BURNABY CAMPUS MECHANICAL SYSTEMS STANDARDS 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. BUILDING MANAGEMENT SYSTEM & EQUIPMENT CONTROLS DIRECT DIGITAL CONTROL SYSTEM REQUIREMENTS IDENTIFICATIONS COMMISSIONING EQUIPMENT & PIPING PAINTING & LABELS HEATING, VENTILATION AND AIR CONDITIONING (HVAC) PLUMBING AND DRAINAGE SANITARY, STORM & LAB SEWER SERVICES NATURAL GAS SERVICES PLUMBING FIXTURES LABORATORY SERVICES ENERGY CONSERVATION DOMESTIC COLD WATER CONSERVATION FIRE SUPRESSION SPRINKLER SYSTEMS 1. BUILDING MANAGEMENT SYSTEM & EQUIPMENT CONTROLS GENERAL .1 Control Contractor shall be responsible for all necessary engineering and installations to provide complete and operating control system as specified and indicated on Drawings. .2 All DDC based controls shall be interfaced with the existing DDC Andover and/or Delta control systems. Andover system shall be installed and/or installations suppervised by Houle Electric Ltd. Delta system shall be installed and/or installations suppervised by ESC Controls Ltd. The company present service contracts guaranty the system operation. .3 All installed control equipment shall be of the same make and model as the existing equipment. .4 All control software shall use the same control algorithms as the existing for the same control sequences. .5 All modifications of the existing DDC controls and the new controls shall be included in the existing control graphics. .6 All new control points shall be from existing or new Infinity Andover or Delta control panels. New panels shall be interfaced with existing systems. .7 Any new panels shall be located in the mechanical rooms. .8 All required up-grade of existing controls graphical displays and all related cost shall be included in the project scope of work. .9 Controls Contractor shall assist Electrical Contractor during the variable frequency drive start-ups and testing. .10 Controls Contractor shall assist Balancing Contractor during the balancing, start-ups and testing of mechanical systems. 1. PROJECT RECORD DOCUMENTS General Conform to requirements specified in this section. Project records and O&M manuals specified in this section are to be completely separate entities. Final Control Diagrams Provide before acceptance in both hard and soft copy. Show: .1 Changes to contract documents as well as addenda and contract extras. .2 Changes to interface wiring. .3 Major routing of conduit. .4 Signal levels, set-points, reset curves, schedules. .5 Where possible, bind with specified Operating and Maintenance Manuals. .6 provide listing of alarm messages. .7 provide soft copy of updated drawings on system and soft copy back-up. .8 provide 1 non-fading "as-built" copy showing control and/or adjustment procedures. seal in plastic laminate in rigid metal bound loose leaf. Language Provide record documents, as-built drawings and Operation and Maintenance manual in English. O&M Manuals General: .1 O&M Manuals (both hard and soft copy) to be custom designed and contain material pertinent to project only, and to provide full and complete coverage of subjects referred to in controls section. .2 Provide 2 soft copies and 2 hard copies in hard-back, 50 mm 3 ring, D-ring binders. .3 Binders to be 2/3 maximum full. .4 Provide index to full volume in each binder. .5 Identify contents of each manual on cover and spine. .6 Include names, addresses, telephone numbers of each sub-contractor having installed equipment, local representative for each item of equipment, each system. .7 Provide Table of Contents in each manual. Assemble each manual to conform to Table of Contents with tab sheets placed before instructions covering subject. .8 Furnish 1 complete set of hard and soft copies prior to system or equipment tests. Furnish remainder upon acceptance. .9 Include complete coverage in concise language readily understood by operating personnel using common terminology of functional and operational requirements of system. Do not presume knowledge of computers, electronics or in-depth control theory. Functional description to include: .1 Functional description of theory of operation. .2 Design philosophy. .3 Specific functions of design philosophy and system. .4 Full details of data communications, including data types and formats, data processing and disposition data link components, interfaces and operator tests or self-test of data link integrity. .5 Explicit description of hardware and software functions, interfaces, requirements for components in functions and operating modes. .6 Description of person-machine interactions required to supplement system description, known or established constraints on system operation, operating procedures currently implemented or planned for implementation in automatic mode. System Operation to Include: .1 Complete step-by-step procedures for operation of system including required actions at each OWS. .2 Operation of computer peripherals, input and output formats. .3 Emergency, alarm and failure recovery. .4 Step-by-step instructions for start-up, back-up equipment operation, execution of all systems functions and operating modes, including key strokes for each command so that operator need only refer to these pages for keystroke entries required to call up display or to input command. Software to include: .1 Documentation of theory, design, interface requirements, functions, including test and verification procedures. .2 Detailed descriptions of program requirements and capabilities. .3 Data necessary to permit modification, relocation, reprogramming and to permit new and existing software modules to respond to changing system functional requirements without disrupting normal operation. .4 Software modules, fully annotated source code listings, error free object code files ready for loading via peripheral device .5 Complete program cross reference plus any linking requirements, data exchange requirements, necessary subroutine lists, data file requirements, other information necessary for proper loading, integration, interfacing, program execution. .6 Software for each new controller and single section referencing all Controller common parameters and functions. .7 Maintenance: document maintenance procedures including inspection, periodic preventive maintenance, fault diagnosis, repair or replacement of defective components, including calibration, maintenance, repair of sensors, transmitters, transducers, Controller interface firmware's, plus diagnostics and repair/replacement of system hardware. .8 Test procedures and reports: record implementation, description of test procedures. Provide for measurement or observation of results. .9 System configuration document: .10 Basic system design and configuration. .11 Provisions and procedures for planning, implementing, recording hardware and software modifications required during installation, test and operating lifetime of system. .12 Information to ensure co-ordination of hardware and software changes, data link or message format/content changes, sensor or control changes in event that system modifications are required. .13 Full documentation of new system configurations. 2. DIRECT DIGITAL CONTROL SYSTEM REQUIREMENTS OPERATOR INTERFACE Access Requirement All functions of the system, storage of data, execution of commands, editing of programs, creation and display of graphics, etc., must be available regardless of the method of access to the system. Functionality must not be dependent on a continuous connection to the DDC in the building, as there may not be a PC installed on-site. SFU staff will be accessing the DDC by the following methods: .1 Through an on-site desktop or notebook PC, connected to the DCC, but not necessarily permanently installed. .2 Through either a desktop PC or a notebook PC, which will connect to the DDC via the internet. .3 SFU requires two modes of access to the DDC: .1 Through a text based terminal emulation interface available at all points of connection to the DDC. .2 Through the full graphics interface described below, where the graphics are resident on any PC, whether connected directly to the DDC or remotely through the internet. Access Security .1 .2 The system shall have a minimum of 4 levels of password access security. Each level of access shall have different functionality assigned. Operator Interface Software .1 Software required to access the control system and carry out all the specified operator interface functions. This software will be for SFU use only, from either on-site or remote access locations. .2 The operator interface software provided with the system shall be compatible with the standard hardware and operating system and be fully supported by the manufacturer for the next five years. .3 Provide disk format to conform to Standard hardware and operating system. .4 Provide the following dynamic graphic data display capabilities: .1 Dynamic data display on each graphic which can accommodate any combination of dynamic (point type) information, graphic symbols and text, displayed at any location on the entire screen. .2 User control over attributes of dynamic data for display, including: - values - units - point names and full descriptions auto/manual indication access to full point parameters text size .3 Dynamic linking of screens via definition of ``hot spots'' at any location on screen. .4 User definable sizing of ``hot spots'' and ability to control colour and transparency of same. .5 User-controllable automatic update of dynamic data. .6 Minimum of 64 dynamic graphic displays per Stand Alone Panel. .7 Minimum of 100 points per graphic display. .8 Ability to print directly from screen, to either a black & while, or colour printer. .9 Automatic display of alarm indication and the ability to disable autodisplay of graphic. Executing the dynamic colour graphics .1 Apply Graphic to match existing SFU systems to all colour graphics specified. .2 Provide all graphics listed in specified in the specification. Static screen graphics generation software Colour graphics generation software must provide the following capabilities: .1 System that allows user to create, modify, and delete static graphics screens. .2 Minimum VGA resolution with sixteen colour capability. .3 Mechanism for copying and editing graphics of similar layout. .4 Mechanism for importing Windows graphics file formats, such as TIFF, GIF, PCX, DXF, BMP. .5 Graphics creation features shall provide: - User creation of symbols that can be stored for future use. - Control of symbol location on screen. - Control of line drawing, type, colour and thickness. - Control of infill colour, background colour. - Control of alpha-numeric text, including font size and colour. PROGRAMMABILITY Database Creation and Modification .1 Provide means for addition, deletion, definition and modification of points and point types through the operator interface. .2 Provide links in the database such that if a point name is changed in database, all database occurrences of that point will automatically be changed. .3 Provide direct keyboard override of all physical and virtual points with an indication on the display of any point that is operating under a keyboard override. .4 The database for each physical or virtual point must only require definition once, regardless of the number of locations where it is used. Alarm Definition and Processing Provide the following: .1 Operator defined digital and analogue alarms including operator defined limits and differentials from set points. .2 Auto lockout of alarms when alarmed system is commanded off. .3 Auto display of operator defined alarm messages. .4 Operator defined routing of alarms. .5 Log of points in alarm. Trends Provide point trend logging capability for any system point as follows: .1 User defined start/stop time or continuous trending. .2 Sampling period user-adjustable from 5 seconds to 24 hours as a minimum. .3 Change of value or change of state initiated. .4 Display and print a minimum of 4 points simultaneously across the page. .5 Ability to automatically dump trend logs to disk in ASCII format. Trend Graphing System shall have the ability to graphically display logs or trended points in colour: .1 Capability for display of a minimum of 4 points simultaneously, both analog and digital on the same graph. .2 Capability for auto-scaling and ability to manually control horizontal and vertical scales. Totalization Provide the capability to accumulate units of all analog and digital