Series 230 Automatic Transfer Switch

advertisement
Series 230 Automatic Transfer Switch
The Recognized Leader in Power Transfer
Switch Technology Offers the Most
Advanced Transfer Switches in the World.
Product Overview
The Series 230 automatic transfer switch consists of an
intelligent controller and a modular load break switch which
automatically transfers the load to the emergency power
source when it detects the normal power source under/over
voltage, under/over frequency, or phase loss. The switch has
three operational positions (Source I, Center-off, Source II).
The two sources are isolated when the switch is in the centeroff position. A center-off position locking mechanism is also
provided.
Application
The Series 230 transfer switch is rated up to 800A and is available from 220 to 415 volts for both 50 and 60 Hz, single and three
phase. Typical applications include commercial and residential buildings, hospitals, telecom, subway and transportation, data
centers, military and fire pumps.
Parameter
Rated Operational Current Ie (A)
Rated Insulation Voltage Ui (V)
Rated Impulse Withstand Voltage Uimp (kV)
16 32 63 80 100 125 160 200 225 250 315 400 500
630
800
1000
1000
1000
1000
8
8
12
12
12
800
220, 230, 240, 380, 400, 415
Rated Operation Voltage Ue (V)
50 / 60
Rated Frequency (Hz)
2,4
Poles
2, 3, 4
Rated Short-Time Withstand Current Icw (kA, RMS)
6 (0.03s)
10 (0.1s)
15 (0.1s)
25 (0.1s)
40(0.1s)/ 20(1s)
Rated Short-Circuit Making Capacity Icm (kA, PEAK)
Withstand and Close-On
Rating Iq (kA)
8
17
31.5
65
80
When Used With Current
Limiting Fuses
65
65
200
200
200
When Used With Specific
Circuit Breakers
15
50
150
150
80
10 Ie
Making and Breaking Capacity
10,000
Mechanical Operation Performance (cycles)
AC-32A, AC-33B
Utilization Category
Operation Voltage
range (AC)
Ue=220V / 230V / 240V /
380V / 400V
Ue= 415V
Wiring Way
Front
Separate Lock Mechanism
1
(0.7~1.15) Ue
Class A
EMC Class
Auxiliary Contact (Optional)
(0.7~1.2) Ue
125~300V
(L-N)
Standard
4 contacts maximum
8 contacts maximum
Series 230 Automatic Transfer Switch Product Features
Performance Features
Switching Mechanism
Meets or exceeds the requirements of the
following regulatory agencies
•Automatic, manual and remote operation are
available
• EN60947-6-1/IEC60947-6-1: Transfer Switching
•Unique contacts design limits contact bounce
• EN60947-3/IEC60947-3: Suitable for Isolation
•Unique clutch design makes manual operation
easy and low force
• EN55022: Radiated and Conducted Emission,
Class A
• EN61000-3-2: Harmonic Current Emission, Class A
• EN61000-3-3: Limits of Voltage fluctuation and
Flicker
• EN 61000-4-5: Immunity to Surge
• EN 61000-4-4: Immunity to Electrical Fast
Transient
• EN61000-4-2: Immunity to Electrostatic
Discharge
• EN61000-4-3: Immunity to Radiated Electric
Fields
• EN 61000-4-6: Immunity to Continuous
Conducted Interference
Structure
•Electrical and mechanical interlocks prevent
two sources from connecting simultaneously
•Innovative motor circuit protection ensures
precision operation
•Cast steel bevel gear mechanism provides high
transmission efficiency, and extends operating
life
Controller
•Different Operating Modes (Source I priority /
No Source priority)
•C300 and C2000 can work with an external
24VDC power supply
•High frequency switching power supply, and
wide power voltage range
•PC Class ATS
•Data (e.g. Event log, Setting, etc) remains intact
if power is lost
•High ability to withstand lightning strikes (40kA
8/20μs)
•Intelligent fault diagnostics enable selfprotecting motor feature
•Simple reliable mechanism, compact and stylish
appearance
