TESTED COMPONENTS National Wind Institute (NWI) Texas Tech University The National Wind Institute (NWI) at Texas Tech University performs debris impact tests on storm shelters, shelter components, and building materials to evaluate their ability to resist various types of projectiles propelled at different speeds in accordance to accepted and proposed test protocols as follows: Protocols for Debris Impact Testing2 Protocol 1 Protocol 2 Protocol 3 Protocol 4 Protocol 5 Hurricane envelope impact by a 9 lb. wood 2”x4” propelled at 34 mph. In accordance to the Florida Building Code, the International Code Council, and the Texas Dept. of Insurance Windstorm Resistant Construction. Hurricane Shelter Speed impact by a 9 lb. wood 2”x4” propelled at 0.40 x the design wind speed (mph) for horizontal impacts and 0.10 x the design wind speed (mph) for vertical impacts, in accordance to the proposed ICC 5001 – ICC/NSSA Standard for the Design and Construction of Storm Shelters. Hurricane Shelter Speed impact by a 9 lb. wood 2”x4” propelled at 0.50 x the design wind speed (mph) for horizontal impacts and 0.33 x design wind speed (mph) for vertical impacts, in accordance with FEMA 320, “Taking Shelter from the Storm,” 2008 edition and FEMA 361 “Design and Construction Guidance for Community Saferooms,” 2008 edition. Tornado shelter speed impact by a 15 lb. wood 2”x4” propelled at 100 mph for horizontal impacts and 67 mph for vertical impacts, in accordance with FEMA 320, “Taking Shelter from the Storm,” 2008 edition, and FEMA 361, “Design and Construction Guidance for Community Saferooms,” 2008 edition. Department of Energy (DOE) impact standards. 1 – The ICC 500 – ICC/NSSA Standard for the Design and Construction of Storm Shelters is scheduled for inclusion in the 2009 editions of the International Residential Code and the International Business Code. This is a Life Safety Standard which will use an Extreme Wind Map for Hurricanes with wind speeds starting at 225 mph and with contours along the Atlantic and Gulf Coast stepping inland in 10mph increments to 160 mph. 2 – All impact tests are consistent with the Debris Impact Requirement of ICC-500. Note: Listing does not imply product endorsement or warranty by TTU, FEMA or NSSA. Unless otherwise noted, the following listings have been tested to Protocol 4, the Tornado Standard Protocol. Rev: 06-08-2015 Components Company 3B Construction Monty Riffer 2320 Jefferson St. Anderson, IN 46016 Ph: (603) 759-9899 Product Tested Date Tested: 07/14 CMU Block Panel 3M Storm Shelters Greg Smith P. O. Box 161652 Fort Worth, TX 76161 Ph: (817) 475-2286 Date Tested: 03/14 Unfinished In-garage floor shelter door A & A Sheet Metal Products/Securall Steel Doors Randall Veatch 5122 N. State Road 39 LaPorte, IN 46350-8782 Ph: (1-888) 326-7890 Date Tested: 05/12 Wall assembly and doors (both in-swinging and out-swinging) A-1 Storm Shelters Brian Cunningham 599 Halls Place West Blacton, AL 35184 Tel: (205) 938-5159 Date Tested: 06/12 Above ground concrete shelter panel with door Adjust-A-Frame Keith Heaberlin 4101 Greenwood Road Shreveport, LA 71109 Ph: (318) 635-0514 Date Tested: 07/14 Wind Resistant Manufactured Housing Skirting Frame System Ambiente Housing Midwest Mike Klumb 21800 Doral Road Waukesha, WI 53186 Ph: (262) 798-8150 Date Tested: 02/08 Hurricane panels, Protocol 2, 225 mph hurricane American Business Continuity Domes, Inc. Maria Hahn 3063 Outlet Center Drive Sealy, TX 77474 Ph: (979) 885-1919 Date Tested: 11/12 Insulating concrete foam (ICF) wall system with tornado resistant glaze Date Tested: 11/12 Concrete dome – flat panel representation American Matrix