points. Scheduling Provide scheduling feature that allows for creation of start/stop schedules use in programs as follows: .1 Weekly - 20 minimum per SAP - time of day, day - weekend, alternate day - direct override by Annual Schedules - 8 daily stops/starts per day .2 Annual - 6 minimum per SAP - entire calendar year available and their Point Definitions .1 .2 Analog Points .1 System shall have the capability to accommodate user defined scale ranges which can be attached to any input or output. .2 Provide conversion tables or other mapping functions for analog input and analog output points that define how the input or output hardware values relate to the engineering units used. .3 This function must accommodate non-linear relationships. .4 If a conversion table type function is used, it must have a minimum of 10 individually definable segments. .5 Provide capability to assign any user defined unit to the analog point (i.e. percent, Deg C, Deg F, etc.). Digital Points .1 Provide the capability to define in database whether a digital input point is normally open or normally closed. .2 Provide the capability to assign any pair of engineering units to the relay open and relay closed positions of digital output points. (i.e. start/stop, on/off, open/closed). Software Controllers .1 Provide controllers, resident in each SAP and/or TUC, including a three-term, proportional, integral, derivative, (PID) control algorithm. .2 Provide, in each controller, the following set up and tuning capabilities: .1 Direct or reverse acting. .2 Output value to control, 0 to 100%. .3 Set point. .4 Proportional Gain. .5 Integral gain. .6 Derivative gain. .7 Sampling time - variable from 1 to 60 seconds. .8 Control loop bias. .3 Provision shall exist for the modification of the above by OCL programs and/or the operator while on-line through a terminal. Operator Control Language (OCL) Capabilities .1 The stand alone panels (SAPs) and soft terminal unit controllers (TUCs) shall have the capability for the operator to develop and run custom application programs. For this, the system shall have a proven OCL which shall be capable of reading the value and/or status of all system points and initiating both digital and analog control actions from any user defined combination of calculations and logical expressions which shall at a minimum include: - Addition, subtraction, multiplication and division; - Square roots, summations, absolute differences; - Logical ``not'', ``and'', ``or'', ``nor'', ``and'', ``less than'', ``greater than'', and ``equal to'' or their logical equivalents; - Time delays in seconds, minutes or hours; - Ability to embed comments in system generated documentation; - Ability to use time-of-day and day-of-year in algebraic calculations; and - Ability to use weekly and annual schedules. .2 Provide code for the following control strategies: .1 If real time is between 8:00 AM and 4:00 PM and minimum space temperature is more than 0.5 deg C below the building objective temperature, then start Pump #1. .2 As soon as Pump #1 has been on for 10 minutes, turn on the boiler. .3 If day of the year is before July 2, then factor A is equal to 0.1667 - (July 2 day of year)/1368, otherwise the factor A is equal to 0.1661 - (day of year - July 2)/1368. .4 Select high of space temperature #2, space temperature #3 and space temperature #6. .5 If the real time is greater than 8:00 AM minus a factor, times the difference between the setpoint and space temperature and if the real time is less than 3:30 PM and if outside air temperature is less than 10 deg C, then enable boiler. .6 The supplied system's OCL shall support the concept of output oriented code, or in other words, a program shall be generated for each controlling output or logical group of outputs. Required programs for each system are listed in the generic start up logic, although manipulation will be required to achieve the intent in each vendor's system. OCL Editor .1 Provide a full screen editor to enable editing of the OCL programs source code down to character by character changes. .2 Provide the capability in the editor of accepting programs from ASCII files that have been created on other MS-DOS compatible computers and word processors. .3 If a point is removed from the database, show an error signal for undefined character on the appropriate line whenever a program using that point is viewed, edited or printed. INTRA-SYSTEM COMMUNICATION Network Communications .1 Stand-Alone Panels (SAPs) .1 Provide a fully networked system of SAPs which use a peer-to-peer communications protocol to support the distributed control features as specified herein. Each SAP shall be connected directly to the network. Each SAP shall have equal network access priority and shall not require a separate interface panel (gateway) to accomplish network communications. .2 Provide a means to ensure communication integrity. Provide detail of your system with proposal. .3 To prevent damage to the system each data highway line shall be provided with a means of isolation, either optically or by some other means. Provide detail of your protection system with proposal. .4 Upon failure of the network to communicate information from one SAP to other SAPs, retain the last legitimate value of each point in the SAPs that require it, and continue to control the systems based on those values. Failure of any SAP, or any part of a SAP on the network, shall not affect the ability of the network to communicate among the remaining SAPs. .5 Each physical or virtual point shall have a user-definable, unique, system-wide logical point mnemonic. The format of this point mnemonic shall conform to BCBC Point Naming Convention. All point functions such as commands, overrides, trends, reports, logs and graphics shall only need to use this unique logical point mnemonic. .6 Values, status's and attributes of physical and software points from one SAP shall be available for use in any other SAPs. Any broadcast points, sendreceive blocks or any other form of table or database that is required to initialize and accomplish this function shall be created solely, and automatically, by the operating system, without the need for operator intervention. Listings of physical and software points shall not include tables referred to in this paragraph. Terminal Unit Controllers (TUCs) For systems which include terminal unit controllers (TUC's). .1 TUC's shall be considered to be any panel connected to a sub- communication network, where access to the features and points of the TUC is only obtainable through the SAP to which the sub-network is connected. TUCs shall have a limited number of inputs and outputs, which are specifically designed to control one component serving a single thermostatic zone (e.g., VAV terminal unit, dual-duct terminal unit, fan-coil unit, zone heat pump, etc.). .2 The terminal unit controllers (TUCs) shall incorporate all of the requirements for the stand-alone panels (SAPs), except for peer to peer communications and auto-networking provisions. .3 The auto-networking requirements defined for SAPs apply between the TUC and the SAP it is connected to. If the TUC is connected to the main peer to peer communication network, the full requirements apply. System Display and Processing Speed .1 .2 For multi SAP systems, the system processing speed is intended to address inter-SAP communications and will be checked during the commissioning phase by evaluating value updates from one SAP as received and displayed in another SAP. This will be done by setting up a display of all SAP counters and checking how frequently each counter is updated on the refreshed display on site Every counter shall show an updated value on the display within TWENTY (20) seconds of the previous update value appearing. Provide confirmation with Proposal that required system processing speed will be achieved. HARDWARE FEATURES Power Conditioning .1 The system shall be protected from power line surges and voltage transients. Provide with proposal, a technical description of this protection. Power Failure Protection .1 Provide automatic retention of RAM and real time clock from any power failure of at least SEVENTY-TWO (72) hours duration. .2 Provide for automatic restart of the system upon power return. .3 The proposal shall describe the power failure protection system to be employed. System may be tested to confirm rated hours. Hardware Failure Isolation .1 Any component malfunction shall not damage any of the remaining components. Provide with proposal a technical description of how this is accomplished. .2 Provide information on over voltage protection on inputs and outputs. Ease of Hardware Replacement .1 SAP and TUC replacement shall be possible without any hardware modification. Database Back-Up and Off-Line Storage .1 The system shall have the capability to be taken off line in the event of failure or for maintenance and returned to operation without the need for entering any portion of the software program manually. To accomplish this, an off-line disk storage device shall be utilized to provide software backup and reload. .2 On-site backup and verification of the entire system, with full applications software, shall be less thanTWO (2) seconds per real point. This feature will be checked during commissioning stage. .3 Explain in the Proposal how the back up is accomplished. Memory .1 Each SAP on the main network proposed shall have enough random access memory (RAM) for all of the following: .1 Trend Logs - One and a Half (1.5) TL for each input and output point connected to the SAP with 100 samples each. .2 Controllers - TWO (2) for each analog output point connected to the SAP. .3 Software Points - THREE (3) for each output point connected to the SAP. .4 Operator Control Language (OCL) - TWENTY (20) syntactically correct lines each with at least 4 operators, for each output point connected to the SAP. .5 Descriptor - ONE (1) for each user definable point, real or software, in the SAP. In addition, on multi-SAP systems, every descriptor in the system must be accessible from every operator interface device. .6 Time Schedules - ONE (1) for every 3 output points connected to the SAP. .7 Totalizers - ONE (1) for each digital point in the SAP. .8 In the event there are TUCs networked to the SAP, which do not have their own memory meeting items .1 through .7, the SAP must have full memory for all TUC points as well as points connected directly. .9 Provide with Proposal, calculations which confirm the foregoing RAM requirements are met for each SAP. SAP Processing Speed .1 Effective SAP Processing Speed - Maximum permissible execution time is TWO (2) seconds. Execution time is defined as the time it takes the SAP CPU to execute all application software in the SAP, with no system timing errors, from some point in the software back to the same point, assuming full memory usage, as defined in Clause 4.5 above, while simultaneously responding to operator or terminal display requests and carrying out normal inter-SAP communications averaged over a ONE (1)-minute period. This will be done during the commissioning phase by setting up a counter in each SAP and monitoring their counting rate. System Display Speed .1 The minimum time to change from one dynamic screen to another is 7 seconds. This test will be carried out from a remote site with the standard modem and will be the average of 10 typical displays for the project. Tests will be carried out with the specified system configuration, excluding multi-user and alarming functions. 