•RS485 communication interface is available
•Modular design, convenient operation, easy
maintenance
•Priority Source Swap
•Three operating positions. Both sources can be
isolated in a center-off position
Arc Extinguish
•The utilization categories are AC-32A, AC-33B,
and the ability to withstand and break is10 Ie
•Rotating dual contact design extinguishes the
arc quickly and effectively
•Arcing contacts and main contacts are separate;
main contacts are protected from arc damage
•Wiping-action contacts are self cleaning
•High short-circuit closing ratings
2
Make Life and Business More Reliable
By Using ASCO
Series 230 Transfer Switch Ordering Information
To order an ASCO Series 230 Automatic Transfer Switch, complete the following catalog number:
E2ADTL
B3
Frame size
Poles
A2ADTL 16 ~ 80A Frame
B1: 2 Poles (L-N)
(2-wire with Neutral)
0800
D
X
0
1H
Controller
Options
Enclosure
Optional
Accessories
H
Amperes
Voltage
Continuous
Code
Rating
0016, 0032
D 220V B
C300*
0063, 0080
02: 2 poles (L-L)
C2ADTL 200 ~ 250A Frame (2-wire without Neutral) 0100, 0125
E 230V D
C1000
F 240V E
C2000
D2ADTL 315 ~ 400A Frame B2: 3 Poles
(3-wire with Neutral)
E2ADTL 500 ~ 800A Frame
03: 3 Poles
(3- wire without Neutral)
0160, 0200
H 380V
0225, 0250
J
0315, 0400
K 415V
B2ADTL 100 ~ 160A Frame
0500, 0630
B3: 4 Poles
(4-wire with Neutral )
0800
* The A2ADTL frame is only available with the embedded C300 controller
3
400V
Insert “X” O Open type 132JA ~ 132JC
If optional
B2ADTL Frame BusBar
accessories C
IP20
are required
132A ~ 132F
Q
IP54
Auxiliary Contacts
72D
C300, C1000 with
RS-485
1H
C2000 with Energy Storage
Optional Accessory Model Description and Order Information
B2ADTL Frame Bridging Bus Bar
132 J A
Poles
A: 2 poles (02356097)
B: 3 poles (02357091)
C: 4 poles (02355942)
4 pole Bridging Busbar
Function Code 132J: Bridging Busbar
For example: 132JC , means Bridging Busbar for a 4 pole transfer switch
Auxiliary Contacts
132 A A
Auxiliary Contact Quantity
BLANK: 1 contact
A: 2 contacts
B: 3 contacts
C: 4 contacts
Function Code 132A-132F: Auxiliary Contact
Auxiliary Contact
For example: 132BA , means 2 sets of contacts, which close when the ATS transfers to the Source II position.
4
Auxiliary Contact Definition
132A-132C : The auxiliary contacts can be used to indicate position with the CLOSE contact, see Schematic 1.
132D-132F: The auxiliary contacts can be used to indicate position with the OPEN contact, see Schematic 2.
Position of The
Transfer Switch
Auxiliary Contact Function Code
132A
132B
132C
Position of The
Transfer Switch
I
I
O
O
II
II
Auxiliary LAP1F100
(16021426)
Contact
LAP1F010
Code (16021427)
√
√
-
-
-
√
Auxiliary LAP1F100
(16021426)
Contact
LAP1F010
Code (16021427)
Auxiliary Contact
Mounting Position
Auxiliary Contact
Mounting Position
(only showing C2ADTL,
D2ADTL, E2ADTL).
(only showing C2ADTL,
D2ADTL, E2ADTL).
72D
C300 or C1000 Controller with RS-485 interface
A RS485 interface installed in the C300 or C1000 controller to enable serial communications,
supporting MODBUS protocol. This Accessory can only be installed in the factory. Use accessory
code 72D when ordering this function.
1H
C2000 Controller with energy storage
The optional controller with energy storage (Accessory 1H) has an added feature to switch the
transfer switch to the center-off position during Source I and Source II failure at the same time. The
controller will remain in center-off until either Source I or Source II power is restored and voltage and
frequency are both stable. This optional feature can work in Source I Priority and No Source Priority
operating modes. This feature is available only after the controller has been powered by AC input
