Circuit 2) to heat rejection equipment. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring. 9. CANbus Connector—Terminal block with terminals 49-1 (CAN-H) and 49-3 (CAN-L) + SH (shield connection). The terminals are used to connect the CANbus communication cable (provided by others) from the indoor unit to the Liebert MC premium model and optional PRE unit. 10. CANbus Cable—CANbus cable provided by others to connect to the outdoor condenser. Cable must meet the following specifications: a. Conductors—22-18AWG stranded, tinned copper b. Twisted pair (minimum of eight twists per foot [305mm]) c. Braided shield or foil shield with drain wire d. Low capacitance—15pf/ft or less e. UL approved temperature rated to 75°C f. UL approved voltage rated to 300V g. UV- and moisture-resistant if not run in conduit. h. Plenum rated—NEC type CMP, if required by national or local codes 8.6 Optional Electrical Connections, DA125 and DA150 Downflow Models Source: DPN002318, Revision 4 (See Figure 33 for connection locations) 11. Factory-installed disconnect switch 12. Smoke sensor alarm—Factory-wired dry contacts from smoke sensor are 91-common, 92-NO and 93-NC. Supervised contacts, 80 and 81, open on sensor trouble indication. This smoke sensor is not intended to function as or replace any room smoke detection system that may be required by local or national codes. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring. 13. Reheat and humidifier lockout—Remote 24VAC required at Terminals 82 and 83 for lockout of reheat and humidifier. 14. Condensate alarm (with condensate pump option)—On pump high water indication, normally open dry contact is closed across Terminals 88 and 89 for remote indication. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring. 15. Remote humidifier—On any call for humidification, normally open dry contact is closed across Terminals 11 and 12 to signal field-supplied remote humidifier. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring. 39 Liebert® DSE™ Electrical Connections 8.7 Optional Low- Voltage Terminal Package Connections, DA125 and DA150 Downflow Models Source: DPN002318, Revision 4 (See Figure 33 for connection locations) 16. Remote unit shutdown—Two additional contact pairs available for unit shutdown (labeled as 37B and 38B, 37C and 38C). Replace jumpers with field-supplied normally closed switch having a minimum 75VA, 24VAC rating. Use field-supplied Class 1 wiring. 17. Common alarm—On any alarm, two additional normally open dry contacts are closed across Terminals 94 and 95 and 96 and 97 for remote indication. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring. 18. Main fan auxiliary switch—On closure of main fan contactor, normally open dry contact is closed across Terminals 84 and 85 for remote indication. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring. 19. Liebert Liqui-tect® shutdown and dry contact—On Liebert Liqui-tect activation, normally open dry contact is closed across Terminals 58 and 59 for remote indication (Liebert Liqui-tect sensor ordered separately). 1A, 24VAC maximum load. Use field-supplied Class 1 wiring NOTE Refer to specification sheet for total unit full load amps, wire size amps and maximum overcurrent protective device size. Figure 32 Electrical field connections for DA125 and DA150 downflow models High-Voltage Field Wiring Pathways Low-Voltage Field Wiring Pathways DPN002317 Pg. 1, Rev. 4 Liebert® DSE™ 40 Electrical Connections Figure 33 Electrical field connections for DA125 and DA150 downflow models Refer to Section 8.5 through 8.7 for keys to numbered items. Liebert IntelliSlot Housing OVERCURRENT PROTECTION DEVICES P67 P64 3 A F B CONTACTORS AND RELAYS C 4 D OVERLOADS 11 E G Notes: Typical orientation of components shown. Component location varies by option and unit size. Refer to DPN002318 for descriptions of numbered callouts. 4 1 Low-Voltage Section 2 9 7 17 13 14 12 19 8 15 5 SH 38C 37B 38B B 82 83 88 89 C 80 81 91 92 93 16 F 49-1 A 75 76 94 95 96 97 37 38 10 Item 10 Installation Conditions G 1. Follow all local installation codes. 2. Do not run CAN cables in same conduit, raceway, or chase as high-voltage wires (120-600V). 3.Separate high-voltage wires from CAN wires by 12 in. (305mm). 