1. COMPONENT 2. DATE F'Y 2004 MILITARY CONSTRUCTION PROJECT DATA AIR FORCE (computer generated) 3. INSTALLATION AND LOCATION 4. PROJECT TITLE MINOT AIR FORCE BASE, NORTH DAKOTA ADD/ALTER MISSILR MAINTENANCE VEHICLE FACILITY 6. CATEGORY 5. PROGRAM ELEMKNT CODE 7. PROJECT NUMBER 214-426 3 5 9 9 6 9. Auth: Approp: QJvF952007 COST 8. PROJECT COST ($000) 3,190 3,050 ESTIMATES UNIT ADD/ALTER MISSILE MAINTENANCE FACILITY COST 2,438 LS 1,550 ADDITION ALTERATIONS I? I SM ANTITERRORISM FORCE PROTECTION SUPPORTING FACILITIES 1,470 ( 2,279) ( 1,550 7 149) ( 11) 430 I UTILITIES LS ( 125) PAVEMENTS LS ( 125) SITE IMPROVEMENTS LS ( DEMOLITION LS I SUBTOTAL CONTINGENCY ( 120) ( 60) 2,868 5.0 %I 143 3,012 TOTAL CONTRACT COST SDPBRVISION, INSPECTION AND OVRRRRAD ( 5.7 %) 172 TOTAL REQUEST 3,183 TOTAL REQUEST (ROUNDED) 3,190 10. Description of Proposed Construction: Concrete foundation, floor slabs, masonry walls, and roof system. Includes fire protection system, utilities, waeh rack, vehicle parking stalls and all necessary support. Comply with DOD interim minimum force protection construction standards. 11. RRQUIRRMENT: ?ROJECT: 3,092 SDl ADEQUATE: 0 SM SUBSTANDARD: 1,542SM Add/Alter missile maintenance vehicle facility. (Current Mission) An adequate facility is needed to insure that missile maintenance vehicles zREQu1RRMRNT: It is required to provide proper vehicle rre in "ready to operate. status at all times. aaintenance, minor repair, and quick response capabilities. A heated facility ie needed It is also important that proper facilities due to the harsh winters in North Dakota. for washing the vehicles are provided to provide corrosion control. These vehicles provide maintenance and supplies to missile equipment and facilities, and they must be ready to respond at all times. b-DRREXT SITUATION: There is currently no adequate facility to house 90 of the missile support vehicles at Minot AFR. Thus, it is difficult to provide adequate maintenance Ear these critical vehicles. The severe cold weather and extremely low windchills, as low as minus 100 degrees Fahrenheit during the winter months, hinder the ability to Perform maintenance and sustain readiness. This impairs mission accomplishment. The vehicles stored outside must be started several times a day to maintain mission This wastes manhours and decreases engine life. Personnel must spend readiness. aanhours clearing snow and ice off the vehicles. The bitter cold was responsible for ruining five vehicle engines in the last two years. The present facility lacks adequate entryways, and often vehicles are moved only to allow another to exit or be worked on. DD FORM 1391, DEC 76 Previous editions are obsolete. Page No. 15 5 1. COMPONENT FY 2004 MILITARY CONSTRUCTION PROJECT DATA AIR FORCE (computer 2. DATE generated) 3. INSTALLATION AND LOCATION 4. PROJECT TITLE MINOT AIR FORCE BASE, NORTH DAKOTA ADD/ALTER MISSILE MAINTENANCE VEHICLE FACILITY 5. PROGRAM ELEMENT 35996 6. CATEGORY CODE 7. PROJECT NUMBER 214-426 QJVF952007 8. PROJECT COST ($000) 3,190 This also wastes manhours and fills the facility with fumes. The existing wash area accommodates only one small vehicle at a time and does not acconuaodate the larger nuclear-certified payload transporters and transporter-erectors resulting in increased :orrosion. Combined, these factors may negatively impact the mission effectiveness and nlert rate. This could affect the strategic posture of our missiles and the nation's security. Without dependable vehicles, crews cannot respond to repair the missiles. CWPACT IF NOT PROVIDED: Lack of a larger heated vehicle facility to house all the vehicles will continue to negatively impact the maintenance of 150 Minuteman III tntercontinental Ballistic Missiles. The maintenance crews will continue to suffer due to severe cold weather. Monthly vehicle maintenance, pre-operational functional inspections and area functional checkouts will continue to be difficult to perform. ?ehicles will continue to be moved into tight quarters, increasing safety risks, ielaying dispatches, and expending additional manhours. Vehicle response times will zontinue to decrease. Personnel will continue to work in freezing conditions to Jenerate frozen vehicles with no alternative. This project meets the criteria/scope specified in Air Force Handbook 32UlDITIONAL: 1084, "Facility Requirements." A preliminary analysis of reasonable options for xcomplishing this project was done. It indicates there is only one option which will neet operational needs. Because of this, a full economic analysis was not performed. A :ertificate of exception has been prepared. Base Civil Engineer: Lt Co1 Leslie Martin, Add/Alter Missile Maintenance Facility: 1,550 SM = 16,678 SF. [701)723-2434. JOINT USE CERTIFICATION: Mission requirements, operational considerations, and location Ire incompatible with use by other components. DD FORM 1391, DEC 76 Previous editions are obsolete. Page No. 156 1. COMPONENT FY 2004 MILITARY CONSTRUCTION PROJECT DATA (computer AIR FORCE 2. DATE generated) 3. INSTALLATION AND LOCATION 4. PROJECT TITLE MINOT AIR FORCE BASE, NORTH DAKOTA ADD/ALTER MISSILE MAINTENANCE VEHICLE FACILITY 5. PROGRAM ELEMENT 6. CATEGGRY CODE 7. PROJECT NUMBER 35996 214-426 8. PROJECT COST ($000) QJVF952007 3,190 12. SUPPLEMENTAL DATA: a. Estimated Design Data: (1) Status: (a) Date Design Started (b) Parametric Cost Estimates used to develop costs l (c) Percent Complete as of 01 JAN 2003 * (d) Date 35% Designed (e) Date Design Complete (f) Energy Study/Life-Cycle analysis was/will be performed 02-APR-02 YES 15% lo-AUG-02 lo-AUG-03 YES (2) Basis: (a) Standard or Definitive Design (b) Where Design Was Most Recently Used - NO (3) Total Cost (c) I (a) + (b) or (d) + (e): (a) Production of Plans and Specifications (b) All Other Design Costs (c) Total (d) Contract (e) In-house ($000) 186 93 279 240 39 (4) Construction Contract Award 03 DEC (5) Construction Start 04 JAN (6) Construction Completion 04 NOV l Indicates completion of Project Definition with Parametric Cost Estimate which is comparable to traditional 35% design to ensure valid scope, cost and executability. b. Equipment associated with this project provided from other appropriations: N/A DD FORM 1391, DEC 76 Previous editaons are obsolete. Page NO. 1. COMPONENT FY 2004 MILITARY CONSTRUCTION PROGRAM 2. DATE AIR FORCE IINSTALLATION AND LOCATION COMMAND: 5. AREA CONST WRIGHT PATTERSON AIR FORCE BASE, AIR FORCE MATERIEL COST INDEX OHIO COMMAND 0.97 6. Personnel PERMANENT STUDENTS SUPPORTED Strength OFF ENL OFF ENL CIV OFF ENL CIV CIV :AS OF 30 SEP 02 2490 13634 81 2730 138 4,169 LEND FY 2007 2622 2564 13184 81 138 4169 7. INVENTORY DATA ($000) Total Acreage: 8,145 Inventory Total as of : (30 Sep 02) ,Authorization Not Yet in Inventory: IAuthorization Requested in this Program: ~Authorization Included in the Following Program: (FY 2005) Planned in Next Four Years Program: Remaining Deficiency: Grand Total: 8. PROJECTS REQUESTED IN THIS PROGRAM: CATEGORY CODE PROJECT TITLE 721-312 Dvrrnitory 9a. Future Projects: Included in the Following Program: No Projects 9b. Future Projects: Typical Planned Next Four Years: 113-321 Replace West Ramp, Ph 2 130-142 Consolidated Fire/Crash Rescue Station Consolidate Materials Computational 31 o-933 Research Facility Consolidated Aeronautical Sciences Laboratory 311-171 311-173 Information Technology Complex, Ph 1 Information Technology Complex, Ph 3 311-173 Alter Acquistion Support Facility 311-173 Consolidate AFMC Law Offices 610-112 61 O-243 Information Technology Complex, Ph 2 Security Forces Admin Facility 61 O-835 Dormitory 721-312 Add/Alter Chapel Activities Center 736-773 Replace Steam Lines/Tunnels Area B, 1822-265 Phase 1 Replace Steam lines/Tunnels Area B, Phase 2 1822-265 ADAL FME Laboratory 1141454 ‘9c. Real Prooerv Maintenance Backloa This Installation TOTAL 23,242 22,698 4,975,367 113,729 10,500 cl 210,400 106,500 5,416,496 (FY 2004) COST DESIGN STATUS SCOPE $,OOO S T A R T C M P L 144 RM Total (FY2005) 10,500 Design-Build 10,500 98,667 3,319 SM SM 8,700 10,600 6,000 SM 16,000 6,838 9,832 9,232 13,400 7,150 10,962 5,765 96 1,300 6,834 SM 18,000 SM 21,000 SM 23,000 SM 17,600 SM 8,000 SM 23,000 SM 12,800 RM 7,400 SM 3.300 1 LS 11,300 1 LS 11,200 SM 18,500 11 158 11. COMPONENT j FY 2004 MILITARY CONSTRUCTION PROGRAM 12. DATE I AIR FORCE I I ICOMMAND: j 5. AREA CONST INSTALLATION AND LOCATION WRIGHT PAT-I-ERSON AIR FORCE BASE, AIR FORCE MATERIEL COST INDEX 0.97 OHIO COMMAND 10. Mission or Major Functions: Air Force Materiel Command headquarters which is responsible management, control, and direction of research, acquisition and logistics support for air and space weapon systems and related components; Aeronautical Systems Center; Air Force Research Laboratory including directorates for Materials, Sensors, air Vehicles, Human Effectiveness, and propulsion; Air Force Institute of Technology; Air Force Museum; Air Force Security Assistance Center; National Aerospace Intelligence Center; National Airborne Operations Center; and air base wing; Air Force Reserve Command airlift wing with two C-141 airlift squadrons; and an AMC airlift flight with C-21 aircraft. 11. Outstanding pollution and Safety (OSHA Deficiencies: a. Air pollution 1,920 I b. Water Pollution c. Occupational Safety and Health d. Other Environmental DD Form 1390,24 Jul 00 I’ 159 1. mRRNT PY 2004 MILITARY CONSTRUCTION PROJECT MTA AIRFORCE (cauputer generated) 3. INSTALIATION AWD LOCATION 4. -CT TITLE WFlIQiT PATTRRSON AIR FORCE BASE, ORIO DORMITORY (144 RR) 5. 2. DATE PRoGRAw - 6. CATRGORY CODR 7. PROJECT Ml16Bw 72896 721-312 9. 8. PROJECT COST ($000) !izTv973211 10,500 COST ESTIMATES DORMIMRY (144 RR) DORMITORY ABTl'ITRRRORISM FORCE PRoTEcTION ( 7,679 1 SDPPORTfbK3 FACILITIRS DTILITILS SITE IMPROVRMEMPS PAWS COAQUDRICATIORS SUPPORT cox?rINGENcY ( 5.0 %) TOTAL co- CO& SUPEFWISION, INSPECTION AND B TOTAL REQUEST TOTALRRQDRST(RODNDRD) I 10,500 LO. Description of Proposed Construction: A three-story facility with reinforced :oncrete fouadation aud floor slabs, masonry walls and roof. Includes roamJath/kitchen-room modules, laundry facility, storage, lounge areas, site preparation, seimnic requirements and all supporting utilities. Ccmplies with DOD interim minimum Eorce protection construction standard. h.ir Conditioning: 11. RIZQ-: 195 Kw. 620 RM Grade Mix: El-E4 ADEQUA~: 3 6 3 RN 144 SUBSTANDARD: ORB! PmJEcT: Construct a dormitory. (Current Mission) A major Air Force objective provides unaccompanied enlisted personuel with housing conducive to their proper rest, relaxation and personal well-being. Properly designed and furnished quarters providing same degree of individual privacy are essential to the successful acccmplisWt of the increasingly cwlicated and important jobs these people must perform. The retention of these highly trained airmen is assential to our readiness posture and continuing world-wide presence. Caaplies with DOD interim minimum force protection construction standard. REQ-: CDRRRNT SITUATION: The base has insufficient on-base housing to accosmodate the unaccanpanied enlisted personnel. This project is in accordance with the Air Force Dormitory Master Plan. Adequate living quarters which provide a level of privacy IMPACTIFNOTPROVIDRD: required for today's airmen will not be available, resulting in degradation of morale, productivity, and career satisfaction for uuacccmpanied enlisted personnel. ADDITIORAL: This project meets the criteria/scope specified in the new uniform barracks construction standard, known as "one-plus-me", established by OSD. Allkaown alternatives were considered during the develaplllent of this project. No other option could meet the mission requirements. Therefore, no economic analysis was needed or DD FORM 1391, DRC 76 Previous editions are obsolete. Page No. 160 1. CoMPoNRm FY 2004 MILITARY CObWrRUCTION PROJECT DATA (cwter generated) N.RFORCR 3. aSTALLATION AND LOCATIOEJ 4. PROJECT TITLE HRIGBT PMTBRSON AIR FORCR BASR, OHIO DORMITORY (144 RM) 5.PROGRAMRLlmQ?r 72096 2. DATE 6. CATBQORY CODE 721-312 7. PROJECT NUMBBR zHTv973211 8. PROJECT COST ($000) 10,500 mrformed. ~Y2001 macccmpanied Rousing RPM Conducted: $66OK. FY2002 unaccacQanied knming Rpll Conducted: $563K. FutureUnaccaupaniedHousingRFMrequiremaents estimated): FYo3: $412K; FYO4: $37011; l'YO5: $27OK. Base Civil Engineer: Hr Gary ~olumon, (937) 257-6214. Dormitory: 4,752 SM = 51,132 SF. Design Build - Design Build :ost (4% of Subtotal Cost): $370,000. FORM 1391, DRC 76 Previous editions are obsolete. Page No. 161 1. CowPoNEwT FY 2004 MILITARY COIUSTRUCTION PROJECT DATA 2. DATE (ccmputer generated) LIRmRcE 3. IWSTALLATION ACID LOCATION 4. - TITLE WRIGBT PATTERSONAIR FORCE BASE, OHIO DORNITORY (144 RB¶) s.PROGRAMm 6.C!ATEGORYCO= 72896 721-312 7.PROJBCTNDHRER B. PROJ-ECT COST ($000) ZHTV973211 10,500 12. SUPP -AI, DATA: a. Estimated Design Data: (1) Project to be accau9lished by design-build procedures (2) Basis: (a) Stan&rd or Definitive Design (b) Where Design Was Host Recently Used (3) All Other Design Costs (4) Constructicm Contract No 284 Award 03 DEC (5) Constnlction start 04 JAN (6) Construction Ccapletion 05 &TON (7) Energy Study/Life-Cycle analysis was/will be performed YES b. Rquipment atpociated with this project provided frau other appropriations: N/A FORM 1391, DRC 76 Previous editions are obsolete. Page No. ‘i. COMPONENT 1 FY 2004 MILITARY CONSTRUCTION PROGRAM 12. DATE AIR FORCE c‘:!. INSTALLATION AND LOCATION 4. COMMAND: 5. AREA CONST 14LTUS AIR FORCE BASE AIR EDUCATION AND COST INDEX (IKLAHOMA TRAiNING COMMAND 0.98 f5. Personnel PERMANENT STUDENTS SUPPORTED :strength ENL OFF ENL CIV OFF CIV OFF ENL CIV TOTAL I4s OF 30 SEP 02 303 1347 1233 147 196 0 0 0 0 3,22(5 fIND FY 2007 303 1353 1251 147 196 0 0 0 0 3,25C 1 i7. INVENTORY DATA ($000) i3. Total Acreage: 5,982 t1. Inventory Total as of : (30 Sep 02) 1,008,68E5 c:. Authorization Not Yet in Inventory: 23,3OC1 (1. Authorization Requested in this Program: 1,141I c2. Authorization Included in the Following Program: (FY 2005) (1 f‘. Planned in Next Four Years Program: 40,251I ! g. Remaining Deficiency: 2,10( 1 t1. Grand Total: 1,075,48:3 13. PROJECTS REQUESTED IN THIS PROGRAM: (ZATEGORY ’ PROJECT TITLE ! :ODE 171-212 C-17 Modify Simulator Bays !3a. Future Projects: Included in the Following Program: (FY 2004) COST DESIGN STATUS SCOPE $000 S T A R T C M P L LS 1,144 Apr-02 Aug-03 Total 1,144 (FY2005) None !3b. Future Projects: Typical Planned Next Four Years: 111-111 Airfield Pavements 111-111 ALZ Land Acquisition 219-944 Base CE Complex 724-417 Construct Visitor Quarters LS 800 AC 9,551 SM 100 PN 4 17,000 1,232 10,019 12,000 40,251 43 E)c. Real Property Maintenance Backlog This Installation 1IO. An air mobility wing with one C-5 squadron, one C-17/C-141 squadron, and one KC-135 air refueling E;quadron -- responsible for training all C-5, C-17, C-141 and KC-135 aircrews in the Air Force. 1Il. Outstanding pollution and Safety (OSHA) Deficiencies: a. Air pollution 0 b. Water Pollution 0 c. Occupational Safety and Health 0 d. Other Environmental 148,000 I 1ID Form 1390,24 Jul 00 163 1. CaIPwmT Fy 2004 MILITARY CONSTRUCTION PROJRCT DATA (computer generated) AIRFORCR 3. INSTALLATIOHAND LOCATICW 4. PROJECT ALTgSAIR FORCRBASE, ORLAECWA C-17 w3DIFY SINDLATOR BAYS 5. PROGRAN 2. DATE KLgyKblT 6. CATXGORY CODR 41130 7. PROJRCI -xR - 0 2 3 0 0 4 171-212 9. TITLE COST ‘i-1 , ESTIWATES UHIT SIMULATOR RAY MDDIFICATION COST 720 L8 304 STJPPORTINI: FACILITIRS SUPPORTINI3 FACILITIES Ls SUBTOTAL .. ( 384) 1,104 1,104 TOTAL CONTRMT COST SDPER~SION, INSPRCTION AND OVERBEAD ( 5.7 63 %I TOTAL REQUEST 1,167 TOTAL REQUEST (ROUNMD) 1,167 Iustall uew roll-up doors, modify bridge 10. Descriptiof-of Proposed Coustruction: crane for l-ton Wpacity, replace carpeting in classrocem, repair ccnnputer roam flooring, upgrade chiller for simulators, modify fire protection/detection systems, and new electrical errvice for simulators. 