LIEBERT® UNIVERSAL MONITOR™ Product Specification/Installation Sheet Description Features The Liebert Universal Monitor is a microprocessor with multisensing, remote monitoring and remote control capabilities. Its Liebert Universal Monitor Two sizes of enclosures advanced technology provides high-availability monitoring around the clock. • • • • • • • • • The Liebert Universal Monitor can operate as an independent, stand-alone controller or in conjunction with Liebert’s SiteScan® Web Enterprise Monitoring System. • • The enclosure of the Liebert Universal Monitor makes it suited for various applications in both new construction and retrofit jobs. The Liebert Universal Monitor can be mounted on a wall’s surface or recessed within a wall. Transformer module* Power On/Off switch 24VAC power connector TB5: COMMON ALARM (TERMINAL BLOCKS ROTATED IN VIEW) (TOP) The modem is preconfigured to work with the panel, eliminating configuration and setup requirements. NO C NC NO C NC (BOTTOM) OM LS1 + TB7: 24V INPUT LCD contrast adjustment P23: BATTERY START P11 Manual override switch (outputs) ENABLE AUDIBLE R40 R2 BATTERY Q11 TOP LCD CONTRAST TB3: RELAY OUTPUTS TP1 VBATT GND ON S2 OFF ON 1 2 DIP 3 4 5 6 7 OUTPUT1 OUTPUT2 OUTPUT3 OUTPUT4 OUTPUT5 OUTPUT6 OUTPUT7 OUTPUT8 CTRLLOCK SENLOCK CMN ALR DS56 DS54 DS63 8 DS83 DS84 DS61 DS60 DS62 DS55 DS57 DS59 DS58 DS53 CAN TX CAN RX Modem R R334 4 4 3 INPUT1 INPUT2 INPUT3 INPUT4 INPUT5 INPUT6 INPUT7 INPUT8 C71 DS70 DS67 DS66 DS65 DS64 2 1 (TOP) D 4 3 24VAC connector* 2 1 ASS 8 7 6 5 (BOTTOM) REV MODEM 4 Digital output connectors (BOTTOM) (TOP) MOP F PROG 574 TX 574 RX 485 RX 485 TX ON OFF PFM2 The Liebert Universal Monitor has a standard, on-board modem for remote monitoring via a telephone line. Common alarm connectors Audible horn Battery pack LIEBERT BAR CODE The display, the gateway to all configuration and monitoring, is password-protected. Liebert Universal Monitor Components and Key Features ON OFF PFM5 The keypad display on the face of the panel is a standard part of the Liebert Universal Monitor. Custom configuration for specific applications Paging capability—up to four pager numbers Preconfigured on-board modem Alarm, Event and Trend logs with time and date stamp Battery backup to ensure alarm notification Backup and download configuration files User interface via RS232 or modem connection On-board audible alarm Configuration data and operating program permanently stored in nonvolatile Electrically Erasable Programmable Read Only Memory (EEPROM) for protection against power loss Real-time clock Status LEDs for verification and diagnostics Digital input connectors 8 7 6 5 TB2: CONTACT INPUTS Analog input connectors 1-2 TOP 3-4 BOTTOM Power On/Off switch* ON MODEM J11: PHONE PIN 3-TIP PIN 4-RING TB10: COMMS 485 (TOP) + (BOTTOM) Power receptacle* Phone line connector — 422 + — + — + + — Serial interface connector (RS232/EIA574) ALL CIRCUITS: CLASS 2 — + — AG TB9: ANALOG GROUND EIA485 connector SiteScan Web connector (EIA422) *Transformer module comes standard in large enclosure only 1 Hardware and Components Two sizes of enclosures provide flexibility and expansion to meet evolving application needs. Both sizes of enclosures come standard with a liquid crystal display (LCD) and controller board. In addition, the large Liebert® Universal Monitor™ has an internal Transformer Module. The enclosure features a key lock for added security and is made of metal to accommodate secure conduit fittings and protect components against environmental debris. The enclosure is designed for easy wire routing and terminations, with top and bottom access slots for communication cables and network wires. The enclosure is 2-3/4" deep, allowing for recess mounting in a wall. Keypad Display Transformer Module The keypad display is a user interface mounted on the enclosure door of each Liebert Universal Monitor. The display provides for complete monitoring and configuration of the panel and is password-protected. The