Designed to reduce OpEx at access telecom sites,
the Outdoor Battery Enclosure stores significant
amounts of energy from multiple power sources.
Description
The Outdoor Battery Enclosure (BFK90401/101) from Emerson Network Power
provides housing for batteries in a temperature controlled and physically protected environment. It is intended for use in access telecom networks. The large
battery capacity and thermal design are well suited to hot, outdoor climate
conditions, making it ideal for use in outdoor hybrid power applications. Multiple
power sources, including renewable energy, are combined with the large battery
storage capacity to operate as one hybrid energy source. This hybrid solution
substantially reduces the operational cost and negative environmental impact of
the telecom site.
nThree-point locking
mechanism and external
padlock on doors provide
solid vandal protection
nAccommodates vertically
mounted 2V-OPzV battery
blocks to max capacity of
1500Ah/48V
IP55 rated to withstand the ingress of water and dust
EN607DRA-OBE / 1012
1
Outdoor Battery Enclosure
Technical Specifications
Diagram
Battery Block Placement
Design And Structure
Enclosure Type
Panels
Support
Outdoor battery enclosure
Inner insulated mild steel panels
3Cr12 floor panel
Environmental Data
Outdoor Temperature Range (Daily)
Outdoor Temperature Peak <3Hrs/Day
Outdoor Humidity
Altitude
-10°C to 45°C
+50°C
All weather applications
0 to 2500m ASL
Mechanical Data
Net Dimensions (H x W x D)
Outdoor Temperature Peak <3Hrs/Day
Net Weight
Climate
Cooling Climate Equipment
Protection
Gas Extraction
Battery
Battery String Space (H x W x D)
Max. No. Of 48V Battery Strings
Battery String Geometry
Protection
Cable Inlet/Outlet
Cable Inlet/Outlet
Interface
Aircon Alarm (Terminal 1 & 2)
Gas Extraction Control (Terminal 3 & 4)
Gas Extraction Fail (Terminal 5 & 6)
1120 x 1853 x 1390 mm (air-con inclusive)
+50°C
200kg approximately
(excluding batteries and climate system)
1 x 48V, 400W DC air-conditioner unit
1 x 15A circuit breaker
1 x 48V,5W,170m3/h fan unit
1298 x 1500 x 997 mm
1 - (24) 2V OPzV800-1500 battery blocks
2 - (48) 2V OPzV600 battery blocks
6 columns, 4 rows
1 x 250A circuit breaker (made of 2 x 125A CBs)
4 cable glands on distribution box
(13 to 16mm cable outer diameter)
Ordering Information
Part Number
BFK90401/101
Accessories
BPB10833/1
BKV177600/4
10475/4
9079
9704
Description
Outdoor battery enclosure
400W DC air conditioner
Fan DC 170m3/h
Swing handle door lock kit
15A DC circuit breaker
125A DC circuit breaker
Open circuit -normal condition,
short circuit - fail condition
Open circuit - off
Short circuit – on
48V normal condition
0V fail condition
EmersonNetworkPower.com/EnergySystems (North America)
EmersonNetworkPower.eu/EnergySystems (EMEA)
© Emerson Network Power Energy Systems North America 2012.
Business-Critical Continuity™, Emerson Network Power™, the Emerson Network Power logo, Emerson® and Consider it Solved are service marks and trademarks of Emerson Electric Co.
EnergyMaster™, eSure™, NetPerform™, NetReach™, NetSpan™, NetSure® and NetXtend™ are trademarks of Emerson Network Power Energy Systems North America.
2
EN607DRA-OBE / 1012
Download