11. RRQlJIRRMRNT: PROJECT: ADBQUATB: C-17 modify simulator bays. SUBSTANDARD: (New Niseion) The plus up of C-17 aircraft require additional training simulators to RRQUIRRblRNT: support this aircraft training mission. CURRRNT SITKIATION: The Air Force C-17 fleet is increasing end Altus as a primary training base will receive additional aircraft. Additional training simulators are required to support increased pilot production. Rxisting simulator bays require modifications to accommdate C-17 simulators. IMPACT IF ROT PROVIDED: Simulators are required to minimize the cost of actual aircraft flying hours and facilities must be prepared to house simulators. Pilot production will be adversely impacted if the facilities are not modified in order to accozmnodate the C17 simulators. This project meets the criteria/scope specified in Air Force Handbook 32ADDITIONAL: 1004, Facility Requirements. A preliminary analysis of reasonable options for accomplishing this project indicates there is only oue option that will satisfy operational require4nents. therefore, a full ecoucmic analysis was not performed. A certificate of exermption has been prepared. Base Civil Engineer: Lt Co1 Robert NcCaugham, (580) 481-6530. JOINT USE CRRTIFICATION: This facility can be used by other components on an "aa available" basic, however, the scope of the project is based on Air Force requirements. DD FORM 1391, DEC 76 Previous editions are obsolete. Page No. 164 1. COxPONmT yY 2004 WILITARY CONSTRUCTION PROJECT MTA 2. DATR (ccmputer generated) AIR FORCE 3. INSTALLATION = I&CATIOW 4. PROJECT TITLE ALTUS AIR PORCR RASE, ORLAECWA C-17 WCDIFY SIWIILATCR BAYS 5. PROCXAW Ew 6. CATEGORY CODE 7. PROJRCT NDWRRR 41130 171-212 8. PROJRCI CDST ($000) AooNO23004 1,167 12. SUPP-AL DATA: a. Estimated Design Data: (1) Status: (a) Date Design Started (b) Parametric Cost Estimates used to develop costs l (c) Percent Complete as of 01 JAN 2003 * (d) Date 35% Designed (e) Date Design Ccdnplete (f) Energy Study/Life-Cycle analysis was/will be performed 02-APR-02 YES 15% lo-SEP-02 20-AUG-03 YES (2) Basie: (a) Standard or Definitive Design (b) Where Design Was West Recently Used - NO (3) Total Cost (c) - (a) + (b) or (d) + (e): (a) Pr&tion of Plane and Specifications (b) All Other Deeign Costs (c) Total (d) Contract (e) In-house ($000) 72 36 108 96 12 (4) Construction Contract Award 03 DEC (5) Construction Start 04 JAN (6) Construction Completion 04 SEP l Indicates ccrmpletion of Project Definition with Parametric Cost Estimate which is conqarable to traditional 35% design to ensure valid scope, cost and executability. b. Equipment associated with this project provided from other appropriations: N/A ID FORM 1391, DEC 76 Previous editions are obsolete. Page No. 165 AIR FORCE I INSTALLATION AND LOCATION TINKER AIR FORCE BASE ICOMMAND: AIR FORCE MATERIEL I AREA CONST S OF 30 SEP 02 Authorization Not Yet in Inventory: Authorization Requested in this Program: Authorization Included in the Following Program: Planned in Next Four Years Program: (FY 2005) 2552.775 59,254 19,060 40,687 238,700 120,775 3,031,251 PROJECT TITLE Building 3001 Revitilization, Phase 1 Cohsolidate Software Support Facility Consolidated Fuel Overhaul, Repair, and Test Facility 2,726 SM 8,000 141-753 ADAL Squadron Operations Facility 2,320 SM 2,400 211-111 Multipurpose 3-Bay Hangar LS 50,000 211-152 Sheet Metal Facility LS 28,500 Building 3001 Revitalization, Ph 2 211-157 LS 20,000 Building 3001 Revitalization, Ph 3 LS 10,000 211-157 Alter Chemical Cleaning Shop 3,020 SM 17,500 211-157 217-742 31st Combat Comm Squad Ops Fat 3.400 SM 9,700 32nd Combat Comm Squad Ops Fat 3,900 SM 217-742 8,800 33rd Combat Comm Squad Ops Fat 4,000 SM 7,800 2 17-742 Comm SqdnllT Dir ABW 10,000 LS 217-742 LS 11,500 Air Base Wing HQ / Law Center 610-I 12 Replace Building’s 4023, 4024, and 2,500 LS 61 O-249 120 RM 8,000 Dormitory 721-312 10,000 Security Forces Squadron LS 731-835 5,000 Child Development Center 2,147 SM 737-884 Alter Primary Overhead Distribution Line 69,000 LM 13,000 812-223 2,600 8,400 LM Extend and Upgrade Gas Mains 824-464 9c. Real Proper-y Maintenance Backlog This Installation 10. Mission or Major Functions: Oklahoma City Air Logistics Center which is responsible for logistics management, support, and depot-level maintenance, repair and overhaul of B-l, B-2, B-52, KC-135 and aircraft and aircraft engines; an air base wing; an Air Combat Command air control wing with four E-3 airborne air control squadrons supporting 24 E-3 aircraft; an Air Force Reserve Command air refueling v with one KC-l 35 squadron; an Air Combat Command combat communications group; and an engineerir installation wing. 166 AIR FORCE COMMAND: INSTALLATION AND LOCATION AIR FORCE MATERIEL TINKER AIR FORCE BASE COMMAND: OKLAHOMA 11. Outstanding pollution and Safety (OSHA Deficiencies: a. Air pollution b. Water Pollution c. Occupational Safety and Health d. Other Environmental 5. AREA CONST COST INDEX 0.89 0 15,192 0 540 167 2 . FY 2004 MILITARY CONSTRUCTION PROJECT DATA 1. coMPoNmT AIR FORCE DATE (computer generated) 3. INSTALLATION AND LGCATION 4 . PRChlECI TINKER AIR FORCE BASE, OICLABOMA BUILDING 3001 REVITALIEATION, PHASE I 5. PROGRAM ELEMENT TITLE 6. CATBGORY CODE 7. PROJECT NUMBER 72896 Auk Approp: wwYK033003 211-157 9. 8. PROJECT COST ($000) COST 19,444 19,060 ESTIMATES UNIT BUILDING 3001 REVITALIEATION, PBASE I COST LS 17,600 CIVIL INFRASTRUCTURR LS ( 4 , 3 0 0 1 MCBANICAL INFRASTRlJCTURR LS ( ELECTRICAL INFRASTRUCTURB LS ( 6 , 1 0 0 1 7,200) SUPPORTING FACILITIES 0 SUBTOTAL 17,600 CGNTINGRNCY ( 5.0 %) 880 T O T A L CONTRACl’ C O S T 18,480 SUPERVISION, INSPECTION AND GVBRBBAD ( 5 . 7 %) 1,053 TOTAL REQUEST 19,533 TOTAL REQUEST (ROUNDED) 19,444 EQUIPMENT FROM OTHER APPROPRIATIONS (NON-ADD) ( 8 , 0 0 0 ) Description of Proposed Construction: Renovate the shop include ventilation, structure, trench drainage, electrical, xnqe and piping. Project aleo includes demolition, repair of &long with aeeociated work to meet current building codes and LO. 11. RRQUIRRMRNT: ?ROJECT: 253.712SM ADEQUATR: 100.552 SM Building 3001 Revitalization, Phase I. area of Building 3001 to lighting, fire protection, roof, concrete flooring, safety requirements. SUBSTANDARD: 153,160SM (Current Mimion) ZBQUIREMBNT: This project ie required to provide an effective use of the existing work apace in building 3001 to meet current and future depot workload in support of TF33, ?lOl, F108, FllO and the FlOO jet engines. Utility syetem infrastructure upgrades are ieeded to provide a reliable source of electricity, heating and cooling for the various !roceseee in the facility. Renovation of the existing work apace is required to improve process flow times, enhance the working environments for compliance with the )ccupational Safety and Health Act (OSHA), provide acceeaibility for preventive and remedial maintenance, and extend the service life of the facility. Reconfiguration of :he Building 3001 industrial area is an element of the AFMC/OC-ALC long term Depot strategy to improve Programmed Depot Maintenance (PDF0 proceeees and timelinee to better mpport warfighter readinese. QRRENT SITUATION: Present Propulsion workload (jet engine repair, maintenance and xrerhaul) and a significant portion of Airborne Acceeeoriee workload (both engine and airframe accessories) is performed in building 3001. This facility is approximately 60 rears old and has utility systems that have reached their limited capacity and are in leed of replacement. Power outages and heating and cooling failures have resulted in lelaye in the process flow and impacted the ability of the ehope to support PDM on many aircraft worked on at Tinker AFB, OK. Over the years the existing shop area8 have been adjusted to accomamdate the changing workloads resulting in shops that are overcrowded md processes that have been piecemealed together. Lack of funding hae limited the Iffort to reconfigure and realign the existing shops in a modern and efficient procese for engine overhaul and PDM for the KC-135 aircraft. DD FORM 1391, DEC 76 Previous editions are obsolete. Page No. 168 1. COMPONENT FY 2004 MILITARY C O N S T R U C T I O N AIR FORCE (computer 3. INSTALLATION AND LOCATION 12896 DATA 2 . DATE 4. PROJECT TITLE BUILDING 3001 REVITALIZATION, PHASE I TINKER AIR FORCE BASE, OKLAHOMA 5. PROGRAM ELEMENT PROJECT generated) 6. CATEGORY CODE 211-157 7. PROJECT NUMBER wwYKo33003 8. PROJECT COST ($000) 19,444 IMPACT IF NOT PROVIDED: Tinker AFB'B goal to achieve effective and efficient space utilization and work-flow/production practices will not be realized in accordance with AF'MC/OC-ALC Long Term Depot Strategy. Working conditions will not be improved. Pereonnel safety will be put at risk. Processes will become longer and create significant impact to Depot long term goals. ADDITIONAL: This project is the first phase of a ten phased effort to revitalize building 3001. There is no criteria/scope specified for this project in Air Force Handbook 32-1084, "Facility Requirements." The requirement for this project was validated by the Joint Service Depot Maintenance Military Construction Review on 15 Aug 01. Base Civil Engineer: Wr. Dean Holt, (485) 734-3451. Design Build - Design Build Cost (4% of Subtotal Cost): $704,000. BASE CIVIL RNGINRER: MALLOTT JOINT USE CERTIFICATION: This facility can be used by other components on an "aa available" basis; however, the scope of the project is based on Air Force requirements. DD FORM 1391, DEC 76 Previous editions are obsolete. Page No. 169 1. COMPONRNT FY 2004 MILITARY CONSTRUCTION PROJECT DATA (computer AIR FORCE 2. DATE generated) 3. INSTALLATION AND LOCATION 4. PROJECT TITLE TINKER AIR FORCE BASE, OKLAEOMA BUILDING 3001 REVITALIZATION, PEASE I 5. PROGRAM ELEMENT 6. CATEGORY CODE 7. PROJECT NUMBER 72896 211-157 8. PROJECT COST ($000) 19,444 WWYEo33003 12. SUPPLEMENTAL DATA: a. Estimated Design Data: (1) Project to be accomplished by design-build procedures (2) Basis: (a) Standard or Definitive Design (b) Where Design Was Most Recently Used - NO 528 (3) All Other Design Costs (4) Construction Contract Award 03 DEC (5) Construction Start 04 JAN (6) Construction Completion 05 AU0 (7) Energy Study/Life-Cycle analysis was/will be performed YES b. Equipment associated with this project provided from other appropriations: PROCURING APPRO FISCAL YEAR APPROPRIATED OR REQUESTED 3010 2004 EQUIPMENT NOMENCLATURE INITIAL OUTFITTING EQUIPMENT DD FORM 1391, DEC 76 Previous editions are obsolete. COST ($000) 8 , 0 0 0 Page No. 170 AIR MOBILITY COMMAND ‘. INVENTORY DATA ($000) ‘otal Acreage: 3,733 nventoty Total as of : (30 Sep 02) 822,985 iuthorization Not Yet in Inventory: \uthorization Requested in this Program: iuthorization Included in the Following Program: ‘Ianned in Next Four Years Program: Remaining Deficiency: brand Total: 43,2OC 8,862 C 51,25f 1,8OC 928,105 (FY 2005) 1. PROJECTS REQUESTED IN THIS PROGRAM: aZATEGORY PROJECT TITLE ZODE Dormitory ‘21-213 )a. Future Projects: Included in the Following Program: )b. Future Projects: Typical Planned Next Four Years: PROJECT TITLE ZODE Repair Airfield Pavements 111-111 Civil Engineer Complex ! 19-000 Dormitory ‘21-312 Child Development Center 740-884 Airfield Lighting Vault 311-149 IC. Real Propery Maintenance Backlog This Installation (FY 2004) COST DESIGN STATUS SCOPE $,OOO S T A R T C M P L 144 RM Sep-0: 8,863 Apr-02 Total 8,863 NONE (FY2005) 141,071 SM 6,016 SM 144 RM 3,800 SM 1,005 SM 8,758 18,500 9,800 9,600 4,600 62 0. Mission or Major Functions: Support of two military airlift wings, one active and one reserve associate; a lint-use airfield supporting international cargo, and general aviation operations terminals; and a remote training lit-field simulation forward operations conditions. 1. Outstanding pollution and Safety (OSHA Deficiencies): a. Air pollution 0 b. Water Pollution 0 c. Occupational Safety and Health 0 d. Other Environmental 0 ID Form 1390,24 Jul 00 1. CamamFf 112004 lULITARYCOHSTRUCFIOAJPROJRCT DATA 2. DATE (computer germrated) AIR FORCE 3.mSTALLATImvmmcATIm 4. PROJECT TITLE amLmToHAIRFoRcRBAsR, DoRllIToRY (144 Rx) 5.pROGRANm souTEcARoLIuA 6. CATEGORY ODE 7. PROJECT - 41896 721-312 9. DKFXO63001 / Approp: 9,042 8,863 71 UNIT COST cosTRsTnmTRa DORMITORY (144 RX) Ls DORMITORY SW PROTBCTIa ANTITRRRORISHFORCE SUPPORTING 8. P 6,518 4,752 1,335 Ls FACILITIES ( 6,344) ( 174) 1,605 DTILITIES Ls ( 515) PAWS Ls ( 292) SITE IMP-s Ls ( 599) SEISHIC Ls ( 200) SUBTOTAG 8,123 corn- 406 'IrS.0 $1 TOTAL COSTRUT COST SDPERvIs1oII. 8,529 IusPKTI~AmJOvEREEm ( 6.0 $1 512 TOTAL REQUEST 9.041 TOTAL REQUEST (ROUSDID) 9,042 RQDIPl4EWI FROXOTEERAPPROPIUATIONS (NON-ADD) ( 1.400) LO. Description of Proposed Construction: Constructs new three-story structure with reinforced concrete fouudation and floor slab, masonry walls, roof, and fire protection. Site rork to Mrwe drainage and provide appropriately landscaped n greeu area. within the dorm campus. Includes rocmr-bath-room mod&lee, laundry rorxas, storage md lounge areas, campus parking, and support. Air Conditioning: 11. RRQUIREblENT: PROJECT: 108 lcw. 899 Rw Grade Xix: El-E4 ADEQUATE: 537RF4 144 SUBSTANDARD: 21SRM Construct a dormitory. (Current Mission) RRQUIRRMENT: It is a major Air Force abjective to provide unaccompanied enlisted personnel with housing conducive to their proper rest, relaxation, and personal wall being. Properly designed and furnished quarters providing scene dagree of individual privacy are essential to the successful acccenpliehment of the increasingly complicated and importapt jobs these people must perform. Private vehicle parking, landscaping, and adequate antiterrorism/force protection measures are required to appropriately c0mplete a new dormitory campus area/green space. There are currently not ermugh adequate dormitories to meet the CDRRRNT SITUATIOlp: billeting requirements of unaccompanied enlisted personnel at this base. Eligible unaccompanied enlisted persoPne1 in the grades of E-l through R-4 non-career, must reside off-base. Due to the distance (15 to 30 minutes driving time) frcrm adequate local cmmmnity housing and limited transportation, off-base housing is not attractive nor affordable for many junior enlisted personnel. IMPACT IF NOT PROVIDED: Substandard living conditions will persist and morale, Productivity, and career satisfaction of the enlisted force will continue to be Failure to provide adequate living conditions will jeopardize the ability to degraded. DD FORM 1391, DEC 76 Previous editions are obsolete. Page No. 1. CCHPCNZNT FY 2004 MILITARY CCNSTRUCTION PROJRCT DATA 4. PROJECT TITLE 3. INSTALLATION AND LOCATION CEARLESTONAIR FORCE BASE, SOUTH CAROLINA 5. PROGRAM ELEldENT 41896 2. DATE (ccmputer generated) AIR PDRCR 6. CATEGORY CODE 721-312 IXXMITORY (144 RM) 7. PROJECT NUMBBR DRPXO63001 8. PROJRCI COST ($000) 9.042 attract and retain the quality personnel eseential to the defense of our country and perform DOD missions throughout the world. ADDITIONAL: This project meats the criteria/scope specified in OSD's new uniform barracks size standard. All known alternatives were considered during development of this project. No other option could meet mission requirements. Therefore, no econdc analysis was needed or performed. Unaccoxqanied Housing RPM: FYOl - $283K, FY02 $466X. Estimated Unaccoqanied Housing RPM: PYO3 - $35OK, PYO4 - $35OK, and FYO5 Base Civil Engineer: Lt Co1 Dowling, (843) 963-4956. Dormitory: 4752 SX I $45OK. 51,132 SF. JOINT USE CERTIFICATION: This facility can be used by other ccmponents on an "as available" basis; however, the scope of the project is based on Air Force requiraments. DD FORM 1391, DEC 16 Previous editions are obsolete. Page No. 1. COWPGNKWT PY 2004 WILITARY CONSTRUCTION PROJECT DATA (ccmputer generated) AIR FORCE 3. INSTALLATION AND LOCATION 4. PROJECT TITLE DORMITORY (144 RW) CHARLRSTGN AIR PGRCR BASE, SOUTR CAROLINA 5. PROGRAM ELRWRWI 2. DATE 6. CATEGORY CODE 7. PRGJECT NDWBRR 8. PRCIJRCI COST ($000) 41896 721-312 DRFXO63001 9,042 12. SUPP LRWENTAL DATA: a. Estimated Design Data: (1) Project to be accomplished by design-build procedures (2) Basis: (a) Standard or Definitive Design (b) Where Design Was Most Recently Used - No (3) All Other Design Costs 250 (4) Construction Contract Award 03 DEC (5) Construction Start 04 JAN (6) Construction Completion 05 JUL (7) Energy Study/Life-Cycle analysis was/will be performed YES b. Equipmant%sociated with this project provided from other appropriations: RGCURING APPRO PISCAL YEAR APPROPRIATED OR RRQURSTRD COST (SOOO) 3080 2006 1,400 EQUIPWENT NOWRNCLATURR COWPRRRENSIVR INTERIOR DESIGN DD FORM 1391, DEC 76 Previous editions are obsolete. Pags No. 174 ~. COMPONENT 1 FY 2004 MILITARY CONSTRUCTION PROGRAM 12. DATE AIR FORCE I 4. COMMAND: 5. AREA CONST I. INSTALLATION AND LOCATION COST INDEX AIR EDUCATION AND ;OODFELLOW AIR FORCE BASE TRAINING COMMAND 0.81 :EXAS STUDENTS PERMANENT SUPPORTED i. Personnel ENL OFF ENL CIV CIV OFF ENL CIV OFF strength 4s OF 30 SEP 02 960 3226 2740 450 2909 78 1680 84 :ND FY 2007 a47 2763 2739 439 2819 78 1680 84 ‘. INVENTORY DATA ($000) 1. Total Acreage: 1,002 1. Inventory Total as of : (30 Sep 02) :. Authorization Not Yet in Inventory: I. Authorization Requested in this Program: (FY 2005) 3. Authorization Included in the Following Program: . Planned in Next Four Years Program: 1. Remaining Deficiency: 1. Grand Total: $. PROJECTS REQUESTED IN THIS PROGRAM: ZATEGORY PROJECT TITLE ZODE Fire Training Classroom Facility 171-621 ‘21-312 Student Dormitory )a. Future Projects: Included in the Following Program: TOTAL 12,12;7 11,44! 3 362,37! 5 (I 19,97( I (I 39,20( I 22,00( I 443,54t 5 (FY 2004) COST DESIGN STATUS1 SCOPE $.OOO S T A R T C M P L 785 SM 1,863 Mar-02 Aug-03 200 RM 18,107 Apr-02 Sep-03 Total 19,970 (FY2005) None )b. Future Projects: Typical Planned Next Four Years: 131-111 Communications Operations Complex 171-623 Intel Academic Training Facility ‘36-773 Chapel Center 3,559 SM 12,542 SM 1,680 SM 6,900 29,000 3,300 )c. Real Property Maintenance Backlog This Installation IO. Mission or Major Functions: A training wing providing technical training in cryptology, intelligence, inguistics, and firefighting career fields. Il. Outstanding pollution and Safety (OSHA) Deficiencies: 0 a. Air pollution b. Water Pollution 0 c. Occupational Safety and Health 0 d. Other Environmental 0 6; ! ID Form 1390,24 Jul 00 175 FY 2004 MILITARY CONSTRUCTION PROJECT DATA 1. COWPONRNT 2. DATE (cmter generated) AIRFDRCR 3. INSTALLATION AND LOCATION 4. PROJECT TITLE GOODFRLLOWAIR rORCE RASE, TRYAS FIRR TRAININg 5. PRMRAW ELRWRNT 6. CATEGORY CODR 84731 171-621 9. 