large Liebert Universal Monitor comes with either 115VAC or 230VAC Transformer Module. • The 115VAC Transformer 115VAC Transformer Module provides step-down power from 115VAC to 24VAC, two Class 2 24VAC 40VA power terminations and one 115VAC outlet to power accessory devices, such as a Portable Operator’s 230VAC Transformer Terminal. • The 230VAC Transformer Module provides step-down power from 230VAC to 24VAC and two Class 2 24VAC 40VA power terminations. An outlet is not provided on this Transformer Module. Keypad The keypad display provides the ability for the Liebert Universal Monitor to operate as a complete standalone panel. Controller Board The controller board supports 22 points: • • • • Eight digital inputs Four analog inputs Eight digital outputs Two Common Alarm outputs The Transformer Module may be ordered separately as an option for the small Liebert Universal Monitor—or any device requiring 24VAC—and mounted outside the enclosure. The digital inputs are dry contacts. The analog inputs are 4-20mA inputs. The digital outputs and Common Alarm outputs are Form C contact relays. I/O Expansion Module The point terminations are made using removable terminal blocks. This allows for easier access to the terminators, streamlining the process of connecting external devices to the Liebert Universal Monitor. The Liebert Universal Monitor I/O Expansion Module, purchased separately, has connectors for 16 digital inputs and eight digital outputs, as shown below. The board has light emitting diodes (LEDs) to display the status of monitored output devices, communications ports for connection to the Liebert Universal Monitor, power connections and other features necessary to monitor and protect your operation. The battery supplies power to the modem for a minimum of 10 minutes, providing the capability to send out a loss-of-power alarm to all configured pagers. Flash ROM may be easily upgraded at the job site, simplifying the process of installing new firmware as it becomes available. I/O Expansion Module Components & Key Features An RS232 operator terminal port is included with each controller board for easy interface to a laptop or desktop PC for setup and device monitoring. 24VAC power connector An integrated on-board modem is included with each controller board for remote access to the Liebert Universal Monitor. An RJ11 phone modem jack is also included. The modem is factory-configured, eliminating field configuration and wiring requirements. Digital output connectors (8) USE COPPER (CU) CONDUCTORS ONLY. POWER INPUT RELAY OUTPUTS Multiflex 168AO 810-3065 D6 EIA485 + (to UM-) 0V EIA485 - (to UM+) S4 S3 S2 V2 V1 V6 V5 V8 V7 V10 V9 V12 V11 V14 V13 V16 V15 S1 K1 K2 OUT1 An IGM422 connection is included with each controller to connect the Liebert Universal Monitor to Liebert’s SiteScan Web Enterprise Monitoring System. This connection allows information and alarms to be monitored from a central command center. V4 V3 K3 OUT2 K4 OUT3 K5 OUT4 K6 OUT5 K7 OUT6 K8 OUT7 Digital output fuses (8) OUT8 Digital output DIP switch DEFAULT SETTINGS FOR USE WITH UNIVERSAL MONITOR EIA485 connector 2 Digital input connectors (16) Dimensions - Enclosures, I/O Expansion Module, Transformer Modules LARGE ENCLOSURE 18" (457.2mm) SMALL ENCLOSURE & I/O EXPANSION MODULE 14.25" (361.95mm) TRANSFORMER MODULES (115V & 230V) 14" (355.6mm) 18" (457.2mm) 12" (304.8mm) Front view 3.83" (97.2mm) Front view Front view 2.85" (72.39mm) 2.85" (72.39mm) Top/bottom view 2.65" (67.3mm) Top/bottom view Bottom view Wiring Specifications Connection Supported Wire Type Maximum Wire Length Rating Digital Input 18-22 AWG Stranded & Unshielded 18 AWG (recommended) Non Plenum - Belden 9740 Plenum - Belden 89740 750 ft. (225m) Dry Contact (24VDC, 10 mA) Digital Output Analog Input 2-Wire Transducer Analog Input 4-Wire Transducer Common Alarm Output 18 AWG* 18-22 AWG Stranded & Unshielded (recommended) 18 AWG (recommended) @3A 50 ft. (15m) Non Plenum - Belden 