3. IDENTIFICATIONS General Provide identification for all new control items. Submittals Submit for approval samples of nameplates, identification tags and list of proposed wording. Language Provide nameplates and identification tapes and tags in English. Nameplates for Panels Identify faces with laminated plastic nameplates. Nameplates for Field Devises .1 Identify by plastic encased cards attached by chain. .2 Data to include: point name, schematic designation number, model, capillary length, size, range, set point, other pertinent data, function, fail-safe position. .3 Companion cabinet: identify interior components using plastic enclosed cards. Nameplates for Room Sensors .1 Interior: identify by stick-on labels. .2 Exterior: identify point name on face of cover using plastic laminate nameplates. .3 Sizes: to suit. .4 Lettering: to suit. Clearly legible. Warning Signs .1 New equipment (e.g. motors, starters) under remote automatic control: provide orange coloured signs warning of automatic starting under control of EMCS. .2 Sign to read: "Caution: This equipment is under automatic remote control of EMCS" or equivalent to the Consultant's approval. Nameplates for Wiring .1 Provide numbered tape markings on wiring at panels, junction boxes, splitters, cabinets, outlet boxes. .2 Colour coding: to CSA C22.1. Use colour coded wiring in communications cables, matched throughout system. .3 Power wiring: identify at each panel. Nameplates for Conduit .1 Colour code all EMCS conduit. .2 Locate coding on conduits, in exposed and concealed locations including removable suspended ceilings, tunnels, shafts, on both sides of walls, floors, and at 45 ft intervals. .3 Coding: use plastic tape or paint, 1” wide, fluorescent orange. Confirm colour with the owner and the Consultant during "Preliminary Design Review". Execution Ensure that manufacturer's nameplates, CSA labels and identification nameplates are visible and legible at all times. 4. COMMISSIONING Commissioning to be carried out under general direction of the Commissioning Engineer (Contractor‟s staff) and in presence of the Consultant and the Owner as requested. Approvals Obtain approval to start commissioning from the Consultant at least 7 days prior to start. Information to include: .1 Systems to be commissioned. .2 Procedures, anticipated results. .3 Names of commissioning personnel. .4 Purpose .5 Assurance that systems meet design criteria, design intents and requirements of specifications. Design Requirements .1 Commissioning Engineer to confirm with the Consultant that Design Criteria and Design Intents are still applicable. .2 Commissioning personnel to be fully aware of and qualified to interpret Design Criteria and Design Intents. Co-ordination Co-ordinate commissioning procedures with other Divisions Timing .1 Commissioning to commence only after satisfactory completion of start-up, verification of performance and specified test period. .2 Commissioning of occupancy-, weather-, and seasonal-sensitive systems to take place during four (4) consecutive seasons, after facility has been accepted, taken over and fully occupied. .3 Commission systems considered as life safety systems before affected parts of facility are occupied. Instrumentation .1 Provide sufficient permanent and temporary instrumentation. Verify locations, access, illumination for readings .2 Instrumentation accuracy tolerances: higher order of magnitude than equipment, or system, being tested .3 Locations to be approved, readily accessible and readable .4 Application: to conform to normal industry standards. Operation of Systems Operate systems as long as necessary to commission entire project. Supervision and Monitoring .1 Commissioning to be supervised by qualified supervisory personnel. .2 Monitor progress. .3 Keep detailed records of activities and results. Documentation Documentation, O&M Manuals and training of O&M personnel to be complete to satisfaction of the Consultant before starting commissioning. Use of O&M Personnel O&M personnel to assist in commissioning procedures as part of training Procedures .1 Test each system independently and then in unison with other related systems. .2 Test weather-sensitive systems twice - once at near winter design conditions and again under near summer design conditions. .3 Co-operate with Commissioning Engineer/Consultant to develop appropriate commissioning procedures for systems. .4 Commission integrated system using procedures prescribed by Commissioning Engineer. .5 Debug system software. .6 Optimize operation, performance of systems by fine-tuning PID values and modifying CDL's as required. Verification of Results Commissioning Engineer shall verify 30 % of reported results. Demonstration Demonstrate to the Consultant and the Owner operation of systems including sequence of operations in regular and emergency modes, under normal and emergency conditions, start-up, shut-down, interlocks, lock-outs. Final Settings Upon completion of commissioning to satisfaction of the Consultant, set and lock devices in final position, permanently mark settings. Final Report .1 Submit report to Consultant. .2 Report to include: Measurements, final settings, certified test results. .3 Bear signature of commissioning technician and supervisor. .4 Be subject to verification by the Owner and the Consultant. .5 Report format to be approved by the Consultant before commissioning started. Commissioning Activities During Warranty Period .1 Continue system debugging and optimization. .2 Perform two (2) checks of environmental conditions. Submit written report to the Consultant. .3 Revise "As-built" documentation, commissioning reports to reflect changes, adjustments, modifications to EMCS as set during commissioning. .4 Recommend additional changes, modifications deemed advisable in order to improve performance, environmental conditions and energy consumption. Maintenance Activities During Warranty Period The intent of this paragraph is not to include normal day-to-day routine operation and maintenance of system. .1 Provide services, materials, equipment and maintain EMCS for specified warranty period. Provide detailed preventative maintenance schedule for system components. .2 Perform as minimum three (3) minor inspections and one major inspection (more often if required by manufacturer) per year. Provide detailed written report to the Consultant. Major inspections to include, but not limited to: .1 Minor inspection. .2 Check signal, voltage and system isolation of new peripherals, interface and panels. .3 Run system software diagnostics as required. .4 The following inspections will be considered minimum requirements, and shall not be interpreted to mean satisfactory performance. Calibrations will be performed using test equipment having traceable, certifiable accuracy at minimum 50% greater than the accuracy of system displaying or logging the value. Check and/or calibrate each field input/output device. Provide dated, maintenance task lists to the Consultant as proof of execution of complete system verification. Maintenance task lists to include the new sensor and output point detail; point name, location, device type and range, measured value, system displayed value, calibration detail, indication if adjustment required, and any other action taken of recommended. .5 Install software and firmware enhancements to ensure new components are operating at most current revision for maximum capability and reliability. Perform network analysis and provide report of results with detailed recommendations to correct any problems found. Minor inspections to include, but not limited to: .1 Perform visual, operational checks to new peripheral equipment, interface equipment and panels. .2 Check equipment cooling fans as required. .3 Perform inspections during regular working hours, 08:00 to 18:00 h, Monday through Friday, excluding legal holidays. .4 Visually check for mechanical faults, air leaks and proper pressure settings on pneumatic components. .5 Review system performance with the Consultant and the Owner and discuss suggested or required changes. Emergency Service Calls: .1 Service calls will be initiated when there is indication that EMCS is not functioning correctly. Have qualified control personnel available during contract period to provide service to "CRITICAL" components whenever required at no extra cost. Furnish the Owner with telephone number where service personnel may be reached at any time. Service personnel to be on site ready to service EMCS within 2 hours after receiving request for service. Perform work continuously until EMCS restored to reliable operating condition. .2 Operation: foregoing and other servicing to provide proper sequencing of equipment and satisfactory operation of EMCS based on original design conditions and to be as recommended by manufacturer. .3 Records and logs: maintain records and logs of each maintenance task. Organize cumulative records for each major component and for entire EMCS chronologically. Complete forms and submit after inspection indicating that planned and systematic maintenance has been accomplished. .4 Work requests: record each service call request, when received separately on approved form. Form to include serial number identifying component involved, its location, date and time call received, nature of trouble, names of personnel assigned, instructions of work to be done, amount and nature of materials used, time and date work started, time and date of completion. .5 System modifications: provide in writing. No system modification, including operating parameters and control settings, to be made without prior written approval of the Consultant and the Owner for the new controls installed under the project. .6 Rectify deficiencies revealed by maintenance inspections and environmental checks. Completion of Commissioning Commissioning to be considered as satisfactorily completed when objectives of commissioning have been achieved to full satisfaction of the Consultant and the Owner. Issuance of Final Completion Certificate Final Certificate of Completion will not be issued until receipt of written approval indicating the successful completion of specified commissioning activities including receipt of commissioning documentation. Commencement of Warranty Period Date of the Consultant and the Owner acceptance of submitted declaration of Substantial Performance shall be date for commencement for the warranty period. 5. EQUIPMENT & PIPING PAINTING & LABELS .1 .2 Equipment Identification .1 All new service isolation valves, control valves, chiller plant equipment, controls and power connections shall be identified with labels acceptable to the owner, the consultant. indicate identifications on as-built drawings. .2 Wording on identification labels to be approved by the consultant prior to manufacture. .3 All identification to be in English. Manufacturers and CSA Labels Visible and legible after equipment is installed. 6. HEATING, VENTILATION AND AIR CONDITIONING (HVAC) The following describes requirements for the Central hot water heating plant & primary distribution system: CENTRAL BOILER PLANT .1 Plant Description Central boiler plant is a multiple boiler high temperature hot water heating plant with three primary heating distribution zones, west, north-east and south-east. All boilers are connected to common supply and return main headers. Each boiler has a water circulating pump providing constant water flow for the boiler. The heating zones are fully independent with independent connections to the main headers and independent zone circulating pump groups. The heating zones operate as variable temperature variable flow systems. The supply temperature is calculated in relation to an outdoor air temperature schedule. The resulting supply water temperature set point is corrected in relation to the temperature differential between the supply and the zone return water temperatures. The zone pump variable frequency drives modulate the zone pump speeds between the set minimum and full speeds to maintain the set pressure differential between the supply and return system piping in the end mechanical rooms of three heating zones. .2 Plant Operating Data Maximum supply water temperature: 120ºC Minimum supply water temperature: 90ºC (summer, DHW heating only) Maximum system operating pressure at boiler plant: 760 kPa (Ground Floor of Library building). DISTRIBUTION SYSTEM .1 General System type: Variable flow variable temperature Maximum supply water temperature: 120ºC Minimum supply water temperature: 90ºC System operating pressure: Variable with system location in relation to University Central Boiler Plant .2 Piping Minimum Requirements: All pipe to be schedule 40 Black Iron. Piping lay-out shall take into account grading, insulation, thermal expansion, stressing and deformation of the piping. Fittings to be from forged steel and flanged or welded for piping sizes over 50 mm in diameter and threaded for piping sizes 50mm and smaller . Standard or long radius elbows and welding tees shall be only specified. Flanges to be of raised face, steel weld-neck, lab or back-welded slip-on type, compatible with mating flanges. Design shall allow for piping system venting at all high points and draining at all low points. .3 New Connections Isolation valves with drain valves shall be