4. Contact factory for runs greater than 350ft (107m). DPN002317 Pg. 2, Rev. 4 D 58 59 70 71 230 18 37C 49-3 6 24 50 51 55 56 84 85 11 12 E 41 Liebert® DSE™ GUIDE SPECIFICATIONS GUIDE SPECIFICATIONS 1.0 GENERAL 1.1 SUMMARY These specifications describe requirements for a Thermal Management system. The system shall be designed to control temperature and humidity conditions in rooms containing electronic equipment, with good insulation and vapor barrier. The manufacturer shall design and furnish all equipment to be fully compatible with heat dissipation requirements of the room. 1.2 DESIGN REQUIREMENTS The Thermal Management system shall be a Liebert self-contained, factory-assembled unit with downflow air delivery. The system shall have a net total cooling capacity of ____ kW (BTUH) with a net sensible cooling capacity of ____ kW (BTUH) based on an entering air temperature of ____ °F (____°C) dry bulb and ____ °F (____°C) wet bulb. The unit is to be supplied with ____ volt ____ ph ____ Hz electrical service. Net capacities shall include losses due to fan motor heat. The system cooling capacity shall be factory certified per ASHRAE127-2007, and the system sensible coefficient of performance (SCOP) shall exceed ASHRAE 90.1-2010. 1.3 SUBMITTALS Submittals shall be provided after the agreement of the proposal and shall include: Single-Line Diagrams; Dimensional, Electrical and Capacity Data; Piping and Electrical Connection Drawings. 2.0 PRODUCT 2.1 FRAME The frame shall be welded, formed sheet metal. It shall be protected against corrosion using the autophoretic coating process. The frame shall be capable of being separated into three parts in the field to accommodate rigging through small spaces. 2.1.1 Downflow Air Supply The supply air shall exit from the bottom of the unit. 2.1.2 Downflow Air Return The return air shall enter the unit from the top 2.1.3 Exterior Panels The exterior panels shall be insulated with a minimum 1 in. (25mm), 1.5 lb. (0.68 kg) density fiber insulation. The main front panel shall have captive quarter-turn fasteners. The main unit color shall be _______________. 2.2 FILTERS-DA080, DA085 2.2.1 Filters, 4" MERV 8 Filters shall be deep pleated 4" filters with an ASHRAE 52.2 MERV8. 2.2.1 Filters, 4" MERV11 Filters shall be deep pleated 4" filters with an ASHRAE 52.2 MERV11. 2.2.1 Filters, 2" MERV8 and 2" MERV11 Filters shall be deep pleated 2" filters with an ASHRAE 52.2 MERV8, plus 2" MERV11 filters. 2.2.2 Extra Filter Set ____ extra set(s) of filters shall be provided per system. Liebert® DSE™ 42 GUIDE SPECIFICATIONS 2.2 FILTERS-DA125, DA150 The filter plenum shall be exterior to the main cooling unit, and shall be field assembled and installed. The filters shall be removable from the front or top of the filter plenum. The filter plenum shall be painted to match the panel colors of the indoor cooling unit. 2.2.1 Filters, 4" MERV 8 Filters shall be deep pleated 4" filters with an ASHRAE 52.2 MERV8. 2.2.1 Filters, 4" MERV11 Filters shall be deep pleated 4" filters with an ASHRAE 52.2 MERV11. 2.2.1 Filters, 4" MERV13 Filters shall be deep pleated 4" filters with an ASHRAE 52.2 MERV13. 2.2.1 Filters, 2" MERV8 and 2" MERV11 Filters shall be deep pleated 2" filters with an ASHRAE 52.2 MERV8, plus 2" MERV11 filters. 2.2.1 Filters, 2" MERV8 and 2" MERV13 Filters shall be deep pleated 2" filters with an ASHRAE 52.2 MERV8, plus 2" MERV13 filters. 2.2.2 Extra Filter Set ____ extra set(s) of filters shall be provided per system. 2.3 FAN SECTION 2.3.1 Electronically Commutated (EC) Fan The fans shall be plug/plenum type, motorized impellers, single inlet and dynamically balanced. The drive package shall be direct drive, electronically commutated and variable speed. The fans shall be located to draw air over the A-frame coil to ensure even air distribution and maximum coil performance. EC fans shall be capable of being lowered into a raised floor (during field installation) with minimum height of 24" (609.6mm). EC fans shall also be capable of operating within the cooling cabinet, instead of under the floor. 2.4 HUMIDIFIER A humidifier shall be factory-installed inside the unit. Bypass air slots shall be included to enable moisture to be absorbed into the air stream. The humidifier capacity shall be 22.1lb./hr (10 kg/hr). The humidifier shall be removable from the front of the cabinet. 2.4.1 Infrared Humidifier The humidifier shall be of the infrared type, consisting of high-intensity quartz lamps mounted above and out of the water supply. The humidifier pan shall be stainless steel and arranged to be removable without disconnecting high-voltage electrical connections. The complete humidifier section shall be pre-piped, ready for field connection to the water supply. The humidifier shall be equipped with an automatic water supply system and shall have an adjustable water-overfeed to prevent mineral precipitation. A high-water detector shall shut down the humidifier to prevent overflowing. A factory provided air gap shall prevent backflow of the humidifier supply water. 2.5 REHEAT The Thermal Management unit shall include a factory-installed reheat to control temperature during dehumidification. 