Technologies James Wiese Technology Innovation Center Iowa City, Iowa 52242 Date Tested: 09/99 Ceramic/glass panel Rev: 06-08-2015 Components Ph: (319) 620-7469 APA (formerly American Plywood Association) PO Box 11700 7011 South 19th Street West Tacoma, WA 98411 Ph: (253) 565-6600 Date Tested: 11/00 Laminated wood panel Arch Technology Corporation Victor Lee 11024 Rippberger Road Plato Center, IL 60170 Ph: (840) 464-5656 Date Tested: 04/00 Shelter wall panel Arizona State University Dr. Thomas Attard School of Sustainable Engineering and the Build Environment P. O. Box 870205 Tempe, AZ 85287-0204 Ph: (480) 965-5623 Date Tested: 10/12 Carbonflex tornado panels Bautex Systems, LLC Duane Holloway 5602 Central Texas Drive San Marcos, TX 78602 (512) 637-1200 Date Tested: 07/14 Bautex Block Panel Bleeding Edge George Sturmon 101 Industrial Park Drive Sullivan, MO 63080 Ph: (314) 422-0613 Date Tested: 01/14 Transparent Armor Window Bob D. Campbell & Co., Inc. Lee S. Johnson 4338 Belleview Ave. Kansas City, MO 64111 Ph: (913) 706-0215 Date Tested: 12/14 Grating System Builders’ First Source Richard Woodward 6550 Roosevelt Blvd. Jacksonville, FL 32244 Ph: (904) 813-2326 Date Tested: 04/08 and 01/09 Layered plywood and steel shelter panel Date Tested: 04/10 Layered OSB shelter panel 170 mph hurricane, Protocol 2 Date Tested: 07/11 Series 1 – Series 3- 170 mph Hurricane shelter wall assemblies (Tested under Domes Int.) Rev: 06-08-2015 Components Burr Computer Environment, Inc. Tim Frank 10400 Rogers Road Houston, TX 77070 Ph: (281) 374-8644 Date Tested: 01/05; 02/08 Corner Grating – outdoor machinery Enclosure Grating - material Composite Building Systems, Inc. (orig. ABC Domes International) Dean Deaton #5 Murphy Street Tishomingo, MS 38873 Ph: (662) 438-7186 Date Tested: 05/06 Fiberglass dome panels, Hurricane Protocols 1 and 2 CEM Wall Joe McClure 1516 20th Street South Birmingham, AL 35250 Ph: (905) 438 0084 Date Tested: 10/11 Tornado Panels Dean Steel Claus Heide 111 Merchant San Antonio, TX 78204 Ph: (210) 226-8271 Date Tested: 06/06 High pressure tests on blast resistant windows (ICC-500 pressures) Date Tested: 05/07 High pressure tests on blast resistant windows (ICC-500 pressures) Date Tested: 05/02 Precast concrete shelter wall panel Dukane Precast Brian Bock 1805 High Grove Lane Naperville, IL 60540 Ph: (630) 355-8118 Empresas Hopsa August Simons Via Transistmica and Calle 64 Oeste Urbanizacion Industrial Los Angeles Panama City, Republica Panama Ph: (001-507) 279-9854 Date Tested: 01/05 EMMEDUE M-2 insulated concrete panels Protocols 1, 2, and 4 Evaptech Inc. Mr. John Ahern 8331 Nieman Road Lenexa, KS 66214 Ph: (913) 209-4543 Date Tested: 05/2015 Metal fan guard. 1/4-in. pencil rods with (3)- 3/4-in. x 3/8in. support bars FiberWeb Imad Qashou 70 Old Hickory Blvd. Old Hickory, TN 37138 Ph: (615) 847-7574 Date Tested: 07/06, 09/06, 09/07 Hurricane envelope Protocol house wrap Future Steel Date Tested: 03/12 Rev: 06-08-2015 Components Lorenzo Turi 73 Ward Road Brampton, Ontario Canada L6S 6A8 Trapezoidal Panels for above-ground shelters GCC of America Hank Hearon 4253 Montgomery Blvd. NE Suite 210 Albuquerque, NM 87109 Ph: (800) 234-2266 Date Tested: 03/05 Insulated concrete panels Protocol 1, 2, 3 and 4 Date Tested: 03/07 Insulated concrete panels Protocols 1 and 1 GE Advanced Materials Polymershapes Insulgard 1291 Rickett Road Brighton, MI 48116 Date Tested: 10/04 TorGard Bal 40 glazing in HP/600T frame 8’x7’ – ICC-500 pressures G&M Tank Co., Inc. Jeff McMahan P. O. Box 333 Purcell, OK 73080 Ph: (405) 527-5342 Date Tested: 12/12 Below ground shelter doors and frame GrafTech International Mark