installed into each supply and return piping connection to the primary distribution system and/or to a building. The drain valves shall be located on the connection side of isolation valves. .4 Pumps Minimum Requirements: .1 Centrifugal base mounted or vertical in-line pump with premium efficiency motor. Motor size up to 0.5HP to be single phase 120V, 0.5HP and bigger to be three phase 480V. Minimum pump operating efficiency 75%. .2 Each pump shall be equipped with a pressure gauge connected to pump suction and discharge side with isolation valves to allow for the pump operating pressure metering with one gauge only. .3 Each operating zone pump(s) shall have one at least one stand-by pump with minimum 85% stand-by .4 Variable pump flow control: Variable frequency drive (VFD) for all motors over 2HP. .5 Manual Valves Minimum Requirements: All valves shall be of same manufacturer throughout where possible. Use pipe size valves. Valves up to 50mm in diameter to be threaded, over 50mm in diameter flanged for use with flanged fittings. Use ball valves for small isolation services and gate or globe valves for services over 50mm. All valves shall be suitable for the system maximum operating pressure at the project location and the maximum operating temperature of 120ºC. .6 Balancing Valves Minimum Requirements: Circuit setter type calibrated balance valve with flange connections, design for maximum operating temperature of 120 C and maximum operating pressure suitable for the system pressure at the valve location. Brass readout valves fitted with integral EPT insert, check valves designed to minimized system fluid loss during the balancing and monitoring process, calibrated nameplate to assure specific valve setting, internal seals to prevent leakage, bronze construction. .7 Triple Duty (Multi-Purpose) Valves Acceptable Manufacturer: Related pump manufacturer. Minimum Requirements: Valve shall combine isolation, balancing and check valve duties; strait or convertible strait/angled design, cast iron body, bronze gland, stainless steel stem sleeve, cast iron non-lubricated plug, brass clapper, brass seat with dual O-ring seal. Valve shall be for horizontal or vertical installation with plug type flow control, memory stops, bubble tight shut-off, pointer and scale, spherical clapper, threaded valve metering connections, nonslam check valve, elastomer seat and no lubrication requirements, design for maximum operating temperature of 120 C and maximum operating pressure suitable for the system pressure at the valve location. . .8 Pump Suction Diffusers Acceptable Manufacturer: Related pump manufacturer. Minimum Requirements: Cast iron or ductile iron body, bronze start up strainer, stainless steel permanent strainer, blow down connection for horizontal installation, design for maximum operating temperature of 120 C and maximum operating pressure suitable for the system pressure at the valve location. .9 Strainers Minimum Requirements: Cast iron or ductile iron body, bronze start up strainer, stainless steel permanent strainer, blow down connection for vertical or horizontal installation, design for maximum operating temperature of 120 C and maximum operating pressure suitable for the system pressure at the valve location. .10 Air Vents Minimum requirements: high capacity type, design for maximum operating temperature of 120 c and maximum operating pressure suitable for the system pressure at the valve location. .11 Drain Valves Minimum Requirements: Globe type with bronze body and trim and composition disc, design for maximum operating temperature of 120 C and maximum operating pressure suitable for the system pressure at the valve location. .12 Variable frequency drives Provide new variable frequency drive(s) (VFD), for operating new variable flow pump motor(s). The drive(s) shall have the following minimum specification: .1 For use with supply voltage 48OVAC, 3-phase, 60Hz, .2 3% integral input line reactor .3 LCD control panel CDP312 mounted on door of the enclosure with alpha-numeric display with local operator control allowing set up of drive parameters, load, fault monitoring functions, speed with multiple programmable speed presets, etc. Control functions to include start & stop (auto and manual modes); jog -manual, uni-direction rotation limitable. .4 Output Frequency, variable 0 to minimum 66Hz (normal full speed at 60Hz), .5 6x 24VDC programmable digital inputs, input voltage 24V, filtering time (HW) 1ms .6 3x analog inputs, 2x0(4)-20mA and 1x +/-0(2)-10V; resolution 12 bit .7 2x programmable analog outputs 0(4)-20mA, resolution 10 bit .8 3x programmable form C relay (digital) outputs, switch over contact 24V or 115/230VAC, max. 2A .9 Reference voltage output: +/-10V, +/-0.5%, max. 10mA .10 Auxiliary power output: +24V, +/-10%, max. 250mA .11 Direct torque control (DTC) technology .12 Load supervision of the motor .13 NEMA 1 enclosure with cable connection box .14 Bottom entry and exit .15 CSA certified .16 Parts and labour warranty for minimum 3 years Drive shall provide operating protections for: .17 Microprocessor fault .18 Single phase (input and output) .19 Over temperature .20 Over current .21 DC under voltage .22 DC over voltage .23 Short circuit/ ground fault in output connector .24 Auxiliary voltage (short-circuit) .25 Loss of analog input with the following selectable options: a. fault/continue to operate b. warning and run at a preset speed c. warning and run at last speed reference .26 Panel loss (if panel is controlling the drive and communication is broken) .27 External fault .28 Motor thermal supervision (software) .29 Motor stalled .30 Ground fault in the motor, motor cable or inverter .31 Over-frequency .32 Under-load function .33 Internal fault Acceptable drive manufacturer: ABB Inc., model ACS800-U1-0011, industrial quality. Provide KLC series output filters sized for the pump motor rating current from TCI for motor protection Provide start-up, commissioning and training service with full documentation by supplier. Allow for sufficient on site time to assist the drive supplier with commissioning and providing training to the Owner. The following tests shall be performed during the certified start-up: 1 Visual inspection 2 Insulation and dielectric tests 3 Electrical functional inspection for supply section 4 Electrical functional inspection for drive section 5 Electrical functional inspection for control section Local manufacturer contact: John Archer P.Eng. of Hampton Power Systems Ltd., tel: 604 273 0561 Certified start-up agent: Inverter Technologies, contact person Collin Morrison, tel: 604 628 2212 MONITORING OF BUILDING ENERGY CONSUMPTION .1 General Requirements Energy metering station shall be installed into each new building piping connection and/or into each new piping connection to the primary distribution system. The station shall consist of a flow meter, remote signal converter and two temperature sensors installed in the supply and return piping. The flow meter can be installed in the supply or the return piping. The temperature sensors and the flow transmitter shall be interfaced with the existing DDC based energy metering system. .2 Flow Meter and Converter General Requirements: In-line magnetic flow meter with remote signal convertor, Approved Manufacturer: Bailey Fisher Porter Flow Meter Minimum Requirements: .1 150# CS flanges and pressure rating, .2 Teflon liner, .3 Flush Hastelloy „C‟ electrodes, .4 CSA approval, enclosure classification NEMA 4X, .5 Fluid: Heating water .6 Max. Water Temp: 1200C Remote Signal Convertor Minimum Requirements: .1 Surface mounting, .2 Microprocessor-based with 4-20 mA DC output and HART communication and empty pipe detection, .3 LCD display with totalizer .4 CSA approval, enclosure classification NEMA 4X, .5 Power Service: 120/1/60 – 10A, max. power consumption less than 23W, .6 10 meters interconnecting cable. Assembly Minimum Requirements: .1 10 meters maximum distance between flow meter and remote signal convertor, .2 Reset flow range capability between 5% and 100% of meter maximum capacity, .3 Minimum accuracy 0.5% of flow rate between 2% and 100% of flow range setting. .3 Installations .1 Install the meter centred to the piping with the water flow direction matching the indication of flow direction on the meter. Review the manufacturer‟s installation instructions prior of the work start and follow them during the installation. The instructions shall be supplied with the meter. .2 Install the remote signal convertor on wall at about 2.1 meters above finished floor and at maximum distance of 10 meters from the flow meter. .3 The existing university DDC based building management system comprises of two hardware systems, Andover operated by Houle Electric and Delta operated by ESC. All DDC based controls shall be interfaced with the existing DDC Andover or Delta control systems and shall be installed or the installation supervised by Houle Electric Ltd or ESC. The companies present service contracts guaranty the system operations. All installed control equipment shall be of the same or compatible make and model as the existing equipment. All control software shall use the same or compatible control algorithms as the existing for the same control sequences. All modifications of the existing DDC controls and the new controls shall be included in the existing control graphics. Coordinate all controls with the Mechanical Contractor. .4 Connect all new control points from existing or new Infinity Andover control panels. Locate any new panels in the mechanical rooms. Install new pressure differential sensor into existing heating piping in ceiling space of women washroom on 5000 Level and relocate existing DDC control system components as required. .5 All required up-grade of existing controls graphical displays and all related cost shall be included in the project scope of work. SATELLITE BOILER PLANTS Any satellite boiler plant proposed for new building shall be design to the operating parameters of the university central heating system. The plant shall be connected to the university central heating distribution system, capable to supply the heating water to the building secondary heating systems and capable to supply heating water into the related central system distribution zone or zone section in an emergency case. The boiler plant capacity shall be consulted with the mechanical superintendent of SFU Facilities Management. SECONDARY HOT WATER HEATING DISTRIBUTION .1 System Operating Data Air Handling Unit Heating Coil Systems: System type: Constant flow variable temperature Maximum supply water temperature: 90ºC Minimum supply water temperature: 55ºC (variable with coil selection and controls) System operating pressure: Variable with system location in relation to University Central Boiler Plant Reheating Coil Systems: System type: Variable flow variable temperature Maximum supply water temperature: 80ºC Minimum supply water temperature: 55ºC (variable with coil selection and controls) System operating pressure: Variable with system location in relation to University Central Boiler Plant Variable pump flow control: Variable frequency drive (VFD) all motors over 2HP. For VFD requirements see section 1.2 Primary Distribution System – Variable Frequency Drives of this Guide Lines. Perimeter Radiation Systems: System type: Variable flow variable temperature Maximum supply water temperature: 80ºC Minimum supply water temperature: 45ºC (variable with heating element selection and controls) System operating pressure: Variable with system location in relation to University Central Boiler Plant Variable pump flow control: Variable frequency drive (VFD) all motors over 2HP. For VFD requirements see section 1.2 Primary Distribution System – Variable Frequency Drives of this Guide Lines. .2 Piping Minimum Requirements: All pipe to be schedule 40 Black Iron or certified copper type L or K with soldered fittings for small sizes. Piping lay-out shall take into account grading, insulation, thermal expansion, stressing and deformation of the piping. Fittings to be from forged steel and flanged or welded for piping sizes over 50 mm in diameter and threaded for piping sizes 50mm and smaller . Standard or long radius elbows and welding tees shall be only specified. Flanges to be of raised face, steel weld-neck, lab or back-welded slip-on type, compatible with mating flanges. Triple duty valves and main zone balancing valves shall