for at least10 minutes to charge a capacitor. This Accessory can only be installed in the factory. Use
accessory code 1H when ordering this function.
5
Auxiliary Contact Function Code
132D
132E
132F
-
-
√
√
√
-
Avoid Losing Critical information
When Power is Lost
Series 230 Dimensions and Weight
A2ADTL Frame
A
108mm(4.25)
120mm(4.72")
18")
m(Ă0.
Ă4.5m
171mm(6.73")
A
18mm(0.71")
Unit: mm(inch)
C
2P
4P
216.0
252.0
1.6
2.0
A2ADTL
Size (mm)
B
45mm(1.77")
110mm(4.33")
124mm(4.88")
121.3mm(4.77")
107mm(4.21")
96mm(3.78")
93mm(3.66")
20.5mm(0.81")
Weight (kg)
Note: unit must be installed in the cabinet using a DIN35 rail
B2ADTL Frame
214mm(8.4")
184mm(7.2")
126mm(5.0")
29mm(1.1")
117mm(4.6")
104mm(4.1")
78mm(3.1")
112mm(4.4")
27mm(1.1")
15mm(0.6")
A
Unit: mm(inch)
B2ADTL
Size (mm)
Weight (kg)
A
2P
3P
4P
241.0
349.0
349.0
2.6
2.8
2.8
Note: unit must be installed in the cabinet using a DIN35 rail
6
168mm(6.6")
12.5mm(0.5")
C2ADTL Frame
20mm(0.8")
126mm(5.0")
150.5mm(5.9")
130mm(5.1")
116mm(4.6")
100mm(3.9")
9mm(0.4")
6mm(0.2")
34mm(1.3")
177mm(32.8")
7.5mm(0.3")
9mm(0.4")
50mm(2.0")
128mm(5.0")
23.5mm(0.9")
172mm(6.8")
194mm(7.6")
182mm(7.2")
Ø6mm(Ø0.2")
C
B
A
2P
3P
4P
A
251.0
285.0
319.0
B
236.0
270.0
304.0
C
68.0
102.0
136.0
4.6
5.2
5.8
C2ADTL
Size (mm)
Unit: mm(inch)
Weight (kg)
15.5mm(0.6")
D2ADTL Frame
120mm(4.7")
Ø7mm(Ø0.3")
206mm(8.1")
44mm(1.7")
10mm(0.4")
B
A
2P
3P
4P
A
317.0
361.0
405.0
B
297.0
341.0
385.0
C
103.0
147.0
191.0
8.6
9.8
11.0
D2ADTL
Size (mm)
Weight (kg)
7
25mm(1.0")
10mm(0.4")
140mm(5.5")
120mm(4.7")
186mm(7.3")
158mm(6.2")
144mm(5.7")
2.5mm(0.1")
199mm(7.8")
52mm(2.0")
228mm(9.0")
215mm(8.5")
173mm(6.8")
C
Unit: mm(inch)
ASCO Power Transfer Switch Solutions
for Powerful Peace of Mind
8mm(0.3")
E2ADTL Frame
10mm(0.4")
174mm(6.9")
195mm(7.7")
290mm(11.4")
265mm(10.4")
208mm(8.2")
160mm(6.3")
Ø9mm(Ø0.4")
228mm(9.0")
65mm(2.6")
14mm(0.6")
13mm(0.5")
45mm(1.8")
C
19mm(0.7")
226mm(8.9")
57mm(2.3")
165mm(6.5")
240mm(9.5")
252mm(10.0")
180mm(7.1")
B
A
2P
3P
4P
A
384
449
514
B
357
422
487
C
146
211
276
14
17
20
E2ADTL
Size (mm)
Unit: mm(inch)
Weight (kg)
Shipping Dimensions and Weights (Including TS and controller, without options)
Frame
Width
(mm)
Height
(mm)
Depth
(mm)
2P
4P
A2ADTL
310
170
175
1.9
2.3
B2ADTL
602
220
C2ADTL
602
D2ADTL
E2ADTL
Weight (kg) with C300
Weight (kg) with C1000
Weight (kg) with C2000
2P
3P
4P
2P
3P
4P
267
4.9
5.5
5.7
5.2
5.8
6.0
335
227
8.9
9.5
10.1
9.2
9.8
10.4
650
350
300
13.0
14.5
16.0
13.4
14.9
16.4
767
350
352
16.0
19.0
22.0
16.5
19.5
22.5
* All information is subject to change, for the latest information please contact ASCO sales team.
8
Series 230 Controller Feature Comparisons
C300 Controller
C1000 Controller
Voltage and Frequency Sensing
Voltage and Frequency Sensing
Voltage and Frequency Sensing
• Single phase under and over voltage settings
on Source I and Source II
• Single phase under and over voltage settings
on Source I and Source II
• Phase loss sensing on Source I and Source II
• Phase loss sensing on Source I and Source II
•Under and over frequency settings on
Source I and Source II
•Under and over frequency settings on
Source I and Source II
•3-Phase under and over voltage settings
on Source I and Source II
•Under and over frequency settings on
Source I and Source II
•Voltage unbalance detection between
phases
Time Delays
Time Delays
•Time delay sensing accuracy is ±1%
•Time delay sensing accuracy is ±1%
•Transfer time delay can be set manually
•Transfer time delay can be set manually
Controller Display and Keypad
Controller Display and Keypad
•LED display
•LED display