7. PROJECT NUMBER CLASSROOM FACILITY 8. PROJECT COST ($000) JC(NO33002 COST 1,863 ESTIMATES UNIT Ls FIRE TRAINING FACILITY TRAINING FACILITY SM AWI'ITRRRORISW FCRCR PROTECTION Ls SUPPORTINa COST 1,519 785 1,925 ( 1,511) ( FACILITIES 8) 176 Ls Ls Ls Ls UTILITIES PAVEMENTS SITE IMPROVEWENTS COWWDNICATIONS ( suwroTArJ 96 ( 40 ( 28 ( 12 1,695 ( 5.0 %) ~ONTINOXEY 85 TOTAL CONrRAcT COST SUPRRvISION, 1,780 INSPECTION AND Uv5MRAD ( 5.7 %) 101 TOTAL REQUEST 1,881 TOTAL REQUEST (ROUNDED) 1,863 - Description of Proposed Construction: Reinforced concrete foundation aud floor reinforced masonry walls with brick veneer, steel frame, standing seam metal roof system, and landscaping. Includes all utilities and force protection as required. Pre-wire for data connectivity and video projection. Construct covered walkway to &cademic building. Comply with DoD interim minimum force protection construction standard. LO. slabs, 75RW. nir Conditioning: 11. RRQuIRRWRNT: ?ROJECT: 12,853SW ADEQUATE: 12,068 SW SUBSTANDARD: OSM Construct a fire training classrocmm facility. (New Mission) The FYO3 Training Flow Management Conference (TFWC) meeting minutes UEQUIRXMENT: identified the firefighter apprentice course as a constrained course beginning in FY03 mcause course could not meet demauds of the field with regard to number of trained The FY03 TPR is 1,742 while the DoD Fire Acadtwqy's maw personnel required (TPR). :aDacity is 1,600. In order to meet FY03 TPR, the Academy must shift from starting 2 :lasses of 10 students every 3 days (80 starts per year) to a schedule that permits 13 additional classrocms are required -lass starts every 2 days (122 starts per year). :o support this new schedule. Each classrm has unique, stand-alone, semi-permanent xaining aids that students must process thru in assembly- line fashion. Classrocm requirements are predicated on the number of class starts required to meet the TPR. :lass starts are a function of instructor availability. The FY 03-05 TPR is an increase >f approx 142 students with a desired optimum capacity of 2440, up 840 from current max. --DRRRWT SITUATION: The Fire Academy is currently teaching its maximun 1,600 students muually for all four services in 22 classrooms. Thirteen new classrooms are required :o support this new TPR. We expect this increased student load to be a permanently DD FORM 1391, DEC 76 Previous editions are obsolete. Page No. 1. COMPONENT 1LIR FY 2004 MILITARY CONSTRUCTION PRCJRCT DATA FORCE 3. INSTALLATION AND I&CATION 4. PROJECT 3OODFELLOW AIR FORCE BASE, TEXAS FIRE TRAINIE%3 5. PROGRAM 2. MTE (caaputer generated) RLEMENT 84731 6. CATEGORY CODE 7. PROJECT 171-621 TITLE NUBIRRR JCGUO33002 CIASSROW FACILITY 8. PROJRCT COST ($000) 1,863 i ncreased TPR, as stated above. The firefighter career field is currently the third most stressed field in the Air Force and firefighters are being stretched to c&er the numerous tasking8 overseas and at ham as a result of Operation Rnduring Freedaa and H aaelaud Security requirements. IXPACT IF NOT PRWIDRD: If not funded the DOD Fire Academy cannot produce the number of f irefighters the Air Force requires to meet contingency tasking8 and Hameland Defense There is no physical way to meet the increase in production without rrequirements. ashutting down other mission critical training such as Weapon of Mass Destruction t.raining for first responders, or urban search and rescue. We are prepared to shift to aL wartime schedule of training six days a week; however, this schedule is not a rustainable wer the several years readred to meet the production goals. This project meets the criteria/scope specified in Air Force Nandbook 32hDDITIONAL: 1.084, “ F a c i l i t y Requirements~. Base Civil Engineer: Lt Co1 Lance C. Iiafeli. (915) 65431464. iroxwr USR CERTIFICATION: This facility can be used by other compxents on an as atvailable basisi however, the scope of the project is based on Air Force requirements. DD FORM 1391, DEC 76 Previous editions are obsolete. Page No. 177 1. COldPONENT FY 2004 MILITARY CGNSTRUCTION PRGJRCT DATA (caqn3ter generated) AIRFORCE 2. DATE 3. INSTALLATION ARD LGCATIGN 4. PROSECT TITLR GGCDFRLLGWAIRFGRCRRASE, TRXAS FIRR TRAININGCLASSRGGRFACILITY 5. PROGRJM ELRMEWl' 6. CATEGORY CODE 7. 171-621 84731 12. SUPP LEMENTAL PROJECT NUHRKR 8. PROJECT COST ($000) JCGUO33002 1,863 MTA: a. Estimated Design Data: (1) Status: (a) Date Design Started (b) Parametric Cost Rstimates used to develop costs l (c) Percent Caaplete as of 01 JAN 2003 l (d) Date 35% Designed (e) Date Design Cauplete (f) Energy Study/Life-Cycle aualysis was/will be performed lo-MAR-02 YES 15% lo-SRP-02 lo-AUG-03 YES (2) Basis: (a) Standard or Definitive Desigu (b) Where Design Was Most Recently Used (3) Total Cost (c) = (a) + (b) or (d) + (e): (a) Production of Plans and specifications (b) All Other Design Costs (c) Total (d) Contract (e) In-house (4) Construction Contract Award No C$OOO) 112 56 168 150 18 03 DRC (5) Construction Start 04 JAN (6) Construction Cwletion 04 DEC l Indicates colqpletion of Project Definition with Parametric Cost Estimate which is comparable to traditional 35% design to ensure valid scope, cost and executability. b. Eguipmsnt associated with this project provided frau other appropriations: N/A ID FORM 1391, DRC 76 Previous editions are obsolete. Page No. 178 1. COMPONENT FY 2004 MILITARY CONSTRUCTION PROJECT DATA 2. DATE (computer generated) AIR FORCE t 3. INSTALLATION AND LOCATION 4. PROJECT TITLE GOODFELLOW AIR FORCE BASE, TEXAS 5. PROGRAW ELBWBBT STUDENT DORMITORY (200 RW) 6. CATEGORY CODE 85796 7. 721-312 9. PROJECT NUWBBR ESTIl PROJECT COST ($000) Auth: Approp: JCGUO13002 COST 8. 18,472 18,107 TES UNIT COST LLK ITEM SIWDENT DORMITORY (200-R&¶) LS 13,045 SM 9,750 1,260 TRAINING MANAGER SPACE SM 500 1,260 ABTITBRRORISM FORCE PROTECTION LS STUDBWTDORWITORY ( 12,285) i SUPPORTING FACILITIES ( 630) ( 130) 3,600 UTILITIES LS ( 1.590) PAVEMENTS LS ( 1,005) SITE IMPROvBWEWTS LS ( 850) COWMUNICATIONS LS ( 155) SUBTOTAL 16,645 ,CONTINGENCY ( 5.0 %) 832 I'OTAL CONTRACT COST 17,477 SUPERVISION, INSPBCIION AWD OVBRBEAD ( 5.7 %) 996 TOTAL RBQUBST 18,473 I'OTAL REQUEST (ROUNDED) 18,472 3 LO. Description of Proposed Construction: Wulti-story with reinforced concrete 1 !oundation/floor slabs, structural steel frame with brick veneer, and roof system. 1 Cncludes room-bath-room modules (two students per room), laundries, training managers crrea, storage, comPrmnications network, and all necessary support. Comply with DOD i interim minimum force protection construction standards. 1iir Conditionins: I11. REQUIREMENT: I ?ROJBCT: 507EW. 884RW Grade Yix: El-B4 ADEQUATE: 647 RW 400 SUBSTANDARD: 0 RM Construct a etudent dormitory. (Current Mission) I ZEQUIRBWBWT: < ,f students. Properly sized and configured dormitories are required to eupport training Air Force objective provides housing conducive to their proper 1rest, relaxation and personal well-being while providing a suitable study environment. I ?roperly designed and furnished quarters providing some degree of individual privacy, ire essential to the successful accomplishment of vital training requirements. This Comply with DOD xoject is in accordance with the Air Force Dormitory Waster Plan. A major interim minimum force protection construction standard. The base has insufficient on-base housing to accommodate the I ZURRBWT SITUATION: I unaccompanied enlisted technical training students. IMPACT IF NOT PROVIDED: Adequate student living quarters wlis continue XI be unavailable resulting in degradation of morale, productivity, and overall training effectiveness of unaccompanied enlisted personnel. Deplorable conditions for our new members of the Air Force have negative effects on retention and training. ADDITIONAL: The new OSD standard does not apply to housing constructed for members receiving entry-level skill training. This project is being designed to the Air Force technical training dormitory construction standard. All known alternative options were DD FORM 1391, DEC 16 Previous editions are obsolete. Page No. 179 1. COMPONENT FY 2004 MILITARY CONSTRUCTION PROJECT DATA AIR FORCE (computer 3. INSTALLATION AND LOCATION 4. PROJECT TITLE GOODFELLOW AIR FORCE BASE, TEXAS 5. PROGRAM ELEMENT 85796 2. DATE generated) 6. CATEGORY CODE 721-312 STUDENT DORMITORY (200 RM) 7. PROJECT NUMBER JCGUO13002 8. PROJECT COST ($000) 18,472 :onsidered during the development of this project. No other option could meet mission requirements. Therefore, no economic analysis was needed or performed. FYOl Unaccompanied Housing RPM Conducted: $l,315K; FYO2 Unaccompanied Housing RPM Zonducted: $106X. Future Unaccompanied Housing RPM Requirements (estimated): FYo3: illOK; FY04 : $113K; FY05: $116K. Base Civil Engineer: Lt Co1 Lance C. Hafeli, 1915) 654-3464. Student Dormitory: 10,250 SM = 110,290 SF. 3ASE CIVIL ENGINEER: Van De Walle TOINT USE CERTIFICATION: Mission requirements, operational considerations, and location Ire incompatible with use by other components. DD FORM 1391, DEC 76 Previous editions are obsolete. Page No. 1. COWPONEWT - FY 2004 MILITARY CONSTRUCTION PROJECT DATA (computer AIR FORCE 2. DATE generated) 3. INSTALLATION AND LOCATION 4. PROJECT TITLE STUDEWT DORMITORY (200 RW) GOODFELLOW AIR FORCE BASE, TEXAS I I I 6. CATEGORY CODE 17. PROJECT NUMBER 18. PROJECT COST ($000) 5. PROGRAM ELEMENT 1 85796 721-312 JCGUO13002 18,412 12. SUPP LEWENTAL DATA: a. Estimated Design Data: (1) Status: (a) Date Design Started (b) Parametric Cost Estimates used to develop costs l (c) Percent Complete as of 01 JAN 2003 l (d) Date 35% Designed (e) Date Design Complete (f) Energy Study/Life-Cycle analysis was/will be performed lo-APR-02 YES 15% 15-SEP-02 20-SEP-03 YES (2) Basis: (a) Standard or Definitive Design (b) Where Design Was Most Recently Used - NO (3) Total Cost (c) = (a) + (b) or (d) + (a): (a) Production of Plans and Specifications (b) All Other Design Costs (c) Total (d) Contract (e) In-house ($000) 831 461 1,292 1,015 277 (4) Construction Contract Award 03 DEC (5) Construction Start 04 JAN (6) Construction Completion 05 AU0 * Indicates completion of Project Definition with Parametric Cost Estimate which is comparable to traditional 35% design to ensure valid scope, cost and executability. b. Equipment associated with this project provided from other appropriations: N/A DD FORM 1391, DEC 16 Previous editions are obsolete. Page No. 181 AS OF 30 SEP 02 I c. Authorization Not Yet in Inventory: d. Authorization Requested in this Program: e. Authorization included in the Following Program: f. Planned in Next Four Years Program: g. Remaining Deficiency: h. Grand Total: (FY 2005) 8. PROJECTS REQUESTED IN THIS PROGRAM: CATEGORY PROJECT TITLE CODE 721-312 Student Dormitory 721-312 Student Dormitory I‘ 9a. Future Projects: Included in the Following Program: 721-312 Student Dormitory :9b. Future Projects: Typical Planned Next Four Years: ‘141-786 Consolidated Mobility Center ADAL Military Working Dog Tmg Cntr ‘171-623 Base PME Center, PME Library ‘171-815 ‘721-312 Dormitory ~721-312 Student Dormitory 721-312 Student Dormitory 722-351 New PP Dining Facility 730-835 Security Forces Consolidated Ops Fat 740-884 Child Development Center at LTA (FY 2004) SCOPE 200 RM 300 RM Total (FY2095) 200 RM Total 10,223 4,731 5.500 96 200 100 2,509 3.067 3,067 SM SM SM RM RM RM SM SF SF COST DESIGN STATUS $.OOO START CMPL 20,966 Apr-02 Sep-03 35.260 Apr-02 Sep-03 56,226 21,142 21,142 14,000 5,600 10,600 7.300 19.300 10.700 5.700 7.500 5,500 64 9c. Real Property Maintenance Backlog This Installation 10. Mission or Major Functions: A Training wing which includes Basic Military Training School, Air Force Security Forces Center, and security forces, cryptographic maintenance, recruting, and Air Force and Navy food service courses; Defense Language Institute English language Center; Department of Defense Military Dog Training Agency; Inter-American Air Force Academy; an Air Force reserve contingency hospital and training squadron, and a major Air Force medical center. 11. Outstanding pollution and Safety (OSHA) Deficiencies: 771 a. Air pollution b. Water Pollution 310 c. Occupational Safety and Health 0 d. Other Environmental 0 DD Form 1390,24 Jul 00 1. cOB¶PoNmT FY 2084 MILITARY CONSTRUCTION PROJECI DATA AIR FORCE DATE 2. (ccmputer generated) 3. INSTALLATION AND LOCATION 4. PROJECT TITLE LACELANDAIRFORC!BBASE, STUDENT 5. PROGRAB ELIWENT TEEM WRMITORY (200 RX) 8. PROJECT COST ($000) 6. CATRGGRY CODE 7. PROJECT NDMBER AlIti 85796 721-312 9. MPLSO13285 COST Approp: 21,389 20,966 ESTIMATES UNIT STUDENT WRBITORY (200 RFD LS STDDBNTDCRl4ITORY 13,863 SM TRAINING MANAGER SPACE ANTITBRROBISM FORCE PROTECTION SUPPORTING COST 9,750 1,333 500 1,333 ( 12,997) I? FACILITIES I ( 667) ( 200) 5,419 I UTILITIES LS ( 930) PAVEMENTS LS ( 445) SITE IMPROvEHENT.9 LS ( 578) CONMDNICATIONS LS ( 275) PIBR FODNDATION LS EEPANDABLBCBILl%RPLANT SM ASBESTOS/LBAD ABATEMENT LS DEMOLITION SM ( 1,250 1,454 6,416 80 ( SUBTOTAL 460) 1,818) ( 400) ( 513) 19,282 CONTINGENCY ( 5.0 %I 964 TOTAL CONTRACT COST 20,246 SUPERVISION, INSPEmION AND OVERHEAD 1,154 ( 5.7 %) TOTAL REQUEST 21,400 TOTAL REQUEST (ROUNDED) 21,389 10. Description of Proposed Construction: Multi-story with reinforced concrete foundation/floor slabs, structural steel frame with brick veneer, and roof system. Includes room-bath-room modules (two students per room), laundries, training managers area, storage, conmunications network, and all necessary support. Comply with DOD interim minimum force protection construction standard. Demolish 2 facilities (6,416 SN) . Air Conditioning: 11. REQUIREBENT: PROJECT: 980 KN. 1.472RM Grade Mix: El-E4 ADEQUATE: 725 Construct a student dormitory. 400 Dl SUBSTANDARD: 547RM (Current Mission) Properly sized and configured dormitories are required to support training REQUIREBEBT: of students. A major Air Force objective is to provide housing conducive to their proper rest, relaxation and personal well-being while providing a suitable studey Properly designed and furnished quarters providing some degree of environment. individual privacy, are essential to the successful accomplishment of vital training This project is in accordance with the Air Force Dormitory Baster Plan. reguirmts. Comply with DoD interim minimum force protection construction standard. CDRRENT SITUATION: The base has insufficient on-base housing to accommodate the uuaccampauied enlisted technical training students. IMPACT IF NOT PROVIDED: DD FORM 1391, DEC 76 Adequate student living quarters will continue to be Previous editions are obsolete. Page No. 1. comoNENT (computer generated) 4. PROJECT TITLE I. INSTALLATION AND LCXATION ;ACKLARD AIR FORCE BASE, TEXAS 5. PRCGRAMELKblKNT 85796 2. DATE FY 2004 MILITARY CONSTRUCTION PROJECT DATA LIR FORCE 6. CATEGORY CODE 721-312 STDDENT DORMITORY (200 RM) 7. PROJECT NIDBER KPLSO13285 8. PROJKCT COST ($000) 21,389 navailable resulting in degradation of morale, productivity, and overall training ffectiveness of unaccompanied enlisted personnel. Deplorable conditions for new smbers of the Air Force have negative effects on rentention and training. DDITIONAL: The new OSD standard does not apply to housing constructed for members eceiving entry-level skill training. This project is being designed to the Air Force ethnical training dormitory construction standard. All known alternative options ncluding conversion, leasing and status quo were considered during the development of his project. No other option could meet mission requirements. Therefore, no economic $4,OOOK; nalysis was needed or performed. FYOl Unaccqanied Housing RPY Conducted: Future Unaccompanied Housing RPM ~02 Unaccompanied Housing Conducted: $2, SOOK. equirements (estimated): FYo3: $2,2OOK; FyO4: $1,6OOK; FYOS: $ 1 , 0 0 0 . ase Civil Kngineer: Lt Co1 Spencer Patterson, Jr., (210) 671-2977. Student Dormitory: ,750 SM = 104.910 SF; Training Managers Area: 500 SM - 5,380 SF. DINT USE CERTIFICATION: Mission requirements, operational considerations, and location .re incompatiblewith use by other components. DD FORK 1391, DEC 76 Previous editions are obsolete. Page No. 1. COMPONENT 2. DATE FY 2004 MILITARY CONSTRUCTION PROJECT DATA (computer generated) AIR FORCE 3. INSTALLATION AND LOCATION 4. PROJECT TITLE LACKLAND AIR FORCE BASE, TEXAS STUDENT DORMITORY (200 RM) 5. PROGRAM ELEWEWT 6. CATEGORY CODE 7. PROJECT NUKBER 85796 721-312 8. PROJECT COST ($000) WPLSO13285 21,389 12. SDPP LEtdENTAL DATA: a. Estimated Design Data: (1) Status: (a) Date Design Started (b) Parametric Cost Estimates used to develop costs l (c) Percent Complete as of 01 JAW 2003 l (d) Date 35% Designed (e) Date Design Ccarplete (f) Energy Study/Life-Cycle analysis was/will be performed (2) Basis: (a) Standard or Definitive Design (b) Where Design Was Most Recently Used - lo-APR-02 YES 15% lo-SEP-02 15-SEP-03 YES YES LACKLAND (3) Total Cost (c) = (a) + (b) or (d) + (e): (a) Prowtion of Plans and Specifications (b) All Other Design Costs (c) Total (d) Contract (e) In-house ($000) (4) Construction Contract Award 03 DEC (5) Construction Start 04 JAW (6) Construction Coqletion 05 DEC l 856 535 1,391 1,070 321 Indicates completion of Project Definition with Parametric Cost Estimate which is comparable to traditional 35% design to ensure valid scope, cost and executability. b. Equipment associated with this project provided from other appropriations: N/A DD FORM 1391, DEC 76 Previous editions are obsolete. Page No. 185 1. coMPoNRNT 2. DATE PY 2004 MILITARY CONSTRUCTION PROJECT DATA AIR FORCE (caovuter generated) 3. INSTALLATION