not be used for isolation services and shall be supplemented with separate isolation valves. Design shall allow for piping system venting at all high points and draining at all low points. .3 New Connections .1 Any secondary hot water heating system connected to the primary heating distribution system shall be separated from the primary system with a 3-way mixing valve or a heat exchanger. Each secondary distribution system shall have circulating pump(s) capable to handle the system flow requirements. .2 Isolation valves with drain valves shall be installed into each supply and return piping connection to the secondary distribution system and/or to a building. The drain valves shall be located on the connection side of isolation valves. .3 All secondary hot water systems shall have sufficient number of individually controlled zones. Each zone shall serve only rooms with same or very similar occupancy and sensitivity to heating loads. .4 Pumps Minimum Requirements: .1 Centrifugal base mounted or vertical in-line pump with premium efficiency motor. Motor size upto 0.5HP to be single phase 120V, 0.5HP and bigger to be three phase 480V. Minimum pump operating efficiency 75%. .2 Each pump shall be equipped with a pressure gauge connected to pump suction and discharge side with isolation valves to allow for the pump operating pressure metering with one gauge only. .3 All main secondary zone pump(s) shall have at least one stand-by pump with minimum 85% stand-by capacity in case of one pump failure. .5 Manual Valves Minimum Requirements: All valves shall be of same manufacturer throughout where possible. Use pipe size valves. Valves up to 50mm in diameter to be threaded, over 50mm in diameter flanged for use with flanged fittings. Use ball valves for small isolation services and gate or globe valves for services over 50mm. All valves shall be suitable for the system maximum operating pressure at the project location and the maximum operating temperature of 120ºC. .6 Balancing Valves Minimum Requirements: Circuit setter type calibrated balance valve with flange connections, design for maximum operating temperature of 120 C and maximum operating pressure suitable for the system pressure at the valve location. Brass readout valves fitted with integral EPT insert, check valves designed to minimized system fluid loss during the balancing and monitoring process, calibrated nameplate to assure specific valve setting, internal seals to prevent leakage, bronze construction. .7 Triple Duty (Multi-Purpose) Valves Acceptable Manufacturer: Related pump manufacturer. Minimum Requirements: Valve shall combine isolation, balancing and check valve duties; strait or convertible strait/angled design, cast iron body, bronze gland, stainless steel stem sleeve, cast iron non-lubricated plug, brass clapper, brass seat with dual O-ring seal. Valve shall be for horizontal or vertical installation with plug type flow control, memory stops, bubble tight shut-off, pointer and scale, spherical clapper, threaded valve metering connections, nonslam check valve, elastomer seat and no lubrication requirements, design for maximum operating temperature of 120 C and maximum operating pressure suitable for the system pressure at the valve location. . .8 Pump Suction Diffusers Acceptable Manufacturer: Related pump manufacturer. Minimum Requirements: Cast iron or ductile iron body, bronze start up strainer, stainless steel permanent strainer, blow down connection for horizontal installation, design for maximum operating temperature of 120 c and maximum operating pressure suitable for the system pressure at the valve location. .9 Strainers Minimum Requirements: Cast iron or ductile iron body, bronze start up strainer, stainless steel permanent strainer, blow down connection for vertical or horizontal installation, design for maximum operating temperature of 120 C and maximum operating pressure suitable for the system pressure at the valve location. .10 Air Vents Minimum requirements: High capacity type, design for maximum operating temperature of 120 c and maximum operating pressure suitable for the system pressure at the valve location. .11 Drain Valves Minimum Requirements: Globe type with bronze body and trim and composition disc, design for maximum operating temperature of 120 C and maximum operating pressure suitable for the system pressure at the valve location. .12 Equipment Connections Each heating equipment shall be equipped with isolation valve(s), balancing valve, drain valve and vent valve where required to allow equipment isolation, draining, removal and reinstallation without shutting down the corresponding secondary heating zone or system. Each equipment shall have provisions for proper venting and balancing of heating water flow. .13 Hot Water Heating Elements .1 Ceiling mounted radiant panels shall not be proposed, only wall hanged wall fin elements, convectors, radiant panels, fan powered convectors etc. shall be used. .2 The fan powered unit heaters and fan coil units shall be limited to storage areas and/or corridors. .1 Radiant floor heating shall be only proposed for student residences or special rooms as lockers, shower rooms, swimming pool decks etc. All radiant floor proposals shall be reviewed and accepted by Mechanical Superintendent of SFU Facilities Management. .2 All heating elements shall sized to only cover the room perimeter (building envelope) heat losses with exception of air curtains or fan coil units protecting building entry doors. CHILLED WATER COOLING PLANTS AND DISTRIBUTION Chiller Plant .1 General Chiller plants shall serve individual buildings or combinations of adjacent buildings. Plants shall be multiple chiller plants where applicable equipment rooms cooling system (process cooling) shall be separated from system(s) serving air-conditioning air handling systems. All chillers shall be connected to common supply and return main headers allowing to interconnect chilled water zones, to take over one failed chiller with remaining chillers and to isolate a failed chiller from remaining chillers without interruption of their operations. The chilled water distribution zones shall be fully independent with independent connections to the main headers and independent zone circulating pump(s). The chiller plants with distribution zones shall operate as variable temperature variable flow systems. The supply chilled water temperature to be calculated in relation to an outdoor air temperature schedule. The resulting supply chilled water temperature set point is corrected in relation to the temperature differential between the supply and return chilled water temperatures. .2 Plant Operating Data Maximum chilled water supply temperature: 7ºC Maximum system operating pressure: 760 kPa. Variable pump flow control: Variable frequency drive (VFD) all motors over 2HP. For VFD requirements see section 1.2 Primary Distribution System – Variable Frequency Drives of this Guide Lines. .3 Chillers Design plants with screw and/or centrifugal chillers as dictated by plant design capacities. Plants with 50 ton and smaller capacities can be design with reciprocating chillers. Chiller refrigerant(s) shall be readily available from the chiller manufacturer with guaranteed delivery during chiller life expectancy and to have acceptable toxicity, ozone depletion factor and green house factor. .4 Chilled Water Cooling with Air Any chiller plant shall be lay-out and design with equipment allowing direct chilled water cooling with a combination of heat exchanger with plant cooling tower(s) and/or plant air cooled fluid cooler(s) when outdoor air temperatures allow. .5 Distribution Systems .6 System Operating Data Air Handling Unit Cooling Coil Systems System type: Constant flow variable temperature Maximum supply water temperature: 10ºC (variable with coil selection and controls) Minimum supply water temperature: 7ºC System operating pressure: Variable with system location in relation to related chiller plant Small Cooling Coil Systems: System type: Variable flow variable temperature Maximum supply water temperature: 12ºC (variable with coil selection and controls) Minimum supply water temperature: 7ºC System operating pressure: Variable with system location in relation to related chiller plant. Variable pump flow control: Variable frequency drive (VFD) all motors over 2HP. .7 Piping Minimum Requirements: All chilled water piping shall be schedule 40 black iron with threaded, flanged, victaulic or welded fittings. installation shall take into account grading, stressing and deformation of the piping. the final installation shall be neat in grouping and appearance. fittings shall be from forged steel suitable for installed steel piping. use standard or long radius elbows and welding tees. Flanges shall be of raised face, steel weld-neck, lab or backwelded slip-on type, compatible with mating flanges. fittings up to 50mm diameter can be threaded, but to meet the maximum cooling system operating pressure of 760 kpa. Provide piping system venting at all high points and draining at all low points. .8 New Connections .1 Each distribution system shall have circulating pump(s) capable to handle the system pressure and flow requirements. .2 Isolation valves with drain valves shall be installed into each supply and return piping connection to a distribution system and/or to a building. The drain valves shall be located on the connection side of isolation valves. .9 Pumps Minimum Requirements: .1 Centrifugal base mounted or vertical in-line pump with premium efficiency motor. Motor size up to 0.5HP to be single phase 120V, 0.5HP and bigger to be three phase 480V. Minimum pump operating efficiency 75%. .2 Each pump shall be equipped with a pressure gauge connected to pump suction and discharge side with isolation valves to allow for the pump operating pressure metering with one gauge only. .3 All main secondary zone pump(s) shall have at least one stand-by pump with minimum 85% stand-by capacity in case of one pump failure. .10 Manual Valves Minimum Requirements: All valves shall be of same manufacturer throughout where possible. Use pipe size valves. Valves up to 50mm in diameter to be threaded, over 50mm in diameter flanged for use with flanged fittings or grooved for use with victaulic fittings. Use ball valves for small isolation services and gate or butterfly valves for services over 50mm. All valves shall be suitable for the system maximum operating pressure at the project location and the operating temperatures. .11 Balancing Valves Minimum Requirements: Circuit setter type calibrated balance valve with flange connections, design for system operating temperatures and maximum operating pressure at the valve location. Brass readout valves fitted with integral EPT insert, check valves designed to minimized system fluid loss during the balancing and monitoring process, calibrated nameplate to assure specific valve setting, internal seals to prevent leakage, bronze construction. .12 Triple Duty (Multi-Purpose) Valves Acceptable Manufacturer: Related pump manufacturer. Minimum Requirements: Valve shall combine isolation, balancing and check valve duties; strait or convertible strait/angled design, cast iron body, bronze gland, stainless steel stem sleeve, cast iron non-lubricated plug, brass clapper, brass seat with dual O-ring seal. Valve shall be for horizontal or vertical installation with plug type flow control, memory stops, bubble tight shut-off, pointer and scale, spherical clapper, threaded valve metering connections, non-slam check valve, elastomer seat and no lubrication requirements, design for system operating temperatures and maximum operating pressure at the valve location. . .13 Pump Suction Diffusers Acceptable Manufacturer: Related pump manufacturer. Minimum Requirements: Cast iron or ductile iron body, bronze start up strainer, stainless steel permanent strainer, blow down connection for horizontal installation, design for system operating temperatures and maximum operating pressure at the valve location. .14 Strainers Minimum Requirements: Cast iron or ductile iron body, bronze start up strainer, stainless steel permanent strainer, blow down connection for vertical or horizontal installation, design for system operating temperatures and maximum operating pressure at the valve location. .15 Air Vents Minimum requirements: High capacity type, design for system operating temperatures and maximum operating