2.5.1 Three-Stage Electric Reheat The electric reheat coils shall be low watt density, 304/304 stainless steel fin tubular construction, protected by thermal safety switches, shall be ____ kW (____ BTUH) controlled in three stages. The reheat elements shall be removable from the front of the cabinet. A ground-current detection device shall disable reheat in the case where a ground-fault is detected in the reheat element. 43 Liebert® DSE™ GUIDE SPECIFICATIONS 2.6 DUAL REFRIGERATION SYSTEM Each unit shall include two (2) independent refrigeration circuits and shall include liquid line filter driers, refrigerant sight glass with moisture indicator and electronic expansion valves. Compressors shall be located outside the airstream and shall be removable and serviceable from the front of the unit. Each compressor circuit shall be connected to the full-face area of the evaporator coil. 2.6.1 Digital Scroll Compressors-DA080, DA085 The compressors shall be scroll-type with a variable capacity operation capability. Compressor solenoid valve shall unload the compressor and allow for variable capacity operation. The compressor shall have vibration isolators, thermal overloads, automatic reset high-pressure switch with lockout after three failures, rotalock service valves, suction line strainer and a maximum operating speed of 3500 RPM. The compressor motor shall be suction gas cooled. 2.6.1 Tandem Digital Scroll Compressors-DA125, DA150 The compressors shall be tandem, scroll-type with a variable capacity operation capability of one compressor of the pair. Compressor solenoid valve shall unload the compressor and allow for variable capacity operation. The compressor shall have vibration isolators, thermal overloads, automatic reset high-pressure switch with lockout after three failures, rotalock service valves, suction line strainer and a maximum operating speed of 3500 RPM. The compressor motor shall be suction gas cooled. 2.6.1.1 Crankcase Heaters The compressors shall include crankcase heaters, powered from the indoor unit electric panel. 2.6.2 Evaporator Coil The evaporator coil shall be A-frame design and have ______ sq. ft. (______ sq m) face area, six rows deep, with each circuit feeding three rows. It shall be constructed of rifled copper tubes and aluminum fins with a maximum face velocity of _____ ft. per minute (_____ m/s) at _____ CFM (_____ CMH). A stainless steel condensate drain pan shall be provided. 2.6.3 R-410A Refrigerant The system shall be designed for use with R-410A refrigerant, which meets the U.S. Clean Air Act for phase-out of HCFC refrigerants. Refrigerant shall be field supplied and field charged by the installing contractor. 2.7 ECONOPHASE CYCLE (OPTIONAL) (SELECT ONLY IF PR085 OR PR125 IS SELECTED) During cold outdoor temperatures, refrigerant pumps shall circulate refrigerant through the cooling system, in lieu of operating the compressors. The compressors shall ramp down during EconoPhase operation, and if able to completely offset the load, the control system shall shut the compressors off. Dual refrigerant pumps shall be housed in an enclosure, with each pump dedicated to its own refrigerant circuit. The EconoPhase system shall include a variable speed drive on each refrigerant pump to enable to pumps' speed to adjust in response to the load. 2.8 MISCELLANEOUS OPTIONS 2.8.1 Non-Locking Disconnect Switch (Optional) The manual disconnect switch shall be mounted in the high voltage section of the electrical panel. The switch shall be accessible with the door closed. The electrical system shall be rated for 65 kA, shortcircuit current rating (28kA at 575V). 2.8.1 Locking Disconnect Switch (Optional) The manual disconnect switch shall be mounted in the high-voltage section of the electrical panel. The switch shall be accessible from the outside of the unit with the door closed and shall prevent access to the high voltage electrical components until switched to the “Off” position. The electrical system shall be rated for 65 kA, short-circuit current rating (28kA at 575V). Liebert® DSE™ 44 GUIDE SPECIFICATIONS 2.8.2 High-Temperature Sensor (Optional) The high-temperature sensor shall be factory-installed in the unit and shall be factory-set to 125ºF (52ºC). It shall immediately shut down the environmental control system when activated. The sensor shall be mounted with the sensing element in the return air. 2.8.3 Smoke Sensor (Optional) The smoke sensor shall immediately shut down the Thermal Management system and activate the alarm system when activated. The smoke sensor shall be mounted in the electrical panel with the sensing element in the return air compartment. The smoke sensor is not intended to function as or replace any room smoke detection system that may be required by local or national codes. The smoke sensor shall include a supervision contact closure. 