Segger 12900 Snow Road Parma, OH 44130 Ph: (216) 676-2547 Date Tested: 07/07 FEMA impact resistant composite panel GrafTech International Mark Segger 12900 Snow Road Parma, OH 44130 Ph: (216) 676-2547 Hardwire LLC John Hammond 1000 Quinn Avenue Pocomoke City, MD 21851 Ph: (410) 957-3660 Date Tested: 07/07 FEMA impact resistant composite panel HI Tech TILT Rick Bush PO Box 21415 Keizer, OR 97307-1415 Ph: (503) 390-0487 (503) 399-0964 Cell: (503) 569-9636 Date Tested: 08/11 Concrete panel with steel stud backup Holz.ban forschungs gnbh Thomas Bogensperger Inffeldgasse 24/1 8010 Graz, Austria Date Tested: 09/08 Laminated timber panels Protocol 4 resistant Rev: 06-08-2015 Components Date Tested: 09/05 FEMA impact resistant composite panel Ph: (+43 316) 873-4608 Hunter Buildings and Manufacturing, LP Joey Dawson 14935 Jacinto Port Blvd. Houston, TX 77015 Tel: (281) 452-9800 Date Tested: 11/13 Steel shelter wall panel IMSI Dr. Rudolph Strobel 7305 Thompson Road Cincinnati, OH 45247 Ph: (770) 518-9414 Date Tested: 09/02 Shelter wall panel composed of 3 wall, 5 cell insulated 8” concrete block w #4 rebars at 2’ in center International Masonry Institute Ms. Diane Throop 27 Worthington Court Simpsonville, SC 29681 Date Tested: 06/14 Utility Brick Veneer Wall Modular Brick Veneer Wall Lee Cor Systems Steven Medlin One Courthouse Square, Suite 4 New Madrid, MO 63869 Ph: (573) 748-0204 Fax: (573) 748-8910 Date Tested: 08/11 Wall Panels Lite Tech Wall Systems Scott Deans 610 Hermits Trail Altamonte Springs, FL 32701 Ph: (800) 482-5402 Date Tested: 12/08 Various panels resistant to hurricane impacts for envelope and shelters LP Building Products Alan Jumper 414 Union Street Nashville, TN 37219 Ph: (919) 363-6400 Date Tested: 10/09 – 11/14 Shelter wall panel using LP LSL logs in HabiFrame System Panel Hail Testing Mason Greenstar Zach Rabon PO Box 1420 Mason, TX 76856 Ph: (512) 698-9879 Date Tested: 03/09 Cellulose and Portland cement block system Resistant to hurricane impacts for building envelopes and shelters Maccaferri Inc. Mr. Ghislain Brunet Rockfall Business Unit Manager for North America 10303 Governor Lane Boulevard Williamsport, MD 21795 Ph: (301) 223-6910 Date Tested: 04/15 & 05/15 Rev: 06-08-2015 Components Series 1 DOE, Debris Impact Barrier. 3000 kilojoule resistance ring net with 3.4 mm type 8-ft. x 10-ft. wire mesh. Series 2 DOE, Debris Impact Barrier. 3000 kilojoule resistance ring net with 3.4 mm type 8-ft. x 10-ft. wire mesh. Series 3 DOE, Debris Impact Barrier. 3000 kilojoule resistance ring net with 3.0 mm type 8-ft. x 10-ft. wire mesh. Series 1 DOE, Debris Impact Barrier. 3000 kilojoule resistance ring net with 2.7 mm type 8-ft. x 10-ft. wire mesh. Medford Enterprises, Inc. Dutch Medford 2877 Aukul Street St. Lihue, HI 96766-2084 Tel: 1-800-232-1052 Date Tested: 01/12 Series 1-3 Wall panels Modular Engineering Sam Ramsey 180 Airpark Drive Wilsonville, AL 35186 Ph: (205) 921-9966 Date Tested: 06/01 FEMA 361 wall and roof steel panels Nusafe Storm Shelter Panel System Country J. Hansen 525 South Locust Denton, TX 76201 Ph: (940) 891-3069 Date Tested: 07/05 Panelized system using metal studs for above ground shelter Precision Mine Repair James Hise 705 West Main Ridgway, IL 62979 Ph: (618) 272-7220 Date Tested: 07/09 Protocol 4 wall impact Protective Structures, LTD George Smith 9780 Lake Forest Way Roswell, GA 30076 Ph: (770) 518-9414 Date Tested: 11/03 Composite wall panel system RediWall Tex-Rite Building Systems Erwin Ritter 6103 Shadowcrest Houston, TX 77074 Ph: (713) 776-3457 Date Tested: 11/03 Precase concrete and steel stuf panel, Protocol 1 Remagen Corporation James E. Waller, P.E. 