pressure at the valve location. .16 Drain Valves Minimum Requirements: Globe type with bronze body and trim and composition disc, design for system operating temperatures and maximum operating pressure at the valve location. .17 Equipment Conections Each chilled water cooling equipment shall be equiped with isolation valve(s), balancing valve, drain valve and vent valve as required to allow for equipment isolation, draining, removal and reinstallation without shutting down the corresponding chilled water zone or system. Each equipment shall have provisions for proper venting and balancing of chilled water flow. .18 Switch Over (Heating/Cooling) Hydronic Systems Switch over hydronic air conditioning systems (two and/or three pipe) including under floor cooling shall not be used unless specifically required and approved. AIR SYSTEMS .1 General Variable air volume air systems shall be used everywhere applicable. The constant airflow systems shall be used for make-up air services, rooms with high occupancy and related high ventilation requirements and/or for areas requiring to maintain specific cross pressurization between individual rooms and/or zones. .2 Air Handling Equipment All air handling units of air systems shall be located in mechanical rooms. Roof mounted package units shall be used only for small dedicated systems. Any roof mounted equipment location shall be coordinated and accepted by SFU Campus Planning & Development department. Fan motor sizes up to 0.5HP to be single phase 120V, 0.5HP and bigger to be three phase 480V. Variable airflow control: Variable frequency drive (VFD) all motors over 1HP. For VFD requirements see section 1.2 Primary Distribution System – Variable Frequency Drives of this Guide Lines. .3 Air System Zoning Each large air system shall be divided into individually controlled thermal zones. The maximum size for a perimeter zone shall be 75 m² and for an interior zone 190 m². Corner rooms with two or more outside wall exposures shall have separate thermal zones. Each room with high and variable occupancy as lecture rooms, classrooms, teaching labs etc. shall have separate thermal zone. Equipment rooms and research labs with 24 hour operation shall not be connected to large air systems but served with small dedicated systems. .4 Indoor Air Quality Minimum ventilation air volumes, minimum and maximum space temperatures and space relative humidity shall be maintain at levels required by WCB and ASHRAE standards and/or activity in research and special occupancy rooms. SFU policy generally does not require space air-conditioning or relative humidity control for people comfort but only where is necessary for equipment operations. EXHAUST SYSTEMS .1 General System exhaust volumes shall be evaluated in relation to the system duty and as recommended by applicable standards, required area and room cross pressurization, lab equipment and good engineering practices. All exhaust fans shall be selected to handle required operation and duties and for highest possible efficiency. Fan motor sizes up to 0.5HP to be single phase 120V, 0.5HP and bigger to be three phase 480V. .2 General Exhaust Systems General exhaust systems shall be used to provide increased room airflows through summer month to increase the room thermal comfort and or provide required space cross pressurization. .3 Washroom Exhaust Systems Washroom exhaust systems shall be sized for airflows recommended for public washrooms by ASHRAE standards. .4 Laboratory Exhaust Systems Systems shall provide airflows required by the equipment manufacturer and by WCB standards for the work area. Where required provide exhaust systems for individual equipment and labs. Wherever allowed, individual room and equipment exhausts shall be combined into larger systems. Heights of fume exhaust stacks and/or equivalent exhaust fan airstreams shall be consulted and approved by SFU Work Safety Office. HVAC SYSTEM COMMISSIONING .1 General Commissioning to be carried out by an independent Commissioning Contractor, under general direction of the Commissioning Engineer (Contractor‟s staff) and in presence of the Consultant and the Owner as requested. .2 Approvals Obtain approval to start commissioning from the Consultant at least 7 days prior to start. Information to include: .1 Systems to be commissioned. .2 Procedures, anticipated results. .3 Names of commissioning personnel. .4 Purpose .5 Assurance that systems meet design criteria, design intents and requirements of specifications. .3 Design Requirements .1 Commissioning Engineer to confirm with the Consultant that Design Criteria and Design Intents are still applicable. .2 Commissioning personnel to be fully aware of and qualified to interpret Design Criteria and Design Intents. .4 Co-ordination Co-ordinate commissioning procedures with other project Divisions .5 Timing .1 New Construction – To meet LEED Certification requirements. .2 Retrofit projects - Commissioning to commence only after satisfactory completion of start-up, verification of performance and specified test period. .3 Commissioning of occupancy sensitive systems to take place after facility has been accepted, taken over and fully occupied. .4 Commission systems considered as life safety systems before affected parts of facility are occupied. .6 Instrumentation .1 Provide sufficient permanent and temporary instrumentation. Verify locations, access, illumination for readings .2 Instrumentation accuracy tolerances: higher order of magnitude than equipment, or system, being tested .3 Locations to be approved, readily accessible and readable .4 Application to conform to normal industry standards. .7 Operation of Systems Operate systems as long as necessary to commission entire project. .8 Supervision and Monitoring .1 Commissioning to be supervised by qualified supervisory personnel. .2 Monitor progress. .3 Keep detailed records of activities and results. .9 Documentation Documentation, O&M Manuals and any recommended training of O&M personnel to be complete to satisfaction of the Consultant before starting commissioning. .10 Use of O&M Personnel O&M personnel to assist in commissioning procedures as part of training. .11 Procedures .1 Test each system independently and then in unison with other related systems. .2 Co-operate with Commissioning Engineer/Consultant to develop appropriate commissioning procedures for systems. .3 Commission integrated system using procedures prescribed by Commissioning Engineer. .4 Repair system deficiencies. .5 Optimize operation, performance of systems by fine tuning equipment operating parameters and modifying equipment operational settings as required. .12 Verification of Results Commissioning Engineer shall verify at least 30 % of reported results. .13 Demonstration Demonstrate to the Consultant and the Owner operation of systems including sequence of operations in regular and emergency modes, under normal and emergency conditions, start-up, shut-down, interlocks, lock-outs. .14 Final Settings Upon completion of commissioning to satisfaction of the Consultant, set equipment operating parameters in final position, permanently mark settings. .15 Final Report .1 Submit report to Consultant. .2 Report to include: Measurements, final settings, certified test results. .3 Bear signature of commissioning technician and supervisor. .4 Be subject to verification by the Owner and the Consultant. .5 Report format to be approved by the Consultant before commissioning started. .16 Commissioning Activities During Warranty Period .1 Continue system operation debugging and optimization. .2 Revise "As-built" documentation, commissioning reports to reflect changes, adjustments, modifications to component settings and system operation during commissioning. .3 Recommend additional changes, modifications deemed advisable in order to improve performance, environmental conditions and energy consumption. .17 Maintenance Activities During Warranty Period The intent of this paragraph is not to include normal day-to-day routine operation and maintenance of system. .1 Provide services, materials, equipment and maintain system operations for specified warranty period. Provide detailed preventative maintenance schedule for system components. .2 Perform as minimum three (3) minor inspections and one major inspection (more often if required by manufacturer) per year. Provide detailed written report to the Consultant. Major Inspections to include, but not be limited to: 1. Minor inspection 2. Run system equipment diagnostics as required. 3. The following inspections will be considered minimum requirements, and shall not be interpreted to mean satisfactory performance. Calibrations will be performed using test equipment having traceable, certifiable accuracy at minimum 50% greater than the accuracy of equipment components. Provide dated, maintenance task lists to the Consultant as proof of execution of complete system verification. Maintenance task lists to include the new equipment details; equipment name, location, device type and range, measured value, system design value, calibration detail, indication if adjustment required, and any other action taken as recommended. Minor Inspections to include, but not be limited to: 1. Perform visual, operational checks to new peripheral equipment, interface equipment and panels. 2. Check equipment components as required. 3. Perform inspections during regular working hours, 08:00 to 18:00 h, Monday through Friday, excluding legal holidays. 4. Visually check for mechanical faults, air leaks and proper operational settings on components. 5. Review system performance with the Consultant and the Owner and discuss suggested or required changes. Emergency Service Calls: 1. Service calls will be initiated when there is indication that system or system component is not functioning correctly. Have qualified personnel available during contract period to provide service to "CRITICAL" components whenever required at no extra cost. Furnish the Owner with telephone number where service personnel may be reached at any time. Service personnel to be on site ready to 2. 3. 4. 5. 6. service system and system components within 2 hours after receiving request for service. Perform work continuously until the system is restored to reliable operating condition. Operation: foregoing and other servicing to provide proper sequencing of equipment and satisfactory operation of systems based on original design conditions and to be as recommended by manufacturer. Records and logs: maintain records and logs of each maintenance task. Organize cumulative records for each major component and for entire system. Complete forms and submit after inspection indicating that planned and systematic maintenance has been accomplished. Work requests: record each service call request, when received separately on approved form. Form to include number identifying component involved, its location, date and time call received, nature of trouble, names of personnel assigned, instructions of work to be done, amount and nature of materials used, time and date work started, time and date of completion. System modifications: provide in writing. No system modification, including operating parameters and settings, to be made without prior written approval of the Consultant and the Owner for the new systems installed under the project. Rectify deficiencies revealed by maintenance inspections. .18 Completion of Commissioning Commissioning to be considered as satisfactorily completed when objectives of commissioning have been achieved to full satisfaction of the Consultant and the Owner. .19 Issuance of Final Completion Certificate Final Certificate of Completion will not be issued until receipt of written approval indicating the successful completion of specified commissioning activities including receipt of commissioning documentation. .20 Commencement of Warranty Period Date of the Consultant and the Owner acceptance of submitted declaration of Substantial Performance shall be date for commencement for the warranty period. AIR & HYDRONIC SYSTEM BALANCING .1 AIR SYSTEM BALANCING Balance air systems and general exhaust systems to air volumes indicated on Drawings. Final balancing shall be done with all fans of served area running at full capacity after completion of their balancing, testing and adjustments. Balancing to be by an independent Balancing Agency (K.D. Engineering, Western Mechanical). Air balance report to