2.8.4 Condensate Pump, Dual Float (Optional) The condensate pump shall have a minimum capacity of 145 GPH (548 l/h) at 20 ft. (58 kPa) head. It shall be complete with integral dual-float switches, pump-and-motor assembly and reservoir. The secondary float shall send a signal to the local alarm and shut down the unit upon high water condition. 2.8.5 Low Voltage Terminal Package (Optional) Factory-installed and wired terminals shall be provided for customer connection to lock out the reheat and humidifier upon contact closure. Two (2) extra N/O common alarm contacts shall be provided. Two (2) extra remote shutdown terminals shall be provided. 2.8.6 Remote Humidifier Contact (Optional) A pair of N/O contacts shall be provided for connection to a remote humidifier. 2.8.7 Main Fan Overload A pair of N/O contacts shall be factory-installed and wired to indicate Main Fan Overload. 2.8.8 Compressor Overload (Optional) A pair of N/O contacts shall be factory-installed and wired to each compressor to indicate Compressor Overload. 2.9 AIR-COOLED SYSTEMS The indoor evaporator unit shall include refrigerant piping and shall have a factory holding charge of nitrogen. The hot-gas and liquid lines shall be spun shut and each shall include a factory-installed Schrader valve. Field-relief of the Schrader valve shall indicate a leak-free system from the factory. Installing contractor shall cut the evaporator piping and shall evacuate and charge the system. Refrigerant shall be supplied by the installing contractor. 2.9.1 Air-Cooled Condenser The Liebert-manufactured outdoor air-cooled condenser shall be the low profile, multiple direct drive, propeller fan type. The condenser shall balance the heat rejection of the compressor at ____ °F (____ °C) ambient. The condenser shall be constructed of a microchannel coil. 2.9.2 Liebert Liqui-tect® Sensors (Optional ____ (quantity) solid state water sensors shall be provided for installation under the raised floor. 2.10 FLOOR STAND The floor stand shall be constructed of a welded steel frame. The floor stand shall have adjustable legs with vibration isolation pads. The floor stand shall be ____ inches (______mm) high. 2.10.1 Seismic Rated Floor Stand (Optional) The floor stand shall be seismic rated per IBC2009, and shall be attached to the unit frame (fieldinstalled). The floor stand shall also be capable of being anchored to the subfloor. 45 Liebert® DSE™ GUIDE SPECIFICATIONS 2.11 RETURN AIR PLENUM FOR DOWNFLOW UNITS The air plenum shall be constructed of 20 gauge steel, powder coated to match unit color. The plenum shall be _____" (_____ mm) high. A door shall be included in the front of the plenum to enable front filter access. Air shall enter the plenum from the top. 3.0 3.0 EXECUTION 3.1 INSTALLATION OF THERMAL MANAGEMENT UNITS The customer or the customer’s representative shall be responsible for the following: 3.1.1 General Install Thermal Management units in accordance with manufacturer's installation instructions. Install units plumb and level, firmly anchored in locations indicated and maintain manufacturer's recommended clearances. 3.1.2 Electrical Wiring Install and connect electrical devices furnished by manufacturer but not specified to be factorymounted. Furnish copy of manufacturer's electrical connection diagram submittal to electrical contractor. 3.1.3 Piping Connections Install and connect devices furnished by manufacturer but not specified to be factory-mounted. Furnish copy of manufacturer's piping connection diagram submittal to piping contractor. 3.2 FIELD QUALITY CONTROL Start cooling units in accordance with manufacturer's startup instructions. Test controls and demonstrate compliance with requirements. These specifications describe requirements for a computer room environmental control system. The system shall be designed to maintain temperature and humidity conditions in the rooms containing electronic equipment. The manufacturer shall design and furnish all equipment to be fully compatible with heat dissipation requirements. Liebert® DSE™ 46 Technical Support / Service Web Site www.liebert.com Monitoring liebert.monitoring@emerson.com 800-222-5877 Outside North America: +00800 1155 4499 Single-Phase UPS & Server Cabinets liebert.upstech@emerson.com 800-222-5877 Outside North America: +00800 1155 4499 Three-Phase UPS & Power Systems 800-543-2378 Outside North America: 614-841-6598 Environmental Systems 800-543-2778 Outside the United States: 614-888-0246 Locations While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2014 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners. United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy +39 049 9719 111 Fax: +39 049 5841 257 Asia 29/F, The Orient Square Building F. Ortigas Jr. Road, Ortigas Center Pasig City 1605 Philippines +63 2 687 6615 Fax: +63 2 730 9572 SL-18926_REV4_09-14 Emerson Network Power Liebert www.emerson.com www.EmersonNetworkPower.com