707 North Bluff Circle Date Tested: 10/09 FEMA 361 wall vent panel Date Tested: 11/12 Rev: 06-08-2015 Components Monteagle, TN 37356 Ph: (931) 692-3961 Above ground shelter panels FEMA 320/361 and ICC 500 Rickborne’s Marine Solution Chris Rickborne 2425 Bancroft Blvd. Orlando, FL Date Tested: 08/09 FEMA 32- shelter wall assembly Resicon International Win Courtney 1205 Cottonwood Brownsville, TX 78520 Date Tested: 06/01 Resin concrete shelter panel Royal Building Systems, LTD John Todd 1 Royal Gate Boulevard Woodbridge, Ontario, Canada L4L8Z7 Ph: (972) 342-9080 Date Tested: 06/01 Shelter wall panel system SafePorch Storm Shelter Mark Pile P. O. Box 40 Lowell, AR 72745 Tel: (479) 659-8830 Date Tested: 09/13 Venting cover Vent cover Safe Shelter Systems. LLC Andy Youngquist 1431 E. Saint Andrew Place Santa Ana, CA 92706 Ph: (949) 862-5616 x110 Date Tested: 01/14 Steel panel, no backing Steel panel with backing Steel corrugated panel, no backing Schnell House S.A. Pierluigi Pettarini Srada Borrana 33 – Zona Ind. Ciarulla 47899 Serravalle – Rep. San Marino Ph: (+378) 0549 960424 Date Tested: 08/09 ICC-500/FEMA 361 hurricane panel Simpson Strong Tie Shelter Randy Shackelford 2221 Country Lane McKinney, TX 75069 Ph: (972) 439-3029 Date Tested: 03/2014 Above-ground panel shelter StormBlocker Composite Panels Mark Latham 1155 West Wall Street #102 Grapevine, TX 76051 Ph: (817) 329-6191 Date Tested: 07/01 Composite wall system on FEMA 320 stud walls Date Tested: 09/04 Protocol 2, 160 mph hurricane Date Tested: 02/05 Protocol 3 with StormBlocker mount on interior of FEMA 320 stud wall system Rev: 06-08-2015 Components Stormtech Systems George Lafferty 4801 Neosho Roeland Park, KS 66205 Ph: (913) 558-0097 Date Tested: 03/10 Steel window shutter system, Protocol 4 Supercell Shelters Carlton Guyse 1021 Brooks Street SE Decatur, AL 35601 Ph: (256) 340-1620 Date Tested: 02/14 Above-ground community shelter end panel Tornado Tech, LLC 1212 West Liberty Ponca City, OK 74601 Date Tested: 01/11 Above Ground Single Sheet Steel Shelter panel Tri-Point Building Products, Inc. 2025 Webster Waco, TX 76706 Ph: (214) 315-9381 Date Tested: 06/0 Aerated concrete panels Vantem Composite Technologies David Densford 710 FM 306 New Braunfels, TX 78130 Tel: (830) 632-1500 Date Tested: 04/12 Series 1-Series 8 Hurricane panels Valley Storm Shelters, LLC 31310 US Hwy. 72 Hollywood, AL 35752 Tel: (256) 652-6818 Date Tested: 08/11 Wall Panel for 5’x8’x6’ tall x ¼’’ plate steel shelter Date Tested: 02/13 Above ground steel plate shelter door panel and window panel Vaughn Concrete Products, Inc. Mike Vaughn 10021 Amarillo Blvd., East Amarillo, TX 79108 Tel: 877-827-8255 Date Tested: 06/12 5 concrete wall construction panels Volkert, Inc. Jonathan D. Grammer 2 20th Street North Suite 300 Birmingham, AL 35203 Tel: (205) 214-5500 Date tested: 01/12 Grating for above-ground shelter Waco Composites Wayne Hampton 481-A Texas Central Parkway Waco, TX 76702 Date Tested: 06/99 Composite wall panel Waco Composites Date Tested: 06/99 Rev: 06-08-2015 Components Wayne Hampton 481-A Texas Central Parkway Waco, TX 76702 Ph: (254) 776-8880 Composite wall panel Westcrete Building Systems Shane Gaddes 2006 Bonner Place Spring Hill, TN 37174 Ph: (415) 943-7124 Cell: (415) 243-5199 Date Tested: 08/11 Series 1 & Series 2 Tornado Panels Western States Clay Products Assoc. Jeff Elder 9780 S. 5200 W. West Jordan, UT 84081 Tel: (801) 280-5200 Date Tested: 04/12 Series 1 - Series 3 Tornado brick products (panels) Word and Boggus Contracting, Inc. Larry Boggus PO Box 278 Guntersville, AL 35976 Ph: (800) 239-5201 Date Tested: Rev: 06-08-2015 Components