AND LGCATION 4. PROJECT TITLE LACKLAND AIR FORCE BASE, TRXAS STUDENTDGRMITGRY (300 ROOMS) 5. PRGGRAM ELKKEUP 8. PROJECT COST ($000) 6. CATEGORY CODE 7. PROJECT NUMRKR I 85796 I 721-312 9. I AWLS023721 COST EST1 Auth: Approp: 35.971 35,260 .TEI - COST UNIT 300 0 14,625 1,333 2,177 2,448 STUDIWT DORMITORY (300 RM) STUD= IZORMITORY DINING FACILITY 26,406 ( 19,495) ( ANTI-TERRORISM FGRCE PRGTRCTION TRAINING UANAGER SPACE 500 1,333 SUPPORTIM3 FACILITIES 5,329) ( 915) ( 667) 6,031 UTILITIES Ls PAWS Ls ( 860) S I T E IUPROVEURNTS Ls ( 575) PIER PGUNDATION L s ( 710) Ls ( 405) CONUUNICATIONS , ( su RXPANDASLEMILLERPLANT 1,500 1,454 ( SUBTOTAL 2,181) 32,437 C0mmKJEmY TOTAL 1,300) CO-T BUPERVISION, 1,622 ( 5.0 %I COST 34,059 INSPECTION AND GVEMEAD 1,941 ( 5.7 %) I'OTAL REQUEST 36,000 TOTAL REQUEST (ROUNDED) 35,971 - Description of Proposed Construction: kulti-story facility with reinforced :oncrete pier foundation/floorslabs, structural steel frame with brick veneer. Cncludes room-bath-roan modules to pipeline dorm standard (two students per roam), laundries, training managers area, storage, cc0mun ications network, 1500 pn dining iall, ana all necessary support. Ccqply with DoD interim minimum force protection :onstruction standard. LO. tir Conditioning: 11. REQUIREMENT: ?RGJRCT: 15ooRw. 1,472RM A D E Q U A T E : 725RAl Construct a student dormitory. SUBSTANDARD: 547RM ( N e w Uission) ZEQ-: Properly sized and configured dormitories are required to support the increased training requirement for the Security Forces Apprentice course and Basic lfficer course. USAF directed an increase security forces pipeline production of 450 Prior to the events of 11 Sept there was a plan which included a raduates for FYO2. The 11 phased training schedule which increased training days from 51-days to 81-days. ;ept event increased awareness of the need for adeguate security and identified a need :o expedite the plan on a war-time footing. -URRRNT SITUATION: we have an urgent and compelling need to *rove security forces :raining in support of force protections operations worldwide. Given the threat and security forces training shortfalls it is critical this training effort be expedited on mrtime footing to meet field coamanders force protection vulnerabilities as quickly as mssible. Currently, the Security Forces Apprentice course is operating at Lackland APB DD FORM 1391, DEC 76 Previous editions are obsolete. Page No. 186 1. COMPONENT FY 2004 MILITARY CONSTRUCTION PROJECT DATA (computer generated) AIR FORCE 3. INSTALLATION AND LOCATION 4. PROJECT TITLE LACKLAND AIR FORCE BASE, TEXAS STUDKNTDORMITORY 5. PROGRAM ELEMENT 85796 2. DATE 6. CATEGORY CODE 7. PROJECT NUMBER 721-312 MPLS023721 (300 ROOMS) 8. PROJECT COST ($000) 35,971 and Camp Bullis. The Basic Officer course is operating at Camp Bullis. The student 1oad for the Apprentice course at Lackland is projected to be 1,601 bed spaces. Lackland can only support an ADSL of 1008 bed spaces. This leaves a shortfall of 593 bedspaces. Construction of a 300- room (600~person) dormitory, dining hall and support Spaces is necessary to support the increased ADSL. IMPACT IF NOT PROVIDED: Adequate on-base quarters are needed to support the Security F 'orces Apprentice course at Lackland Air Force Base. Lackland has insufficient on-base h .ousing to acccumoda te these additional pipeline students. The inability to do this will r esult in an increased cost to the Air Force for off-base housing and will *act 8 ecurity forces pipeline production and the Air Force’s ability to provide combat ready f orces who are trained in dealing with either a homeland base defense operation or f onvardly deployed in a hostile urban environment. The new OSD dormitory standard does not apply to housing constructed for l! DDITIONAL: mmnbers receiving entry-level skill training. This project is being designed to the A .ir Force technical training gpipelinem construction standard. All known alternatives wrere considered during the develomnt of this project. No other option could meet mLission requirements, therefore, no econdc analysis was needed or performed. FYOl unaccompanied Housing RPM Conducted: $4,OOOK; FYO2 UnacccmBmnied Housing RPM Clonducted: $2,5OOK -Future Unaccompanied Housing RPM requirements (estimated): FY03r $1,6OOK; FYO5: $l,OOOK. Base Civil Engineer: Lt Co1 Spencer S 2,OOOK; FYo4: P'atterson, Jr., (210) 671-2977. Student Dormitory: 14,625 SM = 157,365 SF. 9'OINT USE CERTIFICATION: This facility can be used by other ccqponents on an “as a,vailable" basis, however, the scope of the project is based on Air Force requirements. L DD FORM 1391, DEC 76 Previous editions are obsolete. Page No. 187 1. COMPONENT FY 2004 MILITARY CONSTRUCTION PROJECT DATA AIR FORCE 2. DATE (computer generated) 3. INSTALLATION AND LOCATION 4. PROJECT TITLE LACELAND AIR FORCE BASE, TEXAS STUDENT DORMITORY (300 ROOMS) 5. PROGRAM ELEMENT 6. CATEGORY CODE 7. PROJECT NUMBER 85796 721-312 8. PROJECT COST ($000) MPLSO23721 35,971 12. SUPPLEMENTAL DATA: a. Estimated Design Data: (1) Status: (a) Date Design Started (b) Parametric Cost Estimates used to develop costs l (c) Percent Complete as of 01 JAN 2003 l (d) Date 35% Designed (e) Date Design Cmlete (f) Energy Study/Life-Cycle analysis was/will be performed (2) Basis: (a) Standard or Definitive Design (b) Where Design Was West Recently Used - 04-APR-02 YES 15% 20-SEP-02 22-SEP-03 YES YES LAcKLAND (3) Total Cost (c) = (a) + (b) or (d) + (e): (a) Production of Plans and Specifications (b) All Other Design Costs (c) Total (d) Contract (e) In-house ($000) 1,439 900 2,339 1,799 540 (4) Construction Contract Award 03 JAN (5) Construction Start 04 FEB (6) Construction Ccnnpletion 05 DEC l Indicates ccanpletion of Project Definition with Parametric Cost Estimate which is comparable to traditional 35% design to ensure valid scope, cost and executability. b. Equipment associated with this project provided frc%a other appropriations: N/A I DD FORM 1391, DEC 76 Previous editions are obsolete. Page No. FY 2004 MILITARY CONSTRUCTION PROGRAM I. COMPONENT 2. DATE AIR FORCE 3. INSTALLATION AND LOCATION 4. COMMAND: 5. AREA CONST SHEPPARD AIR FORCE BASE AIR EDUCATION AND COST INDEX TEXAS TRAINING COMMAND 1 0.94 PERMANENT 6. Personnel STUDENTS SUPPORTED OFF ENL CIV OFF ENL CIV Strength OFF ENL CIV TOTAL AS OF 30 SEP 02 588 2696 2653 371 4040 0 137 1792 129 12,406 END FY 2007 572 2438 2661 380 3918 0 137 1792 129 12,027 7. INVENTORY DATA ($000) a. Total Acreage: 5,719 b. Inventory Total as of : (30 Sep 02) 1,765,299 c. Authorization Not Yet in Inventory: 53,000 d. Authorization Requested in this Program: 28,590 e. Authorization Included in the Following Program: (FY 2005) 21,284 f. Planned in Next Four Years Program: 164,600 g. Remaining Deficiency: 39.000 h. Grand Total: 2,071,773 -I 8. PROJECTS REQUESTED IN THIS PROGRAM: (FY 2004) CATEGORY COST DESIGN STATUS CODE PROJECT TITLE SCOPE $.OOO START CMPL -~ 721-312 Student Dormitory 300 RM 28,590 Apr-02 Sep-0: Total 28,590 9a. Future Projects: Inclided in the Following Program: (FY2005) 171-625 F-22 Technical Training Facility 11,368 SM 21,284 Total 21,284 9b. Future Projects: Typical Planned Next Four Years: 113-321 Base Operations Ramp 40,067 SM 7,200 141-453 Airfield Ops Center 2,366 SM 9,000 171-627 Repl Trainer Maim/Development Facility 10,688 SM 20,000 171-627 Training Support Facility 5,575 SM 10,500 721-312 Dormitory 144 RM 10,600 721-312 Student Dormitory 300 RM 31,700 721-312 Student Dormitory 300 RM 33,200 721-312 Student Dormitory 300 RM 28,100 740-884 Child Development Center 3,500 SM 14,300 44 9c. Real Property Maintenance Backlog This Installation IO. Mission or Major Functions: A Training wing responsible for aircraft maintenance, civil engineering, comptroller, and health science courses; a flying training wing with T-37/T-38/AT-38 flying training squadrons that train US and NATO pilots under the Euro-NATO Joint Jet pilot Training (ENJJPT) Program; and an Air Force Reserve Command flying training squadron. 11. Outstanding pollution and Safety (OSHA) Deficiencies: a. Air pollution 175 b. Water Pollution 350 c. Occupational Safety and Health 0 d. Other Environmental 0 DD Form 1390, 24 Jul 00 189 1. COMPONRNT (computer generated) 3. INSTALLATION 4. PROJECT AND LOCATION 6. CATEGORY PROGRAMRLRMRNT 85796 TITLE STUDY DORNITORY ( 3 0 0 R N ) SHEPPARD AIR FORCE BASE, TRXAS 5 . 2. DATE FY 2004 MILITARY CONSTRUCTION PROJBC'I DATA AIR FORCE CODE 7. PROJECT NDMRRR 9. AUthZ Approp: VNVPO53002 721-312 COST 8. PROJRCI COST ($000) ESTIMATES UNIT WTJDENT DORHITORY (300 RM) SN ANTITRRRORISM FORCR PROTECTION LS COST 21,041 LS STlJDRNTDORXITORY SUPPORTING 29,167 28,590 14.625 1,425 ( 2 0 , 8 4 1 ) ( 200) 5,260 FACILITIES UTILITIES LS ( 1.700) PAWS LS ( 1 , 4 7 0 ) SITE IMPROVRblRNTS LS ( 1,440) COZWDNICATIONS LS ( 650) 26,301 SUBTOTAL CONTINOENCY $5.0 1,315 $1 27,616 TOTAL CONl'RACT COST SDPERVISION, INSPECTION AND OVERBEAD ( 5.7 %) 1,574 TOTAL RZQUEST 29,190 TOTAL REQUEST (ROUNDED) 29,167 LO. Description of Proposed Construction: Multi-story with reinforced ooncrete Eouudation/floor slabs, structural steel frame with brick veneer, and roof syetemr. Includes room-bath-room modules (two students per room), laundries, training managers area, storage, cozzwnicatione network, and all necessary support. ComplywithDoD .nterim minimum force protection conetruction etandard. 65OKW. tir Conditioning: Ll. RRQUIRRNRNT: 'ROJECT: 2,530RM Grade Mix: El-R4 ADEQUATE: 37OFtM 300 SUBSTANDARD: 2,264RM Construct a student dormitory. (Current Mistzion) Properly sized and configured dormitories are required to support training WQUIRRbIRWI: >f students. A major Air Force objective is to provide housing conducive to their xoper rest, relaxation and personal well-being while providing a suitable study Properly designed and furnished quarters, providing Bome degree of 3nviromaent. individual privacy, are essential to the eucceeeful accozpliehment of vital training requirements. This project is in accordance with the Air Force Dormitory Master Plan. :ozply with DOD interim minimum force protection construction standard. WRRRNT SITUATION: Four of the eleven student dormitories at Sheppard have central Latrine8 and are in deteriorated condition. They are plagued by broken toilets, einks, Severe moisture and mildew problemur are creating health 3ewer , and water lines. Frequent electrical power outages cause damage to personal property euch as lazarde. :elevisione and computers. Severe heat and cooling inconsistencies, exacerbated by the inability to open windows contribute to stifling conditions for personal etudiee. Adequate student living quarter6 will continue to be CNPACT IF NOT PROVIDED: unavailable reeulting in degradation of morale, productivity, and overall training affectivenees of unaccompanied enlisted personnel. Deplorable conditions for new members >f the Air Force have negative effects on retention and training. DD FORM 1391, DEC 76 Previous editions are obsolete. Page No. 1. COMPONENT 2. DATE FY 2004 MILITARY CONSTRUCTION PROJECT DATA (computer generated) PIR FORCE 3. INSTALLATION AND LOCATION 4. PROJECT TITLE SHEPPARD AIR FORCE BASE, TEXAS STUDENT DOPXITORY (300 RM) 5. PROGRAM ELEMENT 85796 6. CATEGORY CODE 721-312 7. PROJECT NUUBER VNVPO53002 8. PROJECT COST ($000) 29,167 The new OSD dormitory standard does not apply to housing conetructed for DDITIONAL: embers receiving entry-level skill training. This project is being designed to the Air 'orce technical training "pipeline' construction etanderd. All known alternatives were oneidered during the development of this project. No other option could meet mieeion Therefore, no economic enalyeie was needed or performed. FYOl equiremente. haccompanied Homing RPM Conducted: FYOZ Unaccolnpanied Housing RPM $3,76OK; Future Unaccompanied Housing RPM Requirements (estimated): PYo3: $855K. 'onducted: $9433; FYOS: $99OK. Base Civil Engineer: Co1 Hal M. Tinsley. (940) FYo4: 9893; 76-2158. lormitory: 14,625 SM = 157,365 SF rOINT USE CERTIFICATION: Mission requirements, operational coneideratione, and location me incompatible with use by other coqmnente. FORM 1391, DEC 76 Previous editions are obsolete. Page No. 1. coBfPCNRm 2. DATE FY 2004 MILITARY CCNSTRUCYION PRCJRCT DATA (computer generated) AIR FCRCR 3. INSTALLATION AND LOCATION 4. PROJECT TITLE SHEPPARD AIR FORCE BASE, TEXAS STUDBNT DORMITORY (300 RM) 5. PROGRAM ELRbXRNT 6. CATROORY CODE 7. PROJECT NUMBER 85796 721-312 8. PROJECT COST ($000) VNVPO53002 29,167 12. SUPP LRMRNTAL DATA: a. Estimated Design Data: (1) Status: (a) Date Design Started (b) Parametric Cost Eetimates used to develop costs l (c) Percent Complete as of 01 JAN 2003 l (d) Date 35% Designed (e) Date Design Complete (f) Energy Study/Life-Cycle analysis was/will be performed (2) Basis: (a) Standard or Definitive Design (b) Where Design Waae Most Recently Used - OZ-APR-02 YES 15% zo-SEP-02 ZO-SEP-03 YES YES SHEPPARD (3) Total Cost (c) - (a) + (b) or (d) + (e): (a) Prodktion of Plans and Specifications (b) All Other Design Costs (c) Total (d) Contract (e) In-house ($000) 1,168 730 1,898 1,460 438 (4) Construction Contract Award 03 DRC (5) Construction Start 04 JAN (6) Construction Completion 05 NOV * Indicates completion of Project Definition with Parametric Cost Estimate which is comparable to traditional 35% deeign to ensure valid mope. cost and executability. b. Eguipment associated with this project provided from other appropriations: N/A DD FORM 1391, DEC 76 Previous editions are obsolete. Page No. 1 FY 2004 MILITARY CONSTRUCTION PROGRAM COMPONENT 12. DATE AIR FORCE I ICOMMAND: USTALLATION AND LOCATION 15. AREA CONST AIR FORCE MATERIEL COST INDEX IILL AIR FORCE BASE, COMMAND 1.04 JTAH STUDENTS PERMANENT SUPPORTED i. Personnel CIV OFF ENL CIV OFF ENL ENL itrength OFF CIV TOTAL 4229 9919 3488 4702 627 937 1 0 rS OF 30 SEP 02 803 24,701 4230 9525 3488 4702 .ND FY 2007 608 937 1 0 803 24,29 ‘. INVENTORY DATA ($000) 6,973 -otal Acreage: nventory Total as of : (30 Sep 02) 2,902,09 iuthorization Not Yet in Inventory: 64,291 iuthorization Requested in this Program: 15.81 \uthorization Included in the Following Program: (FY 2005) 13,11: ‘Ianned in Next Four Years Program: 186,201 iemaining Deficiency: 72,151 brand Total: 3,253,66 1. PROJECTS REQUESTED IN THIS PROGRAM: (FY 2004) :ATEGORY COST DESIGN STATUS PROJECT TITLE =ODE SCOPE $.OOO S T A R T C M P L Munitions Maintenance Facility !I 5554 LS $1,000 Design-Build 122-264 Replace Munitions Storage Igloos, Ph I 4,059 SM 13,000 Design-Build 122-264 Small Diameter Bomb Storage Igloos 1,811 Design-Build 15,811 3a. Future Projects: Inclided in the Following Program: 740-674 Fitness Center 580 SM Total (p/2005) 6.000 SM Total 3b. Future Projects: Typical Planned Next Four Years: Consolidated Fire/Crash Rescue Station 4,737 S M 130-142 141-753 F-16 Squadron Operations Facility 2,600 SM Consolidated Software Support Facility, 6,735 SM 141-764 Phase 1 141-765 Consolidate Quality Control Propellant 2,220 SM Lab Consolidated AEF Deployment Center 141-786 5,112 SM 2,020 SM Consolidate CLSS Training I Storage 171-625 Facility 5,500 SM Fueled Hangar Facility !ll-116 Maintenance Hangar, 4 dock, Phase 2 10,077 SM !ll-116 2,454 SM Consolidated Industrial Commodities !I I-152 Aircraft Structural Maintenance Facility 830 SM !ll-152 7,350 SM Composite Repair Facility, Phase 1 !ll-152 2,710 SM Composites RCS Facility !12-212 1,700 SM 729th ACS OperationIMaint Complex t14-425 2,850 SM Munitions Maintenance Facility ,I 5-552 3,535 SM Consolidate Missile Storage Facilities 522-259 Replace Munitions Storage Igloos, Ph I 4,059 SM 122-264 2,050 SM Consolidated 649th Munitions Facility 510-144 96 RM Dormitory 721-312 13.113 13,113 9,200 6,000 19,000 6,500 5,700 3,800 13,000 32,000 4,500 2,200 24,500 10,600 4,900 4,500 14,200 13,000 4,600 8,000 9: 3c. Real Propery Maintenance Backlog This Installation IO. Mission or Major Functions: Ogden Air Logistics Center which is responsible for logistics management, jupport, and depot-level maintenance of tactical missiles, F-16 aircraft, Minuteman and Peacekeeper ICBMs, I\N/FPS-117 Radar, Composite (including B-2 Composites), Power Systems, and Software workload; a test squadron with F-16, HH-1, MH-60, and HCINC-130 aircraft; an air base wing; an Air Combat Command ighter wing with three F-16 squadrons; and an Air Force Reserve fighter wing with one F-16 squadron. 193 AIR FORCE INSTALLATION AND LOCATION HILL AIR FORCE BASE, UTAH COMMAND: AIR FORCE MATERIEL ICOMMAND 11. Outstanding pollution and Safety (OSHA Deficiencies: a. Air pollution b. Water Pollution 5. AREA CONST COST INDEX 1 1.04 1,000 120 c. Occupational Safety and Health I d. Other Environmental 0 I 194 l.coHeoNEwT FY 2004 MILITARY CONSTRUCTION PRChJECT DATA 2. DATE (caaputer generated) IUR FORCS 3. INSTALLATICM AND LOCATION 4. PROJECT TITLE aILLxLRFoRcBBmE,uTAIi NUNITIONS V FACILITY 5. PROGRAM - 6.CATEGORYCODE 7.PROJECT=ER 215-554 27248 9. 8. PROJBCT COST ($000) RRSMO23011 1,000 COST EBTMTES UNIT COST o/K- I!mm KINITIONS m FACILITY 3UPPORTING FACILITIES Ls 1,000 0 3uBToTAL 1,000 lDTAL Coarmucr COST mAL REQUEST 1,000 1,000 rOTAIn I=QU=T (R-) 1,000 .o . Description of Proposed Construction: .l.REQj: -: =QL ADEQUATE: Ls LB Ata required. : Det+ls Under Separate Cwer. D SI'RXZLTIONr special access requuird. 