•Touch key for clearing alarm and manual
operation
•Touch pad for clearing alarm and manual
operation
•Switch position indicator lights
•Switch position indicator lights
•Source acceptability indicator lights
•Source acceptability indicator lights
Operating Modes
•LCD display
•Touch pad for programming the features
and settings
•Switch position indicator lights
•Source acceptability indicator lights
Operating Modes
•Automatic and manual operation available
Operating Modes
•Automatic and manual operation available
•Source I Priority/ No Source Priority
•Priority Source Swap
•Source I Priority/ No Source Priority
•Priority Source Swap
Center-off with time delay and
center-off with protection
Center-off with time delay and
center-off with protection
•The center-off time delay can be set to
avoid large current inrush to inductive
loads
•The center-off time delay can be set to
avoid large current inrush to inductive
loads
•Center-off with protection is available to
protect critical loads (e.g. Fire Pump)
•Center-off with protection is available to
protect critical loads (e.g. Fire Pump)
Remote Control and
Communication
Remote Control and
Communication
•Can control switch remotely (e.g. Position
Control, Time Delay, etc.)
•Can control switch remotely (e.g. Position
Control, Time Delay, etc.)
•Fire control signal input (24VDC)
•Fire control signal input (24VDC)
Power Supply of Controller
Power Supply of Controller
• Operation Voltage (VAC): 220/ 230/ 240
•Operation Voltage (VAC): 220/ 230/ 240/
380/ 400/ 415
• C300 has ability to work with 24VDC power
supply
9
C2000 Controller
Time Delays
•Time delay can be set by operating
parameter setting menu
•Time delay sensing accuracy is ±1%
•Time delay can be set under different
working modes
•Transfer time delay can be set manually
Controller Display and Keypad
•Automatic and manual operation available
•Source I Priority/ No Source Priority
•Priority Source Swap
Center-off with time delay and
center-off with protection
•The center-off time delay can be set to
avoid large current inrush to inductive
loads
•Center-off with protection is available to
protect critical loads (e.g. Fire Pump)
Events Display
•Event log displays: 100 most recently
logged events with time and date of each
event, event type and event reason
Remote Control and
Communication
•Uses RS485 interface, and supports
MODBUS Communication
•Can control switch remotely (e.g. Position
Control, Time Delay, etc.)
•Fire control signal input (24VDC)
Power Supply of Controller
•Operation Voltage (VAC): 220/ 230/ 240/
380/ 400/ 415
•C2000 has ability to work with 24VDC
power supply
24-hour Protection No Matter When
Trouble Strikes
Rated Operation Voltage Ue(V)
Rated Frequency (Hz)
Display Indicator
Source(I,II) Available
ATS Position
Control Mode
Manual/Automatic
Source I Priority
No Source Priority
Remote Control
Unique Control Funcation
Remote control Priority (1)
Priority Source Swap
Center-off with protection when Source I and II are lost (3)
Diagnosis fault intelligent with self -protection function
Source Sensing Setting
Voltage Sensing(4)
Frequency Sensing
Power loss
Phase loss (5)
Undervoltage
Overvoltage (6)
Overfrequency Transfer
Underfrequency Transfer
Time Delay Setting
Override Momentary Source Outage
Transfer to Source II
Transfer to Source I
Engine Cooldown
Center-Off Position Delay
Others
RS-485
Additional 24V DC Power Input
Generator Control Signal Output
Fire Control Signal Input
Alarm
Auxiliary Contact
Event Log
Display Type
Installation
C300
C1000
C2000
220/230/240
50/60Hz
220/230/240/380/400/415
50/60Hz
220/230/240/380/400/415
50/60Hz





