9740 @2A 100 ft. (30m) Plenum - Belden 89740 @1A 200 ft. (60m) 18-22 AWG Stranded & Unshielded 18 AWG (recommended) Non Plenum - Belden 9740 Plenum - Belden 89740 18-22 AWG Stranded & Unshielded 18 AWG (recommended) Non Plenum - Belden 8489 Plenum - Belden 88489 18 AWG* 18-22 AWG Stranded & Unshielded (recommended) 18 AWG (recommended) @3A 50 ft. (15m) Non Plenum - Belden 9740 @2A 100 ft. (30m) Plenum - Belden 89740 @1A 200 ft. (60m) Communication Null Modem Cable RS232 Communication 18-22 AWG Stranded & Shielded 22 AWG (recommended) IGM422 Non Plenum - Belden 9461 SiteScan Plenum - Belden 88761 18-22 AWG Stranded & Shielded Communication 22 AWG (recommended) EIA485 Non Plenum - Belden 9461 Plenum - Belden 88761 Phone/Modem 4 Wire (Pins 3 & 4) Line RJ11 Connector 18-22 AWG Stranded & Shielded 18 AWG (recommended) Non Plenum - Belden 8770 Plenum - Belden 88770 Power Connections (Transformer Module) 24VAC Power Connection 115VAC 230VAC 14 AWG Stranded & Unshielded Non Plenum - Belden 5101UE 14 AWG Stranded & Unshielded Non Plenum - Belden 5101UE 3 20 AWG 22 AWG @3A 40 ft. (12m) @3A 25 ft. (7m) @2A 60 ft. (18m) @2A 35 ft. (10m) @1A 100 ft. (30m) @1A 75 ft. (23m) 4-20 mA Signal Input Selectable Power Source (12/24VDC) 4-20 mA Signal Input Selectable Power Source (12/24VDC) 750 ft. (225m) 750 ft. (225m) 20 AWG 24VAC @3A 22 AWG @3A 40 ft. (12m) @3A 25 ft. (7m) @2A 60 ft. (18m) @2A 35 ft. (10m) @1A 100 ft. (30m) @1A 75 ft. (23m) 24VAC @3A 50 ft. (15m) N/A 1000 ft. (300m) N/A 3000 ft. (900m) N/A N/A N/A 150 ft. (45m) 24VAC @1.3A 150 ft. (45m) 115VAC @5A 150 ft. (45m) 230VAC @0.5A Specifications Small Enclosure Input Power Requirements Dimensions W x D x H, in. (mm) Weight (Assembled) Enclosure Type Liquid Crystal Display Mounting Surface Ambient Operating Environment Modem/Clock Specifics Modem Type Clock Type Clock battery backup type Clock battery life Modem battery backup type Modem battery life Communications Local Remote: Modem Remote: Supported pagers SiteScan Web Expansion Board (optional) Agency Listings UL CE FCC Compliance Inputs & Outputs (Quantity) Digital Inputs Analog Inputs Digital Outputs Common Alarm Outputs Large Enclosure 115VAC 230VAC UMS02400 UML11500 UML23000 24VAC±10% of 115VAC±10% of 230VAC±10% of nominal; 50/60 Hz, nominal; 60Hz, nominal; 50Hz, 1.3A, 30VA 4A, 460VA 0.5A, 115VA 14-1/4 x 2-3/4 x 12 18 x 2-3/4 x 18 (361.95 x 69.85 x 304.8) (457.2 x 69.85 x 457.2) 7.68 lb. (3.48 kg) 20.56 lb. (9.33 kg) NEMA 1 Four line, 20 character, backlit Building Wall or Structural Member 32°F to 104°F (0°C to 40°C) 0% RH to 95% RH (non-condensing) Embedded 14.4K bps Real-Time Clock Lithium Cell (non-replaceable) 7 years, constant, no power Nickel Cadmium (replaceable) 10 minutes at full load EIA232 Baud rate 9600 bps; Parity=None; Data bits=8; Stop bits=1 9600 E-7-1 supports TAPI protocol version 1.8 IGM Protocol, EIA422 EIA485 UL3121 Yes CFR 47 Part 15 UL1012 UL1585 Yes N/A Dry Contact Closure 24VDC, 10 mA (8) 4-20mA signal input with selectable power source of 12VDC or 24VDC (4) 24VAC, 3A (8) 24VAC, 3A (2) I/O Expansion Module UMEXP 24VAC±10% of nominal; 50/60 Hz, 0.6A, 15VA, Class 2 14-1/4 x 2-3/4 x 12 (361.95 x 69.85 x 304.8) 7.68 lb. (3.48 kg) NEMA 1 — — — — — — — — — — — — — EIA485 — — — Dry Contact Closure 24VDC, 10 mA (16) — 240VAC, 2A (8) — Ordering Information Quantity Product # UMS02400 UML11500 UML23000 TM115 TM230 UMEXP Description Liebert Universal Monitor small enclosure Liebert Universal Monitor large enclosure with 115VAC Transformer Module Liebert Universal Monitor large enclosure with 230VAC Transformer Module Transformer Module 115VAC with two 24VAC outputs (40VA each) and 115VAC receptacle Transformer Module 230VAC with two 24VAC outputs (40VA each) I/O Expansion Module Liebert Corporation 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 Telephone: 1-800-877-9222 Facsimile: 1-614-841-6022 www.liebert.com © 2005 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners. SL-31061_REV2_02-13 4