3LpAcTIFmTPmvIDED: DD Special access required SuBsTANmNDt Ls DEC 76 Special access required. Previous editions are obsolete. Page No. 195 l.cOMPONmT FY 2004 MILITARY CONSTRUCTION PROJECT DATA AIRFORCE 2. DATE (computer generated) 3. INSTAILATI~ AND LOCATIOU 4. PRCJRCT TITLE HIx&xmFoRcwBAsE,DTAH REPIACE MURITIOEW STORAGR IGLOOS 5. PROGRAW - 6. CATHIORY CODR 7. PROJECT MIIIBRR 422-264 72896 9. 8. PROSECT COST ($000) RRSM003013 COST 13,000 RSTIWATES REPLACE NtJNITIOW m IgLOOS SUPPORT- yACILITIRS UTILITIRS PAWS SITS -s DWOLITIOR -CATIOUS WPPORT LO. Description of Proposed Constructicmr Construct 21 earth covered reinforced mncrete Hayman Type igloos, 26' x 80', capable of storing 500,000 pounds of Class 1.1 nunitions. work includes access roads, reinforced aprons, utilities and other necessary support. ~emrolish seven facilities totaling 2,069 SR. ll.RRQpJRumRm: 41,168SN ADEQUATE: 21,505 SM SDBSTAUDERD: 20,519SM Replace Munitions Storage Igloos. (current M.ission) : Properly sired and configured munitions storage facilities are required to wasupport the increased Standard Air Wunitions Packages (STAMP) mission for Precision radded Munitions (PcpI) assets. The AF Ammmition Control Point and the Air Staff have STAW designated the additional STAMP requireman t8 to be accamaoda tedat Hill AFB. assets are war reserve munitions (WRN) required by all Combat Air Forces (Cnr) involved inanytype of coutingencyrorlduide. This project is needed to provide safer and more efficient exglosives handling aud storage capabilities and increase storage capability within the existing explosive safety footprint. These igloos must be capable of storing 500,000 Rounds Ret Rquivaleut Weight (NSW) of class 1.1 explosives. PRCJRCT: CgRREWf SITUATION: Existing igloo configurations are inadequate to actcamdate the new munitions being shipped as full up rounds. Uew containers are much larger and will not fit through the existing doors without extensive maneuvering. The current igloo shape and size do not allow for the most efficient use of space to maneuver and store the 3TAMP aSSetS. gxisting aud plauued construction for other missions in the explosives storage area have restricted the RRW that can be stored in the various existing igloos M reduced the bases ability to store hazard class 1.1 munitions by 2.8 million pounds. blew, modern igloos prcvide additional storage space and allow an increase of 1.5 nillion pounds of class 1.1 munitions to be stored within the existing explosive safety This project is the key element to the overall revitalization and Ewtprint. levelopmnt of the munitions storage area at Hill AFR. DD FORM 1391, DEC 76 Previous editions are obsolete. Pags No. 1. CauPom FY 2004 HILITARY BIOBl AIRFORCE (wter P R O J E C T DATA 2 . DATE generated) 3 . IBlSTN&&TIW AUD LOCATION 4. PROJECT HILLAIRmmcl3BA(A, REP- NUUITIOUS S- IGLOOS 5 . PROGRAW .72896 UTAH 6. * CATEGORYCOm 7 . 422-264 TITLZ PROJECT- 8 . PROJBCT C O S T ($000) lmmloo3013 13rooo There will continue to k a nhortfall of storage capability for IMPACTIFM)T~: hazard class 1.1 munitions. lkcesdve maneuvering of asseta in and out of the existing igloos will continue to place these amets and crew at rink. Imdequate storage capability will impact the m of new sunitions at Kill h?B and will have a significant negative impact ca4 STAMP assets availability to wrt Ws involved in contingency operations worldwide. NJDITIOMN,r This projects mtn the criteria/scope specified in Air Force Xamlbook 32All known alternative options were considerrd&urLng the 1084, "Facility Requirements.m ilevelapment of this project. rJootheroptioncouldmeetthem.isaion requirements; therefore, no econcdc anelymia raa needed or performed. A certificate of exception has Base civil mgineert Co1 Wea Somers (801) 777-3071. Munitions Storage been Prepared. Igloos: 4,059 8X = 43,680 SI. Design Build - Design Build Cost (4% of Subtotal Cost): $465,000. JOINT USI8 CERTI~ICATIOU: This f a c i l i t y cau b e used b y O t h e r c-ante available. basisi however, the scope of the project is baeed on o n a n “as Air Force requireemnts. l - DD FORM 1391, DEC 76 Previous editions are obSOlet6. Page No. 197 l.CONPO~ M 2004 UILITARY COUSTRUCTIOU PROJECT MTA (canputer generated) AIRmRcE 2. DATE 3. IUSTALLATIOU m LOCATIOU 4. PROJECT TITLE HILLAIRFoRcEHasE,uTAH REPWCE HDUITIOUS SMRAaE IQLOOS 6. CATEGORY CODE 7. PROZECT MJ#BKR 8. PROJSCT COST ($000) 5.PRmm 422-264 72896 12. SUPP-AL KRSHoo3013 13,000 MTA: a. Ihstimated Design Data: (1) Project to be accce@ished by design-build procedures (2) Basis: (a) Standard or Definitive Design (b) Where Design Was Nest Recently used - uo (3) All Other Design Costs (4) Construction Contract 348 Award 03 DEC (5) Constxuction start 04 mu (6) construction Cwleticm 05 WAY (7) Energy Study/Life-Cycle analysis was/will be performed uo b. Equipment apociated with this project provided from other appropriations: U/A FORM 1391, DEC 76 Previous editions ar6 obsolete. Page No. 198 r l.cCWPoNENT FY 2004 WILITARY CCNSTRtlCTIOW PRCUECT DATA 2. DATE (ccmputer generated) AIRFORCF, 3. INSTALLATION AND LOCATION 4. PRCJECT TITLE EILLAIRFORCE SWALLD IAmTERBoWB.sToRAm18LoDS BASE,DTAB 5. PROQRAM m 6. CATEQIJRY CODE 7. PROJBCT NCWBER 8. PR- COST ($000) Auth: 27327 422-264 9. RRSWo33005 &prop: 1,848 1,811 COST ESTIWATES UUIT COST U/&WTY 8WALLDIAWBTER~STORAGEIOUX)S EUPPORTINQ FACILITIES SN DTILITIBS 580 Ls PAWS 4 Ls Ls SITE IWPRwEbIEMPS CCAMWICATIOWS SDPPORT 2,327 1,350 315 ( 90) ( 115) ( 90) ( 20) 3uBToTAL 1,665 zouTIuQmeY ( 5.0 %) I'OTAL CoNpRAcT COST 83 1,748 57JPERVISION, INSPECTICBI AND OVERBEAD ( 5.7 %) 100 L'OTAL REQUEST 1,848 roTAL REQWST (RaoluDED) 1,848 .o. Description of Proposed Construction: Coustruct 3 earth covered reinforced :oncrete Hayzuan Type igloos, 26' x EO', capable of storing 500,000 paunds of Class 1.1 unitions. Work includes access roads, reinforced aprons, utilities aud other mcessary support. ADEQUATE: 21,505 SN 41,748SW SUBSTANDARD: 20,519SW .l. REQIJ1REWBWT: 'RCUECT: Construct small diameter baab (SDB) storage igloos. (New Mission) u3QlJIREWEWT: Properly sized sud configured munitions storage facilities are reguired to upport the new Standard Air Wuuitions Packages (STAMP) mission for SDB assets. The AF uazuuition Control Point and the Air Staff have designated the STAMP reguirmmuts to be tcccuzmdated at Hill AFB. STAWP assets are war reserve munitions (WRW) required by all :w&at Air Forces (W) involved in many types of coutingencies worldwide. Separate structures are required to support single Point load out locations to meet STAWP :ontingency support and to provide safe and efficient exDlosives handling and storage :aPabilities within the existing qlosive safety footprint. These igloos zzz3t be :apable of storing 500,000 Pounds Wet Eqlosives Weight (WEW) of Class 1.1 explosives. The SDB is an ACC neu mission requirement. SDB STAMP assets are 'URREWT SITUATION: tackaged in a pre-loaded configuration inside a ll-foot long container as uell as udividual bcmbs. The existing igloos are not the correct size or shape to efficiently mxamodate the new assets. III addition, the existing igloos are utilized to their ksxhum capacity. Existing and planued construction Project5 for other missions within he explosive storage area are part of au overall master plan to increase the storage rapability for Class 1.1 munitions within the existing explosives safety footprint. lithout the plauued changes there is insufficient capacity for the current workload and LO cagability to acccemodate new mi55ions assigned to Hill AFB. HPACT IF NCT PROVIDED: Failure to Provide adequate SDB storage facilities would result .n costly prOdUCtiOn and fielding delays. Additionally, the SDB would not be izuuediately .vailable to warfighters if STAMP storage facilities are not provided. DD FORM 1391, DEC 76 Previous editions are obsolete. Page No. (1.cuMPoNKNT ( FY 2004 MILITARY CONSTRUCTION PROJECT DATA 2. DATE (cclqputer generated) AIRFORCE 3. INSTALIATION AM) LOCATION 4. PROJECT TITLE HILLAIRFORCE swALLDIAwETRR BmxSsToRAGR1QLooS RASE,UTAR 5. PROGRAM D 27327 6. CATEQORY CODE 7. PROJECT NUWEER 422-264 RRm033005 8. PROJECT COST ($000, 1,848 ADDITIONAL: This projects meets the criteria/scope specified in Air Force Eandbook 321084, "Facility Requiremrents." pase Civil Eagiaeer: Co1 We8 Saner8 (801) 777-3071. SDE Storage Igloos: 580 SM = 6,240 SF. Demign Build - Design Build Cost (4% of Subtotal): $68,586. JOIWT USE CERTIFICATION: This facility can be used by other canponents on an "as available" basis; however, the scope of the project is based oa Air Force requirements. DD PORN 1391. DEC 76 Previous editions are obsolete. Page No. FY 2004 MILITARY CONSTRUCTION PROCIBCT DATA 1. CoHPoNENT (computer generated) AIRFORCR 3. INSTALLATION AND LOCATION 4. PRO4-RCT TITLE EILLAIRFORCERASE,UTAE SM?LLLDW BOzmsTORA~IQLQOS 5. PROGRAM - 6. C!.ATEQORY CODR 7. PROJ'ECT. NUMRRR 422-264 RRSMo33005 27327 8. PROJ'RCT COST ($000) 1,848 12. SUPP -AL DATA: a. Estimeted (1) Project Design Data: to be accanplished by design-build procedures (2) Basis: (a) Standard or Definitive Design (b) Where Design Was Bbst Recently Used - No (3) All Other Design Costs 52 (4) Construction Contract Award 03 DE! (5) Construction Start 04 SAN (6) Construction Completion 04 Nov (7) Rnergy Study/Life-Cycle analysis was/will be performed YES b. Rquiplaent associated with this project provided frmn other appropriations: N/A DD FORM 1391, DRC 76 Previous editions are obsolete. Page No. 201 AIR FORCE I I 3. INSTALlATlON AND LOCATION 4. COMMAND: 5. AREA CONST AIR COMBAT COMMAND COST INDEX LANGLEY AIR FORCE BASE, VIRGINIA 0.94 STUDENTS SUPPORTED 6. Personnel PERMANENT ENL CIV ENL CIV OFF OFF ENL StMigtll OFF CIV TOTAL AS OF 36 SEP 02 1853 6819 1717 117 304 20 243 11,073 END FY 2697 1912 6839 1655 117 394 20 243 11,099 7. INVENTORY DATA ($990) a. Total Acreage: 3,152 b. Inventory Total as of : (39 Sep 02) 1,296,235 c. Authorization Not Yet in Inventory 172,999 d. Authorizatfon Requested in this Program: 24,969 e. Authorization Included in the Following Program: (I7 2995) 6,292 f. Planned in Next Four Years Program: 42,796 g. Remaining Deficiency: 63,296 h. Grand Total: 1,517,398 8. PROJECTS REQUESTED IN THIS PROGRAM: u=Y 2004) CATEGORY COST DESIGN STATUS PROJECT TlTLE 8.999 START CMPL SCOPE 4,196 SM 116-672 F-22 Clear Water Rinse Pad 2,383 Jun-92 Sep-93 6,891 SM 211-111 F-22 Squadron OperatinsAMUMangar 20,013 Jun-92 Sap-03 1,486 SM 218-712 2,573 May-62 Sep-03 F-22 Vertical Wing Tank Storage Total 24,989 (FY2995) 9a. Future Projects: Included In the Following Program: 96RM 8,292 721512 Dom W-(96 RN,, ,,‘$ Total 8,292 9b. Future Projects: Typical Planned Ne$‘Four Years: 154,858 SM 11,799 113-321 Repair Primary Parking ApronITaxiway 102,999 SM 15.000 113-321 Repair West Parking ApronITaxiway 2,778 SM 5,866 171-475 Indoor Small Arms Range 96 RM 7,200 721-312 Dormitory (95 RM) 358 SM 3,990 736-771 ADAL Bethel Manor Chapel 75 9c. Real Property Maintenance Backlog This Installation: 10. Mission or Major Functions: Headquarters Air Combat Command; a fighter wing with three F-l 5 fighter squadrons; an airlift flight; an intelligence group; Aerospace Command and Control lntellii, Surveillance and Reconnaissance Center (ACPISRC), Detachment of the USAF Doctrine Center; and the Air Force Rescue Coordination Center. 11. Outstanding Pollution and Safety (OSHA) Deficiencies: a. Air pollution b. Water Pollution c. Occupational Safety and Health d. Other Environmental 2. DATE FY 2004 MILITARY CONSTRUCTION PROJECT DATA 1. COMPONENT (computer generated) AIR FORCE 4. PROJECT TITLE 3. INSTALLATION AND LOCATION F-22 SQUADRON OPERATIONS/AMU/RANGAR LANGLRY AIR PORCR RASE, VIRGINIA 5. PROGRAM ELEMENT 6. GATRGORY CODE 27138 7. PROJECT NUMRER 211-111 9. PROJECT COST ($000) Auth: Approp: MURJO43001 COST 8. 20,418 20,013 ESTIMATES ?-22 SQUADRON OPRRATIONS/AHlJ/RANGAR LS SQUADRON OPRRATIONS/AMU SM 2,641 1,424 / ( 3,761) HANGAR SM 4,250 1,296 ) ( 5,509) ANTITERRORISM PORCR PROTRCTION LS SUPPORTING ( ! FACILITIES 46) 9,070 LS ( 3,010) LS ( 2,026) DRMOLITION LS ( SPECIAL FOUNDATIONS SM PASSIVE SEcURITYMRASURRS LS SOIL RBMRDIATI& LS UTILITIES PAWS/SITE : , IBIPROYSRRNTS 2,550 1,483) 190 ) I ( iwToTAL ( 485) ( 415) 1,651) 18,385 ZONTINGmCY ( 5.0 %I 919 L'OTAL CONTRACT COST 19,305 IUPERVISION, INSPECX'ION AND OVERHEAD ( 5.7 %) YOTAL REQUEST !OTAL REQUEST (ROUNDED) ~UIPMRNT FROM OTRRR APPROPRIATIONS (NON-ADD) .O. 1,100 - 20,405 I I 20,418 ( 21.0) Description of Propoeed Coaetruction: Construct F-22 squadron opera:ions/AMU angar to include special foundation pilings, masonry block walls and standing seam metal roofs. The infrastructure and the utilities will be upgraded. Includes minumum oD force protection measures. 15oRw. .ir Conditioning: .l. RRQUIRRWRNT: 'ROJRCT: 7,923 816 ADEQUATE: 0 SM .’ I SUBSTANDARD: 6,458SU Construct P-22 squadron operations/AMD and hangar. (New Missic 1) XQUIREWRNT: The F-22 squadron operations/AMU and hangar is required to .;upport the 'eddown of the F-22. New technology and composite materials for stealth rdssion apability require specialized maintenance facilities that do not compromise security The facility will support personnel and equipment due to arrive in Mar 06 lrocedures. nd aircraft scheduled to arrive in Dee 06 for the third F-22 squadron. QRRRNT SITUATION: The base does not have adequate facilities to conduct squadron level Over the last '.~n years, the maintenance and operations for the F-22 fighter squadron. ,ir Force has experienced significant restructuring of its combat wings, I-ssulting in he shifting of roles aad responsibilities for maintaining and operating aircraft. perational squadrons are required to work, train, deploy, and fight in c‘ose Currently, s luadron ooperation with their corresponding maintenance functions. perations and maintenance facilities are geographically separated, under ;-:oed, in poor ondition, and not configured to support high operations tempo fighter sq:adrons. The xisting hangars are over 70 years old. Hangar door; do not operate prop :,y, roofs FORM 1391, DEC 76 Previous editions arc- I‘age No. 203 / 1. CmPoNRm FY 2004 MILITARY CONSTRDCTION PROJRCT DATA AIRFORCE 2. MTR (canputer generated) 3. INSTAUATIWANDLOCATION 4. PROJRCT TITLE LANgIRYAIRFORCERASE, VIRGINIA F-22 SQUADRON o&RAmnU?/;luro/RANSAR 5. PROGRAM m 6. CATRQORY CODE 7. PRoJecT NDMSRR 211-111 27138 9. 8 -wmEcT COST (8000) Auth: APP~P: mlBI043001 20,4 18 20,013 COST ESTIMAm COST WIT ll.QLm F-22 SQUADRON OPRRATIONS/AMU/RANGAR Ls SQUADRON OPERATIONS/AMJ ANTITRRRORISMFORCR SN PROTECTION 9,316 2,641 1,424 ( 3,761) 4,250 1,296 ( 5,509 ) ( ,"I EUPPORTINQ FACILITIES 46) 9,070 DTILITIRS PAWS/SITE IMP-S -LITION SPECIAL FODNDATI~ PASSIVE SEIJRITY B8zAsmEs SOIL RRMRDIATI& Ls Ls Ls SN Ls Ls ( 3,010) ( 2,026) ( 1.483) ( 485) ( 415) ( 1.651) 190 1 2,550 8uBmTAL 18,385 919 CoNr( 5.0 %) IWI'AL CZOWPRACT COST ¶PRRVISION, INSPECTION AND OVERHEAD 19,305 1,100 ( 5.7 %I POTAL REQDRST 20,405 L'OTAL RFQDEST (RODNDQ) EQDI~FROMOTSRRAPPROPRIATIONS 20,418 ( 21.0 ) (NDN-ADD) LO. Description of Proposed Construction: Construct F-22 squadron operations/Am xangar to include special foundation pilings, masonry block walls and standing seam metal roofs. The infrastructure and the utilities will be upgraded. Includes roinumum 3oD force protection measures. 4ir Conditioning: 11. RRQuIRmmWr: ?ROJECT: 1soRw. 7,923 SN ADEQUATR: OSN SUEzSTANDARD: Construct F-22 squadron operations/AMU and hangar. 6,458SM (New Mission) 3EQUIREMEEsT: The F-22 squadron operations/AMU and hangar is required to support the mddowa of the F-22. New technology aud canposite materials for stealth mission :apability require specialized maintenance facilities that do not canpromise security wocedures . The facility will support personnel and equipment due to arrive in Nar 06 md aircraft scheduled to arrive in Dee 06 for the third F-22 squadron. WRRRNT SITUATION: The base does not have adequate facilities to conduct squadron level naintenaace and operations for the F-22 fighter squadron. O v e r t h e l a s t t e a y e a r s , t h e iir Force has errperienced significant reStmCtUring of it8 ccmbat Wings, reSUltiW in he shifting of roles and responsibilities for maintaining and operating aircraft. -rational squadrons are required to work, train, deploy, aud fight in close moperation with their corresponding maintenance functions. currently, squadron operations and maintenance facilities are geographically separated, undersized, in poor :onditioa, aud not configured to support high operations tempo fighter squadrons. The uristing hangars are over 70 years old. Hangar doors do not operate properly, roofs DD PORN 1391, DFJZ 76 Previous editions are obsolete. Page No. 1. CoNPoNmT FY 2004 MILITARY CONSTRUCTION PROJECT DATA AIR FORCR 3. INSTALLRTICM AND LOCATION 4. LAIWLRYAIRFORCRRASE, VIRGINIA F-22 5. 