be to A.A.B.C. standards and 2 copies submitted to the Consultant for review. The project will not be considered complete until the balance report has been approved. The balance report shall include, but not be limited to the following: A. Fan Data Sheet -Make, model, serial number -Motor HP, voltage, rated amps, running amps -Fan RPM -Design and actual supply airflow in l/s at full speed -Fan operating inlet, discharge and total pressures in Pa. B. Air Outlet Sheet -Outlet number, make, model -Required l/s, actual l/s C. Drawings Single line drawing with outlets numbered corresponding to air outlet sheet .2 FUME HOOD EXHAUST SYSTEM TESTING Testing to be by an independent Balancing Agency (K.D. Engineering, Western Mechanical, Precision Air). System test report to be to A.A.B.C. standards and 2 copies submitted to Mechanical Consultant for review. The project will not be considered complete until the test report has been approved. The report shall include, but not be limited to the following: Fume Hood System Exhaust Fan: A. Fan Data Sheet -Make, model, serial number -Motor HP, voltage, rated amps, running amps -Fan RPM -Exhaust airflow in l/s at fully open and fully closed sash of fume hood cabinet -Fan operating inlet, discharge and total pressures in Pa. Test and balance fume hoods to indicated airflows at sash opening at 400mm height at recommended face velocity in relation to fume hood duties. Mark the sash height at design airflows on fume hood faces. .3 HYDRONIC SYSTEM BALANCING Balance the water flows through hydronic systems at individual zone connections, terminal equipment and components to flows indicated on drawings. Record terminal equipment and components performances with corresponding entering and leaving water temperatures. Submit balancing report indicating the specified and obtained water flows and recorded operating performances and temperatures. Test and balance system pumps to flows indicated in Equipment Schedules. The tests and test reports shall include, but not be limited to the following: A. Pump Data Sheet -Make, model, serial number -Motor HP, voltage, rated amps, running amps -Pump RPM -Design and actual water flows in l/s -Design and actual head pressures in kPa 7. PLUMBING AND DRAINAGE .1 General All new buildings and substantial building additions requiring non potable services shall have separate potable and non potable domestic water services. Central reduced pressure back flow stations shall protect potable water services at connection points of non potable services. .2 Piping All water piping shall be certified copper type L or K with soldered fittings. Installation shall take into account grading, stressing and deformation of the piping. The final installation shall be neat in grouping and appearance. Use standard radius elbows. Maintain a minimum of 25mm space between adjacent valves and fittings. .3 Valves (Rev. 1) .1 Isolation Valves Provide valves of same manufacturer throughout where possible. Use pipe size valves. Valves up to 50mm diameter to be with sweat connections suitable for soldering, over 50mm diameter to be threaded or flanged for use with threaded or flanged fittings. Use ball valves for small isolation services up to 50mm diameter and gate or globe valves for services over 50mm. All valves shall be suitable for the potable water service, the system maximum operating pressure of 1,040 kpa and for the system operating temperatures between 4° - 60°c. Isolation valves up to 50mm size: Minimum Requirements: All bronze construction. Isolation Valves Over 50MM Size: Minimum Requirements: Bronze body, stainless non-rising stem, bronze or stainless steel gate or disc, 150 class flanges. .2 Drain Valves Minimum Requirements: Globe type hose bib suitable for 19mm hose connection with bronze body and trim and composition disc suitable for domestic water service and system operating pressure (1,040 kPa) and operating temperatures (4° - 60°C). .3 Air Vents: Minimum Requirements: High capacity type suitable for potable water service, system operating temperature and system operating pressure. Acceptable Manufacturers: Watts, Armstrong, Taco or equal. 4 Check Valves: Minimum Requirements: Spring loaded non-slam type suitable for potable water service, system operating temperature and system operating pressure. .5 Strainers: Minimum Requirement: Way-pattern body with 316 ss. screen, screen cover and drain valve, suitable for potable water service, system operating temperature and system operating pressure. .6 Reduced Pressure Back Flow Preventer (RPBFP) Line size reduced pressure zone assembly, temperature range 1° - 80°C, maximum working pressure 1,040 kPa, bronze body construction, ball valve test cocks, internal relief valve, single access cover and modular check construction and low pressure drop. .4 Domestic Hot Water Heating Non slam check valves shall be installed into all cold water connections to domestic water heaters heated by the university hot water heating system. .5 Service Zones Building water services shall be separated into service zones. Isolation valves with drain valves shall be installed into each zone connection to building distribution systems. The drain valves shall be located on the connection side of isolation valves. .6 Building Connections .1 Isolation valves with drain valves shall be installed into each piping connection to the university primary cold water distribution system. Each major building expansion and/or new building shall have separate connection. The drain valves shall be located on the connection side of isolation valves. .2 Water metering station shall be installed into each piping connection to major building expansion and/or new building. Design of metering stations shall not include any by-pass around the stations. .3 University primary cold water distribution system operating pressure is between 620 and 690 kPa at the main system distribution station by Water Tower. .4 All new building connections to primary cold water distribution system must be protected with a pressure reducing stations capable to handle required water flows and to reduce incoming service pressure to 485 kPa. All new pressure reducing stations must be design with multiple parallel pressure reducing valves allowing sufficient “stand-by capacity” in case of one valve failure. .7 Domestic Hot Water Recirculation System recirculation pumps shall be sized for a maximum water flow of 0.25 l/s. Maximum piping flow velocity shall not exceed 1m/s. 8. SANITARY, STORM & LAB SEWER SERVICES .1 General All new buildings and substantial building additions shall have separate storm and sanitary sewer services and where required acid sewer services. Acid sewer services shall terminate in a treatment and neutralization station before their connection to sanitary service. .2 Piping All acid drain piping connected to lab sinks and fume hoods shall be of polypropylene acid resistant piping recommended for lab installations with manufacturer recommended fittings. All acid drain vent piping shall be from PVC. All other drain and vent piping shall be from copper DWV piping, ABS piping and or cast iron piping with recommended fittings as required by B.C. Plumbing code. .3 Floor Drains All floor drains to be primed including existing floor drains in renovated rooms. 9. NATURAL GAS SERVICES .1 General All new buildings and substantial building additions requiring non potable services shall have separate potable and non potable domestic water services. Central reduced pressure back flow stations shall protect potable water services at connection points of non potable services. .2 Piping All gas piping shall be Schedule 40 Black Iron with threaded fittings. Installation shall take into account grading, stressing and deformation of the piping. The final installation shall be neat in grouping and appearance. Use standard radius elbows. Install isolation valve into each gas connection and dirt leg on bottom of each pipe riser in front of the final horizontal connection to the gas appliances, equipment and terminals. .3 Service Zones Building gas services shall be separated into service zones. Isolation valves shall be installed into each zone connection to building distribution systems. .4 Building Connections .1 Isolation valve shall be installed into each piping connection to the university primary natural gas distribution system. Each major building expansion and/or new building shall have separate connection. .2 Gas metering station shall be installed into each piping connection to major building expansion and/or new building. Design of metering stations shall not include any by-pass around the stations. .3 University primary natural gas distribution system operating pressure is 35 kPa at the main gas connection at Library Building. .4 All new building connections to primary natural gas distribution system must be protected with a pressure reducing stations capable to handle required gas flows and to reduce incoming service pressure to required building pressure. All new pressure reducing stations must be design with multiple parallel pressure reducing valves allowing sufficient “stand-by capacity” in case of one valve failure. .5 Satellite Boiler Plant Satellite boiler plant shall be connected directly to the university central gas distribution system. 10. PLUMBING FIXTURES General .1 Install isolation valves in to all plumbing fixture connections to plumbing fixtures and equipment. .2 All plumbing fixtures must be of low flow design for water conservation. Water closets to meet the maximum 6 litre per flush requirements and minimum level of 250g of solid waste removal per flush. .3 All toilets to meet maximum performance test (MaP) rating of 250 as per Canadian Water and Wastewater Association (CWWA) approved testing. 11. LABORATORY SERVICES Laboratory Water .1 Install non potable services. .2 Where requested, install special water treatment stations in to supply lines to lab equipment and plumbing fixtures. LABORATORY GAS .1 Install required nitrogen gas, compressed air and other gas services with recommended piping and fixtures. 12. ENERGY CONSERVATION General All mechanical systems and equipment shall have efficiencies exceeding by 25% the latest issue of ASHRAE Energy Standard for Commercial and Institutional Buildings. Central air system minimum ventilation (outside air) volumes shall be controlled by CO2 concentration based performance controls. 13. DOMESTIC COLD WATER CONSERVATION General .1 All new air-conditioning system equipment shall be directly air-cooled or cooled by an air cooled closed loop hydronic and/or glycol system. .2 All lab process equipment and systems requiring cold water shall be installed with water recirculation and treatment systems. Only the minimum required make-up water shall be used. .3 All make-up water connections to mechanical systems shall be installed with water metering stations. 