 (2)




Optional

L1-N,L2-N,L3-N


L1,L2,L3
65%, 70%, 80%, 85%
120% / OFF
115%
85%
L1-L3


L1,L3
70%, 85%
120% / OFF
115%
85%
L1-L2,L2-L3,L3-L1


L1,L2,L3
70% 〜 98%
102% 〜 120% / OFF
102% 〜 115%
85% 〜 98%
1s
0s, 5s, 30s, 5min
1s, 30s, 5min, 30min
2min
OFF / 5s
1s
0 〜 5min
1s 〜 30min
2min
OFF / 5s
0 〜 3s
0 〜 5min
0 〜 30min
0 〜 60min
0 〜 5s
Optional




Optional
Optional



Optional
LED
DIN rail installation and Panel
installation
LED
DIN rail installation and Panel
installation





Optional

LED+LCD
Panel installation
:Yes, Standard; Blank: Not Available/ Not Applicable
Remarks: 1. Only available for source priority mode
2. C1000 controller with priority swap function requires special soft ware to be field installed
3. Need to use controller with energy storage (Accy 1H)
4. For C300 controller, Source II Voltage sensing is only on L1
5. For C300 controller, Source II Phase loss sensing is only on L1
6. When the controller is used on 415V, its Overvoltage Droupout is 115% both on Source I and Source II
10
C300 Controller Port Function Description
Accessory 72D
Optional RS485 Port
24V
24V DC
Power
Input
11
RS485
24V
Generator
Start
Alarm
GEN
ALM
Fire Control Transfer to
Input
Position O
FIRE
DI 1
Transfer to
Position I
Transfer to
Position II
Push to
test
RS485
DI 2
DI 3
DI 4
485 Port
72D
C1000 Controller Port Function Description
Accessory 72D
Optional RS485 Port
RS485
24V
Generator
Start
Alarm
Fire Control
Input
Transfer to
Position O
Transfer to
Position I
Transfer to
Position II
RS485
GEN
ALM
FIRE
DI5
DI6
DI7
485 Port
X3 User Terminal
72D
X4
C1000 CONTROLLER
X1 Power Terminal
X2 Control Terminal
Power and Voltage Detection
Transfer Switch Position Detection
and Transfer Control
To
Transfer
Switch X1
To
Transfer
Switch X2
12
C2000 Controller Port Function Description
24V
Alarm
ALM
O
I
II
TS Position
DO1
DO2
DO3
Generator
Start
RS485
GEN
485 PORT
Fire Control Transfer to Transfer to Transfer to
Input
Position O Position I Position II
FIRE
DI5
DI6
DI7
X4 User Terminal
C2000 CONTROLLER
X1 Power Terminal
Power and Voltage Detection
To
Transfer
Switch X1
X2 Control Terminal
X3 User Terminal
Transfer Switch Position Detection
24V DC
and Transfer Control
Power Input
To
Transfer
Switch X2
24V
Lost
Power
X5
Capacitor.
Output
Energy
storage
output
Accessory 1H
Optional Built-In Capacitor used as a
(rechargeable) one-time motor-control
transfer after complete power loss.
This accessory also requires a different
connector board on the Transfer Switch Unit.
13
1H
Critical Loads Demand ASCO
Controller Dimensions and Weight*
C1000 Controller (With or Without optional 72D Accessory)
80.7
58.7
93.5
111.5
46.2
47±0.5
94±0.5
Panel Opening Dimensions
Weight: 0.74kg
Unit: mm(inch)
C2000 Controller
191±1
Source I
86
Source II
134±1
142
132
80
Run Auto Alarm
UP
Esc
Transfer Switch Position
197
Enter
Down
189
Panel Opening Dimensions
Weight: 1kg
Unit: mm(inch)
14
Critical Loads Demand ASCO
C2000 Controller with Energy Storage (Accessory 1H)
128.7 122.2
189.0
Run Auto Alarm
Source I
Source II
132.0
142.0
UP
Esc
Transfer Switch Position
Enter
Down
197.0
Weight: 1.64kg
Unit: mm(inch)
*Not Shipping weight, Actual unit weight
15
About Emerson Network Power
Emerson Network Power, a business of Emerson (NYSE:EMR), protects and optimizes critical infrastructure for data centers, communications networks,
healthcare and industrial facilities. The company provides new-to-the-world solutions, as well as established expertise and smart innovation in areas
including AC and DC power and renewable energy, precision cooling systems, infrastructure management, embedded computing and power, integrated
racks and enclosures, power switching and controls, and connectivity. Our solutions are supported globally by local Emerson Network Power service
technicians. Learn more about Emerson Network Power products and services at:
www.emersonnetworkpower.com
About Emerson
Emerson (NYSE: EMR), based in St. Louis, Missouri (USA), is a global leader in bringing technology and engineering together to provide innovative
solutions for customers in industrial, commercial, and consumer markets around the world. The company is comprised of five business segments: Process
Management, Industrial Automation, Network Power, Climate Technologies, and Commercial & Residential Solutions. Sales in fiscal 2013 were $24.7 billion.
For more information, visit:
www.emerson.com
Official Wechat
Official Weibo
Legal statement: While every precaution has been taken to ensure accuracy and completeness herein, Emerson assumes no responsibility,
and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications subject to change
without notice.
Emerson Network Power Co., Ltd.
Pre-sales hotline:
After-sales hotline:
Address: Block B2 Nanshan Park No.1001 Xueyuan
Road Nanshan Dist. Shenzhen, 518055 China
China Telephone: 86-755-86010808
Postcode: 518055
400-887-6526
400-887-6510
www.emersonnetwork.com.cn
Emerson Network Power, ASCO, the Emerson Network Power logo and ASCO logo are trademarks and service marks of Emerson Electric Co. ©2015 Emerson Electric Co.
E-X6216497-0915