2. DATE (canputer generated) PROGRAM RLEMRNT 27138 6. CATRgORY CODE 211-111 PROJECT TITLE SQUADRON OPERATIONS/AMtl/RANGM 7. PROJECT NDNRRR MuEJo43001 8. PROJ'RCT COST ($000) 20,418 .eak, lead paint and asbestos are present, lighting is substandard, mechanical and electrical systems are inadequate, exterior masonry walls are deteriorating, aud fire m-otection aad security systa are non-existent. Also, the hangars are inadequately bized aad *raperly configured to actamodate the wider F-22 aircraft without violating safety criteria. ~ACTIFNOTPROVIDRD: Adequate facilities will not be available to perform essential nainteuauce and reDair ou the F-22 aircraft. Operational squadrons will be undersized md geographically separated frcan the maintenance functions, creating aperatioual leficiencies. Ragmented operations will increase the Dotential for security :aqwanises . With no acceptable work-arounds, high risk solutions will be *l-ted, impacting aperational capabilities aud violating safety criteria. LDDITIONAL: This project meets the criteria and scope outlined in Air Force Handbook 32-1084, "Facility RequirWts". A preliminary analysis of reasonable aptions for m=anDlishing this project (status quo, renovation, upgrade/remroval, new construction) oas done. It i.nd+ates there is only one aption that will meet aperational A certificate Of mC&XDtion ha8 been Drepered. Ease Civil Eugineer: Lt requirmnmts. Squadron Operations/ANW/Rangar: 2,641SM = 28,417 201 Neal NcElhannon, (757)-764-2025. SF; Ranger: 4,250 SN = 45,730 SF. JOINT USE CRRTIFIcATICRl: Mission reguirmmnts, operational considerations, and ire incauDatible with use by other cwents. 76 Previous editions are obsolete. location Page No. 1. CWPONENT FY 2004 MILITARY CONSTRDCTION 2. MTR PROJRCT DATA (cvter generated) AIR FORCE 3. INSTAIJATION AM) LOCATION 4. PROJRCT TITLE LANGIRY AIR FORCR RASE, VIRGINIA F-22 SQUADRON OPERATIONS/AARJ/~ 5. PROGRAM ELEMwlT 6. cATEo0RY c0DE 7. pRo;IEcT NmmR 12. 8DPPI PROJRCT MuSJ043001 211-111 27138 8. COST ($000) 20,418 M T A : a. Estimated Design Data: (1) Status: (a) Date Design Started (b) Parametric Cost Estimates used to develop costs * (c) Percent Cwlete as of 01 &AN 2003 * (d) Date 35% Designed (e) Date Design Cauplete (f) Energy Study/Life-Cycle analysis was/will be performed lo-JON-02 YES 15% 01-AIJG-02 Ol-SRP-03 YES (2) Basis: (a) Standard or Definitive Design - No (b) Where Design Was Most Recently Used (3) Total Cost (c) = (a) + (b) or (d) + (e): (a) Production of Plans and Specifications (b) All Other Design Costs (c) Total (d) Contract (e) In-house (4) Construction Contract ($000) 1,225 613 1,838 1,532 306 04 JAN Award (5) Construction Start 04 FE8 (6) Construction Completion 06 N?dt * Indicates completion of Project Definition with Parametric Cost Estimate which is c-arable to traditional 35% design to ensure valid scope, cost and executability. b. RguiInaeut associated with this project provided frau other appropriations: APPROPRIATION FISCAL YEAR APPROPRIATED ORREQDRSTRD 3400 2004 PROCURIIW RQUIPMRNT NoNNNcLATuRE CONMDNICATIONS FQDIPMEWI DD FORM 1391, DRC! 76 Previous ea~rlons are omsorece. (EL 21 rage NO. 206 1. COWPORBRT 2. DATE FY 2004 MILITARY CONSTRUCIION PROJECT DATA (computer generated) AIR FORC8 3. INSTALLATION AND LOCATION 4. PROJECT LANGLEYAIBFORCEBASE, F-22 VERTICAL WING TANR STORAGE 5. PROGRAW m VIRGINIA 6. CATEGORY TITLE 8. PROJECT COST ($000) CODE 7. PROJECT M.BdBER Auth: 27138 mHJ043003 218-712 9. COST Approp: 2,625 2,573 ESTINATES VERTICAL WING TANR STORAGE F-22 VERTICAL WING TANE STORAOE FACILITY ( 2,297 ) ANTITERRORISW FORCE PROTRWION SUPPORTING FACILITIES DTILITIES PAVEBENTS SITE IWPROvE16ENTS -CATIONS SUPPORT SUBTOTAL coNTINGENcY cm.0 %I TOTAL CONTRACT COST SUPERVISION, INSPECTION AND OVERE8AD TOTAL REQUEST TOTAL REQUEST (ROUNDED) 10. Description of Proposed Construction: Construct external aircraft fuel tank storage facility with masonry siding and standing seam metal roof. Includes minimum DoD standard force protection measures. 11. RBQUIRRWENT: PROJECT: 1,486SW ADEQUATE: 0 SY SUBSTANDARD: 0 SM Construct vertical wing tank storage facility. (New Mission) REQOIREWEWT: An adequately sized and configured facility is required for the storage and maintenance of 320 F-22 external wing tanks as part of the F-22 beddown. This facility will house the external aircraft fuel tank storage system (RAETSS) that is being used on the new F-22 aircraft. CURRRRT SITUATION: Langley AFB does not currently have a facility that is adequate in In addition, the size or a building that can be converted to support this requirement. existing horizontal wing tank storage pad currently violates airfield criteria creating unacceptable risks and a flight safety hazard. Furthermore, this external storage is unacceptable due to the high corrosive nature of Langley AFB being located near the Atlantic Ocean. IMPACT IF NOT PROVIDED: Langley AFB will be unable to store and maintain critical wing tanks as required for the F-22 aircraft. Wing tanks will continue to have corrosive problems due to the salt water environment. ADDITIONAL: This project meets the criteria and scope outlined in Air Force Handbook A preliminary analysis of reasonable options for 32-1084, "Facility Requirementsw. accomplishing this project (status quo, renovation, upgrade/removal, new construction) was done. It indicates there is only one option that will meet operational Base Civil Engineer: Lt A certificate of exception has been prepared. requirements. Co1 Neal McElhannon, (757) 764-2025. Vertical Wing Tank Storage: 1,486 SW = 15,989 SF. DD FORM 1391, DEC 76 Previous editions are obsolete. Page No. 207 1. COMPONEm FY 2004 MILITARY CONSTRUCTION PROJECT DATA LIR FORCE (computer 2. DATE generated) 4. PROJECT TITLE 5. INSTALLATION AND LOCATION LANGLEY AIR FORCE BASE, VIRGINIA 5. PROGRAM ELEMENT 6. CATEGORY CODE 27138 218-712 F-22 VERTICAL WING TANK STORAGE 7. PROJECT WMBER mmJo43003 8. PROJECT COST ($000) 2,625 'OIRT USE CERTIFICATION: Mission requirements, operational considerations, and location .re incompatible with use by other components. DD FORM 1391, DEC 76 Previous editions are obsolete. Page No. 208 1. COMPONERT FY 2004 MILITARY CONSTRUCTION PROJECT DATA 3. INSTALLATION 2. DATE (computer generated) AIR FORCE AND LOCATION 4. PROJECT TITLE F-22 VERTICAL LANGLEY AIR FORCE BASE, VIRGINIA 6. CATEGORY 5. PROGRAM ELEMENT 27138 218-712 CODE 7. PROJECT NUMBER WING TANK STORAGE 8. PROJECT COST ($000) lmsnJ043003 2,625 1 2 . SUPP-AL DATA: a. Estimated Design Data: (1) Status: (a) Date Design Started (b) Parametric Cost Estimates used to develop costs (c) Percent Complete as of 01 JAN 2003 l l (d) Date 35% Designed (e) Date Design Complete (f) Energy Study/Life-Cycle analysis was/will be performed 24-MAY-02 YES 15% Ol-AUG-02 Ol-SEP-03 YES (2) Basis: (a) Standard or Definitive Design (b) Where Design Was Nost Recently Used - NO (3) Total Cost (c) = (a) + (b) or (d) + (e): (a) Prodpction of Plans and Specifications (b) All Other Design Costs (c) Total (d) Contract (e) In-house ($000) 158 79 (4) Construction 04 JAN 237 211 26 Contract Award (5) Construction Start 04 FEE (6) Construction 05 JUL l Completion Indicates completion of Project Definition with Parametric Cost Estimate which is comparable to traditional 35% design to ensure valid scope, cost and executability. b. Equipment associated with this project provided from other appropriations: EQUIPMENT NOMENCLATURE FUEL TANX STORAGE SYSTEM DD FORM 1391, DEC 76 PROCURING APPROPRIATION FISCAL YEAR APPROPRIATED OR REQUESTED 3400 2004 Previous editions are obsolete. COST ($000) 645 Page No. 209 2. FY 2004 MILITARY CONSTRUCTION PROJECT DATA 1. COWPORRRT DATE (corquter generated) AIR FORCR 3. INSTALLATION AND LOCATION 4. PROJRCT LANGLRYAIR FORCR RAM, VIRGINIA F-22 CLEAR WATER RINSE PAD 5. PROGRAW 6. CATEGORY RLRWRRT CODE 7. PROJRCI: 9. N[lwBRR 8. PROJECT COST ($000) Auk Approp: HUEaT 116-672 27138 TITLE COST ESTIMATES UNIT CLEAR WATRR RINSB Ls CLRARWATRRRINSE PAD SM RINSE SYSTRW SUPPORTING 2,431 2,383 COST 1,483 4.100 130 LS 533) ( ( 950) 704 FACILITIES UTILITIES LS ( PAVEMENT LS ( DRWOLITION LS SOIL RRWRDIATION Ls 220) 175) ( ( SUBTOTAL 65) 244) 2,187 CONTINGENCY i-:-o 109 %) TOTAL CONTRACI' COST 2,296 SUPERVISION, INSPRCTION ARD OVERBEAD ( 5.7 %) 131 TOTAL REQUEST 2,427 TOTAL REQUEST (ROUNDED) 2,431 LO. Description of Proposed Construction: Construct an F-22 drive through clear nater rinse pad adjacent to existing parking apron. Work to include all utilities, pavements, oil/water separater, and infrastructure as required for a complete and usable facility. 11. RRQUIRRMRRT: PROJECT: 4,100S.M ADEQUATE: 0 SM Construct F-22 clear water rinse pad. SUBSTANDARD: OSM (New Mission) RRQUIRRWRWT: An adequately sired and configured drive/taxi - through clear water rinse New technology and composite materials pad is required to support the F-22 beddown. Ear stealth mission capability requires extensive maintenance procedures to preserve operational capabilities. This facility supports the maintenance of the low observable (LO) coatings and composites by accomplishing rinsing operations after completing combat sorties. This project supports aircraft arrival in Nov 04. CURPRWT SITUATION: The base does not have a drive through clear water rinse pad to accomplish rinsing operations after combat mission sorties. The F-22 aircraft will be subjected to the highly corrosive atmosphere associated with coastal environments. In addition to the corrosive nature of a coastal environment, the abrasive impact associated with the crystallization of salt on F-22 will cause significant degradation of the LO coatings. IWPACT IF NOT PROVIDED: Adequate facilities will not be available to perform essential preventive maintenance on the F-22 aircraft. Without this clear water rinse facility, the maintainers will be forced to accomplish washing operations within the LO/Composite Repair facitity eventually creating a maintenance backlog. The corrosive and abrasive effects due to the coastal environment will accelerate the degradation of the LO coatings and composite materials, thus impacting operational readiness. DD FORM 1391, DEC 76 Previous editions are obsolete. Page No. 210 1. coMPoNENT (computer generated) 4. PROJECT TITLE 3. INSTALLATION AND LOCATION LANGLRY AIR FORCE BASE, VIRGINIA 5. PROGRAW ELEMENT 27138 2. DATE FY 2004 MILITARY CONSTRUCTION PROJECT DATA AIR FORCE 6. CATRGORY COD8 116-672 F-22 CLRAR WATRR RINSE PAD 7. PROJECT NURRRR MUHJO43006 8. PROJECT COST ($000) 2,431 DDITIONAL: This project meets the criteria and scope outlined in Air Force Handbook 2-1084, "Facility Requiremeuts". A preliminary analysis of reasonable options for ccoaplishing this project (status quo, renovation, upgrade/removal, new construction) It indicates there is only one option that will meet operational ras done. requirements. A certificate of exception has been prepared. Baee Civil Engineer: Lt !ol Neal McRlhannoa, (757)-764-2025. Clear Water Rinse Pad: 4,100 SN I 44,116 SF. lOINT USE CERTIFICATION: Mission requirements, operational considerations, and location me incompatible with use by other conponents. DD FORM 1391, DEC 76 Previous editions are obsolete. Page No. 211 2. DATE FY 2004 MILITARY CONSTRUCTION PROJECT DATA 1. coEPoNEWT (computer generated) AIR FORCE 3. INSTALLATION AND LOCATION 4. PROJECT TITLE LANGLEY AIR FORCE BASE, VIRGINIA F-22 CLRAR WATER RINSE PAD 5. PROGRAM 6. CATEGORY ELEWBRT 116-672 27138 1 2 . CODE 7. PROJECT NUWBER 8. PROJECT BlIlHJO43006 COST ($000) 2,431 SUPPLRWEBTAL DATA: a. Estimated Design Data: (1) Statue: (a) Date Design Started (b) Parametric Cost Estimates used to develop costs * (c) Percent Complete as of 01 JAN 2003 l (d) Date 35% Designed (e) Date Design Ccn@ete (f) Energy Study/Life-Cycle analysis was/will be performed lo-JUN-02 YES 15% Ol-AUG-02 Ol-SEP-03 NO (2) Basis: (a) Standard or Definitive Design (b) Where Design Was Most Recently Used - NO (3) Total Cost (c) - (a) + (b) or (d) + (e): (a) Production of Plane and Specifications (b) All Other Design Costs (c) Total (d) Contract (e) In-house ($000) 146 (4) Construction 04 JAN Contract Award 73 219 195 24 (5) Construction Start 04 FEB (6) Construction Completion 04 NOV * Indicates completion of Project Definition with Parametric Cost Estimate which is comparable to traditional 35% design to ensure valid scope, cost and executability. b. Equipment associated with this project provided from other appropriations: N/A D FORM 1391, DEC 76 Previoua edition8 are obsolete. Page No. 212 1. comoRmT 2. DATE FY 2004 MILITARY CONSTRUCTION PROJECT DATA AIR FORCE (computer generated) 3. INSTALLATION AND LOCATION 4. PROJECT TITLE AIR COMBAT CORMAND, VIRGINIA PRBDATOR SQUADRON OPBRATIONS/AMU/IiANGAR 5. PROGRAM BLBMBRT 27245 8. PROJECT COST (SOOO) 6. CATEGORY CODE 7. PROJECT N[JbIBBR I 211-111 .9. ACC043015 I COST Auth: I I EST11 UNIT SQUADRON OPBRATIONS/ABlU/S SQUADRON COST LS OPERATIONS AMu/HANGAR SUPPORTING i6,25 1 25.73 I APD~OP: 12,546 SM 1,487 1,971 ( 2,931) SM 4,926 1,952 ( 9,616) FACILITIES 11,100 UTILITIES/PAVEMENTS/SITB IMPR-S LS ( 2.100) AIRFIELD PAVRNBRTS/LIGRTING LS ( 2.700) INF'RASTRUCTURBUPGRADB LS ( 6.300) SUBTOTAL 23,646 CORTING~CY ( 5.0 $1 1,182 I'OTAL CONTRACT COST 24,829 SUPERVISION, INSPECTION AND OVBRRRAD ( 5.7 %) 1,415 TOTAL REQUEST 26,244 I'OTAL REQUEST (ROUNDED) 26,251 LO. Description of Proposed Construction: Reinforced concrete foundation and floor Slab, structural steel frame, standing seam metal roof, fire detection/protection, utilities, site improvements, landscaping, upgrade/expand utility systems, roads/parking, airfield pavements/lighting/marking. comnunicatioa support, and all >ther necessarv eumort. I. 11. RBQUIRBblBNT: J?ROJK!T: 6,413SM ADEQUATE: 0 SBl SUBSTANDARD: 0 SM Construct Predator Squadron Operations/AMU/Haugar. (New Miesion) This project supports the AF objective of a real-time l Hunter/Killerm IUZQUIRBMBNT: c:apability by ensuring adequate facilities are available to support unmauned aerial 1rehicle (UAW operations and maintenance activities. This project supports the stand-up <,f new combat coded, training and test UAV Predator A (MQ-1) and Predator B @IQ-S) Y veapon systems. Permanent facilities are required to support funded aircraft production The Squadron ()perations/AMU facility is required to eupport mission planaiag, flight operations, IIrtaintenance functions, mission briefing and debriefing, and administrative functions. 1Phe maintenance dock is required to support direct maintenance of assigned UAV aseete. fire protection) 1tnfrastructure (water, sewer, electrical, pavfnnents, ccmmunications, A in F~O3/04 with new airframes arriving in FY05, aud over 1100 personnel. IInust be provided to the undeveloped beddown site. (mR= SITUATION: The beddowu location does not have excess facilities that can br! reconfigured to support the operations and maintenance requirements of this mission. Failure to provide facilities to support this new mission IMPACT IF NOT PROVIDED: beddown will significantly *act UAV operational capabilities. Adequate facilities will not be available to perform critical flying operations and maintenauce logistics functions. This will force inefficient work around8 that will degrade mission The Air Forces capability to train personnel for this critical mission accomplishment. DD FORM 1391, DBC 76 Previous editions are obsolete. Page No. 213 1. COMPONENT FY 2004 MILITARY CONSTRUCTION PROJECT DATA AIR FORCE (computer generated) 3. INSTALLATION AND LOCATION 4. PROJECT TITLE AIR COMBAT COMMAND, VIRGINIA PREDATOR SQUADRON OPERATIONS/AMU/HANGAR 5. PROGRAM ELEMENT 6. CATEGORY CODE 27245 211-111 I. PROJECT NUMBER ACC043015 8. PROJECT COST ($000) 26,251 :ould be severely inhibited. This project meets the criteria/scope specified in Air Force Handbook 32A preliminary analysis of reasonable options for accomplishing this project was done. It indicates there is only one option that will Beet operational requirements, therefore, a full economic analysis was not performed. A :ertificate of exception has been prepared. (Squadron Operations: 1,487 SM = 16,000 SF; MCI/Hangar: 4,926 SM = 5 3 , 0 0 4 S F ) DDITIONAL: .084, "Facility Requirements." POINT USE CERTIFICATION: Mission requirements, operational considerations, and location ire incompatible with use by other components. DD FORM 1391, DEC 76 Previous editions are obsolete. Page No. 214 1 . CONPONENT FY 2004 MILITARY CONSTRUCTION PROJECT DATA AIR FORCE (computer 3. INSTALLATION AND LOCATION 4. PROJECT TITLE AIR COMBAT COMMAND, VIRGINIA PREDATOR SQUADRON OPERATIONS/AMU/HANGAR 5. PROGRAM ELEMENT 6. CATEGORY CODE I. PROJECT NUMBER 27245 211-111 2. DATE generated) 8. PROJECT COST ($000) ACC043015 26,251 12. SUPPLEMENTAL DATA: a. Estimated Design Data: (1) Status: (a) Date Design Started (b) Parametric Coet Estimates used to develop COet8 * (c) Percent Complete ae of 01 JAW 2003 * (d) Date 35% Designed (e) Date Design Complete (f) Energy Study/Life-Cycle analysis was/will be performed 24-JUL-02 YES 15% Ol-SEP-02 15-SEP-03 YES (2) Basis: (a) Standard or Definitive Design (b) Where Design Wae Most Recently Used - NO (3) Total Cost (c) = (a) + (b) or (d) + (e): (a) Production of Plans and Specifications (b) All Other Design Coats (c) Total (d) Contract (e) In-house ($000) 1,575 700 2,363 1,969 394 (4) Construction Contract Award 04 JAN (5) Construction Start 04 FEB (6) Construction Completion 05 SEP l Indicates completion of Project Definition with Parametric Cost Estimate which ie comparable to traditional 35% design to ensure valid scope, cost and executability. b. Equipment associated with thie project provided from other appropriations: N/A DD FORM 1391, DEC 7b Page No. 1. coIdPoNmm 2. MTE FY 2004 MILITARY CONSTRUCTIOt+ PROJECT DATA (caoputer generated) 4IRFoRcE j. INSTALLATION AND LOCATIOly 4. PROJECT TITLE ~QUS&l',DISTRICTO~COLDHEIA cxAssIFIED MILCoBl PRoJEep 5.PROGRAMW 6.CATEGORYCODR 27248 999-999 9. 