14. FIRE SUPRESSION SPRINKLER SYSTEMS General University cold water distribution system pressures are indicated in Section 10 “Hot and Cold Domestic Water Services” of this Mechanical Design Guidelines. Piping All sprinkler piping shall be Schedule 40 Black Iron with threaded, victaulic or welded fittings. Installation shall take into account grading, stressing and deformation of the piping. The final installation shall be neat in grouping and appearance. Use standard radius elbows. Sprinkler System Impairment Contractor is responsible for all required arrangements and notifications required during any shut-down of existing sprinkler system if required for the installation of new mechanical systems. If required, all notifications, sprinkler permit application, Schedule B1 and B2 Letters of Assurance for sprinkler modifications and other arrangements shall comply with code NFPA 13A and with requirements of local authority having jurisdiction. Before the sprinkler system shut down, the contractor shall: .1 Determine the exact extent of the intended impairment .2 Inspect the area of building to be involved and determine the sprinkler system zones involved and increased risk .3 Submit recommendations to the Owner about temporary protections and termination of any hazardous operation at least 48 hours prior of any work. .4 Notify the Burnaby fire department about the shutdown. .5 Notify the Fire Alarm Company about the shutdown. .6 After restoring the sprinkler zone to normal working order the contractor shall: .7 Verify that all control valves of the modified sprinkler zone are fully open .8 Conduct drain and alarm test on each sprinkler zone affected. .9 Maintain as large a portion of the system in service as possible. .10 Advise the Burnaby fire department and the Owner that protection has been restored. .11 Notify the Fire Alarm Company of Work in progress. .12 The Owner will be responsible for notifications of shut-down and restoration of sprinkler protection to the building insurer and the building supervisors. MAJOR EQUIPMENT START-UP & TRAINING General .1 Equipment suppliers shall provide start-up and training of the Owner‟s maintenance staff in the equipment operation and maintenance. .2 Mechanical Contractor shall provide manpower to assist the equipment supplier with the equipment start-up and training of the Owner‟s maintenance staff in the equipment operation and maintenance including equipment controllers. SUBSTANTIAL COMPLETION Prior to the request for the Substantial Completion and the substantial completion site progress review, the Contractor shall provide “List of Deficiencies” and following items shall be completed: .1 Commissioning of systems, all equipment to be operational. .2 Equipment cleaned inside and outside, lubricated, painted and touch-up completed. .3 First calibration of controls completed. .4 Testing of small air-conditioning and exhaust systems completed and the test report sent for the Consultant‟s review. .5 All testing of plumbing systems completed including final acceptance reports from “Authorities Having Jurisdiction”. .6 Balancing of air and hydronic systems completed and the balancing report sent for the Consultant‟s review. 1.2.22 PROJECT CLOSING & CLOSING DOCUMENTS .1 DEMONSTRATION AND INSTRUCTION TO OWNER After fulfilling substantial performance requirements, demonstrate to and instruct the owner representatives on the installed work using assistance of sub trades and/or manufacturer's representatives. It is intended that all mechanical equipment and controls installed will be checked and demonstrated in presence of the Owner and the Mechanical Consultant. Obtain a signed statement from the Owner certifying that the demonstration and instructions have been given. Include the letter in the maintenance manuals. .1 Provide instructions to the owner's representative on the operation and maintenance procedures required for all installed systems and components related to the work. Such instruction shall include familiarization of the maintenance staff with the operation and maintenance manual, an explanation of how each system operates and procedures to follow when the systems fail to operate normally. .2 Provide written confirmation from the owner's representative that such instructions have been given and accepted, within the understanding of the staff. .2 Operating and Maintenance Manuals Submit four (4) copies of operating and maintenance manuals for all mechanical and control equipment installed under this contract. Documents shall be submitted in hard covered binders. Submit documents to the Consultant for review prior to being submitted to SFU Facilities Management. .1 Provide three copies of the operation and maintenance manual, which is to include all information required to enable the building maintenance staff to effectively operate and maintain all installed mechanical equipment and modified systems under the project contract. .2 The manual shall include the following information in hard covered, three-ring binder labeled “chiller plant replacement”, indexed for the different sections: .3 A DESCRIPTION OF MAINTENANCE PROCEDURES AND SCHEDULES FOR EACH MECHANICAL SYSTEM INCLUDING SUPPORTING ELECTRICAL SYSTEMS INSTALLED UNDER THE PROJECT CONTRACT. .4 A SCHEDULE OF THE EQUIPMENT SUPPLIERS AND SUB-TRADES, MANUFACTURER'S OPERATING AND MAINTENANCE INSTRUCTION BULLETINS WITH EQUIPMENT SIZES, WITH PARTS LISTS AND SCHEMATICS AS APPLICABLE, INCLUDING PICTORIAL DATA WHICH IDENTIFIES OPTIONS AND SPECIAL FEATURES USED, SO AS TO FACILITATE ORDERING REPLACEMENTS. .5 A PLAIN PAPER APPROXIMATELY HALF-SIZE REPRODUCTION OF EACH “AS-BUILT" CONTRACT DRAWING, SIZED SO THAT, WHEN FOLDED TWICE, THERE WILL BE A BINDING EDGE FOR FIXING INTO THE MANUAL AND THE FOLDED FORMAT SHALL MATCH A NORMAL PAGE OF THE MANUAL. .6 Specified balancing and test reports, .7 Certificates of tests. .3 RECORD DRAWINGS Maintain 1 set of construction drawings on the construction site all the time. Mark-up with red colour any changes to the construction drawings on the end of each day. Hand over the set to the Consultant for Consultant‟s review after the project completion. .1 Maintain in the jobsite office in up-to-date condition one complete set of white prints of each of the contract drawings and one specification, including revision drawings, marked clearly, legibly and indelibly in red, indicating 'as-built' conditions where such conditions deviate from the original directions of the contract documents and indicating final installation of piping and equipment. Such markings shall include but shall not be limited to the following: .2 ALL CHANGES IN EQUIPMENT, PIPE SIZES AND LAY-OUT. .3 At completion of construction employ a competent cad drafting service to transfer all of the above as built information into auto cad v14 or later compatible drawing files of each contract drawing. paper and soft copy of all such information shall be given to the owner and the consultant as described elsewhere herein. all associated costs shall be included in the contract amount. .4 Each 'as-built' paper copy as defined above shall bear the contractor's identification, signature, date of record and the notation "this document represents the indicated part of the work as built". .5 Provide sufficient paper copies of the above for: .1 Each operation and maintenance manual, .2 The consultant‟s records, .4 CARE, OPERATION AND START-UP .1 Provide instructions to the owners representative on the operation and maintenance procedures required for each system and for each component of each system. Sch instruction shall include familiarization of the building staff with the 0 & m manual, an explanation of how each system operates, where and how it is controlled manually, where and how it is controlled electrically, where and how it is controlled for safety, and advising of normal set positions and set points if applicable, and procedures to follow when systems malfunction. .2 Provide written confirmation from the owner‟s representative that such instructions have been given and that they have been understood, within the understanding of the operating staff. 1.2.23 GUARANTEE .1 Guarantee the satisfactory operation of all new equipment and systems supplied and installed for a period of not less than one year from the date of substantial completion as declared by the consultant to the contractor. replace within 15 days any part which fails or is found defective during this period at no cost to the owner, providing that such failure is not due to the improper usage by the owner. .2 No certificate given, payment made, or partial or entire use by the owner shall be construed as acceptance of defective work or materials by the owner. the guarantee is not to be shortened nor the terms altered due to the temporary usage of any equipment or systems during the construction period. .3 Any equipment, which has been used in the past by the owner and to be relocated and/or reinstalled for use on this project, shall be cleaned and repaired as necessary before being installed under this project. this contractor shall guarantee any equipment repair work and the relocated equipment installation. .4 This general guarantee shall not act as a waiver for any guarantee which is intended to last for a period longer than one year. 1.2.24 TEMPORARY AND TRIAL USAGE The owner is entitled to the temporary and trial use of any and all mechanical equipment or systems installed under this division of the work, even though such equipment or system may not have been formally accepted by the consultant. The owner shall have the privilege of such temporary or trial usage for such reasonable length of time as deemed sufficient as soon as the contractor claims that portion of the work has been completed in accordance with the contract documents. 1.2.25 FIELD QUALITY CONTROL & TESTS .1 All tests, correction of deficiencies and retests are the sole responsibility of the contractor, and shall be performed after system installation has been completed and prior to the system being put into continuous operation. .2 Dive 48 hours notice to the consultant in advance of each set of tests, indicating in writing: the testing agency, the schedule of tests, the testing procedure, and the type of measuring equipment. obtain written approval prior to conducting such tests, submitting detailed, typewritten test reports to the consultant within seven (7) days of the completion of any test. .3 The contractor shall also be responsible for performing or coordinating any of the following tests: 1. INSPECTION FOR DAMAGE OF ALL NEW OR REUTILIZED EQUIPMENT ASSOCIATED WITH THIS WORK. .4 Also conduct and pay for the following tests: .1 HYDROSTATIC PRESSURE TEST AT SYSTEM WORKING PRESSURE TO ALL MODIFIED AND ADDED PIPING OF CHILLED WATER COOLING AND PLUMBING SYSTEMS REQUIRED FOR THE PROJECT. THE TEST DURATION SHALL BE AT LEAST FOR 8 HOURS WITHOUT PRESSURE LOSS. THE MODIFIED SPRINKLER SYSTEM TESTING SHALL CONFORM TO THE REQUIREMENTS OF NFPA 13 AND 13A. .5 PERFORM TESTS IN THE PRESENCE OF THE CONSULTANT WHERE SPECIFIED, AND PROVIDE WRITTEN RECORD OF READINGS TO THE CONSULTANT UPON REQUEST OR AS DIRECTED. .6 Provide instruments, meters, equipment and personnel required to conduct tests during and at conclusion of project and for any retests subsequently necessary and relating to this work. .7 If requested, test any piece of equipment, device or material for a reasonable length of time and at such time as the consultant or the owner may require to make a complete and thorough test of the same to verify performance requirements before final acceptance and completion of the work. .8 Such tests shall not be construed as evidence of acceptance of any part of the contract and it is agreed and understood that no claim for damage will be made for any injury or breakage to any part or parts or by defective materials or workmanship of any kind whatsoever. 1.2.26 RESPONSIBILITY .1 Supply all labour, materials, equipment, tools and incidentals necessary to provide a complete mechanical installation as indicated on the drawings and as set out in this specification. .2 Visit the site before tendering and examine all local and existing conditions on which the work is dependent. no consideration will be granted for any misunderstanding of work to be done resulting from failure to visit and examine the site. .3 Advise the owner and the consultant of any specified equipment, material or installation of same which appears inadequate or unsuitable, in violation of laws, ordinances, rules or regulations of authorities having jurisdiction, or of any necessary items of work omitted from the contract drawings during the project tender and before proceeding with the work. .4 Check project documents of other trades and coordinate with them the mechanical installations to ensure orderly project progress and adequate equipment space. work out jointly, with the consultant, the owner and all sub-contractors on the site, solutions to interference problems. .5 Coordinate all work before fabricating or installing any material or equipment. It is important to ensure that all materials and equipment fit into the allocated spaces and that all equipment can be properly serviced and replaced if and when required. Advise the owner and the consultant of any space problems before fabricating or installing any material or equipment. .6 Demonstrate to the consultant on completion of the work that all equipment and material installed can be properly and safely serviced and replaced if and when required. .7 Make no deviations from the design intent, equipment performances and/or involve extra cost without obtaining the consultant's written direction. .8 Where mechanical work and materials are noted as being provided by the owner or under other divisions of this specification, the responsibility for integrating such work and materials into the complete mechanical installation shall remain within this division of the specification.