DC Power for
Business-Critical Continuity™
NetSure™ 701
DC Power System for Hybrid Applications
nMultiple input power options
include: grid, diesel generator,
solar panel and wind turbine
The NetSure™ 701 provides a reliable supply of energy
to telecom access sites blending an engineered
combination of power sources, such as grid, diesel
generator, solar panels and wind turbines.
nProvides up to 17.5 kW rectifier
capacity
Description
nSeparate sub-racks deliver up to
12 kW solar converter capacity
System configuration can be optimized to meet initial requirements in a cost-effective
manner, while allowing for future expansion. Configurable distribution and various
rectifier modules are available to meet different needs. Solar converters can be added
to the system in separate, self-contained sub-racks.
Key Features
nSupports up to 6 kW wind
turbine (-48V)
nFront access and top cabling
design for installation and
maintenance
nUtilizes UL approved rectifiers
R48-3200 and high-efficiency
R48-3500e
nEasily add or swap units without
system interruption
nConfigurable distribution for
high or low priority supply
nAC input accepts three phase
(400V star connected) or single
phase (230V) nominal input
nPrevents deep battery discharge
with two levels of load
disconnect
EN241DRB-NS701 / 1112
1
NetSure™ 701
Technical Specifications
System Electrical Specifications
Nominal Output Voltage
Operating Voltage Range
Output Power
Input Voltage
Frequency
Regulation
Output Noise
Safety
-48Vdc
-42 Vdc to -58 Vdc
17.5kW (max)
3-phase, 400V or single phase, 230V
45 HZ to 65 HZ
<± 0.5%
<200 mV (pk-pk)
EN60950
System Physical Specifications
Height x Width x Depth
Weight (without Rectifier modules)
Operating Temperature Range
Operating Relative Humidity Range
311 x 482 x 335mm
<25kg
-5˚C to +45˚C
≤95%RH
Distribution
Battery Input
Wind Turbine Input
Output Routes
Equipment
Advanced Controller Module – ACU+
Rectifiers – R48-3200
Rectifiers – R48-3500e
Solar Converter – S48-3000
Solar Converter Sub-Rack
2 x 125A MCB
1 x 125A MCB
High priority: 2 x 32A, 1 x 63A MCB
Low priority: 3 x 32A, 2 x 63A MCB
Refer to separate data sheet
Refer to separate data sheet
Refer to separate data sheet
Refer to separate data sheet
Refer to separate data sheet
EmersonNetworkPower.com/EnergySystems (North America)