7.PRoJEcTMlMBER 8. PROJECT COST ($000, PAY2040004 COST 3,250 ESTIWhTES UNIT Ia !Lrm81FIRD MILCOBl PRosmcT UPPORTIW FACILITIES mmhL COST 3,250 0 3,250 'OTAL COWPRhCT COST 3,250 WrhL REQWST 3,250 'OThL REQUEST (ROUNDED) 3,250 0. Description of Prapoeed Construction: l.REQLulRRMmTrL8 ROdBCT: Em ADEQuhm: Ls SUBSThNMRD: LS hs raqu~red. : Special access required. DD FORM 1391, DRC 76 Previous editions are obsolete. Page No. 216 OUTSIDE THE UNITED STATES COMPONENT 1 FY 2004 MILITARY CONSTRUCTION PROGRAM 12. DATE AIR FORCE 4. COMMAND: 5. AREA CONST INSTALLATION AND LOCATION COST INDEX AIR COMBAT COMMAND 4JES FIELD, AZORES ORTUGAL 1.3 Personnel trength S OF 30 SEP 02 ND FY 2007 PERMANENT OFF ENL CIV 96 853 692 96 854 963 STUDENTS OFF ENL CIV 20 69 6 20 69 6 INVENTORY DATA ($000) 944 Total Acreage: Inventory Total as of: (30 Sep 02) Authorization Not Yet in Inventory: Authorization Requested in this Program: Authorization Included in the Following Program: Planned in Next Four Years Program: Remaining Deficiency: Grand Total: SUPPORTED OFF ENL 4 6 4 6 a. Future Projects: Included in the Following Program: None TOTAL 1,79’ I 2,06: 3 732,16( I (I 4,0825 (I 57,90( I 15,20( I 809,34t 5 (FY 2005) PROJECTS REQUESTED IN THIS PROGRAM: ATEGORY ODE PROJECT TITLE 42-674 Add To And Alter Fitness Center CIV 45 45 (FY 2004) COST DESIGN STATUS, SCOPE $.OOO S T A R T C M P L 1,735 SM 4,086 Feb-02 Sep-0: 3 4,086 Total (FY2005) b. Future Projects: Typical Planned Next Four Years: 11-111 Repair Aircraft Maint Hangar 8,818 SM 14,800 14-425 Transportation Complex 3,818 SM 9,300 21-315 Transient Quarters Phl 4,900 SM 12,200 21-315 Transient Quarters Ph2 5,880 SM 14,600 2,821 SM 7,000 30-I 42 Fire/Crash Rescue Station 13 c. Real Propery Maintenance Backlog This Installation: 0. Mission or Major Functions: The host air base wing has no permanently assigned force structure but rovides en route support to transiting aircraft and hosts Headquarters US Forces Azores. Lajes Field erves as a logistical bridge to Europe, Africa, and Southwest Asia by providing a ground refueling and stopver capability, functioning as a tanker staging location for in-flight refueling and serving as a primary divert ase for deploying aircraft. 1. Outstanding Pollution and Safety (OSHA) Deficiencies: 0 a. Air pollution b. Water Pollution 0 c. Occupational Safety and Health 0 d. Other Environmental 0 D Form 1390,9 JulO2 217 1. COWPONENT FY 2004 MILITARY CONSTRUCTION PROJECT DATA 2. DATE (computer generated) AIR FORCE 3. INSTALLATION AND LOCATION 4. PROJECT TITLE LAJES FIELD, PORTUGAL ADD TO AND ALTER FITNESS CENTER 5. PROGRAM ELEWRNT 8. PROJECT COST ($000) 6. CATEGORY CODE 7. PROJECT NUMSER 27596 WQNAO53002 742-614 9. COST 4,086 ESTIWATES UNIT COST LS ADD/ALTER FITNESS CENTER 3,494 HAWC ADDITION SM 425 2,850 ( 1,211 RENOVATION SM 1,549 1,470 ( 2,277 ANTITERRORISW FORCE PROTECTION LS SUPPORTING FACILITIES I (6 144 I PAVRWENTS LS SITE IWPROVKMEWTS LS ( 101 ( SUBTOTAL 44 3,638 2ONTINGENCY ( 5.0 %) 182 M)TAL CONTRACT CQST 3,020 SUPERVISION, INSPECTION AWD OVERHEAD ( 6.5 %) 240 l'OTAL REQUEST 4,069 POTAL REQUEST (ROUNDED) 4,086 EQUIPMENT FROM OTHER APPROPRIATIONS (NON-ADD) ( 18.0 1 to. Description of Proposed Construction: Construct a 425 SM addition for the health md wellnees center (HAWC!). Renovate existing HAWC to eupport storage and administration. Renovate main lobby. Install new floors in gymnasium and aerobic8 room. Refinish racquetball courts. Complete HVAC syetem. Force protection will :omply with minimum DOD etandards. Lir Conditioning: Ll. RBQuIRKbfEWT: 'ROJECT: 15oRW. 5,556SW ADEQUATE: 2,707 SM SUBSTANDARD: 174SM Add to and alter fitness center. (Current Mission) LEQUIREWEWT: Amodern, adequate sized and properly configured fitness center to conduct mmpreheneive and balanced programs for physical fitness programs required for Lajee AFR ,ereonnel and their dependents which ie a major quality of life and retention Pereonnel require eafe fitneee program8 including aerobics, health, :equirement. lental, and nutritional training, indoor recreational athletic activities, and a health tnd wellneee center at thie overseas base. WRRENT SITUATION: Lajes Field ie classified as a medium baee per the USAF Fitness Facilities Design Guide. Thie is the only existing fitness center on Lajee Field for US The HAWC is co-located within this facility. Generally, the facility is in )ersonnel. iair condition but is inadequately sized. Limited facilities for HAWC and existing :equirements are 20% deficient per USAF Fitness Facilities Design Guide standard. :MPACT IF NOT PROVIDRD: Physical conditioning and recreational programs will remain imited due to space restrictiona. This condition, coupled with deficiencies in all :ore areas, will continue to adversely affect the physical conditioning, morale, well ,eing, and retention rate of assigned military personnel thus impacting Lajes' :apability to accomplieh its mieeion. Additionally, testing, training, and :eam/individual eporte will continue to be hindered due to inadequate playing surfaces. FORM 1391, DEC 76 Previous editions are obsolete. Page No. 218 1. COBIPONENT FY 2004 MILITARY CONSTRUCTION PROJECT DATA 2. DATE (computer generated) AIR FORCE 3. INSTALLATION AND LOCATION 4. PROJECT LLJES FIELD, PORTUGAL ADDTOANDALTERPITNESS~R 5. PROGRAW ELEMENT 27596 6. CATEGORY CODE 742-674 7. PROJECT TITLE MJF5ER ’ MQNAOSSOOZ 8. PROJECT COST ($000) 4,086 DDITIONAL: ~hie project meets the criteria/scope specified in AFB 32-1084, "Facility A preliminary analyeie of reasonable options for accomgliehing thie !equirementen. zoject (statue quo, renovation, new construction) was done. It indicate8 there ie only me option that will meet requirementa. Because of this, a full economic analyeie wae rot performed. A certificate of exception hae been prepared. Base Civil Engineer: Lt !ol Terry Watkins, 011-351-295-576113. HAWC Addition: 425 SM - 4,573 SF; Renovation: .,549 SM - 16,667 SF. lOIWT USE CERTIFICATION: Wiieeion requirementa, operational coneideratione, and location me incompatible with uBe by other components. DD FORM 1391, DEC 76 Previous editions are obsolete. Page No. 219 . coNPoNENT FY 2004 MILITARY CONSTRUCTION PROJECT DATA 2. DATE (computer generated) IR FORCE . INSTALLATION AND LQCATION 4. PROJECT TITLE AJES FIELD, PORTUGAL ADD TO AND ALTER FITNESS CENTER 6. CATEGORY CODE 7. PROJECT NUMBER . PROGRAMRLBMBNT 742-674 27596 2. SUPPLEMENTAL 8. PROJECT COST ($000) MQNAO53002 4,086 DATA: a. Estimated Design Data: (1) Statue: (a) Date Design Started (b) Parametric Coat Estimatea used to develop costs * (c) Percent Complete ae of 01 JAN 2003 * (d) Date 35% Designed (e) Date Design Complete (f) Rnergy Study/Life-Cycle analysis was/will be performed Ol-FRR-02 YES 15% Ol-AUG-02 Ol-SEP-03 YES (2) Bade: (a) Standard or Definitive Design (b) Where Design Was Moat Recently Ueed - NO (3) Total Coat (c) I (a) + (b) or (d) + (e): (a) Pro%ction of Plans and Specifications (b) All Other Design Costa (c) Total (d) Contract (e) In-house ($000) 245 123 368 327 41 (4) Conetruction Contract Award 04 JAN (5) Conetruction Start 04 FEB (6) Conetruction Completion 05 PEB l Indicates cqletion of Project Definition with Parametric Cost Estimate which is comparable to traditional 35% design to ensure valid scope, cost and executability. b. Equipment associated with this project provided fram other appropriations: EQUIPMRNT NOMKNCLATDRR COBR4UNICATION FORM 1391, DEC 76 EQUIP/WIRING PROCURING APPROPRIATION FISCAL YgAR APPROPRIATED OR RBQDESTRD 3400 2004 Previous edition@ are obsolete. COST ($000) 18 Page No. 220 AIR FORCE 3. INSTALLATION AND LOCATION 4. COMMAND: ?AMSTElN AIR BASE, UNITED STATES AIR SERMANY FORCE, EUROPE 5. Personnel PERMANENT STUDENTS strength OFF ENL CIV OFF ENL CIV 4s OF 30 SEP 02 1247 6655 2366 120 1199 124 END FY 2009 1256 6669 2343 120 1199 124 ‘. INVENTORY DATA ($000) 3. Total Acreage: 3,102 I. Inventory Total as of : (30 Sep 02) :. Authorization Not Yet in Inventory: 1. Authorization Requested in this Program: ?. Authorization Included in the Following Program: (FY 2005) ‘. Planned in Next Four Years Program: 1. Remaining Deficiency: 1. Grand Total: 3. PROJECTS REQUESTED IN THIS PROGRAM: ZATEGORY =ODE PROJECT TITLE 131-454 1st Combat Communication SQ, PH. II 742-674 Fitness Center Annex la. Future Projects: Included in the Following Program: 122-264 Small Diameter Bomb )b. Future Projects: Typical Planned Next Four Years: 113-321 Ramp 1, PH. II 113-321 Ramp 1, PH. III Theather Aerospace Op Spt Center I40-000 141-000 Contingency Response Group, PH. II 141-000 86 AES Facility 141-000 Squad OPSIAMU 37AS 141-786 Air Expeditionary Force Processing Center !1 l-l 11 C-l 3OJ-30 Aircraft Hangar !ll-111 C-l 30 Fuel Cell Hangar Zl4-425 CTS Vehicle Maintenance Z14-425 Vehicle Maintenance Facility !18-712 AGE Maintenance Civil Engineer Sqd Midfield Complex !I9443 510-261 Warrior Preparation Center 5. AREA CONST COST INDEX 1.22 SUPPORTED OFF CIV ENL 302 586 49 302 586 49 TOTAL 1264 I8 12.64 .8 2,801,70 IO 154.30 16 35,61 6 2.06 86 216,95 ‘0 185,25 0 3,395,88 8 (FY 2004) SCOPE 7,100 SM 5,356 SM Total (FY2005) 1.190 SM Total 77,000 61,000 4,366 7,700 2,020 3,713 7,559 3,500 3,600 1,314 2,450 2,402 2,570 10,591 SM SM SM SM SM SM SM SM SM SM SM SM SM SM COST DESIGN STATUS SO00 S T A R T C M P L 19,713 Apr-02 Sep-03 15,903 Mar-02 Aug-03 35,616 2,066 2,066 23,600 14,100 25,700 19,100 9,050 12,500 28,420 8,660 9,400 4,350 8,100 6,950 6,347 40,673 87 )c. Real Propery Maintenance Backlog This Installation IO. Mission or Major Functions: A host airlift wing supporting a C-130E squadron, a C-9A squadron and a squadron momposed of C-26A, and C-21A aircraft; Headquarters, United States Air Forces in Europe and Headquarters, Allied Air -orces Central Europe. Il. Outstanding pollution and Safety (OSHA) Deficiencies: 0 a. Air pollution: b. Water Pollution: 0 c. Occupational Safety and Health: 0 d. Other Environmental: 14,700 221 1. COMPONENT 2. DATE PY 2004 MILITARY CONSTRUCTION PROJECT DATA (ccmputer generated) AIR FORCE 3. INSTALLATION AND LOCATION 4. PROJECT TITLE RAw3TlnNAIRBAw, GBRNANY CONSOLIMTED 1ST COMBAT COMMUNICATION SQUADRON, PH 2 5. PROGRAM m 6. CATRgORY CODR 7. PROJECT ND'MRER 27596 131-111 TwRO230462 8. PROJECT COST ($000, 19,713 COST ESTIMATES 9. CONSOLIDATED 1ST CoI(BAT COISSJNICATION COMEIAT CONNUNI CATIONS ( 12,908) ANTITERRORISM PORCR PROTECTION SUPPORTS FACILITIES UTILITIES -CATION SUPPORT PAWS PASSIVE FORCE PROTECTION -8 SITS =R-S 8uBToTAL COWF- ‘I’OTAL COWI’RACT ( 1,349) ( 1.124) l ( 5.0 COST %) SUPRRVISION, INSPECTION AND OVERMUD TOTAL REQUEST TOTAL REQUSST (ROUNDED) 19,688 SQUIPMRWI PROBl OTHER APPROPRIATIONS 19,713 ( 400.0) (NON-ADD) LO. Description of Proposed Construction: All civil, structural, mechanical, alectrical, fire prevention/alarm and oomwnication supporting work necessary for the :onstruction of a ccmbat camamications compound. Consists of mawnry or nmdular :onstructed facilities with eloped roofing systa. Provides space for maintenance and vehicle parking, utilities, and all other support. Includes minimum DOD interim force protection standards. 11. RRQUIRXWEUT: 8,686SM ADEQUATE: 1,586 SM SUBSTANMRD: 7,060BM Consolidate combat camun ications squadron. (current Mission). 3BQUIREMwIT: Adequately sized and configured facilities to provide optimum support for the canhat ccamaunications squadron. Adequate facilities are required to efficiently and affectively house all functions of the the combat cwmnm ications squadron inluding rapid seployable camaun ications and air traffic control services throughout Europe, Africa. aud the Middle East. The unit also supports the United Nations, Joint Chiefs of Staff, Sorth Atlantic Treaty Organization, United States European Coamand, Department of State, and US/coalition task forces during wartime, exercises, and military operations other :han war as directed by United States Air Forces in Europe. PROJECT: VRRRNT SITUATION: Current facilities, which consist of an old flight operations wilding and a series of hardened aircraft shelters, are not adequate to meet mission Leeds. These facilities were meant to be used on a temporary basis. The geographic leparation of unit functions makes operations, CampllLapd, and control inefficient and Personnel are working in undersized offices/areas and facilities not liffioult. lesigned for their mission. These conditions reduce productivity and morale. Parking DD FORM 1391, DRC 76 Previous editions are obsolete. Page No. 222 FY 2004 MILITARY CONSTRUCTION PROJECT DATA 1. CoBPomzm (caaputer kIRFORCE 2 . MTE generated) 3. INSTALLRTION AND LOCATION 4. PROJECT TITLE IzAMsmINAIRAIR, Gmx?LNY CONSOLIMTRD 1ST COMBAT COWWNICATION SQUADRON, PH 2 5. 6 . PROgRAR m CATSGORY CODE 7 . 131-111 27596 PROJECT TyFRO230462 8. PROJRCT COST ($000) 19,713 pace for the unit's mobility vehicles is extrmly limited. The current location estricts the ability to rapidly assemble and transfer the assets to assigned staging ocationa due to conetricted traffic patterna and roads. BIPACTIFNOTPROVIDRD: Ccebatc~cations sguadronwillcontinuetobe hindereddue o inefficient, undersized, and less than optimum operating conditions and location. he unit will not be able to perform and provide fisrt-rate ccsmaan d and control ~ommmications for forces within their mandatory response time. Functions will continue .t decreased productivity for customers and negatively irspact their mission. DDITIONAL: This project is not currently eligible for NATO funding. A precautionary me-finance statement will be filed in the event eligibility is established. This moject meets the criteria/ecope specified in Air Force Handhook 32-1084, Vacility mquireanentsw . A preliminary analysis of reasonable optione was done and indicates that knly one option meets operational requirements. A certificate of exception has been This is the second phase of a two-phase project. Base Civil Rngineer: Co1 prepared. reffrey L Leptrone, 011-49-6371-6228. combat camnun ications: 7,100 wd = 76,424 SF. yIREI~cuRmQxYx FCF Budget Rate used: EURO-DOLLAR 1.1386 K)INT USR CRRTIFIC!ATIONr This facility can be used by other cceumnents on an "as Lvailablew basis, however, the scope of the project is based on Air Force requirements. FORN 1391, DRC 76 Previous editions are obsolete. Page No. 223 1. COHPONRNT TY 2004 NILITARY CONSTRUCTION PROJECT DATA (cawuter generated) AIR roRQ 3. 4. INSTALLATION MID IBCATIOU PROJECT TITLE CONSOLIMTKD 1ST COMBAT COlQSRRC&TION RAMsTnu~BAsE, - SQUAUROU, 5. PROGRAM 6 . - CATEGORYCOM 7 . PH 2 P R O J E C T - 8. PROJECT COST ($000, TYFRO230462 131-111 27596 1 2 . 2. DATE 19.713 SUPP-AL DATA: a. Estimated Design Data: (1) Status: (a) Date Design Started (b) Parametric Cost Rstimatea used to develop costs * (cl Percent Ccamlete as of 01 irAR 2 0 0 3 l (d) Date 35% Dosigned (e) Date Design Complete (f) Qlergy Study/Life-Cycle analysis was/will be performed 02-APR-02 YES 15% Ol-xX3-02 Ol-SRP-03 YES (2) Basis: ( a ) S t a n d a r d o r Definitive D e s i g n - uo (b) Where Design Was Ncmt Recently Used (3) Total Cost (c) - (a) + (b) or (d) + (e): ( a ) Produktion (b) (c) (d) (e) of ($000) 1,183 591 1,774 1,478 296 Plans and Specifications All Other Design costs Total Contract In-house (4) Construction Contract Award 0 4 (5) construction start 04 FEB (6) 0 6 l Construction CaaDletioa m NAR Indkates completion of Project Definition with Parametric Cost Estimate which is c-arable to traditional 35% design to ensure valid scope, cost and executability. b. Rquimt associated with this project provided from other appropriations: EQuIplaesT-m -CATION RQUIPHQTT DD FORM 1391, DRC 76 AFPROPRIATIOU FISCAL Y-mm APPROPRIATRD OR RRQURSTRD 3000 2004 Previous editions are 0Dsolete. COST ($000) 400 Page No. 224 2. DATE FY 2004 MILITARY CONSTRUCTION PROJECT DATA 1. COMPONENT (computer generated) AIR FORCE 3. INSTALLATION AND LOCATION 4. PROJECT TITLE RAWSTEIN AIR BASE, GERWANY FITNESS CRWTER ANNRX 5 . PROGRAW ELRWENT 6. CATEGORY CODE 7. PROJECT 742-674 27596 9. NLR+BRR 8. PROJECT TYFR023043 COST COST ($000) 15,903 ESTIMATES COST UNIT II/=I ~ITNRSS CRNTRR FITNESS CENTER ANNRX ANTITERRORISM FORCE PROTECTION SM 5,356 0 =y I 5,356 2,432 13,096 ( 1 3 , 0 2 6 ) ( I LS I L XIPPORTING FACILITIES 70) 1,186 UTILITIES LS ( PAVEMENTS LS ( 3 3 5 ) LS ( SITE IMPROVRMRNTS PASSIVE FORCE PROTECTION LS MEASURES LS COWWDNICATION SUPPORT E XTBTOTAL 318) ( 42) ( 70) 14,282 C !GNTINGENCY '1 DTAL 421) 714 &.o %) CONTRACT COST E KTPERVISION, 14,996 INSPECTION AND OVRRRRAD ( 6.5 %) 975 'J XlTAL REQUEST 15,971 '1 :OTAL 'REQUEST (ROUNDRD) 15,903 E~QUIPWRRT FROM OTHER APPROPRIATIONS ( (NON-ADD) 2.0 1 Description of Proposed Construction: A two-story structure with reinforced 1.o. C 'oncrete foundation and floor slabs, masonry walls, roof system, fire protection. I ncludes space for weight lifting, group and individual exercise areas, men's and women's locker rooms / showers / latrines, indoor running track, and all necessary u.tilities and support. Includes minimum DOD interim force protection standards. 1 l. RRQUIRRWRWT: 17,898 SM ADEQUATE: 12,542 SM SUBSTANDARD: 0 SM (Current Mission) Construct a fitness center Annex. E~ROJRCT: A modern, adequate sized and properly configured fitness center to conduct EQUIRRWRWT: s C cnuprehensive and balanced programs for physical fitness programs required for Ramstein AFR personnel and their dependents which is a major quality of life and retention Personnel require safe fitness programs including aerobics, health, rrequirement. mlantal, and nutritional training, indoor recreational athletic activities, and a health and wellnese center at this overseas base. They !GURRRNT SITUATION: The existing Air Force fitness centers are over 45 years old. The combined r,equire constant repair and maintenance to remain operational condition. 8 quare meters of the four existing fitness centers do not equal the authorized square mieters outlined in AFH 32-1084 and in the new AF Fitness Center Design Guide for the n umber of personnel working and living in the area. The lack of adequate space leads to 0 vercrowded, unavailable facilities for much of the base population. Daily use of the R amstein fitness centers increased from 800 to 1200 people daily in the last 4 years. F acilities cannot accomodate the electrical requirements of state-of-the-art fitness e quipment and the ventilation system is inadequate. Space shortages exist throughout Weather t he facilities, in the locker rooms, weight rooms, and aerobic rooms. FORM 1391, DEC 76 Previous editions are obsolete. Page No. 225 PY 2004 MILITARY CONSTRUCTION PROJECT DATA 1. COMPONENT 2. DATE (computer generated) AIR FORCE 3. INSTALLATION AND LOCATION 4. PROJECT TITLE RAMSTEIN AIR BASE, GERMANY FITNESS CRNTER ANNRX 5. PROGRAM ELEMRNT 6. CATEGORY CODE 7. PROJECT NxDmRR 742-674 21596 TYFR023043 8. PROJECT COST ($000) 15,903 zonditions in Ge rmany validate the need for an indoor running track. Long hours of larkneas, rain and icy condition6 prohibit personnel from running outside year-round. :o maintain adequate fitness levels a year-round use facility is needed. MPACT IF NOT PROVIDED: Physical condition will continue to be limited due to inadequate space requirements. Thie will negatively affect the morale, quality of life, xoductivity, and impacta retention and combat readineee. Inadeguate ventilation will :ontinue to make it uncomfortable and unhealthy to exerciee; furthermore, electrical shortfalls will not support additional equipment. Thie project ie not eligible for NATO funding. Thie project meets the K)DITIONAL: :riteria/scope epecified in AP Handbook 32-1084, "Facility Requirementan and the Air ?orce Fitness Center Maeter Plan criteria. This ie a corporate Air Force directed project eesential for personnel quality of life, and retention of highly skilled Only one option meets the miesion requirement. Therefore, a full economic ?arsonnel. malysis was not,completed. A certificate of exception has been prepared. Base Civil Co1 Jeffrey L. Leptrone, 011-49-6371-47-6228. Fitnese Center Annex: 3ngineer: 5,356 Dl I 57,652 SF. ZORBIGN CURRRNCY: FCF Budget Rate Deed: RURO-DOLLAR 1.1386 JOINT USE CERTIFICATION: This facility ie progransned for joint use with all other nilitary components; however, it ie fully funded by the Air Force. DD FORM 1391, DEC 76 Previous editions are obsolete. Page No. 226 1. COWPONENT FY 2004 MILITARY CONSTRUCTION PROJECT DATA AIR FORCE 3. INSTALLATION AND LOCATION 4. PROJECT TITLE RAWSTEIN AIR BASE, GERWANY FITNESS CENTER ANNEX 5. PROGRAM ELEMENT 2. DATE (computer generated) 6. CATEGORY CODE 7. PROJECT NUWRER 27596 742-674 8. PROJECT COST ($000) TYFRO23043 15,903 12. SUPP LEblENTAL DATA: a. Eetimated DeBign Data: (1) s t a t u e : (a) Date Design Started (b) Parametric Coat Eetimates used to develop costs * (c) Percent Complete ae of 01 JAN 2003 l (d) Date 35% Designed (e) Date DeBig3I Complete (f) Energy Study/Life-Cycle analysis wae/will be performed 15-H&R-02 YES 15% Ol-AUG-02 Ol-AUG-03 YES (2) Basis: (a) Standard or Definitive Design (b) Whey- Design Wae Moat Recently Used - NO (3) Total Cost (c) = (a) + (b) or (d) + (e): (a) Production of Plans and Specifications (b) All Other DeBigI3 Costs (c) Total (d) Contract (e) In-houee ($000) 954 477 1,431 1,272 159 (4) Conetruction Contract Award 04 FEB (5) Construction Start 04 FEB (6) Construction Completion 05 DEC * Indicates completion of Project Definition with Parametric Coat Estimate which is comparable to traditional 35% design to ensure valid scope, cost and executability. b. Equipment aseociated with thie project provided from other appropriatione: EQUIPWRNT NOMENCLATURE EXERCISE EQUIPWENT DD FORM 1391, DEC 76 Previous PROCURING APPROPRIATION FISCAL YEAR APPROPRIATED OR REQUESTED 3080 2004 editions are obsolete. COST ($000) 2 Page No. 227 1. COMPONENT FY 2004 MILITARY CONSTRUCTION PROGRAM 12. DATE I AIR FORCE :I. INSTALLATION AND LOCATION 4. COMMAND: 5. AREA CONSJ ESPANGDAHLEM AIR BASE, UNITED STATES AIR COST INDEX ;;ERMANY FORCE, EUROPE 1.23 Ei. Personnel PERMANENT STUDENTS SUPPORTED 5strength CIV OFF EN1 CIV OFF EN1 OFF EN1 CIV TOTAL F4s OF 30 SEP 02 324 3806 644 1 168 4,94 EIND FY 2009 320 3822 642 1 168 4,95 7‘. INVENTORY DATA ($000) iI. Total Acreage: 1,374 t). Inventory Total as of : (30 Sep 02) 1,472,90; C :. Authorization Not Yet in Inventory: 33,21; C I. Authorization Requested in this Program: 25,33’ E:. Authorization Included in the Following Program: (FY 2005) f Planned in Next Four Years Program: 70,642 33,081 c 1. Remaining Deficiency: tI. Grand Total: 1,635,17E EI. PROJECTS REQUESTED IN THIS PROGRAM: C:ATEGORY PROJECT TITLE d :ODE 1‘41-786 Passenger Terminal 7‘31-142 Fire Station Annex and Traning Facility 7‘42-674 Fitness Center E151-147 South Gate E)a. Future Projects: Included in the Following Program: None slb. Future Projects: Typical Planned Next Four Years: 1121-111 POL Admin Ops Facility 1141-786 Mobility Processing Center 1141-962 Control Tower ;F14-426 ADAL Vehicle OPS Complex 2!18-712 AGE Facility 4142-758 MRSP/Supply Warehouse MUNS Maint Admin Maint Facility cj10-129 i‘21-312 Dormitory (96 PN) i‘21-312 Dormitory (96 PN) i722-351 Dining Facility i‘24-417 Visitors Quarters (FY 2004) COST DESIGN STATUS SCOPE 650 SM 1,150 SM 6,950 SM 16,960 LS Total $.OOO S T A R T C M P L 1,546 Apr-02 Sep-03 3,865 Apr-02 Sep-03 17,117 Mar-02 Sea-03 2,800 Mar-03 Se;03 25,328 (FY 2005) 662 SM 2,220 SM 724 SM 4,330 SM 2,560 SM 4,554 SM 560 SM 3,674 SM 9,600 SM 1,712 SM 4,273 SM 1,592 6,150 4,200 2,500 5,000 14,400 1,550 9,700 10,000 6,150 9,400 27 E rc. Real Propery Maintenance Backlog This Installation 1,O. Mission or Major Functions: A USAFE installation that is home to the largest fighter operation in Germany. A host F:ighter Wing commands three fighter squadrons and an air control squadron flying F-l 6 C&Ds and OA/A-1 OS. 1 1. Outstanding pollution and Safety (OSHA) Deficiencies: a. Air pollution 0 b. Water Pollution 0 c. Occupational Safety and Health 0 d. Other Environmental 0 C 228 FY 2004 MILITARY CONSTRUCTION PROJECT DATA 1. COMPONENT (computer AIR FORCE 2. DATE generated) 3. INSTALLATION AND LOCATION 4. PRoJgCT TITLE SPANGDARLRMAIR FIRR STATION ANNEX AND TRAINING FACILITY BASE, GRRMANY 5. PROGRAM ELXHXNT 6. CATRGORY CODR 7. 27596 VYRXO13203 731-142 9. PROJECT NUMRRR 8. PROJECT COST ($000) 3,865 COST ESTIMATES PIRR STATION ANNEX/TRAINING FACILITY FIRE STATION ANNRX FACILTY FIRE TRAININGARRA ANTITERRORISM FORCE PROTECTION SUPPORTING FACILITIES COMMIJNICATIONS SUPPORT SITE IMPROVRMSNTS UTILITIES PAVRbIRNTS PASSIVE FORCE Pi%TK!TIONMRASURRS SUBTOTAL ( 5.0 %) POTAL CONTRACT COST ZONTINGRNCY WPRRVISION, INSPECTION AND OVRRRRAD POTAL REQUEST POTAL REQUEST (RODNDRD) -0. Description of Proposed Construction: Reinforced concrete foundation/floor slabs md masonry walls. Construction to include roll-up doors, fire protection eyatem. .iving quarters. pitched roof, utilities, site improvements, vehicle parking, and a :oncrete fire training area with 2Ocm (6") thick concrete pavement and installation of L fire training structure. Includes minimum DOD interim force protection standards. Il. RRQUIRRMXNT: 'ROJRCT: 3,563SY ADEQUATE: 605 SM SUBSTANDARD: 1,267SY Construct a Fire Station Annex and Training Area (Current Mission). LEQUI- : A properly sized and functionally adeguate fire station annex is required :o aupport fire fighting responses on Spangdahlem AR. Annex muet be manned 24 lours/day, 7 days/week, with overnight acconmrodationa. Project provides a fire station ~nneac strategically located to enable fire fighting personnel to meet 3-minute response :imes to the furthest end of the runway and to structures within a two-mile radius per IoD Instruction 6055.6. Additionally, an adequate fire training area is required to maintain fire fighter proficiency. 'URRRRT SITUATION: Spangdahlem AS currently has only one SO-year old fire atation to upport all airfield, base structure, and houeing responses. Fire trucks cannot meet .equired response times to all areas of the base, and vehicles must cross active axiwaye to reach most of the base facilities. The current station is undersized for :he number of trucks and personnel for today's mission. Furthermore, due to the Rhein rain transition/expansion activities, the current fire training area will be demolished .o make way for the new aircraft parking ramp. AT/FP costs for this project are higher DD FORM 1391, DEC 76 Previous editions are obsolete. Page No. 229 r. 1. COMPONENT PY 2004 MILITARY CONSTRUCTION PROJECT DATA 2. DATE (computer generated) AIR PORCR 3. INSTALLATION AND LOCATION 4. PROJECT TITLE SPANGDAHLEN AIR RARE, GERMANY FIRE STATION ANNRX AND TRAINING FACILITY 5. PROGRAMRLRMRRT 6. CATRGORY CODE 27596 731-142 7. PROJECT NDMRRR VYSlCO13203 8. PROJECT COST ($000) 3,865 ban standard DOD guidance due to stricter USCINCRDR AT/FP OPORD 01-01 force protection tandards requiring higher-level structural hardening, splinter protection, and stronger ,indow treatments. Fire fighter reaponse on Spangdahlem AB will continue to be MPACT IF NOT PROVIDED: Lelayed due to the need to cross active taxiways to respond to daily calls for support. lelays in response increase the possibility of loss of life, aircraft and other 'eeourcee critical to the mission. In addition, fire fighters will continue to work in .nferior, inefficient facilities which adversely impact their ability to provide ,deguate fire protection for the entire base populace and will lack a training area to maintain their fire fighting and crash rescue proficiency. SDITIONAL: This project is not eligible for NATO funding, however, a precautionary Ire-finance statement will be filed in the event eligibility is established. This broject meets the criteria/scope specified in Air Force Handbook 32-1094, *Facility !equirements" . i‘preliminary analysis of reasonable options was done and indicated that nly one option meets operational requirements. A certificate of exception has been Irepared. Ease Civil Engineer: Lt Co1 Kurt J. Kaieler, 011-49-6565-6302. Fire Station 1,150 SM - 12,374 SF; Training Area: 2,500 SM - 26,910 SF. UlXleX: PORRIGN CURRENCY: FCF Budget Rate Used: RDRO-DOLLAR 1.1386 lOINI USE CERTIFICATION: Miaaion requirements, operational considerations, and location Lre incompatible with use by other components. DD FORM 1391, DRC 76 Previous editions are obsolete. Page No. 230 FY 2004 MILITARY CONSTRUCTION PROJECT DATA 1. coHPoNmT 3. INSTALLATION AND LGCATION SPANGDARLEM AIR EASE, 4. PROJECT TITLE GERMANY 5 . PROGRAM ELEMENT FIRE STATION ANNEX AND TRAINING FACILITY 6. CATEGORY CODE 7. PROJECT NUMEER 731-142 VYHKO13203 27596 1 2 . 2. DATE (computer generated) AIR FORCE 8. PROJECT COST ($000) 3,865 SUPPLEWENTAL DATA: a. Estimated Design Data: (1) Status: (a) Date Design Started (b) Parametric Cost Estimates used to develop costs l (c) Percent Complete as of 01 JAN 2003 l (d) Date 35% Designed (e) Date Deaign Complete (f) Energy Study/Life-Cycle analysis was/will be performed 20-APR-02 YES 35% 30-AUG-02 Ol-SEP-03 YES (2) Basis: (a) Standard or Definitive Design (b) Where Deeign Was Btost Recently Used - NO (3) Total C&t (c) I (a) + (b) or (d) + (e): (a) Production of Plans and Specifications (b) All Other Design Costs (c) Total (d) Contract (e) In-house ($000) (4) Construction Contract Award 04 FEB (5) Construction Start 04 MAR (6) 05 FRB Construction 232 116 348 309 39 Completion * Indicates completion of Project Definition with Parametric Cost Estimate which is comparable to traditional 35% design to ensure valid scope, cost and executability. b. Equipment associated with this project provided from other appropriations: F I S C A L YRAR PROCURING APPROPRIATION APPROPRIATED OR REQUESTED FURNITURE 3400 2005 75 COWKUNICATION EQUIPWENI 3400 2005 75 EQUIPMENT NOWENCLATURE DD FORM 1391, DEC 76 Previous editions are obsolete. COST ($000) Page No. 231 l.CCRPONRNT FY 2004 MILITARY CONSTRUCTION PROJRCT DATA AIR FORCR (cauputer generated) 3. INSTALLATION AND LCCATION 4. PROJRCT TITLE SP-AIRBASE, PASSRImRRTRRMmAL GERxaNY S.PRCGRAMELmmNT 6. CATRGORY CODE 7. 27596 141-786 9. IONSTRUCT 2. DATE PROJECT RUMSRR 8. PROJECT COST ($000) VYRRO23001 1,546 COST ESTINATES PAS- TRRMIW& PASSENOKR TmMINAL ( 1,082 1 ANTITRRRORISMFORCR PROTECTION 3DPPORTIIW FACILITIES PAWS UTILITIES SIW6 IRPRWRt4RRTS COMMUNICATION SUPPORT 3uBToTAL ZoNTnmENcY ( 5.0 %) roTALcoBrrRAcT co& 3UPRRVISION, INSPRCTION AND WRRRRAD roTAL REQUEST L'OTAL REQUEST (ROUNDRD) 1,546 .O. Description of Proposed Constructioll: Construction includes concrete foundations md floor slab, masonry walls, structural steel frame, pitched roof, fire protection lysttrm, all utilities, incorporate force protection measures, pavememts, RVAC, site mprwements, and any additional work associated with this project. .l. RRQUIRIDISWT: 65OSM ADEQUATE: 0 SM SUBSTANMRD: OSM Construct a Passenger Terminal. (New Mission) LEQUIRENENT: Construct a facility to support in-transit passengers while aircraft lerpicing or repairs are made. Facility will also be used for processing originating lasseugers onto aircraft in support of worldwide contingency operations. Providean mclosed secure, cwered area for up to 150 passengers to off-load and wait for required aircraft mainteuance to be performed prior to re-boarding and proceeding to the final Location needs to be separated frcm other base activities since passengers lestiuation. till have processed through security at their originating location. Include capability .o process passengers on au emergency basis to other aircraft due to mechanical delays m- unforeseen requirements. Ccumunications requiremeuts include LAN connectivity, :lobal Air Terminal Execution System, and a public address system. 'RCnJECT: VRRRUI SITUATION: Due to Rheiu-Main Air Base closing by Dee 2005, the airlift mission .s being relocated between Ramsteiu aud Spaugdahlem. Siuce this base will be a key kropeau location for in-transit aircraft supportiug contingency and peacetime perations, it will be used for re-fueling, performing minor maintenance, and changing kcrews, before continuing ou to the final destination. In-transit passengers will be .eguired to wait up to three hours outside the aircraft in the harsh weather conditions, br in vehicles until aircraft servicing is completed. MPACT IF NOT PROVIDRD: In-transit troops and passengers will have to wait in tnsecured/non-sterile locations, in harsh weather conditions prior to re-boarding DD FORM 1391, DEC 76 Previous editions are obsolete. Page No. 232 FY 2004 MILITARY CONSTRUCTION PROJECT DATA 1. coMPoruWr 2. DATE (cmputer generated) AIRFORCE 3. INSTALLATION AND LOCATION 4. PROJECT TITLE sP-AIRBAw,- PASSRNGRRTERMIWG 6. C!AmRY CODE 7. PROJECT - 5.PRoGRAMELRHEuT 141-786 27596 vniuO23001 8. PROJECT COST ($000) 1,546 drcraft to destination. The ramp and hsngars will continue to be used for troops ad passengers waiting to re-board aircraft. ~his project is not eligible for HATO funding. This project meets the :riteria/sxope specified in Air Force Handbook 32-1084, nFacility requirementen. A preliminary analysis of reasonable options was done and indicates that anly one optics mete operational requirements. A certificate of exception ha8 been prepared. Base :ivil mgineeer: Lt co1 lcurt Kaisler, 011-49-6565-61-6302. Passenger Terminal: 650 SN iDDITION?aL: : 6,994 SF. ?oRR1GNCURRmxY: FCF Budget Rate Used: EURO-DOW 1.1386 TOINT USE CRRTIFICATION: This facility is prOgraIIEWd for joint use with all Other ailitary cmponentsl however. it is fully funded by the Air Force. DD FORM 1391, DEC 76 Previous editions are obsolete. Page No. 233 l.CcR#PoNENT FY 2004 MILITARY CONSTRUCTION PROJECT DATA (cwter generated) AIR FORCR 3. INSTALLATION AND LOCATION 4. PROJECT TITLE sPNa3MmEHAIRBASE‘GEmlAm PAS- TlmKnmL s.PRoGRAMm 2. DATE 6. CATRGORY CODR 7. PROJECT NOHBER 27596 141-786 8. PROJECT COST ($000) VYEUO23001 1,546 12. SUPP-AL DATA: a. lhthated Design Data: (1) Status: (a) Date Design Started (b) Parametric Cost Estimates used to develop costs l (c) Percent Canplete as of 01 m 2003 l (d) Date 35% Designed (e) Date Design Ca@ete (f) Qlergy Study/Life-Cycle analysis was/will be performed 04-APR-02 YES 15%' Ol-mm-02 Ol-SEP-03 YES (2) Basis: (a) Standard or Definitive Design (b) ~bere Design Was Most Recatly Used - No (3) Total Coat (c) = (a) + (b) or (d) + (e): (a) Production of Plans aad specificatioau (b) All &r De~sign costs (c) Total (d) Ccmtract (e) In-house ($000) 93 46 139 124 15 (4) Construction Contract Award 04 JAN (5) Construction Start 04 FEE (6) Construction Cmletion 05 WAR l Indicates canpletion of Project Definition with Parametric Cost Estimate which is c-able to traditional 35% design to ensure valid scope, cost and executability. b. Equipment associated with this project provided fran other appropriationsi N/A yrevxoua eaxxone are ormosece. Page No. 234